Peer Reviewed 2014 Solar Research Conference

Similar documents
Simulation Studies on Performance of Solar Cooling System in UAE Conditions

Modeling and analyzing solar cooling systems in Polysun

Available online at ScienceDirect. Energy Procedia 101 (2016 )

Renewable Energy Based Active Cooling System

Solar Absorption Aqua-Ammonia Absorption system simulation base on Climate of Malaysia

EFFICIENT SOLAR COOLING

SOLAR COOLING: STATE OF THE ART, TECHNICAL ANALYSIS AND FIRSTS APPLICATIONS

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

Australian Solar Cooling Interest Group (ausscig) Conference Financial analysis of solar cooling systems in Australia

Great Ocean Rd Ice Creamery

Figure 1: Uncovered and covered PVT collectors

DESIGN AND RECOMMANDATIONS FOR DECENTRALIZED SOLAR DISTRICT HEATING SYSTEMS IN FRANCE

ST-4 Polygeneration plant. Parc de l Alba Cerdanyola del Vallès

The Potential and Challenges of Solar Boosted Heat Pumps for Domestic Hot Water Heating

Application of Near-Optimal Tower Control and Free Cooling on the Condenser Water Side for Optimization of Central Cooling Systems

Content. State of the Art in Solar Cooling. Solar cooling technology developments. Market developments & barriers

Chapter Six{ TC "Chapter Six" \l 1 } System Simulation

APPLICATION OF CUSTOMIZED ABSORPTION HEAT PUMPS WITH HEATING CAPACITIES ABOVE 500 kw PROJECT: ACKERMANNBOGEN, MUNICH

SorTech package solution description

Study on Ejector - Vapor Compression Hybrid Air Conditioning System Using Solar Energy

Available online at ScienceDirect. Energy Procedia 91 (2016 )

Active solar heating system with concrete plate heating analysed with dynamical thermal simulations

Development of an Innovative 2.5 kw Water- Silica Gel Adsorption Chiller

The Effects of Set-Points and Dead-Bands of the HVAC System on the Energy Consumption and Occupant Thermal Comfort

Experimental investigation of single-phase and twophase closed thermosyphon solar water heater systems

SIMULATION AND MODEL CALIBRATION OF A LARGE-SCALE SOLAR SEASONAL STORAGE SYSTEM

DISTRIBUTED SOLAR THERMAL NET METERING IN SMALL-SCALE DISTRICT HEATING SYSTEMS

RETRO-COMMISSIONING OF A HEAT SOURCE SYSTEM IN A DISTRICT HEATING AND COOLING SYSTEM Eikichi Ono 1*, Harunori Yoshida 2, Fulin Wang 3 KEYWORDS

Design of a new concentrated photovoltaic system under UAE conditions

Investigations of Intelligent Solar Heating Systems for Single Family House

Available online at ScienceDirect. Energy Procedia 49 (2014 ) SolarPACES 2013

SIMULATION MODEL IN TRNSYS OF A SOLAR HOUSE FROM BRAŞOV, ROMANIA

Australian Solar Cooling 2013 Conference April 12th, 2013 North Ryde, Australia. All-in-oneSolar Thermal CoolingandHeatingSystem

Heat Load Calculation for the Design of Environmental Control System of a Light Transport Aircraft

Electrical/thermal performance of hybrid PV/T system in Sharjah, UAE

EXPERIMENTATION AND MODELLING OF A SMALL-SCALE ADSORPTION COOLING SYSTEM IN TEMPERATE CLIMATE. July 22, 2013

EVALUATION OF SOLAR SORPTION REFRIGERATION SYSTEM PERFORMANCE IN LATVIA

Exergy analysis of a flat plate solar collector

MODELLING OF COMMERCIAL ABSORPTION HEAT PUMP WITH INTEGRAL STORAGE

BUILDINGS & OFFICE SPACES INDUSTRIAL SOLUTIONS. Combined production of Heat and Power. Waste Heat Recovery Bottoming Cycle

275 GEORGE STREET, BRISBANE CASE STUDY. Andrew Gentner Norman Disney & Young, Spring Hill QLD, Australia

CombiSol project. Solar Combisystems Promotion and Standardisation

A simulation of the performance of PVthermal (PVT)systems for residential application in Tokyo

ARE YOUR VARIABLE SPEED PUMPING APPLICATIONS DELIVERING THE PREDICTED SAVINGS? IMPROVING CONTROL TO MAXIMIZE RESULTS

Study of Performance of Solar Photovoltaic Thermal Collector at Different Temperatures

AR No. # - Solar Thermal

MATHEMATICAL MODELING OF A DOUBLE PASS UNDERFLOOR HEATING SYSTEM

Green Star Shopping Centre Design PILOT Energy Calculator Guide

Optimisation and Cost Analysis of a Lithium Bromide Absorption Solar Cooling System

Héctor Rubio Plana Gas Natural, SDG S.A. 18th. June 2009

Heat pump system control: the potential improvement based on perfect prediction of weather forecast and user occupancy

STUDY OF HEATING AND COOLING SYSTEMS TO DESIGN ZERO ENERGY BUILDINGS

PHYSICAL AND OPERATING CONDITIONS EFFECTS ON SILICA GEL/WATER ADSORPTION CHILLER PERFORMANCE

Solar Powered Air Conditioning System

An Integrated Solution for Commercial AC Chillers Using Variable Speed Scroll Compressors

Computational Study of Hybrid Water Heater with Evacuated Glass Tube Solar Collector and Rice Husk Combustion

Demonstrating Cost Effective Thermal Energy Storage in Molten Salts: DLR s TESIS Test Facility Christian Odenthal, Freerk Klasing and Thomas Bauer

THERMAL AND ELECTRICAL PERFORMANCES OF A NEW KIND AIR COOLED PHOTOVOLTAIC THERMAL SYSTEM FOR BUILDING APPLICATION

Energetic Assessment of Two Solar Cooling Systems in Piura using the TRNSYS Software

Advanced Thermal Energy Storing with the most efficient use of the ressources. Peter Badstue Jensen Vice President - Partner

Design of Experiment for Solar Water Heater Performance Analysis

NSX ANNOUNCEMENT. Public Letter to Shareholder

Experimental analysis of heat-pump integrated with solar energy

ScienceDirect. Compact hot water storage systems combining copper tube with high conductivity graphite and phase change materials

Thermally operated mobile air-conditioning system

Energy Efficient Solar Milk Chiller

BASIC EUROPEAN GLAZED COLLECTORS & SOLAR DOMESTIC

Heat Recovery Ground Source Heat Pump System in Smart Community Takao KATSURA Faculty of Engineering, Graduate School of Hokkaido University

Feasibilty of Wind-Solar Hybrid System for Cleveland, Ohio, USA

Bore field sizing : Theory and applications

DESIGN AND MODELING THE Φ-F

SOLAR ENGINEERING OF THERMAL PROCESSES

Simulation and Optimization of Vacuum Tube Solar Collector Water Heating System in Iran

DEVELOPMENT OF A HIGH EFFICIENCY ABSORPTION CHILLER-HEATER AND A COMPACT ABSORPTION CHILLER-HEATER

Proceedings of BS2013: 13th Conference of International Building Performance Simulation Association, Chambéry, France, August 26-28

Available online at ScienceDirect. Energy Procedia 91 (2016 ) 20 26

Performance Comparison of Air-source Heat Pumps Using Economizer Vapor Injection and Internal Heat Exchanger in Cold Regions

PERFORMANCE ANALYSIS OF PARABOLIC TROUGH SOLAR COLLECTOR FOR THREE DIFFERENT FLOW RATES

The optimization of the mechanical night cooling system in the office building

A Solar Wall System Utilized in Rural Houses of Northeast China

SOLAR COOLING FOR ENERGY SAVING. CAN WE AFFORD NOT TO USE THE HEAT OF THE SUN?

Research on Ground Source Heat Pump Design

OPTIMIZATION OF DISTRICT HEATING SYSTEMS

Chromasun Micro-Concentrator

Utilization of f-chart Method for Designing Solar Thermal Heating System

On the Night Heat Losses in Thermosyphon Solar Water Heaters

Thermal performance of a closed wet cooling tower for chilled ceilings: measurement and CFD simulation

ANNUAL ENERGY PERFORMANCE OF SOLAR THERMAL SYSTEMS IN BRAŞOV, ROMANIA

Experimental study of an air-source heat pump for simultaneous heating and cooling - Part 1: Basic concepts and performance verification

IMPACTS OF CLIMATE CHANGE ON SOLAR PV POWER SYSTEM: A CASE STUDY IN SUBTROPICAL ROCKHAMPTON, AUSTRALIA

PERFORMANCE OF SOLAR COLLECTORS UNDER LOW TEMPERATURE CONDITIONS: Measurements and simulations results

Study on the heat transfer characteristics of an evaporative cooling tower B

PERFORMANCE STUDY OF SOLAR THERMAL BINARY POWER CYCLES

Performance Evaluation of a Lithium-Chloride Absorption Refrigeration and an Assessment of Its Suitability for Biomass Waste Heat

Italcementi Center for Research and Innovation

EVALUATION OF THE THERMAL PERFORMANCE OF FIVE REFRIGERATED VANS

Product catalogue A25s. Solar Cooling systems

DTS & ENERGY MODELLING PROTOCOL GUIDE Version 1.0

BUILDING DESIGN FOR HOT AND HUMID CLIMATES IMPLICATIONS ON THERMAL COMFORT AND ENERGY EFFICIENCY. Dr Mirek Piechowski 1, Adrian Rowe 1

ABSTRACT INTRODUCTION

Transcription:

Peer Reviewed 2014 Solar Research Conference Simulation results of a high-temperature solar-cooling system with different control strategies Sergio Pintaldi 1,4, Ali Shirazi 2, Subbu Sethuvenkatraman 4, Stephen White 4, Gary Rosengarten 1, Robert A Taylor 2,3 1 School of Aerospace, Mechanical and Manufacturing Engineering, Royal Melbourne Institute of Technology, 115 Queensberry St, Carlton, Australia 2 School of Mechanical and Manufacturing Engineering, The University of New South Wales, Kensington, New South Wales, Australia 3 School of Photovoltaic & Renewable Energy Engineering, The University of New South Wales, Kensington, New South Wales, Australia 4 Energy Flagship, Commonwealth Scientific and Industrial Research Organisation, 10 Murray Dwyer Circuit, Steel River Industrial Park, Newcastle, Australia E-mail: sergio.pintaldi@csiro.au Abstract High-temperature absorption chillers (double-effect and triple-effect) have a higher coefficient of performance (COP) than single-effect chillers. This can reduce the collector s footprint and cost in a solar-cooling plant. Though single-effect, absorption chiller-based solar-cooling systems have been studied for the past 20 years, very little information is available on the performance benefits of high-temperature solar-cooling systems. The behaviour of a solar-driven, triple-effect absorption chiller with thermal storage, when serving an office building load, have been analysed in this paper. Characteristic equations for the triple effect chiller have been developed from their operating performance data. The effect of different control strategies and design parameters on the annual performance of the system have been captured in this paper. These results indicate that it is possible to achieve very high solar fractions (> 0.9) by choosing the right size of system components and a suitable control strategy. 1. Introduction Various design options for solar driven air conditioning systems exist (Pintaldi et al., 2015). These include choices related to component sizing, (collector and storage size) integration of backup heat source and control strategy. These choices are also load dependent. Considering the multiple variables involved, system level simulations have been used by researchers to identify a suitable system layout for a given application. The Transient System Simulation TRNSYS (Solar Energy Laboratory, University of Wisconsin, 2011) has been widely used by researchers as a tool during these evaluations (e.g. (Al-Alili et al., 2012; Eicker and Pietruschka, 2009)). Eicker and Pietruschka have used TRNSYS based simulations to evaluate design and performance of solar air conditioning systems for office buildings. They used single effect absorption chillers in their studies to characterise energy and economic benefits. Al-Alili et al. have optimized a solar powered absorption system for Abu Dhabi s weather conditions using TRNSY and GenOpt optimization algorithm. Hang et al (Hang et al., 2013) have used multi objective optimization techniques to identify optimum solar absorption cooling and heating system configuration for medium sized office buildings in various locations of USA. Solar cooling system configurations for various other locations have also been studied through simulations (Mateus and Oliveira, 2009; Tsoutsos et al., 2010).

However, literature with system level benefits of high temperature solar cooling systems is very limited. Qu et al. (Qu et al., 2010) have analysed the benefits of a double effect chillerbased system for a building using system level simulations. There is no published literature on the optimization of a solar cooling system utilizing triple effect absorption chillers. Thus, a model to capture the performance of a triple effect chiller has been developed and the approach is presented in this paper. Utilizing this model, system level benefits of a triple effect solar cooling system configuration for an office building are evaluated in this paper. 2. Model description and simulation methodology The solar cooling system configuration is shown in Figure 1. It consists of parabolic trough collectors for generation of high temperature heat (> 200 o C), a backup heat source and a storage tank to aid in solar intermittency and to serve as a backup during non-solar periods. The triple-effect absorption chiller with cooling tower makes up the cooling generation system. This layout is simulated using TRNSYS. Details of component specification in the model are provided in Table 1. As a detailed validation of the model is not possible (due to lack of test data), sanity checks such as chiller energy balance and total system energy balance were monitored throughout the simulations. Figure 1. Simulated solar-cooling layout 2.1. Building load The building model used in this study represents a typical office building, located in medium and large Australian cities, and falling under building category A of the Australian Building Codes Board 1. The building has a fully enclosed area of ~1000 m 2 ; the dimensions of the sides are 31.6 x 31.6 m, and the floor-to-ceiling height is 2.7 m. 1 ACADS-BSG Pty Ltd, Elms Consulting Engineers (May 2002) ABCB Energy modelling of office buildings for climate zoning, stages 1, 2 & 3, p. 2; ABCB www.abcb.gov.au; Major Initiatives > Energy Efficiency > Multi-Residential, Commercial and Public Buildings > Archived Documents (www.abcb.gov.au/majorinitiatives/energy-efficiency/multi-residential-commercial-and-public-buildings).

The building walls and fabric were designed to meet the minimum requirements provided by the Building Code of Australia. The internal loads were based on 100-person occupancy and a low infiltration rate (0.25 air changes/h). Loads associated with lighting and equipment were included in the model. Temperature set-points for cooling and heat mode operations were 24 C and 20 C, respectively. To meet the comfort requirements, the operating time for the air-conditioning system was set between 0700 and 1800 hours. These conditions resulted in an annual cooling and heating demands of 15 MWh and 0.310 MWh, respectively, for a building located in Newcastle, Australia. Table 1 summarises the main parameters and coefficients used in the simulations. The chiller model and the system controllers are discussed in Section 2.2 and Section 3, respectively. Table 1. Description of the main system component parameters Component Weather data Solar collector Thermal store Back-up system Cooling tower Pumps Description Newcastle, Williamtown Airport Efficiency parameters for the solar collector are η 0 = 0.689, a 1 = 0.36W/m 2 K, a 2 = 0.0011W/m 2 K 2. Water is the working fluid in the collector loop. Hot storage tank of height-to-diameter ratio of 3.5. Overall heat loss coefficient set to 0.83 W/m 2 K. Instantaneous gas burner with a set-point temperature of 220 C. The back-up position can be set to series or parallel. Wet cooling tower in a counter-flow configuration. A controlled, variable-speed fan maintained the outlet temperature of cooling water at a constant value of 32 C. The system used five pumps, as shown in Figure 1. The solar pump (P1) worked in variable-speed mode or fixed-speed mode depending on the controller type. Details of these controls are explained in Section 3. All other pumps (P2 P5) operated in ON OFF mode. 2.2. Triple-effect absorption chiller model Thermodynamic models for absorption chillers are complex to implement and computationally expensive for detailed annual energy performance simulations. Thus, various empirical and semi-empirical modelling approaches for predicting absorption chiller performance have been documented (Labus et al., 2013; Puig-Arnavat et al., 2010). The current model is based on the characteristic temperature function ΔΔT, as described by Kühn and Ziegler (2005). The energy balance equations are: QQ AAAA = QQ EE + QQ GG + QQ aaaaaa (1) CCCCCC = QQ EE QQ GG +QQ aaaaaa (2) QQ = mm cc pp (TT oo TT ii ) (3) The expression of the evaporator and generator power is: QQ = ss tt + rr (4) Where the characteristic temperature function is: tt = tt GG + aa tt AAAA + ee tt EE (5) The subscripts are: G for chiller generator, AC for absorber and condenser, E for evaporator, aux for auxiliary, o for output, i for input, T for temperature and t for average temperature

between the inlet and the outlet. The model has been calibrated using triple-effect, hot-waterfired absorption chiller data provided by Thermax (Thermax and CSIRO, 2014). Statistical analysis was performed according the second method described by Puig-Arnavat et al. (2010) and Microsoft Excel was used for multi-variable regression analysis of the cooling capacity. The characteristic temperature function parameters obtained from the above process were then used for a mono-variable regression analysis of the generator capacity to obtain the generator parameters of Equation 4. Table 2 summarises the coefficients used in Equations 3 5. Table 2. Triple-effect absorption chiller parameters Characteristic equation Value Additional parameters Value parameters a 2.63156 Chiller capacity 10 kw e 3.95614 COP-rated conditions 1.81 se 1.19813 Hot water flow rate 510 kg/hr re 76.91607 Cooling water flow rate 3170 kg/hr sg 0.54388 Chilled water flow rate 1950 kg/hr rg 25.95760 Cp water 4.19 kj/kgk The thermal load data was scaled to fit the chiller size. To satisfy wide variations in cooling demand, the chiller was allowed to work between 20 and 140% of its nominal capacity. The simulations used water as the working fluid in the chiller loop. 3. System control This system used three controllers, as described below. The solar and back-up systems are activated to fulfil the load and temperature requirements of the chiller. The simulations used fixed temperatures for the chilled water inlet (7 C) and cooling water inlet (32 C). 3.1. Collector control The collector is activated by a controller. The first control approach modulates the pump mass flow rate to match a collector outlet set-point temperature (210 C), which is the rated hot water temperature inlet condition for the chiller. The second control approach (known as hysteresis controller) operates the pump in an on/off mode. Depending on the temperature difference between the collector and the tank, the controller turns the pump on (T coll,out T tank,bottom >15 K) or off (T coll,out T tank,bottom <5 K). The controller system activates the collector only when the sun s radiation is higher than 150 W/m 2 during working days. 3.2. Tank, back-up and bypass control The tank controller, which is based on two temperature sensors positioned at heights of 25% from the top and bottom locations, switches the back-up burner on or off. In the parallel configuration (shown in Figure 1), the tank is completely decoupled from the back-up heat source. In this configuration the chiller is supplied, at any given time, with either heat from the tank or heat from the burner. In the series configuration, the tank is always discharged, and the burner is switched on only if the fluid is not hot enough. Thus heat comes simultaneously from both solar and gas. In both configurations, the controller operates a bypass valve to regulate the recirculated flow rate and obtain the requested chiller supply temperature. 3.3. Chiller control

The absorption chiller is activated when the building requires cooling. A controller in the cooling tower controls the fan speed to maintain a temperature of 32 C at the chiller inlet. As described above, chiller cooling capacity is regulated by varying the generator supply water temperature. 4. Results In order to investigate the system performance for different control configurations, and the influence of different system design parameters (e.g. storage volume, collector area), a parametric study has been carried out. The system was simulated for 80 scenarios, using combinations of four collector area values, five storage tank volumes, two collector controllers and two back-up burner system configurations. The analysed parameters are the solar fraction (ratio between the solar heat to the total heat used by the system) and the collector yield (collected energy per unit of collector area). Storage volume is represented as residence time (ratio of tank volume to the chiller flow). The results are shown in Figures 2 4. The annual solar fraction for various storage sizes and collector areas when using a hysteresis controller is shown in Figure 2. As expected, the solar fraction rises as collector area increases. For a given Specific collector Area (SA) in m 2 per kw of chiller capacity, the solar fraction falls as storage volume increases. This is attributed to greater heat losses from larger storage tanks. Figure 3 shows that tank losses increase about eight times due to a 30x increase in storage volume. This stresses the importance of choosing the correct insulation for high-temperature solar-cooling systems. The effect of back-up burner positioning in the overall system layout can also be seen in the Figure 2. Parallel positioning of the back-up heat source results in a higher solar fraction, which is evident for large storage tank volumes. Analysis of component-level heat contribution shows the solar collector provides nearly similar heat to the system for series and parallel burner positioning. However, tank heat losses from a parallel positioned configuration are less, due to decoupling of the tank from the back-up heat source. For example, in the operating case with 0.615 specific collector area and 300 min storage residence time, tank heat loss for a series configuration was nearly twice that of a parallel back-up configuration. The mean tank temperature was also nearly 20 C higher for a series back-up heating configuration.

0.615 SA 1.23 SA 1.85 SA 2.46 SA 0.9 0.8 0.7 Solar Fraction [-] 0.6 0.5 0.4 Backup in parallel 0.3 Backup in series 0.2 0 50 100 150 200 250 300 350 Storage tank residence time (min) Figure 2. Solar fraction variation for different collector areas and storage volumes while employing a hysteresis controller Figure 3. Effect of storage volume on heat losses: hysteresis controller, back-up in series. Figure 4. Influence of specific collector area on collector yield: hysteresis controller, back-up in series. Figure 4 shows the effect of collector area and storage tank volume on collector yield. Collector yield falls as collector area increases for all storage tank volumes. This trend is due to the hysteresis control strategy, which places no restriction on the collector outlet temperatures. This results in higher temperature output for larger solar collector area values; the collector outlet temperature is >250 C for a specific collector area of 1.85 or above. The high collector fluid temperatures make the collector less efficient, thereby decreasing collector yield. This trend is similar to the results obtained by Eicker and Pietruschka (2009) for an evacuated-collector, single-effect chiller-based solar air-conditioning system. Reduction in collector yield is more pronounced for smaller storage tanks than for larger tanks. Larger tanks have lower collector inlet temperatures, resulting in lower collector losses.

Figure 5 shows the effect of backup heat configuration, tank volume and collector size on solar fraction while using a temperature controller. During operation of this control, a variable speed pump alters the flow rate through the collector to maintain a fixed set point temperature at collector outlet. Comparison of this control strategy with hysteresis control strategy shows higher solar fraction obtained by this controller for higher specific collector area values. This controller is able to generate solar fractions higher than 0.9. Collector outlet temperature set point values closer to chiller requirements results in higher tank outlet temperatures for the temperature controller driven systems. As a result, the backup burner is less utilized to meet the cooling load resulting in higher solar fractions. 5. Conclusions A high-temperature solar-cooling system with triple effect absorption chiller for an office building has been studied using system-level simulations. Characteristic equations approach has been used to model the performance of a triple effect chiller. Eighty test cases have been used to study the influence of collector size, storage size, control strategy and backup burner positioning on annual solar fraction. These results indicate that the solar collector outlet temperature control strategy with parallel gas backup configuration, provides higher solar fractions. Though the effect of collector area on the collector yield is similar to previous studies of single effect chiller based systems, these studies have shown tank heat losses play a more significant role in deciding annual solar fraction for high temperature solar cooling systems. 1 0.615 A 1.23 SA 1.85 SA 2.46 SA 0.9 0.8 0.7 Solar fraction [-] 0.6 0.5 0.4 Backup in parallel 0.3 Backup in series 0.2 0.1 0 0 50 100 150 200 250 300 350 storage tank residence time (min) Figure 5. Solar fraction variation for different collector areas and storage volumes while employing a temperature controller References Al-Alili, a., Islam, M.D., Kubo, I., Hwang, Y., Radermacher, R., 2012, Modeling of a solar powered absorption cycle for Abu Dhabiʼ, Appl. Energy, 93, p160 167.

Eicker, U., Pietruschka, D., 2009, ʻDesign and performance of solar powered absorption cooling systems in office buildingsʼ, Energy Build., 41, p81 91. Hang, Y., Du, L., Qu, M., Peeta, S., 2013, ʻMulti-objective optimization of integrated solar absorption cooling and heating systems for medium-sized office buildingsʼ, Renew. Energy, 52, p67 78. Kühn, A., Ziegler, F., 2005, ʻOperational results of a 10 kw absorption chiller and adaptation of the characteristic equationʼ, In: Proceedings of the 1st International Conference on Solar Air Conditioning, Bad-Staffelstein, Germany. Labus, J., Bruno, J.C., Coronas, A., 2013, ʻPerformance analysis of small capacity absorption chillers by using different modeling methodsʼ, Appl. Therm. Eng., 58, p305 313. Mateus, T., Oliveira, A.C., 2009, ʻEnergy and economic analysis of an integrated solar absorption cooling and heating system in different building types and climatesʼ, Appl. Energy, 86, p949 957. Pintaldi, S., Perfumo, C., Sethuvenkatraman, S., White, S., Rosengarten, G., 2015, ʻA review of thermal energy storage technologies and control approaches for solar coolingʼ, Renew. Sustain. Energy Rev., 41, p975 995. Puig-Arnavat, M., López-Villada, J., Bruno, J.C., Coronas, A., 2010, ʻAnalysis and parameter identification for characteristic equations of single- and double-effect absorption chillers by means of multivariable regressionʼ, Int. J. Refrig., 33, p70 78. Qu, M., Yin, H., Archer, D.H., 2010, ʻA solar thermal cooling and heating system for a building: Experimental and model based performance analysis and designʼ, Sol. Energy, 84, p166 182. Solar Energy Laboratory, University of Wisconsin, M., 2011, TRNSYS 17, ʻA Transient Simulation Programʼ. Thermax, CSIRO, 2014, ʻPrivate communication with Thermax in March 2014ʼ. Tsoutsos, T., Aloumpi, E., Gkouskos, Z., Karagiorgas, M., 2010, ʻDesign of a solar absorption cooling system in a Greek hospitalʼ, Energy Build., 42, p265 272. Acknowledgments The authors thank Thermax Limited for providing data for the triple-effect absorption chiller.