Active solar heating system with concrete plate heating analysed with dynamical thermal simulations

Similar documents
The Effects of Set-Points and Dead-Bands of the HVAC System on the Energy Consumption and Occupant Thermal Comfort

System sizing of a new central solar heating plant with a seasonal duct storage in Geneva

ANNUAL ENERGY PERFORMANCE OF SOLAR THERMAL SYSTEMS IN BRAŞOV, ROMANIA

SIMULATION MODEL IN TRNSYS OF A SOLAR HOUSE FROM BRAŞOV, ROMANIA

HOW CURRENT TRENDS IN THE DESIGN OF FACADES INFLUENCE THE FUNCTIONAL QUALITY OF INTERIOR SPACES

LOW-COST LOW-TEMPERATURE HEATING WITH HEAT PUMP

Design guidelines for direct ground cooling systems in different climates

Passiv Haus Institut. Certification as "Quality Approved Passive House" Criteria for Non-Residential Passive House Buildings

SUMMER THERMAL COMFORT IN TYPICAL FRENCH RESIDENTIAL BUILDINGS: IMPACT ASSESSMENT OF BUILDING ENVELOPE INSULATION ENHANCEMENT

EUROPEAN MYTHOLOGY AND HELLENIC REALITY ABOUT ZERO ENERGY BUILDINGS

Energy-Efficient Passive House using thermal mass to achieve high thermal comfort

A STUDY ON DESIGN OPTIMIZATION OF A NEAR NET-ZERO ENERGY HOUSE

Special Features of Energy Conservation in Historical Buildings

Using passive solutions to improve thermal summer comfort in timber framed houses in South-west France

Available online at ScienceDirect. Energy Procedia 91 (2016 )

Renewable Energy for Indoor Agriculture

DESIGN AND RECOMMANDATIONS FOR DECENTRALIZED SOLAR DISTRICT HEATING SYSTEMS IN FRANCE

BUILDING DESIGN AND THERMAL INERTIA: WHEN, WHY, WHERE

STUDY OF HEATING AND COOLING SYSTEMS TO DESIGN ZERO ENERGY BUILDINGS

Dienstleistung. Certification as "Quality Approved Passive House" Criteria for Residential-Use Passive Houses

Student Modeling Competition

On the Night Heat Losses in Thermosyphon Solar Water Heaters

ZEM ds : Case studies

Energy Efficient Buildings in Germany An Introduction

NUMERICAL STUDY ON THERMAL DEPLETION OF THE GROUND AROUND A GEOTHERMAL HEAT PUMP S PROBE

Observation of Liquid-filled Window without Presence of Liquid in Test Chamber

Glazed photovoltaic-thermal component for building envelope structures

OPERATION AND CONTROL OF THERMALLY ACTIVATED SLAB HEATING AND COOLING SYSTEMS

Figure 1: Uncovered and covered PVT collectors

Available online at ScienceDirect. Energy Procedia 91 (2016 ) 20 26

LOW-ENERGY HOUSING ESTATE SUNDAYS

THERMAL MASS IMPACT ON ENERGY PERFORMANCE OF A LOW, MEDIUM, AND HEAVY MASS BUILDING IN BELGRADE

Passive house optimization for Southern Italy based on the New Passivhaus Standard

STEADY STATE AND DYNAMIC THERMOPHYSICAL PARAMETERS OF TRANSPARENT BUILDING COMPONENTS

SOLAR XXI: A Portuguese Office Building towards Net Zero-Energy Building

SOLAR ENGINEERING OF THERMAL PROCESSES

Thermal insulation of buildings and cooling demand

Passive Houses in South West Europe

INTEGRAL BUILDING AND ENERGY DESIGN OF AN OFFICE BUILDING COMPARISON OF INITIAL DESIGN IDEAS WITH MONITORED RESULTS

Case Study. The stainless steel solar façade of a highway maintenance building at Bursins, Switzerland

Optimization of Thermosiphon Solar Water Heating systems working in a Mediterranean Environment of Cyprus

Fraunhofer Gesellschaft Hansastrasse 27c, München,

F. Flourentzou Lefkosia new townhall passive bioclimatic Minergie design. Flourentzos Flourentzou: Innovation park EPFL Lausanne, Switzerland

Effect of Distance between Double Glazing on the Performance of a Solar Thermal Collector Control

ZEMedS: Case studies

THE INFLUENCE OF ENVELOPING ON ENERGETIC AND ECOLOGICAL EFFICIENCY OF PASSIVE HOUSES

Apartment building Sodastraße 40 in Ludwigshafen, DE

THERMAL MASS IMPACT ON ENERGY PERFORMANCE OF A LOW, MEDIUM AND HEAVY MASS BUILDING IN BELGRADE

The Centre for Sustainable Building (ZUB) * A Case Study

Energy Efficient Building Envelope Kiev,

Energy Audit of two Apartment Buildings in Cagliari using Energy Simulation

Potential of ventilative cooling in German residential buildings

Senior Design Project for UNO. Design of the International Studies Building: An Environmental Analysis

TRANSSOLAR. 6 th Canadian German Conference on Energy Efficiency Retrofits in Buildings. September 22, 2015 Toronto

Energy consumption and thermal comfort in a passive house built in Romania

THERMAL AND ELECTRICAL PERFORMANCES OF A NEW KIND AIR COOLED PHOTOVOLTAIC THERMAL SYSTEM FOR BUILDING APPLICATION

FEDERATION TOWER MOSCOW DIFFERENT ROOM CLIMATES UNDER ONE ROOF

Modelling Analysis of Thermal Performance of Internal Shading Devices for a Commercial Atrium Building in Tropical Climates

Computational and the real energy performance of a single-family residential building in Poland an attempt to compare: a case study

1/58 Components of solar systems

Optimization of air tightness and night ventilation for Passive houses in Italian climates under Fanger and Adaptive comfort models

Passivhus Norden 2013

The SOLCER Energy Positive House: Whole System Simulation. Phillip Jones, Xiaojun Li, Ester Coma and Jo Patterson

BASIC EUROPEAN GLAZED COLLECTORS & SOLAR DOMESTIC

Investigation of a Solar active glass facade

Simulation Assisted Monitoring of a Multi-Family House a renovation case study

Solar and Internal Gains in Low-Energy and Passive Houses

OKO House by YOUMEHESHE architects

Great Ocean Rd Ice Creamery

Passive Houses Worlswide: International Developments

ISO INTERNATIONAL STANDARD. Energy performance of buildings Calculation of energy use for space heating and cooling

Solar Home Design and Thermal Mass

EnerPHit. Criteria for Residential-Use Refurbished Buildings

CEN/TC 89 - Thermal performance of buildings and building components

Life cycle analysis of thermosyphon solar water heaters

Solar thermal heating systems in European Union

SIMULATION OF A TYPICAL HOUSE IN THE REGION OF ANTANANARIVO, MADAGASCAR DETERMINATION OF PASSIVE SOLUTIONS USING LOCAL MATERIALS

Renewables. Vacuum Tube Solar Systems. Solar Energy to the Power of

Bruck an der Mur. Project summary. Energy concept: Background for the renovation reasons

Modeling Energy Consumption Effects of Glazing

Passive House Project documentation

Solar Thermal Radiant Heating at Pohakuloa Training Area

IMPACT OF COLUMNS AND BEAMS ON THE THERMAL RESISTANCE OF THE BUILDING ENVELOPE

En partenariat avec. Chaire ParisTech "Éco-Conception des ensembles bâtis et des infrastructures" Soirée Réhabilitation, 11 mai 2009.

Solar Energy Technologies

PASSIVE HOUSE OBJECT DOCUMENTATION

In general, passive-solar components can be described by the U-value (heat loss coefficient) and

MODELLING BUOYANCY INDUCED FLOWS OF PASSIVE COOLING SYSTEMS Pedro Correia da Silva 1, Vítor Leal 1 and J. Correia da Silva 2

BUILDING ENERGY SYSTEMS

Modeling and analyzing solar cooling systems in Polysun

LOW-ENERGY BUILDING HEATING SYSTEM MODELLING

DESIGN AND USE OF RADIANT BARRIERS AS THERMAL INSULATION FOR HIGH INERTIA HOUSES IN TROPICAL CONDITIONS A CASE STUDY

2000 Antwerp, terraced house

NZEB: The new challenge of HVAC Manufacturers. ASTRO Tower (Archi Urbain)

Earth, Wind & Fire Natural Airconditioning [1] Research objectives and Methods

Assessment of the energy demand in energy-saving office buildings from the viewpoint of variations of internal heat gains

Energy Efficiency Best Practices

Introduction to basics of energy efficient building design

PBW engineering office Wahlbuhl and Günther Ingenieure

Transcription:

Active solar heating system with concrete plate heating analysed with dynamical thermal simulations Dr. D. Pahud SUPSI DCT Laboratory of Energy, Ecology and Economy, phone + 41 91 935 13 53, fax + 41 91 935 13 09, daniel.pahud@dct.supsi.ch Abstract A single family house is planned on the south side of the Alps with the objective of integrating renewable energies in the heating design. Several ways of decreasing the thermal needs of the house are analysed. They involve the building envelope, ventilation system with heat recovery and an active solar heating system coupled to the active concrete plates of the house. The dynamic simulation programme TRNSYS is used to simulate the house, the active concrete plates and the solar heating system together. Dynamic simulations are used to confirm the technical feasibility of the studied concept, to check the thermal comfort and to establish the thermal potential of the solar heating system. The effective over-cost associated with each measure is assessed, which also takes into account the increase in price of auxiliary heat. From the economic point of view, a solar heating system measure is equivalent to a solar passive measure. Introduction A single family house is planned in Tenero (south side of the Alps, Tessin, Switzerland), with the objective of integrating renewable energies into the heating design. The strategy is to decrease the thermal needs of the house, so that its concrete plates can be activated for heating purposes. A prerequisite is that the structure of the house is heavy. In particular the floors should be made of concrete plates whose thickness is about 20 cm. This is often the case in Tessin. An active plate is a concrete plate in which pipes have been fixed for the circulation of a heat carrier fluid. It is a heat emitter with a very large heat capacity, much greater than that of a floor heating system. Active concrete plates can serve as heat storage for a solar heating system. They are connected directly to the solar collectors (via a heat exchanger). The water tank storage used for hot water does not need to be enlarged, thus saving space and investment costs. This is an advantage when the space available in the house is a problem for technical utilities. A significant solar fraction of space heating and hot water demands can be reached without the need for a large water tank. Such a solution requires dynamic thermal simulations of the whole system, house included, in order to assess the feasibility of the system concept and learn about its thermal behaviour. In particular, heating is characterised by a very large thermal inertia and a low specific thermal power. It conditions the house design and its heating requirement. Dynamic system

simulations are also indispensable to check thermal comfort conditions and assess system thermal performances. They also help for the system sizing and control. Based on the house project and site climate, the main objectives of the study are to: develop a simulation tool of the solar heating system coupled to the house; establish a list of prerequisites to make active concrete plate heating possible; assess the active solar heating potential of solar collectors coupled to active concrete plates (in a climate characterised by dry and sunny weather conditions in winter); assess and compare the economic aspect of several measures devised to decrease the auxiliary energy requirements of the house. Simulation tool The dynamic TRNSYS simulation programme (Klein and al., 2000) is used to construct a thermal calculation tool. It simulates the house, the concrete active plates and the solar heating system together (Pahud and Travaglini, 2000). A simple system control concept is developed to ensure that the house temperature remains within limits for satisfactory thermal comfort (which corresponds to a maximum predicted percentage of dissatisfaction of 10%). Provided that the house can be entirely heated with active concrete plates, simulations confirmed the technical feasibility of the system concept. They showed the importance to controlling independently the active solar system from the auxiliary heater. The task of the auxiliary heater is to maintain the house temperature just above the lowest permissible values. With the solar heating system, the system control has to prevent the house temperature from exceeding the maximum tolerated values. A simplified drawing of the system design is shown in figure 1. Hot water store Auxiliary energy Hot water Solar collectors Valve Cold water Pump Valve Heat exchanger Auxiliary energy Heating with active concrete plates Figure 1 Drawing of the active solar heating system layout.

Thermal characteristics of the house The house is built on two storeys that totalise a heated floor area of 240 m 2 (external dimensions). The main façade, oriented south-southeast, has an area of 100 m 2, of which 20 m 2 are windows. The ratio between the total window area over the heated floor area is 0.14. The house lies at the bottom of a wide east-west orientated valley at an altitude of 220 m. The situation is open from the point of view of solar radiation. The annual global solar radiation on a horizontal plane is measured at 1 200 kwh/m 2. The monthly average outdoor air temperature varies between 2 and 21 C, with an average annual value of 11 C. Heating with active concrete plates differs from floor heating in the fact that pipes are fixed directly in the concrete plate and not in the light-weight concrete layer that covers it. Heat emission takes place mostly through the ceiling rather than the floor. A previous study has shown that an optimal solution is a concrete plate thickness of about 20 cm with pipes positioned in the middle (Fromentin et Sujevs, 1996). The heat transfer coefficient between the heat carrier fluid and the heated zone is in practice about 4 W/m 2 K (pipe spacing of 20 cm in the concrete). In order to make concrete plate heating possible, building envelope and active concrete plate area have to be designed so that heating is ensured with a specific thermal power of 20 30 W per square meter of active concrete plate. As a result, heating can be achieved with fluid temperatures lower than 30 C. The advantage is the auto regulation property: heat emission can be stopped or even inversed when heat gains are generated in a room. When possible, there is one more level of active concrete plate than storeys, so that every storey can be sandwiched between the active concrete plates. In the case of this house, this is not possible for the first floor. The alternative is to activate concrete walls. Thermal needs of the house can be calculated once the house envelope, the air change rate, the internal gains and the weather conditions are defined. Type 56 of the TRNSYS programme, configured to simulate the house, is used to both calculate the annual heating energy demand and the design thermal power of the heating system (the design outdoor air temperature is -2 C for heating). Thermal insulation is placed on the outside of the building envelope, in order to make the reduction of thermal bridges easier and keep the thermal mass inside. Two cases are defined; the first one, called standard, corresponds to the level of insulation which conforms to the 1988 Swiss building code 1 (SIA 380/1, 1988). The active concrete plate case is defined to make heating with active concrete plate possible. The total area of active concrete plate is, in the case of the house studied, limited to a maximum of 220 m 2. Contrary to the standard variant, a two-flow ventilation system with heat recovery is foreseen. This is also an advantage in controlling humidity problems and pollutant concentrations that arise from the air-tight envelope of a low energy house. The characteristics of the house are shown in table 1 for both cases. 1 Requirements of the building code changed in 2001. The trend is toward improved building envelopes, improved thermal comfort and lower heating energy demand.

Parameter Standard case Active concrete plate case Insulation thickness: roof / external walls 10 cm / 10 cm / 5 cm / walls and floors in contact with ground 20 cm / 15 cm / 10 cm Window U-values 2.8 W/m 2 K 1.3 W/m 2 K * Ventilation system with heat recovery No (0.4 h -1 ) Yes (0.2 h -1 ** ) Annual energy demand for space heating 72 kwh/m 2 an 28 kwh/m 2 an Heating power 8 kw 5 kw per m 2 heated area 33 W/m 2 20 W/m 2 per m 2 active concrete plate (160 m 2 ) 50 W/m 2 31 W/m 2 per m 2 active concrete plate (220 m 2 ) 36 W/m 2 23 W/m 2 * ** selective double pane window with Argon filling ; U-value including frame. the equivalent air change rate for ventilation heat losses is decreased by a factor of 2 relative to the case without ventilation system. One assumes a heat recovery factor of 2/3 with the ventilation system, and an air change rate of 0.1 h -1 caused by air infiltrations through the house envelope (0.1 h -1 + (1-2/3) x 0.3 h -1 = 0.2 h -1 ). Table 1 Thermal characteristics of the house for the two cases and corresponding annual heating demand and heating power. Dynamic system simulations In figure 2, the thermal behaviour of active concrete plate is best illustrated. The house with the active concrete plate characteristics is simulated with a solar collector area of 15 m 2 for hot water and space heating. The window area in the south-southeast façade is, as previously mentioned, fixed at 20 m 2. Passive solar gains generated in the house are shown with the dashed line. The dotted line shows the heating thermal power injected in the concrete plates which results from the circulation and cooling of the heat carrier fluid. During the last day shown in the graph (the 18 th of February), the auxiliary heater is switched on as solar gains are not sufficient to keep the house indoor air temperature high enough. Although active solar gains are injected in the concrete plates at the same time as passive solar gains are collected, the concrete plate heat emission is stopped and even inversed by these latter. It means that passive solar gains are also stored in the concrete plates although active solar gains are injected in them. This illustrates the auto-regulating thermal behaviour of active concrete plates. It should be noted that the forward fluid temperature in the concrete plate flow circuit did not exceed 30 C, whereas the return fluid temperature remained below 24 C. Another advantage of the large heat capacity of concrete plates is that injection of large active solar gains during a short period of time results in a low and constant thermal power emitted in the house.

10 indoor air temperature 25 Thermal power kw 8 6 4 2 0 passive solar gains active solar gains thermal power emitted by active concrete plates auxiliary power outdoor air temperature -2-5 day 15 day 16 day 17 day 18 day 19 February 20 15 10 5 0 Temperature C Figure 2 Dynamic thermal behaviour of active concrete plates. Passive solar gains can stop and even inverse heat emission from active concrete plates. Active solar gains injected inside the plates are emitted in the house throughout the day. Reduction of the auxiliary heating energy The case active concrete plate (see table 1) is taken as a reference for simulations. The lowest active concrete plate area (160 m 2 ) is selected. Thermal performances of the solar heating system with the greater area (220 m 2 ) barely improve. It shows that active concrete plates have to be sized primarily for space heating. In figure 3, the reduction potential of auxiliary energy for space heating is shown for both active solar heating and passive solar gains. The space heating solar fraction is defined in terms of auxiliary energy reduction. The zero solar fraction is set by the reference case. This latter is characterised by 20 m 2 of window area in the south-southeast façade and 5 m 2 of solar collector solely used for hot water.

Auxiliary heating energy kwh/m 2 year Window area in south façade m 2 20 30 40 50 30 25 20 15 10 5 0 20-30-40-50 m2 windows 5-10-15-...-40 m2 single glazed solar collectors Serie2 5 10 15 20 25 30 35 40 Solar collector area m 2 0% 25% 50% 75% 100% Space heating solar fraction Figure 3 Active and passive solar potential assessed in terms of space heating auxiliary energy reduction. The hot water solar fraction is about 65% up to a collector area of 20 m 2, and tends to increase up to 80% with a collector area of 40 m 2. Without space heating, the solar hot water system is sized for 5 people (1 m 2 per person). It can be seen from figure 3 that 5 m 2 of additional solar collectors is equivalent to 25 30 m 2 of additional windows in the south façade. Simulations with unglazed solar collectors show the same equivalence with 10 m 2 of additional solar absorbers. These equivalences allow us to select the most advantageous option in relation to its respective cost. However the economic criterion is not the only one and the final choice is conditioned by factors such as architecture, durability, maintenance, etc. Nevertheless, the auxiliary heat reduction potential is greater with an active solar heating system. Over-cost estimation Over-cost, or more precisely additional investment estimation for each measure is required for an economical analysis. Considering the great variability of cost estimation, results presented in this study have to be considered with prudence. Lifetime associated to each measure is based on indications given in the Swiss Ravel programme (Ravel, 1997). The starting point for evaluating a combination of measures is the standard case (see table 1), whose annual heating demand is calculated to 72 kwh/m 2 year. The heating energy demand is covered by an oil burner whose annual mean efficiency if fixed to 85%. Hot water demand is covered by an electric boiler. The electric energy consumed by the electric hot water boiler amounts to 18 kwh/m 2 an. The space heating and hot water energy index of the standard house is calculated to 103 kwh/m 2 an.

The auxiliary energy saving measures are evaluated in the following order: A. Improved building envelope and ventilation system. The ventilation system is without heat recovery. The main functions of the ventilation system are to guarantee a good indoor air quality and control humidity related problems. B. Heat recovery on the ventilation system. The measures A + B correspond to the active concrete plate house (see table 1). C. Solar Kit for hot water heating. Hot water is heated with 5 m 2 of single glazed solar collectors. D1. Solar collectors coupled to active concrete plates. The collector area is increased from 5 m 2 to 15 m 2 to satisfy space heating requirements as well (see system layout in figure 1). D2. Additional windows. Instead of increasing the solar collector area (D1 measure), the window area in the south-southeast façade is increased from 20 to 40 m 2. According to practical experience, the cost of active concrete plates is equivalent to that of a floor heating system (Cornu, 2000). In consequence, no over-cost is counted for active concrete plates. In figure 4, additional investment for each measure is shown in relation to the energy index of the house. 200 Additional investment [CHF/m 2 ] 160 120 80 40 D1: active solar for space heating and hot water D2: window area increase C: "solar Kit" for hot water B: ventilation heat recovery A: house envelope 0 0 20 40 60 80 100 Space heating and hot water energy index [kwh/m 2 an] Figure 4 Additional investment per square meter of heated floor area for each measure in relation to space heating and hot water energy index. The total construction cost of a house is about 2 000 CHF/m 2 (CHF is Swiss francs). The sum of the additional investments, performed up to the two variants D1 and D2, remains inferior to 10% of the total construction cost. The over-cost associated to the active solar heating system (hot water and heating) is less than 5%.

Effective over-cost Each measure leads to a reduction of auxiliary energy, and thus decreases the energy that has to be purchased every year. The effective over-cost takes into account auxiliary energy savings during the lifetime of a measure. It is formed by the annual capital cost of the corresponding additional investment (annuity), from which is subtracted the annual cost of the auxiliary energy saved. It should also contain the maintenance cost, but is not taken in consideration in this study. As the price of auxiliary energy is increasing with time, the annual saving is also increasing. The mean annual saving becomes more important if the lifetime of a measure is longer. Inflation rate, interest rate and increases in the cost of energy were taken according to recommendations given in the Swiss Ravel programme (Ravel, 1997). The mean effective over-cost is shown in table 2 for each measure. It is calculated according to three scenarios, depending on energy cost increase (electricity and oil). The maximum scenario corresponds to the largest increase rates, which, of course, tends to make the measures economically more favourable. No subvention, tax reduction or CO 2 tax were taken into account in the calculations. Measure / variant effective overcost in CHF/an Minimum scenario Average scenario Maximum scenario A : envelope 470 200-170 B : ventilation heat recovery 260 230 190 C : glazed solar kit (hot water) 60-50 -160 D1 : active solar heating 720 680 620 D2 : additional windows 730 690 650 Total variant 1 (A+B+C+D1) 1 510 1 060 480 Total variant 2 (A+B+C+D2) 1 520 1 070 510 NB : these numbers have to be considered with prudence. They were obtained with constant inflation, interest and energy increase rates, and thus calculated with exponential functions during time periods up to 30 years (house envelope measure). Table 2 Effective over-cost for each measure, taking into account three possible scenarios for the increase in the cost of energy. Calculated values in table 2 have to be considered with prudence. In particular, they only show the economic aspect. They do not reflect advantages such as improvement of thermal comfort with better house envelopes, indoor air quality and humidity problem reduction with a ventilation system, the higher mean indoor air temperature with an active solar system, etc. Auxiliary energy should further be reduced with a more sophisticated system control, which would, for example, take into account weather forecast.

Conclusion The window area enlargement measure (D2) has an additional investment cost which is about the same as the active solar heating measure (D1). Although the auxiliary energy reduction of measure D2 is significantly lower than measure D1, their respective effective over-cost is about the same. This results comes from the lifetime of windows (25 years) which is assumed to be longer than solar collectors (20 years). These measures (D1 and D2) are also the most expensive as they come last on the list of interventions. However, the sum of the effective over-cost for each of the two variants is reasonable, and amounts to about 100 CHF per month. The solar collector measure gives a greater flexibility to the architecture in the sense that the constraint on the window area to be inserted in the south façade is removed. The most advantageous measure is the solar kit for hot water. It also has the advantage of not depending on the realisation of another measure, such as for example the improvement of the house envelope. This is not the case for an active solar heating system coupled to active concrete plates, although this solution significantly reduces the auxiliary heat demand of a low energy house (from 30 to 60%). Acknowledgements The Swiss Federal Office of Energy is acknowledged for its financial support. Mr. Cornu is also cordially acknowledged for his interest in this study and his constructive discussions. References Recommandation SIA 380/1 (1988) L énergie dans le bâtiment. Société suisse des ingénieurs et des architectes, Zurich, Suisse. Fromentin A., Sujevs D. (1996) Comportement thermique dynamique d une maison solaire à stockage intégré. Rapport final, Office fédéral de l énergie, Berne, Switzerland. Klein S. A. et al. (2000) TRNSYS. A Transient System Simulation Program. Version 15, Solar Energy Laboratory, University of Wisconsin, Madison, USA. Pahud D. et Travaglini G. (2000) Etude d une maison solaire active avec stockage en dalles au Tessin Rapport final, Office fédéral de l énergie, Berne, Suisse. (http://www.leee.dct.supsi.ch/urec.htm) Ravel (1997) Impuls Compact Ravel è conveniente. Guida pratica per i calcoli della redditività. Pubblicazioni Ravel, n 724.397.42.01i, UFCO, Svizzera. Cornu C. (2000) Private communications.