CHAPTER 13 GROUNDING AND BONDING

Similar documents
SECTION GROUNDING AND BONDING

SECTION GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY

A. All materials shall be tested and listed by an OSHA approved Nationally Recognized Testing Laboratory (NRTL).

CHAPTER 11 CONDUITS AND FITTINGS

CONDUITS AND FITTINGS

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

Public Works Division Lighting District Supplemental Specifications For Solar School Flashing Beacon Installation March 2007

(Condensed from National Electric Code)

Please check with your local inspection authority for any additional requirements before installation.

The University of Texas at Austin September 30, 2011

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

UNDERGROUND SERVICES - GENERAL SERVICE AND MULTI-UNIT RESIDENTIAL

thermoweld The Contractors Choice GREAT PRODUCTS GREAT SERVICE GREAT PEOPLE

ELECTRICAL SERVICE UPGRADE RESIDENTIAL AND COMMERCIAL QUICK INFORMATION REFERENCE

OVERHEAD SERVICE. Table of Contents - Section 400

DESIGN GUIDELINES WIRING AND CONDUITS PAGE 1 of 7

UNDERGROUND SERVICES SECONDARY

Specifications for Residential Underground Electric Service Installation

WOOD POLE SPAN WIRE SIGNAL SYSTEMS

2015 Code Rollout Meeting Q & A

SECTION SUBSTATION BUS ASSEMBLIES ERGLE SUBSTATION

Dimensions in Millimeters (Inches) A Bushing Diameter. B Bushing Height

EFFECTIVE DATE: November 1, 2011, unless a later date is cited at the end of a section. [ NMAC - Rp,

Standard of Practice - Campus Electrical Distribution System

OVERHEAD SERVICES - RESIDENTIAL & GENERAL SERVICE. See Chapter 3, Section 3.01 for more information about point of entrance (POE).

Douglas County Traffic Signal Installation Guidelines (January 2013)

UNDERGROUND SERVICES (RESIDENTIAL) SINGLE FAMILY RESIDENTIAL, DUPLEXES, OR TOWNHOUSES

CHAPTER 12 HANDHOLES, PULLING VAULTS, AND JUNCTION BOXES

TEMPORARY METER POLE INSTALLATION

Effective June, Eaton-Durham Model # UTRS223ACH. Siemens, Model # SUAS877-PG. (or Landis & Gyr # UAS877-PG) Milbank. Model # U1980-O.

6. SECONDARY SERVICES (under 600 volts) 6.1 AVAILABILITY For the electrical characteristics of available secondary services see Section 3.4.

HANDHOLES, PULLING VAULTS AND JUNCTION BOXES

Section 2: Underground

DOWNTOWN UNDERGROUND NETWORK SECONDARY SERVICES GUIDELINES

SECTION OUTLET, PULL, AND JUNCTION BOXES

This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update.

PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES

EFFECTIVE DATE: July 1, 2008, unless a later date is cited at the end of a section. [ NMAC - Rp,

TS 804 CABLES TABLE OF CONTENTS TRAFFIC SIGNAL EQUIPMENT POLE WIRING DIAGRAM LOCATIONS WITH CENTRE MEDIANS

SECTION INSULATED WIRE AND CABLE

2003 International Residential Code ELECTRICAL PROVISIONS ONLY October 2005 EDITORIAL CHANGES SEVENTH PRINTING

UNIFIED FACILITIES GUIDE SPECIFICATIONS

CONSOLIDATED EDISON COMPANY OF NEW YORK, INC Van Dam Street Long Island City, NY ELECTRIC METER SHOP DEPARTMENT

SECTION P -- CABLE VAULT AND CABLE ENTRANCE FACILITY

Revisions for the 2011 National Electrical Code - Part 2

CONSTRUCTION SPECIFICATION FOR INSTALLATION OF POLES

CONSTRUCTION SPECIFICATION FOR TRAFFIC ACTUATION EQUIPMENT

WIRING RULES AND REGULATIONS OF TOMBIGBEE ELECTRIC POWER ASSOCIATION

Specifications for Residential Overhead Electric Service Installation

OKLAHOMA DEPARTMENT OF TRANSPORTATION SPECIAL PROVISIONS FOR BUY AMERICA

TS 805 POLES TTS CONSTRUCTION SPECIFICATION FOR POLE INSTALLATION TTS MATERIAL SPECIFICATION FOR STEEL POLES BASE MOUNTED

Details of technical leaflets/write-up on various pieces of equipment.

General Symbols, Ducts and Cables

THE OFFICIAL TRADE JOURNAL OF BICSI

PATHWAYS FOR COMMUNICATIONS SYSTEMS

DIVISION 26 ELECTRICAL Electrical Power Conductors and Cables

Foundation Specifications

B. Insulated Conductors: Stranded copper wire, green or green with yellow stripe insulation, insulated for 600 V, and complying with UL 83.

1. Telecommunications mounting elements. 2. Backboards. 3. Telecommunications equipment racks and cabinets. 4. Grounding.

TS 801 ELECTRICAL WORK - GENERAL TABLE OF CONTENTS

ELECTRICAL SAFETY Information Bulletin

Special Specification 6292 Radar Vehicle Detection System for Signalized Intersection Control

FOR ALL STAKEHOLDERS TO HAVE A SUCCESSFUL PROJECT

UNM IT/Telecommunications Guide Specification Communications Underground Ducts, Raceways and Structures /27/06

ITEM L-119 AIRPORT OBSTRUCTION LIGHTS DESCRIPTION

CONSTRUCTION STANDARDS SECTION CS 15 STREET LIGHTING

Specifications for Residential Overhead Electric Service Installation

County of Sacramento Standard Construction Specifications January 1, 2008 TECHNICAL PROVISIONS

Basic Requirements for Residential Electrical Installations

Welcome to Douglas County PUD

2008 NEC Guide Lines for Home Owner Doing Electrical Work on their Property

B. Provide a complete conduit system with associated couplings, connectors, and fittings.

CONSTRUCTION SPECIFICATION FOR INSTALLATION OF CABLE

Basic Service. This Section provides information regarding a. Introduction

Practical Guide To Electrical Grounding

This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update.

ELECTRIC METERING GENERAL

Installation of CSST Gas Piping Systems

CONSTRUCTION SPECIFICATION FOR FOOTINGS AND PADS FOR ELECTRICAL EQUIPMENT

Building Attachments and Services

Underground Residential Distribution (Specifications for Installation) PES March 2008 Spec 11

4. POINTS ON SWITCH AND CIRCUIT BREAKER PLATFORM GROUNDING.

NEC 2014 Code Changes

SECTION 4 - SECONDARY CONSTRUCTION OVERHEAD TABLE OF CONTENTS

Unit Price Labor. INSTALL 138KV DISCONNECT SWITCH WITH MOTOR OPERATOR AND AUXILIARY SWITCHES ON EXISTING STRUCTURE 1 ea.

SECTION 1000 ELECTRICAL SECTION 1001 ROADWAY STREET LIGHT CONSTRUCTION DESCRIPTION

INSTALLATION INSTRUCTIONS FOR ELECTRICAL CONTRACTORS

SECTION 600: STREET LIGHTING & TRAFFIC SIGNALS

TESTING PTE EARTHING

8.1.2 Under no circumstances shall a service entrance be left unmetered. Notify the Company if an unmetered service is encountered.

St. Clair County Electrical Code Regulations

1. Approved Manufacturers: Carlon Electrical Products, Cantex, or approved equal.

The Equipotential Plane in New Livestock Facilities

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 5/12/10 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

Part VI - Traffic Engineering Electrical & Pavement Markings

SERVICE ENTRANCES. OPPD S Electrical Service Designer (ESD) shall designate the Point Of Entrance.

TABLE OF CONTENTS CHAPTER 2 WIRING AND PROTECTION CHAPTER 1 GENERAL RULES... 19

Grounding Principles. The need to ground! Definitions. Introduction. Grounding Codes and Standards. 2 Ph:

SECTION WIRE AND CABLE Raceways and Conduit Motor Power and Control Wiring.

Foundation Manual. Part Number: Version: Updated: July 5, S. Meadows Pkwy. A-9, #329 Reno, NV

Transcription:

GROUNDING AND BONDING CHAPTER 13 GROUNDING AND BONDING Grounding and bonding must be in accordance with Article 250 of the National Electrical Code (NEC). Bonding is defined in the NEC as the permanent joining of metallic parts required to be electrically connected. In a traffic control signal or lighting system, the term is used to describe the electrical and mechanical connection of conduit, metal poles, cabinets, and service equipment. Grounding is defined in the NEC as a conducting connection, whether intentional or accidental, between an electrical circuit or equipment and the earth, or to some conductive body that serves in place of earth. By directing current along a path to earth, bonding and grounding reduces, but does not eliminate, the danger of unwanted electrical current reaching the surface of equipment, causing damage and electrical shocks to anyone working on the system. For traffic control signal systems grounding electrodes (ground rod electrodes) are installed at all service points, in the handhole adjacent to the mast arm pole bases, and within pedestal concrete foundations as specified in the contract documents. All MnDOT service equipment pads (signals and lighting) must have two grounding electrodes installed. Additionally, any rebar grids must also be bonded to ground. Figure 13-1: Bonding Figure 13-2: Grounding Figure 13-3: Grounding Electrode System 13-1

13.1 Connections Rigid steel conduit runs are tied together by screwing each length of conduit together so that the ends of the conduit butt or come together for the full circumference to provide an electrically bonded and grounded connection throughout the entire length of the conduit run. 13.1.1 GROUNDING WIRE Rigid steel conduit runs are bonded together in handholes by a solid 6 AWG bare copper wire attached to the lug on thread bushings which are installed on the open ends of conduit at the end of the run. A 6 AWG stranded green insulated conductor is also pulled through rigid steel conduit as indicated in the contract documents. In pole bases, rigid steel conduit and grounding conductors are tied to the grounding stud provided in the metal base utilizing an active clamping grounding lug with mounting tang. On an equipment pad, the ground rod and grounding connection is located in the signal service cabinet. Bonding of all ground rod electrodes to the 6 AWG stranded green insulated ground wire must be accomplished by exothermic welding. Service equipment is tied to a ground rod if the service is not on the equipment pad (see Figure 13-8). Figure 13-4: Steel Conduit Figure 13-5: Conduit in Handholes Figure 13-6: Grounding Stud Figure 13-7: Green Insulated Ground Wire Figure 13-8: Ground Rod Tie All new traffic control signal systems must have a 6 AWG green insulated stranded grounding wire installed from the signal cabinet to each pole base. This grounding wire may be daisy chained from signal pole base to signal pole base. Consult the field wiring diagram for details. Each signal pole must have its own ground rod located in the handhole adjacent to the signal base. A 6 AWG 13-2

green insulated stranded grounding wire must run from the ground rod to the pole base. The ground wire coming from the ground rod will be spliced to the grounding wire running to the signal cabinet and to the 6 AWG grounding wire running to the ground lug on the transformer base using exothermic welding. 13.1.2 EQUIPMENT GROUND BUS The equipment ground bus must be grounded to the source of power ground rods with a 6 AWG green insulated stranded ground wire. If cracks or pavement joints are encountered, refer to Standard Plate No. 8130 for complete details of installation requirements. When ground rod electrodes are required to be installed outside of the foundation and rock is encountered preventing the ground rods from being installed vertically, follow the installation requirements for rod electrodes in accordance with the NEC. If it is not possible to install ground rods according to the installation requirements of the NEC, install plate electrodes in accordance with Standard Specification 3818 as directed by the engineer. As presented in Figure 13-11, a 6 AWG equipment grounding wire must be properly connected from the equipment ground bus in the cabinet to the neutral bonding bar of the service equipment and to each incoming RSC conduit grounding bushing lug if RSC conduit is used. A separate 6 AWG green insulated grounding conductor is run through the conduit system and used for equipment ground purposes. The separate 6 AWG green insulated conductor is used in both non-metallic conduit (NMC) and rigid steel conduit (RSC) systems. Oxide inhibitor agent for use on electrical conductors must be applied to all 6 AWG grounding connections after both assembly and final connection. Figure 13-7: Grounding Wire in Pole Base Figure 13-8: Ground Wire in a Signal Cabinet Figure 13-9: Oxide Inhibitor Agent 13-3

When existing conduit is incorporated into a new system, the contractor must furnish and install new bonding and grounding jumpers and new threaded conduit bushings on open ends of in place conduit as directed by the engineer. Additional details on this subject are in the contract documents and must be reviewed. Standard Specifications 2545.3.R and 2565.3.D.4.b provide additional guidance. 13.2 Direct Buried Lighting Cable The direct buried lighting cable must be 4 conductor 4 AWG (4/C 4 AWG) and meet the specifications in the contract documents. Install supplemental ground rod electrodes in locations specified in the contract. Provide two grounding electrodes at the service points and every other light pole foundation and at the light pole foundation located at both ends of a run, unless otherwise specified in the contract. See Standard Specification 2545.3R for additional information regarding bonding and grounding. Figure 13-10: Direct Buried Lighting Cable The direct buried lighting cable must be grounded and bonded as follows: The copper shield must be terminated on the equipment ground bus in the service cabinet. The green insulated grounding conductor must be terminated on the equipment ground bus in the service cabinet. Figure 13-11: Proper Ground Connection in a Lighting Service Cabinet In the light pole base, the copper shield and grounding conductor must be bonded together by drilling the copper shielding and placing it underneath the grounding lug before bolting the assembly to the pole base. The grounding conductor should then be terminated in the active clamping grounding lug. Oxide inhibitor agent must be applied to all grounding connections after both assembly and final connection. Figure 13-12: Grounding Connection 13-4

13.3 Chapter 13 Resources Article 250 of the National Electrical Code (NEC) MnDOT Standard Specifications for Construction 2545.3.R, 2565.3.D.4.b and 3818 Standard Plate 8130 13-5

This Page Intentionally Left Blank 13-6