Testing in Accordance with SFM Standard 12-7A-1: Fire Resistive Standard for Exterior Wall Siding and Sheathing

Similar documents
Common Applications: FRT plywood Type X Gypsum wall board

WFCi Report # Conducted For: Supress Products LLC. 5/8 Supress Sound-Engineered Drywall SED58410C; U305 Design

Image courtesy of KTGY, Inc. ENGINEERED FOR FIRE CODE COMPLIANCE AND DESIGN FLEXIBILITY

Changes to California s Building Code for Construction in Wildfire Prone Areas: Impact on Wood and Wood-based Materials

WILDLAND URBAN INTERFACE (WUI) PRODUCTS

Joint Evaluation Report ICC-ES (800) (562)

REPORT HOLDER: LOUISIANA-PACIFIC CORPORATION 414 UNION STREET, SUITE 2000 NASHVILLE, TENNESSEE EVALUATION SUBJECT:

Specifications. Materials and Fabrication. Physical Properties. Environmental Impact. Sizes. Installation - General Requirements.

A. Meet at Project site <insert number> days before starting installation.

Shipping Container R&D Test Plan

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: SIDING REPORT HOLDER: SHAKERTOWN 1992, INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: CLAY ROOF TILES REPORT HOLDER: BORAL ROOFING LLC

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: PLASTIC SIDING REPORT HOLDER: CERTAINTEED CORPORATION

ESR-1365 Reissued March 2014 This report is subject to renewal April 1, 2015.

LP SmartSide Strand Substrate Treated-Engineered-Wood Lap & Panel Siding Louisiana-Pacific Corporation Revised December 2, 2016

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE RUBBER SHAKES REPORT HOLDER: DAVINCI ROOFSCAPES, LLC

REQUESTED BY : Atlas Roofing and Flooring PO Box Queenswood CONTRACT No : FTC12/088. AUTHOR(S) : K. van Dyk. DATE : 13 September 2012

REPORT HOLDER: OMEGA PRODUCTS INTERNATIONAL, INC CALIFORNIA AVENUE CORONA, CALIFORNIA EVALUATION SUBJECT:

REPORT HOLDER: PAREX USA, INC EAST LA PALMA AVENUE, SUITE 250 ANAHEIM, CALIFORNIA EVALUATION SUBJECT:

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: MODIFIED BITUMINOUS SHEET ROOFING REPORT HOLDER:

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: SHOP-APPLIED WOOD COATINGS SECTION: SHEATHING REPORT HOLDER:

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL ROOF PANELS REPORT HOLDER: METAL SALES MANUFACTURING CORPORATION

REPORT HOLDER: THE DOW CHEMICAL COMPANY 1501 LARKIN CENTER DRIVE MIDLAND, MICHIGAN EVALUATION SUBJECT:

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: 3A COMPOSITES USA INC.

LP OSB Sheathing & Structural 1 Sheathing

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION SECTION: WATER-RESISTIVE BARRIERS/WEATHER BARRIERS

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER:

INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS UNIFORM EVALUATION SERVICES EVALUATION CRITERIA FOR

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: PLASTIC SIDING REPORT HOLDER: DERBY BUILDING PRODUCTS INCORPORATED

Magnum Board Section Digicon Information Inc. Page 1

FIRE ISSUES IN ENGINEERED WOOD COMPOSITES FOR NAVAL WATERFRONT FACILITIES 1

TEST REPORT. Fire resistance load-bearing test of a 136mm thick Ozone Panels wall system tested in accordance with AS

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: FIBER CEMENT SIDING REPORT HOLDER: RIEDER FASERBETON ELEMENTE GmbH

application instructions

Gold Bond BRAND Gypsum Sheathing

TEST REPORT. Bushfire resistance test of an external wall system to BAL A40 in accordance with AS EWFA Report No:

Innovating Continuous Exterior Insulation. Theresa A. Weston, PhD. 1

REPORT HOLDER: RARE MANUFACTURING INC A AVENUE SURREY, BRITISH COLUMBIA V4N 4P2 CANADA EVALUATION SUBJECT: IRONWOOD SHAKE

Approved Manufacturing Location Boral Composites Inc.

BRE Global Test Report

CRITERIA FOR TESTING IMPACT & NON IMPACT RESISTANT BUILDING ENVELOPE COMPONENTS USING UNIFORM STATIC AIR PRESSURE

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: ROOFING AND SIDING PANELS REPORT HOLDER: KINGSPAN INSULATED PANELS, INC.

IAPMO ES. Cover Sheet. Evaluation Criteria of. COLD-FORMED STEEL or WOOD FRAMED / STEEL-SHEATHED SHEAR WALLS

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: STRUCTURAL PLASTICS REPORT HOLDER: HB&G BUILDING PRODUCTS, INC.

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: STRUCTURAL PANELS REPORT HOLDER: FOUR SEASONS SOLAR PRODUCTS

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: WATER RESISTIVE BARRIERS/WEATHER BARRIERS REPORT HOLDER: PAREX USA, INC.

Trusted ICC ES DIVISION: 07 LTD. PLASTI FAB CANADAA PLASTISPAN. Look. Conformity! Evaluation. ICC-ES Evaluation

ESR-2894 Reissued April 2014 This report is subject to renewal April 1, 2016.

REPORT HOLDER: FEROOF CO., LTD SEONWON LI SEONNAM MYEON SUNGJU GUN KYEONGSANGBUK DO SOUTH KOREA EVALUATION SUBJECT:

Questar ThermWise Duct Technical Specifications

LP SmartSide Perfection Shingle

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: DEMILEC (USA) INC.

Use of Coatings to Improve Fire Resistance of Wood

General. Moisture. Secondary Water-Resistive Barrier. Storage. Gaps & Sealants. Stud Spacing. Flashing, Windows, Doors & Openings

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: PLASTIC SIDING REPORT HOLDER: KP BUILDING PRODUCTS

ICC-ES Evaluation Report. ESR-3102 Reissued July 1, 2013 This report is subject to renewal August 1, 2015.

ANSI/APA PRS Standard for Performance-Rated Structural Insulated Panels in Wall Applications

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: PARKLEX USA

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: CITADEL ARCHITECTURAL PRODUCTS, INC.

REPORT HOLDER: HUBER ENGINEERED WOODS, LLC ONE RESOURCE SQUARE DAVID TAYLOR DRIVE, SUITE 300 CHARLOTTE, NORTH CAROLINA 28262

December 3, 2012 PARTIES INTERESTED IN INTUMESCENT FIRE-RESISTANT COATINGS FIELD-APPLIED TO PREFABRICATED WOOD I-JOISTS

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: DEMILEC (USA) INC.

Eclipse Energy Guard. Product Information & Installation Manual General Installation Requirements

Originally Issued: 11/04/2016 Revised: 11/28/2017 Valid Through: 11/30/2018

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER:

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: PLASTIC SIDING REPORT HOLDER: GENTEK BUILDING PRODUCTS, INC.

EMPIRE SHAKE, EMPIRE PLUS SHAKE, AND EMPIRE SLATE POLYOLEFIN COMPOSITE TILES

WOOD USE IN NONCOMBUSTIBLE BUILDINGS

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: FUNDERMAX GMBH

RAY-CORE Structural Insulated Roof and Wall Panels

Robert S. Kiefer (ext ) James F. Smith (ext )

Originally Issued: 03/21/2014 Revised: 04/12/2018 Valid Through: 03/31/2019

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: ARCONIC ARCHITECTURAL PRODUCTS, LLC

REPORT ON COMPARATIVE AIR LEAKAGE PERFORMANCE:

CHAPTER 26 PLASTIC SECTION BC 2601 SECTION BC 2603 GENERAL FOAM PLASTIC INSULATION

July 23, 2010 PARTIES INTERESTED IN REFLECTIVE FOIL INSULATION

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: RHINO LININGS CORPORATION

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: DEMILEC (USA) LLC

ESR ICC Evaluation Service, Inc. Issued November 1, 2003 This report is subject to re-examination in one year.

TEST PROCEDURE FOR AIR PERMEABILITY TESTING OF RIGID, DISCONTINUOUS ROOF SYSTEMS

Originally Issued: 05/03/2013 Revised: 06/06/2016 Valid Through: 05/31/2017

DIVISION: FINISHES SECTION: FIRE RETARDANT COATINGS REPORT HOLDER: FIRE RETARDANT COATINGS OF TEXAS, LLC

Engineering Analysis of NFPA 285 Tested Assemblies

Appreciating the Nuances of Structural Defect Issues and Related Legislation

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: WOOD I JOISTS REPORT HOLDER: LOUISIANA PACIFIC CORPORATION

BRE Global Classification Report

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: TRESPA NORTH AMERICA, LTD.

ICC-ES Evaluation Report Reissued November 2014 This report is subject to renewal November 2016

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION SECTION: AIR BARRIERS REPORT HOLDER:

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: DEMILEC (USA) INC.

REPORT HOLDER: GEORGIA PACIFIC GYPSUM LLC 2861 MILLER ROAD DECATUR, GEORGIA EVALUATION SUBJECT: DENSELEMENT BARRIER SYSTEM

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: STRUCTURAL PANELS REPORT HOLDER: ENERCEPT, INC.

Code Compliance Research Report CCRR-0266

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: FLEXIBLE FLASHINGS REPORT HOLDER: HUBER ENGINEERED WOODS, LLC

EcoTouch Insulation with PureFiber Technology

Relationship between Moisture Content and Mechanical Properties of Gypsum Sheathing Phase 2 Research

June 1, 2010 PARTIES INTERESTED IN EVALUATION REPORTS ON REFLECTIVE FOIL INSULATION

Transcription:

Testing in Accordance with SFM Standard 12-7A-1: Fire Resistive Standard for Exterior Wall Siding and Sheathing LP FlameBlock Fire-Rated OSB Sheathing (7/16 Minimum Nominal Thickness) with Various Claddings: SmartSide Lap and Panel Siding (Precision Series - strand substrate) ½ Cedar Shingles PN# 10023 Report No. 10023.1 Rendered to: LP CORPORATION TESTING COMPLETED: MAY 4, 2010 ISSUE DATE: MAY 28, 2010

TABLE OF CONTENTS INTRODUCTION... 3 SUMMARY OF THE TEST METHOD... 4 SAMPLE DESCRIPTION... 5 TEST RESULTS... 7 CONCLUSION AND EXTENTION OF RESULTS... 8 SIGNATURES... 9 REVISION SUMMARY... 10 APPENDIX A: SAMPLING REPORT... 11 APPENDIX B: TEST PICTURES (from representative tests)... 13 Kelso, Washington Page 2 of 20

INTRODUCTION This report documents the CSFM 12-7A-1 testing of representative exterior wall assemblies constructed with LP FlameBlock fire-rated OSB sheathing and two types of wall claddings: ½ cedar sidewall shingles and LP Precision Series Lap siding. The testing of the LP FlameBlock with Precision Series lap siding was originally reported under WFCi Report No. 10023, dated April xx, 2010. The purpose of this testing was to evaluate the SFM 12-7A-1 fire test performance characteristics of representative wall assemblies constructed with the client s LP FlameBlock fire-rated OSB sheathing as a base component in order to demonstrate conformity with Paragraph 704A.3.1 the California Building Code, Chapter 7A, Section 704A requirements. Two test series were performed: 1. Test Series No. 1 was originally reported under WFCi Report No. 10023, and covered the testing of a wall assembly incorporating LP FlameBlock fire-rated OSB sheathing and LP Precision Series Lap Siding (strand based). The lap siding selected for this testing was considered to define a worst-case condition for wall assemblies clad with Precision Series strand-based siding. The testing was also deemed to represent the expected fire test performance of LP Precision Series panel siding installed over FlameBlock. 2. Test Series No. 2 covers what is deemed to be an example of a severe-case wall assembly condition employing the use of cedar sidewall shingles having a ½ butt thickness as exterior cladding over the LP FlameBlock OSB sheathing product. The ½ butt thickness (referred to as 4/2 by the cedar shingle industry) was selected as representative of the heaviest shingle thickness in order to develop a worst-case testing scenario for cedar sidewall shingle installations over FlameBlock sheathing. This testing is intended to cover cedar shingle siding applications with a shingle butt thickness of ½ or less, as well as plain bevel cedar siding of unlimited widths. Cedar shakes are not covered. Kelso, Washington Page 3 of 20

SUMMARY OF THE TEST METHOD The CSFM 12-7A-1 test methodology incorporates a protocol utilizing a 4 wide x 39 long diffusion burner positioned at the base of a 4 wide by 8 high wall construction with the fire exposure conducted at 150 kw for a period of 10 minutes. After fire exposure, the wall specimens are observed for a 60-minute post-exposure period for signs of progressive combustion and/or flame penetration through to the unexposed side of the assembly. Signs of flame penetration at any time during the test, or presence of glowing combustion at the end of the 60-minute post exposure period constitute a failure to meet the conditions of acceptance. Tests are conducted in triplicate for conformity with the California Building Code, Chapter 7A requirements. Excerpted from CSFM 12-7A-1: Fire Resistive Standards for Exterior Wall Siding and Sheathing: (a) Application. The minimum design, construction and performance standards set forth herein for exterior wall siding and sheathing are those deemed necessary to establish conformance to the provisions of these regulations. Materials and assemblies that meet the performance criteria of this standard are acceptable for use in Very High Fire Hazard Zones as defined in California Building Code, Chapter 7A. (b) Scope. This standard determines the performance of exterior walls of structures when exposed to direct flames. (i) Conduct of Tests. 1. Airflow. The wall test shall be conducted under conditions of ambient airflow. 2. Number of tests. Conduct the tests on three replicate wall assemblies. 3. Burner output verification. Without the wall assembly in place, adjust the burner for 150 ± 8 kw output. 4. Burner configuration. Center the burner relative to the width of the cladding-wall assembly and 0.75 in. (20 mm) from the wall. The distance from the floor to the top of the burner shall be 12 in. (300 mm). 5. Procedure i) Ignite the burner, controlling for constant 150 ± 8 kw output. ii) Continue the exposure until flame penetration of the cladding-wall assembly occurs, or for a 10-min period. iii) If penetration does not occur, continue the test for an additional 60 min or until all combustion has ceased. An infrared thermometer has been found to be useful to detect the increase of temperature on the back side of the sheathing and an aid to identify the areas of potential combustion. Conditions of Acceptance: 1. Absence of flame penetration through the wall assembly at any time. 2. Absence of evidence of glowing combustion on the interior surface of the assembly at the end of the 70-min test. Kelso, Washington Page 4 of 20

SAMPLE DESCRIPTION The wall assemblies were constructed by WFCi personnel, and were prepared in accordance with the 12-7A-1 test standard. Assembly and fastening details of the FlameBlock sheathing and indicated cladding types were consistent with the manufacturer s installation instructions. Test Series No. 1 Sheathing: LP FlameBlock 4 x8 Fire-Rated OSB sheathing, 7/16 minimum nominal thickness (reference ICC ESR-1365) o Minimum Pyrotite thickness of 0.06 ) applied to fiberglass mat o Pyrotite laminate applied to one face of OSB sheathing [exposed (fire) side] Cladding: SmartSide Precision Series Lap siding (limited to strand substrate) Test Series No. 2 Sheathing: LP FlameBlock Fire-Rated OSB sheathing, 7/16 minimum nominal thickness (reference ICC ESR-1365) o Minimum Pyrotite thickness of 0.06 applied by direct process to OSB sheathing o Pyrotite applied to one face of OSB sheathing [exposed (fire) side] Cladding: Cedar Sidewall Shingles, ½ butt end thickness (installed in accordance with industry standard/manufacturer s instructions) Manufacturing of the LP FlameBlock sheathing was witnessed by Progressive Engineering, Incorporated (PEI), as attested to in the PEI Product Sampling Report included in Appendix A. The test material was received at the laboratory carrying the marking of the inspection agency. Conditioning: Prior to assembly, the FlameBlock sheathing, lap siding and cedar sidewall shingles were conditioned to equilibrium moisture content at 70±5 F and 50±5% relative humidity. The test assemblies were tested shortly after construction. Test Series No. 1: Construction Photographs Lap Siding (note butt joints every other course) Kelso, Washington Page 5 of 20

Test Series No. 1: Completed test assembly Lap Siding Test Series No. 2: Completed Wall Assembly Kelso, Washington Page 6 of 20

TEST RESULTS Test 1 Testing of the FlameBlock with Lap Siding was completed on March 3, 2010, with the results summarized in Table 1 below. Individual tests from a series of three successful consecutive test runs are reported as Trial A, B and C (with actual project test id s in parentheses). The moisture content of the FlameBlock sheathing and the SmartSide Lap siding was determined to be 8.5% and 5.5%, respectively, using the ASTM D 4442 oven-dry method. The moisture content of the 2x4 studs comprising the base wall structure was 9-10%. An IR imaging camera was employed to assess panel temperature changes on the unexposed side during each burn. Pretest weathering was not conducted. The test burner was calibrated to 150kW prior to testing. Photographs from a representative test are included in Appendix B. Table 1 Trial A (Test 5) B (Test 7) C (Test 8) Result Pass- no signs of flamethrough or glow on unexposed side Pass- no signs of flamethrough or glow on unexposed side Pass- no signs of flamethrough or glow on unexposed side Notes Cladding ignited at 50 s with vigorous flaming, flames out at 16 min, glowing combustion at various locations on sample surface until test terminated at 70 minutes - IR imaging shows diminishing temps on unexposed side at test termination Cladding ignited at 45 s with vigorous flaming, all flame out prior to 20 min, glowing combustion at various locations on sample surface until test terminated at 70 minutes - IR imaging shows diminishing temps on unexposed side at test termination Cladding ignited at 49 s with vigorous flaming, glowing combustion at various locations on sample surface until test terminated at 70 minutes - IR imaging shows diminishing temps on unexposed side at test termination Test 2 Testing of the FlameBlock with cedar sidewall shingle cladding was completed on May 4, 2010, with the results summarized in Table 2 below. Individual tests from a series of three successful consecutive test runs are reported as Trial A, B and C (with actual project test id s in parentheses). The moisture content of the FlameBlock sheathing and the shingle siding was determined to be 8.5% and nominally 8%, respectively, using the ASTM D 4442 oven-dry method. The moisture content of the 2x4 studs comprising the base wall structure was 9-10%. An IR imaging camera was employed to assess panel temperature changes on the unexposed side during each burn. Pretest weathering was not conducted. The test burner was calibrated to 150kW prior to testing. Kelso, Washington Page 7 of 20

Table 2 Trial A (Test 10) B (Test 11) C (Test 12) Result Pass- no signs of flamethrough or glow on unexposed side Pass- no signs of flamethrough or glow on unexposed side Pass- no signs of flamethrough or glow on unexposed side Notes Shingles ignited at 28 s with vigorous flaming, flames out at 23 min, glowing combustion at various locations on sample surface until test terminated at 70 minutes - IR imaging shows diminishing temps on unexposed side at test termination Cladding ignited at 28 s with vigorous flaming, all flame out at 27 min, glowing combustion at various locations on sample surface until test terminated at 70 minutes - IR imaging shows diminishing temps on unexposed side at test termination Cladding ignited at 23 s with vigorous flaming, glowing combustion at various locations on sample surface until test terminated at 70 minutes - IR imaging shows diminishing temps on unexposed side at test termination CONCLUSION AND EXTENTION OF RESULTS The wall assemblies comprised of LP FlameBlock sheathing with SmartSide Precision Series Lap siding (strand substrate) and ½ butt cedar shingles as tested and described in this report are deemed to meet the CSFM 12-7A-1 test requirements of California Building Code Chapter 7A. The test program was design to assess the effect of two severe-case exterior cladding applications over minimum nominal 7/16 FlameBlock Fire-Rated OSB sheathing. These siding applications included LP Smartside Precision Series Lap Siding (strand based) and ½ cedar sidewall shingles. Based on a review of the LP SmartSide Precision Series strand-based product line, the Lap siding is deemed to represent a worst case condition for this product line. Furthermore, based on previous laboratory testing experience with solid wood siding products, the ½ (4/2) cedar sidewall shingles were selected as representative of a worst case for cedar shingle siding, owing to the fact that the heaviest (in terms of butt thickness) available shingle was tested. The test results reported in Tables 1 and 2 are judged to apply to the following range of siding products installed over FlameBlock sheathing: SmartSide Precision Series lap and panel siding Cedar shingles of ½ (4/2) butt thickness and less Plain Bevel solid wood siding (cedar and other species, various widths Kelso, Washington Page 8 of 20

SIGNATURES Testing supervised by: Mike White Laboratory Manager Reviewed and approved, Howard Stacy Director, Testing Services WESTERN FIRE CENTER AUTHORIZES THE CLIENT NAMED HEREIN TO REPRODUCE THIS REPORT ONLY IF REPRODUCED IN ITS ENTIRETY The test specimen identification is as provided by the client and WFCi accepts no responsibilities for any inaccuracies therein. WFCi did not select the specimen and has not verified the composition, manufacturing techniques or quality assurance procedures. Kelso, Washington Page 9 of 20

REVISION SUMMARY DATE PAGE(S) SUMMARY May 28, 2010 None Original issue Kelso, Washington Page 10 of 20

APPENDIX A: SAMPLING REPORT Kelso, Washington Page 11 of 20

Kelso, Washington Page 12 of 20

APPENDIX B: TEST PICTURES (from representative tests) Kelso, Washington Page 13 of 20

Test Series No. 1 Lap Siding/FlameBlock Test time = 1 minute Midway through burner exposure Kelso, Washington Page 14 of 20

Prior to burner termination Immediately after termination of burner Kelso, Washington Page 15 of 20

Exposed face at test termination Kelso, Washington Page 16 of 20

Unexposed side at test termination Kelso, Washington Page 17 of 20

Test Series No. 2, Cedar Shingles/FlameBlock Prior to test T = 7.5 minutes Kelso, Washington Page 18 of 20

Termination of burner exposure Exposed face at T = 41 minutes Kelso, Washington Page 19 of 20

Unexposed face at test termination Kelso, Washington Page 20 of 20