WC SERIES SPECIFICATION SECTION ACCESS FLOORING

Similar documents
Tate Access Floors, Inc. All Steel 1000 Access Floor Panel 600 mm Bolted Stringer Understructure System

Tate Access Floors, Inc. ConCore 1250 Access Floor Panel Bolted Stringer Understructure System

DATA CENTER ACCESS FLOOR SYSTEM

RAISED ACCESS FLOOR SYSTEM TECHNICAL SPECIFICATION

Tate Access Floors, Inc. ConCore Access Floor Panel on Bolted Stringer Understructure System

Solidfeel Access Flooring v1.0 (1 October 2012) 1

PROPERTY OF UNIFLOOR INDIA

SECTION ( ) RAISED ACCESS FLOORING

- Oversize panels to be used at perimeters as necessary in order to maintain minimum cut panel size.

Data Center Catalog. Flexibility, Strength, and Energy Savings

SECTION ENTRANCE FLOOR GRILLES STAINLESS STEEL GRATING

UNIFIED FACILITIES GUIDE SPECIFICATIONS

RMF Intercell. NBS Specification 2013 K41

SECTION ACOUSTICAL PANEL CEILINGS

You Can Help the Environment with Green Building Technology

SECTION RADIATION SHIELDING ENCLOSURE Low Intensity Radiation Protection

HAWORTH PORCELAIN FLOORING SYSTEM CSI Specifications 03/29/2017. A. Concrete work and concrete floor sealer is specified in Section

Preassembled steel stairs with concrete-filled treads.

Student Services & Classroom Addition

SECTION FIBERGLASS REINFORCED POLYMER (FRP) PANELS

SECTION METAL FLOOR PLATE STAIRS

SECTION VIBRATION ISOLATION

UNIFLOOR. Raised Access Flooring Solutions

SECTION TOILET COMPARTMENTS. A. Section Metal Fabrications: Concealed steel support members.

BEARING METAL STUD FRAMING

ACOUSTICAL WALL TREATMENT SECTION 09840

SECTION HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS

Floor Insulation Underlayment Section Sound Control Matting

SECTION COLD-FORMED METAL FRAMING

Corium Brick Rainscreen System Specifications

CS SERIES. Access Flooring Made Affordable.

ENKASONIC FLOOR UNDERLAYMENT 9110

LINEAR METAL CEILINGS Section

SECTION ACCORDION FOLDING PARTITIONS

Trench Duct Class Catalog 5230CT9601R10/08

Louis Armstrong New Orleans International Airport NOAB Project # North Terminal Development Program Phase 1

A. Section includes hydraulic-cement-based, polymer-modified, self-leveling underlayment for application below interior floor coverings.

Union County Vocational - Technical Schools Scotch Plains, New Jersey

PRESTON HEALTH SERVICES ARCHITECT'S NO. 2700

SECTION SHEET MEMBRANE SOUND REDUCTION, CRACK ISOLATION / JOINT BRIDGING, AND WATERPROOFING

SECTION OVERHEAD COILING FIRE DOORS MODEL 662 OVERHEAD COILING COUNTER FIRE DOORS WITH INTEGRAL FRAME

SECTION [ ] COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here)

SECTION IMPACT RESISTANT WALL PROTECTION

A. Submit the following in addition to the standard requirements.

ARCHITECTURAL GUIDE SPECIFICATIONS - DESCRIPTIVE

SECTION VINYL ACRYLIC CLAD WOOD DOORS PART 1 GENERAL 1.1 RELATED DOCUMENTS

A. Types of lightgauge metal framing units include the following: 1. C-shaped structural steel studs Uniform Building Code.

SECTION LAGUNA SERIES TOP HUNG SLIDING DOOR SYSTEM

Section Wood Grille Ceiling Panels

SECTION ACOUSTICAL PANEL CEILINGS PART 1 - GENERAL

SECTION RESILIENT SHEET FLOORING

RESILIENT CORK TILE 3 PART SPECIFICATION #Z 624

SECTION ORNAMENTAL ALUMINUM RAILING. ** NOTE TO SPECIFIER ** Superior Aluminum Products, Inc.; Ornamental aluminum railing products.

Chevy Chase Club June 30, 2008 Bowie Gridley Architects SECTION GYPSUM BOARD SHAFT WALL ASSEMBLIES

Section SoundPly LR M25 Acoustic Ceiling Panels

SECTION ELEVATED BLEACHERS (Angle Frame Semi-Closed Deck)

MODERNFOLD GWS 100SR-G MOVEABLE GLASS WALLS

SECTION BRICK FACED ARCHITECTURAL PRECAST CONCRETE. Display hidden notes to specifier by using Tools / Options / View / Hidden Text.

1. Base plates, setting plates and anchor rods for columns. 8. Lintels if connected to structural steel columns.

DIVISION 10 SPECIALTIES SECTION OPERABLE PARTITIONS

1.02 DESCRIPTION A. This Section specifies furnishing and installing Surface Applied Detectable/Tactile Warning Surface Tiles where indicated.

SECTION SPRAY APPLIED FLOOR ADHESIVE

Date of Authorization June 29, 2006 BMEC Authorization Authorization Report - Camino Modular Floor System: SC Series

C. Concrete Inertia Bases: Drawings showing required concrete steel reinforcing, construction details, and dimensions.

SECTION SLOPED TRANSLUCENT METAL SKYLIGHT SYSTEM

Specification Lightning Protection Systems

Product Guide Specification

Specifying Pre-Engineered CFS Floor and Roof Trusses 551f-98

1. The subfloor must be structurally sound and able to withstand live and dead loads with a deflection limitation of L/360.

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

Structural Tests and Special Inspections Form. Inspection of Fabricators (1704.2)

SECTION STILE AND RAIL WOOD DOORS

PASSAIC COUNTY TECHNICAL INSTITUTE CCA 1422 NEW S.T.E.M. BUILDING 2017

Acceptable Floor Substrates: Concrete, cured mortar bed, plywood, and backer board.

WHY I SHOULD SPECIFY AND USE FAS TRACK 1000?

MFMA Guide Specification for Sleeper and Sleeper with Plywood Floor Systems

DBI-SALA Uni 8 Overhead Horizontal Lifeline Cable System SECTION HORIZONTAL FALL PROTECTION - OVERHEAD CABLE

TILE TILE

CONTRACT NUMBER: W912DQ-08-C % CORRECTED DESIGN 28 JULY 2008

SECTION STEEL DECKING

Page 1 of 5

Section PANEL SIGNAGE

SECTION MANUFACTURED ROOF EXPANSION JOINTS

Data Center The New Standard in Data Center Design... ASM H-D System

HIR 1 ACOUSTICAL, IMPACT RESISTANT, TACKABLE WALL PANEL SPECIFICATION

LUX Specifications. Section S - Preformed Steel Siding

SECTION NON-STRUCTURAL METAL FRAMING

SECTION ORNAMENTAL ALUMINUM FENCING

B. American Society for Testing and Materials: 1. ASTM F708 - Standard Practice for Design and Installation of Rigid Pipe Hangers.

SECTION CANOPIES. Display hidden notes to specifier. (Don't know how? Click Here) Copyright ARCAT, Inc. - All rights reserved

Patent No. 9,045,900 Technical Glass Products Architectural Specification Manual

SECTION ALUMINUM WINDOWS

SECTION SHEET MEMBRANE WATERPROOFING AND CRACK ISOLATION

B. Polyethylene samples shall be submitted for Owner approval of color and quality.

SECTION CRC575 UNITARY CLEANROOM WALL SYSTEM STUDLESS CLEANROOMWALL SYSTEM ME175 3-IN-1 CLEANROOM WALL SYSTEM

Northpointe Renovation EPN #1701 F/A Project #17027 September 8, 2017

EXCEL Medical Waste - Equipment Installation Section SECTION GYPSUM BOARD

SECTION COMMON WORK RESULTS FOR ELECTRICAL

SECTION (Master Template Final-05) ELECTRICAL BOXES. A. Provide boxes for electrical equipment and wiring devices as follows:

SECTION VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS

Transcription:

PART 1 - GENERAL 1.1 Section Includes A. Work of this section includes, but is not limited to: access floor panels, factory applied floor finishes, understructure, grommets, cut outs and grounding connectors. 1.2 Related Sections A. Concrete sealer (by Division 3) shall be compatible with pedestal adhesive. B. Electrical contractor (Division 26) shall provide necessary material and labor to electrically connect the access floor grounding connectors to the building ground. Grounding connectors provided by Division 26. 1.3 Environmental Conditions for Storage and Installation A. Area to receive the access floor shall be enclosed and maintained at ambient temperature between 55 to 85 F, and at humidity level between 20% to 70% relative, and shall remain within these environmental limits throughout installation and occupancy. All floor panels shall be stored and maintained within these limits upon delivery to storage sites. 1.4 References A. CISCA (Ceilings & Interior Systems Construction Association) - Recommended Test Procedures for Access Floors shall be used when presenting load performance product information. 1.5 Performance Certification A. Product tests shall be witnessed and certified by independent engineering and testing laboratory with a minimum of five years experience testing access floor components in accordance with CISCA Recommended Test Procedures for Access Floors. Panels shall be randomly selected from job site for Concentrated Load testing. 1.6 Quality Assurance A. Install access floor system using manufacturer's own forces or an accredited franchiser installer under the control and responsibility of the system manufacturer. Have a senior, qualified field representative on Site to direct the Work at all working times. B. Access floor panels core material and understructure shall be stamped and fabricated by a manufacturing facility that has demonstrated a successful 10-year track record of local installations of similar size and complexity. C. Mock Up: Before installation of entire access floor system, provide a 2.4 m x 2.4 m (8 x 8 ) mock up of the floor system determined by Architect/Construction Manager which serves as the minimum standard for the remaining access floor system delivered to, and installed at the Site. Build such mock up where directed by Architect/Construction Manager. The mock up will be installed prior to issuing a contract to enable the owner and consultants to conduct a comparative review of products. Page 1

1.7 Performance Requirements 1.7.1 Pedestals: A. Axial Load: Pedestal assembly shall provide a minimum 2272 kg (5000 lb.) axial load without permanent deformation. B. Overturning Moment: Pedestal assembly shall provide an average overturning moment of 112.98 Nm (1000 in-lbs.) when glued to a clean, sound, uncoated concrete surface. Structural calculations shall be required attesting to the lateral stability of the system under seismic conditions. Provide independent seismic certification from a Professional Engineer registered in the State or Province where the project is located. 1.7.2 Floor Panels: A. Design Load: Panel supported on system understructure shall be capable of supporting a minimum concentrated load of 5.6 KN (1250 lbs.) at any location on the panel. This rating signifies that the system will withstand the concentrated load without yielding and be capable of withstanding a minimum of 2 X the design load. Design and ultimate loads are applied to 1 square inch of the panel at the weakest point of the system. B. Uniform Load: Panel shall be capable of supporting a minimum uniform load of 21.5 kpa (450 lbs./sq.ft.) at any location on the panel with a maximum top surface deflection of 1.5 mm (0.060 inches). Panel shall not exceed a permanent set of.25 mm (0.010 inches), after the load is removed. C. Safety Factor: Panel shall be capable of withstanding a minimum of (2) two times the design load anywhere on the panel without failure. Failure is defined as the point at which the system will no longer accept the load. D. Rolling Load: Panel and supporting understructure shall be able to withstand the following rolling loads at any location on the panel without developing a local and overall surface deformation greater than 0.040 inches. Note: wheel 1 and wheel 2 tests shall be performed on two separate panels. Wheel 1: Size: 3 dia x 1 13/16 wide Load: 568 kg (1250 lbs.) Passes: 10 Wheel 2: Size: 6 dia x 2 wide Load: 398 kg (875 lbs.) Passes: 10,000 E. Impact Load: Panel and supporting understructure shall be capable of supporting an impact load of 57 kg (125 lbs.) dropped from a height of 1 meter (36 inches) onto a 25mm x 25mm area (1 sq. inch) at any location on the panel. F. Flammability: System (not including floor covering) shall meet the following flammability requirements when tested in accordance with CAN/ULC S102.2. Provide independent test reports as part of submittal. Flame Spread: 5 Smoke Development: 15 G. LEED: Floor system shall be manufactured with components to help secure the following LEED-NC Version 3credits: MR C4: Recycled Content Page 2

MR C5: Regional Materials IEQ C2: Increased Ventilation IEQ C4.1: Low Emitting Materials, Adhesives and Sealants IEQ Credit 8.1 & 8.2: Daylight & Views 1.8 Design Requirements: A. Access floor system, where indicated on the design documents, shall consist of modular and removable steel clad panels with wood core supported by adjustable height pedestal assemblies. B. Panel shall be easily removed by one person with a lifting device and shall be interchangeable except where cut for special conditions. C. Quantities, finished floor heights (FFH) and location of accessories shall be as specified on the contract drawings. 1.8.1 Submittals for Review A. Detail sheets, for each proposed product type, which provide the necessary information to describe the product and its performance. B. Test reports, certified by an independent testing laboratory with a minimum of five years experience testing access floor components in accordance CISCA Recommended Test Procedures, certifying that component parts perform as specified. 1.8.2 Submittals for Information A. Manufacturer s installation instructions and guidelines. B. Manufacturer s Owner Manual outlining recommended care and maintenance procedures. PART 2 - PRODUCTS 2.1 Support Components 2.1.1 Pedestals: A. Pedestal assemblies shall be corrosive resistant, all steel welded construction, and shall provide an adjustment range of +/- 1 for finished floor heights 6 or greater. B. Pedestal assemblies shall provide a means of leveling and locking the assembly at a selected height, which requires deliberate action to change height setting and prevents vibration displacement. C. Pedestal head shall be designed with locating tabs and integral shape to interface with the panel for positive lateral retention and positioning without fasteners. Pedestal head shall be fabricated with integral sound deadening gasket. D. Hot dip galvanized steel pedestal head shall be welded to a threaded rod which includes a specially designed adjusting nut. The nut shall provide location lugs to engage the pedestal base assembly, such that deliberate action is required to change the height setting. Page 3

E. Threaded rod shall provide a specially designed anti-rotation device, such that when the head assembly is engaged in the base assembly, the head cannot freely rotate (for FFH of 6 or greater). F. Hot dip galvanized pedestal base assembly shall consist of a formed steel plate with no less than 16 square inches of bearing area, welded to a 7/8 square steel tube and shall be designed to engage the head assembly. 2.1.2 Stringers (Data Centre Only): A. 2 ft. x 2 ft. bolted stringer system shall remain mechanically locked or snapped in place to pedestal locating tabs to provide positive lateral retention and positioning with or without fasteners. B. Stringers shall support each edge of panel. C. Steel stringer shall have sound deadening gasketed coating. 2.2 Panel Components 2.2.1 Floor Panels Office Area (Carpet finish by others): A. Panels shall be manufactured with a high density composite wood core material encased in steel. B. Panel shall have a durable non-corrosive finish treatment to steel surfaces. C. Corner of panel shall have a locating tab and integral shape design to interface with the pedestal head for positive lateral retention and positioning with or without fasteners. D. Fastening of panels to pedestal heads shall be accomplished by the use of 4 machine screws per panel to a stringerless understructure. 2.2.2 Floor Panels Data Centre: A. Panels shall consist of a top steel sheet and formed steel bottom pan encasing a high density wood based composite core material. B. Panel shall have a durable non-corrosive finish treatment to steel surfaces. C. Steel Airflow Panels: Perforated steel airflow panels designed for static loads shall be interchangeable with standard field panels and shall be capable of supporting a concentrated load of 1000 lbs. All panels shall have 20% open surface area. 2.3 Acceptable Manufacturers: Camino Modular Systems Inc., Tel. 416-675-2400 2.4.1 Miscellaneous Accessories: A. Provide factory cutouts in access floor panels for all PVD Service centers, grommets and all diffusers. Provide field cut outs for any base building electrical or mechanical pipes. Page 4

B. Provide manufacturer's standard gasket or caulking air sealant at all perimeter cut panels at walls, columns and building concrete curbs. Sealing of cutouts for electrical/mechanical pipes or sheet metal to be performed by the trade supply the electrical or mechanical component. C. Provide 100 spare floor panels, 200, spare pedestals and 400 spare screws used in the project for maintenance stock. Deliver to project in manufacture's standard packaging clearly marked with the contents. D. Provide 12 panel lifting devices. 2.5 Finishes A. Finish the surface of floor panels with floor covering material as indicated on the contract drawings. Where floor coverings are factory applied by the access floor manufacturer, the type, color and pattern shall be selected from manufacturer's standard. Provide bolted stringer understructure for any factory applied floor coverings such as vinyl or laminates. B. Finish the surface of floor panels with an anti-static high pressure covering material. The type, color and pattern shall be selected from manufacturer s standard. Nevamar grade HDM or equal. C. High-pressure laminate floor coverings shall have a trim condition that is integral to the tile, and mechanically located in place. Glued or pressure fit trim is unacceptable. D. Surface to Ground Resistance of Standard High Pressure Laminate Anti-Static Covering: Average test values shall be below 20,000 Mega ohms (2.0 x 10 e10 ohms), as determined by testing in accordance with the test method for conductive flooring specified in NFPA 99, but modified to place one electrode on the floor surface and to attach one electrode to the understructure. Resistance shall be tested at 500 volts. 2.6 Fabrication Tolerances A. Floor panel flatness measured on a diagonal: +/- 0.030 B. Floor panel flatness measured along edges: +/- 0.025 C. Floor panel width or length of required size: +/- 0.015 D. Floor panel squareness tolerance: +/- 0.020 PART 3 - EXECUTION 3.1 Preparation A. Examine structural subfloor for unevenness, irregularities and dampness that would affect the quality and execution of the work. Do not proceed with installation until structural floor surfaces are level, clean, and dry as completed by others. B. Concrete sealers, if used, shall be identified and proven to be compatible with pedestal adhesive. Verify that adhesive achieves bond to slab before commencing work. C. Verify dimensions on contract drawings, including level of interfaces including abutting floor, ledges and doorsills. Page 5

D. The General Contractor shall provide clear access, dry clean subfloor area free of construction debris and other trades throughout installation of access floor system. Area to receive access floor shall be enclosed and be maintained at a temperature range of 55 to 85 F and a humidity range of 20% to 70% relative. Access floor panels must be stored in this environment at least 24 hours before installation begins. 3.2 Installation A. Pedestal locations shall be established from approved shop drawings so that mechanical and electrical work can be installed without interfering with pedestal installation. B. Installation of access floor shall be coordinated with other trades to maintain the integrity of the installed system. All traffic on access floor shall be controlled by access floor installer. No traffic but that of access floor installers shall be permitted on any floor area for 24 hours to allow the pedestal adhesive to set. C. Floor system and accessories shall be installed under the supervision of the manufacturer s authorized representative and according to manufacturer s recommendations. D. No dust or debris producing operations by other trades shall be allowed in areas where access floor is being installed to ensure proper bonding of pedestals to subfloor. E. A clean subfloor shall be turned over to the access floor installer prior to commencement of the access floor installation. Access floor installer shall keep the subfloor clean as the installation progresses. F. Partially complete floors shall be braced against shifting to maintain the integrity of the installed system where required. G. Additional pedestals as needed shall support panels where floor is disrupted by columns, walls, and cutouts. H. Understructure shall be aligned such that all uncut panels are interchangeable and fit snugly but do not bind when placed in alternate positions. I. Finished floor shall be level, not varying more than 0.062 in 10 feet or 0.125 overall. J. Acceptance: General contractor shall accept floor in whole or in part prior to allowing use by other trades. K. Allow for return visit to perform final inspection and adjustments before turn over to owner/tenant. General Contractor to initiate inspection prior to installation of carpet and furniture. ### End ### Page 6