How the design of a cooling tower impacts energy usage and operating costs

Similar documents
Introducing the Marley MD Cooling Tower. / We re bringing something new to packaged counterflow towers. / Our name.

Marley MD 5000 COUNTERFLOW COOLING TOWER

MD steel cooling tower

More Capacity. More Value. More of What Makes Marley the Best.

SECTION COOLING TOWER

More Capacity. More Value. More of What Makes Marley the Best. Lenntech. Tel Fax.

Cooling Tower Fundamentals

NC steel cooling tower MORE CAPACITY. MORE VALUE.

COOLING TOWER DESIGN FOR CENTRAL GENERATORS OF CUET, BANGLADESH. Mohammad Sharif Khan, Golam Mainuddin, Abu Sadat Mohammad Sayem, Nadeem Nafis

Lenntech. Tel Fax / Marley MS Cooling Tower /

QuadraFlow cooling tower

Mechanical Project Proposal

Plant Utilities and Energy Efficiency CH505

Energy Management Workshop

Cooling Tower Noise Control

CONTENTS. 1 Product Introduction. 2 Unique Features. 4 XE Model Cooling Towers. 6 Series 3000: Induced Draft Crossflow Cooling Towers

B. System Design and Performance Requirements

Georgetown University New Science Center

Heat Rejection using Cooling Towers

Intelligent System Design

ENGINEERING DATA. NC steel COOLING TOWER

/ Marley Series 10 Series 15 Cooling Tower /

Chapter Six{ TC "Chapter Six" \l 1 } System Simulation

ENVIRONMENTAL NOISE CONTROL FOR SEMICONDUCTOR MANUFACTURING FACILITIES

7 th NATIONAL CERTIFICATION EXAMINATION Nov FOR ENERGY MANAGERS & ENERGY AUDITORS

.2 Section Waste Management and Disposal..4 Section Vibration Isolation and Seismic Control Measures.

AMCOT COOLING TOWER CORPORATION LRC-H & LRC-LNS CROSS FLOW COOLING TOWER OPERATIONS AND MAINTAINENCE MANUAL

EXPERIMENTAL INVESTIGATION AND OPTIMIZATION OF COOLING TOWER EFFICIENCY BY FORCED DRAFT SYSTEM

NC fiberglass cooling tower MORE CAPACITY. MORE VALUE.

Large University Central Chiller Plant Design Considerations

TM Series Induced Draft Cooling Tower Specifications

Complete cooling performance. Air cooled exchangers for the oil, gas and power markets

The following document can be provided to an Engineer, Contractor, or Owner to allow them to properly specify MESAN s MXR-KM series Cooling Towers.

Series V Cooling Tower

EES Energy Efficient Systems Rotary Screw Air Compressors kw Horsepower

Application of Variable Frequency Drives for Energy Savings

Chilled Water Plant Design American Standard Inc.

NC fiberglass cooling tower MORE CAPACITY. MORE VALUE.

FXT Open Cooling Towers... B46. Benefits... B48. Construction Details... B49. Custom Features and Options... B50. Accessories...

DELTA. Cooling Towers, Inc. Delta Cooling Towers. Leader in Non-Corrosive Cooling Tower Technology

ERT 318/4 UNIT OPERATIONS SEMESTER 1 (2013/2014)

Pioneer Forced Draft Cooling Tower Specifications

Project Information. Measure Description

Chilled Water System Optimization

Underf loor For Schools

Section A: CUSTOMER INFORMATION. Customer Name Electric Account Number Rate Application Number. Facility Address City State Zip Code

Utilization of Atmospheric Heat Exchangers in LNG Vaporization Processes:

Delta T Kiln Control Technology

Easy. Safe. Simple. Access for Maintenance to Cooling Towers

Thermal Cooling Tower Noun : The Source

Geothermal Power Plant

Condenser Water System Retrofit Opportunities. Figure 1. Condenser water system schematic. isolation valve. cooling tower

THERMAL ENVIRONMENT OF OUTDOOR UNITS OF VRV SYSTEM IN HIGH- RISE BUILDING. Gang Wang, Yafeng Hu, and Songtao Hu

Motor Systems Optimization Case Studies in the Peoples Republic of China

This session is approved for 0.2 IACET or 1.5 PDH. Many states accept this for Professional Continuing Education.

University of Southern California Main Campus Plant Energy use reduction of 49% compared to previous plants and control strategies.

PREMIER Low Profile Induced Draft Cooling Tower Specifications

Content. Cooling Tower Water Treatment...1. Maintaining Water Quality...1. Startup Conditions...1. Blowdown...1. Chemical Treatment...

PRASAR BHARATI (India s Public Service Broadcaster) OFFICE OF THE ADDL. DIRECTOR GENERAL (E)(EZ) ALL INDIA RADIO & TELEVISION, KOLKATA

Products and Services

Pioneer Forced Draft Cooling Tower Specifications

Project Case Study. Motor City DCP. Project: District Cooling Plant, Motor City Start Date: 2007 Completion Date: 2010

An Investigation in Performance Enhancement of Induced Draft Counter Flow Wet Cooling Tower

ENGINEERING DATA AND SPECIFICATIONS. NC alpha STEEL COOLING TOWER

YORK UNITIZED ENERGY RECOVERY VENTILATOR (ERV) Superior air-flow 300 6,200 CFM

Chapter Two { TC "Chapter Two " \l 1 } Detailed System Description

ORIGINAL YEAR OF CONSTRUCTION NUMBER OF BUILDING STORIES 02/06/2013 BUILDING SURVEY DATE

COOLING TECHNOLOGY INSTITUTE

/ Hybrid Cooling Towers

September 22, Roy Hubbard HVAC Systems Technology

Module 9 : Sewage And Storm water Pumping Stations. Lecture 11 : Sewage And Storm water Pumping Stations

2-Pipe fan coil terminal units were selected as the parallel system to handle the remaining sensible cooling load.

IMPLEMENTATION OF ANALYTICAL MODELS FOR PASSIVE DOWN-DRAFT EVAPORATIVE COOLING (PDEC) TOWER WITH SPRAY SYSTEMS

ADDENDUM NO. 01. Include this signed and dated addendum to your proposal.

NEBBinar: Managing Building Performance through Commissioning. March 28, 2013

Intelligent Process Cooling Technology Saves on Water and Energy, Improves Productivity

Performance Improvement and Efficiency Optimization of an Industry through Energy Audit

VARI-CANT Jet Aeration Systems. Water Technologies

Performance Efficiency Standard for Evaporative Cooling Equipment

Xavier Energy Initiative

A Primer on Recovery Efficiency Ratio

Variable Frequency Drives Opportunities in Agriculture

INVESTIGATION OF THE THERMAL PERFORMANCE OF A CROSS-FLOW WATER COOLING TOWER WITH DIFFERENT PACKINGS

ENGINEERING UPDATE JULY VOLUME 11 THIS PACKAGE INCLUDES A COLLECTION OF ARTICLES FROM VOLUME 11 OF THE JULY 2013 ENGINEERING UPDATE.

Fiberglass Cooling Towers

RETROFIT SOLUTIONS. For Gas Turbines And Rotating Machinery

COOLING TOWERS. Selection, Design and Practice

Water cooled chiller plant with economiser (vp)

OUTDOOR AIR, HEAT WHEELS AND JCPENNEY: A NEW APPROACH TO RETAIL VENTILATION

Chapter 3.7: Cooling Towers

Opportunity for cost savings & Performance Improvements

Ground Source Heat Pumps

HOW TO SELECT THE MOST EFFECTIVE BLOWER TECHNOLOGY FOR WASTEWATER APPLICATIONS

FAIRBANKS NIJHUIS SUBMERSIBLE SOLIDS HANDLING PUMPS.

NATIONAL CERTIFICATION EXAMINATION 2004 FOR ENERGY MANAGERS

MHWW-09-H-1 Chilled/Hot Water Hi-Wall Fan Coil. Heat / Cool Fan Coil 9,000 BTUH. Rev. 1.3

MHWW-18-H-1 Chilled/Hot Water Hi-Wall Fan Coil. Heat / Cool Fan Coil 18,000 BTUH. Rev. 1.3

Transcription:

Introduction A variety of cooling tower technologies and configurations exist in the market today. Each type can offer different component technologies, different materials of construction, and different means of achieving the interaction of process water with outdoor air. The choice or selection of these characteristics in a given cooling tower will inevitably affect a variety of important performance attributes, such as: Cooling Tower Longevity Fan Motor Energy Consumption Process Pump Energy Consumption Variable Flow Compatibility Recirculation Potential Performance in Cold Weather Environments The Costs of Maintenance Accessibility for Maintaining the Tower The Maintenance Capabilities Without Tower Shutdown Water Treatment In this paper, we will focus on how design and configuration of a given cooling tower impacts the amount of energy required for it to operate. Nearly as important as the level of performance a given product offers is its ability to deliver that performance while maintaining a high level of energy efficiency. Today, energy efficiency is one of the more significant focus items for designers, end users, and equipment manufacturers as they seek to reduce equipment operational costs to strengthen their position in a competitive marketplace. Cooling towers are no different from any other product in this regard. In a cooling tower, energy is consumed in driving the fan or fans, necessary to achieve proper air movement through the tower. Also, the pump head requirement of a cooling tower contributes to the energy expended in the operation of the condenser water pump. Because of this, manipulation of one or both of these power consuming aspects will have an effect on the cooling tower s energy requirement. Let us compare two common cooling tower design configurations in order to illustrate this fact. Two common cooling tower configurations are shown below in figures 1 and 2. 1 Figure 1 - Forced Draft, Counter-Flow Tower Marley MCW Product Shown Figure 2 - Induced Draft, Cross-Flow Tower Marley NC Class Product Shown

Figure 1 illustrates a counter-flow, forced draft cooling tower. A forced draft tower uses a fan located in the ambient airstream entering the cooling tower. The fans force air through the fill media and out the top of the tower enclosure. Forced draft towers are characterized by high air entrance velocities and low exit velocities. Accordingly, they are extremely susceptible to recirculation and because the fans are located in the cold entering ambient air stream, forced draft fans can become subject to severe icing during operation in winter months. Usually, forced draft towers are equipped with centrifugal blower type fans which, although requiring considerably more horsepower than propeller type fans, have the advantage of being able to operate against the high static pressures associated with ductwork. Therefore, they can either be installed indoors (space permitting), or within a specially designed enclosure that provides significant separation between intake and discharge locations to minimize recirculation. In counter-flow towers, air moves vertically upward through the fill, counter to the downward fall of water. Because of the need for extended intake and discharge plenums, the use of high-pressure spray systems, and the typically higher air pressure losses, some of the smaller counter-flow towers are physically taller, require more pump head, and utilize more fan power than their cross-flow counterparts. See Figure 3 to the right. Figure 3 - Counter-Flow Water Distribution Gravity-flow water distribution pans Pressurized water spray system Figure #2 depicts an induced draft cooling tower. Induced draft towers have a fan or fans located on the air exiting side of the cooling tower, and they draw air through the tower rather than force the air through it. These towers have an air discharge velocity of from 3 to 4 times higher than their air entrance velocity, with the entrance velocity approximating that of a 5 mph wind. Therefore, there is little or no tendency for a reduced pressure zone to be created at the air inlets by the action of the fan alone. The potential for recirculation on an induced draft tower is not selfinitiating and, therefore, can be more easily quantified purely on the basis of ambient wind conditions. Location of the fan within the warm air stream provides excellent protection against the formation of ice on the mechanical components. Widespread acceptance of induced draft towers is evidenced by their existence on installations as small as 15 gpm and as large as 700,000 gpm. Figure 4 - Cross-Flow Water Distribution Cross-flow towers have a fill configuration through which the air flows horizontally, across the downward fall of water. Water to be cooled is delivered to hot water inlet basins located atop the fill areas, and is distributed to the fill by gravity through metering orifices in the floor of those basins. This eliminates the need for a pressurespray distribution system, and places the resultant gravity system in full view for ease of maintenance. By the proper utilization of flow control valves, routine cleaning and maintenance of a cross-flow tower s distribution system can be accomplished sectionally, while the tower continues to operate. See Figure 4 to the left. 2

To begin the energy utilization comparison between these two tower arrangements, let us first consider the fan energy requirements of each tower. For a forced-draft tower, both blower fans and propeller fans can be used. This impacts the energy utilization significantly, as blower fans characteristically require twice the horsepower of propeller fans. So the first factor to consider is what type of tower arrangement is being utilized and what fan technology does it incorporate? Also, how many fans are needed, and what is the resulting total horsepower requirement to meet the project conditions? Take the following comparison of a two, 200-ton cooling towers with a 600gpm flow rate, 95 F hot water, 85 F cold water, and 78 F wet bulb: For a counter-flow, forced-draft cooling tower utilizing blower type fans, the horsepower requirement would be 25HP total. Based on seasonal operation of approximately 2,000 hours with a VFD controlled fan, the tower fan motor would consume 33,288.3 kwh and the system pump energy consumption would be approximately 4,000 kwh. For a cross-flow, induced-draft cooling tower, utilizing a propeller type fan, the horsepower requirement would be 7.5HP total. Based on seasonal operation of approximately 2,000 hours with a VFD controlled fan, the tower fan motor would consume 11, 297.7 kwh and the system pump energy consumption would be approximately 3,416 kwh. Under identical design conditions for a seasonal cooling tower application, a counter-flow, forced draft cooling tower will consume well over twice the energy as a comparable capacity cross-flow, induced draft cooling tower. At $0.08 per kwh, a comparison of energy costs shows the following: 200 Ton Counter-flow, Forced-draft cooling tower operating seasonally (95 HW 85 CW 78 WB) Fan Energy Consumption with VFD: 33,288.2 kwh 4,000.8 kwh Total Energy Cost at $0.08 per kwh: $2,983.00 200 Ton Cross-flow, Induced-draft cooling tower operating seasonally (95 HW 85 CW 78 WB) Fan Energy Consumption with VFD: 11,297.7 kwh 3,416.1 kwh Total Energy Cost at $0.08 per kwh: $1,177.00 The Cross-Flow, Induced-draft tower offers an annual energy cost savings of $1,806.00 over the Counter-flow, Forced-draft tower. So there are significant on going cost reductions available for this technology, just based on energy efficiency alone. On top of this, a comparably equipped Cross-Flow, Induced Draft tower at the 200 ton capacity level is only $1,200.00 more costly than the Counter-flow, Forced-draft tower. The return on the investment of the additional $1,200.00 up front is accomplished within the first 8 months of operation. From that point on, the energy savings are pure operational cost reduction. Let s look at the same cooling tower technology comparison, only moving up to a 400 ton design. Here are the results: 3

For a 400 ton counter-flow, forced-draft cooling tower utilizing blower type fans, the horsepower requirement would be 60HP total. Based on seasonal operation of approximately 2,000 hours with a VFD controlled fan, the tower fan motor would consume 88,747.1 kwh and the system pump energy consumption would be approximately 9,940.5 kwh. For a 400 ton cross-flow, induced-draft cooling tower, utilizing a propeller type fan, the horsepower requirement would be 20HP total. Based on seasonal operation of approximately 2,000 hours with a VFD controlled fan, the tower fan motor would consume 30,275.5 kwh and the system pump energy consumption would be approximately 7,974.6 kwh. Again, under identical design conditions for a seasonal cooling tower application, a counter-flow, forced draft cooling tower will consume well over twice the energy as a comparable capacity cross-flow, induced draft cooling tower. At $0.08 per kwh, a comparison of energy costs shows the following: 400 Ton Counter-flow, Forced-draft cooling tower operating seasonally (95 HW 85 CW 78 WB) Fan Energy Consumption with VFD: 88,747.1 kwh 9,940.5 kwh Total Energy Cost at $0.08 per kwh: $7,895.00 400 Ton Cross-flow, Induced-draft cooling tower operating seasonally (95 HW 85 CW 78 WB) Fan Energy Consumption with VFD: 30,275.5 kwh 7,974.6 kwh Total Energy Cost at $0.08 per kwh: $3,060.00 This comparison adds a twist to the story. At the 400 ton capacity level, the Cross-flow, Induced-draft tower is actually LESS costly up front. Not only are the energy savings double, the price tag is less as well. This trend would continue as larger capacity cooling towers are considered in this same type of comparison. It can be clearly seen that the induced draft, cross-flow cooling tower is vastly superior in operational energy efficiency. Because of this fact, manufacturers of counter-flow, forced-draft cooling towers have in some cases resorted to utilizing propeller fans in lieu of blower fans, in order to lessen some of their excessive energy consumption. This makes an improvement in energy efficiency. However, the nature of the counter-flow, forced-draft tower design still necessitates higher horsepower requirements to accomplish the same duty as a comparable capacity cross-flow, induced-draft cooling tower. For example, a 200 ton counter-flow, forced draft tower with propeller fans might employ three (3) 3HP fan motors in contrast to the cross-flow, induced-draft tower s (1) 7.5HP motor. This still results in superior energy conservation on the part of the cross-flow, induced draft tower. To counter this fact, it is sometimes proposed by counter-flow, forced draft cooling tower manufacturers that during certain conditions where capacity requirements are reduced or the wet bulb temperature is much lower than the design condition, that they can modulate off a fan motor and achieve better energy efficiency with (2) 3HP fan motors running at a given rpm as compared with (1) 7.5 HP fan motor running at a lower rpm. This argument is not well-founded, as it depends not only on circumstantial conditions, but also proving that at higher rpm of the (2) 3HP fan motors, they can achieve better energy efficiency than the (1) 7.5 HP fan motor running at a lower RPM. In considering this, it is important to recall that 4

on fan loads, the horsepower requirement varies as the cube of the speed, so the slower the fan speed, the less energy required. A fan running at 80% speed will consume only 50% of the power of a fan running at full speed. At 50% fan speed, power consumption is only 16%. In conclusion, energy efficiency is a major concern for all facility managers. There is a clear solution to increasing energy efficiency of a cooling tower by simply considering the technology that is specified for use on the application. A crossflow, induced draft cooling tower offers many benefits to an end user, and one of them is superior energy efficiency. Resources: Cooling Tower Energy and Its Management, SPX Cooling Technologies, Technical Report, 1982 Marley Cooling Towers Since its beginnings in 1922 in Kansas City, Marley continuously developed its position as the world s only full line cooling tower manufacturer from the first crossflow cooling tower in 1936 to the first hyperbolic natural draft tower in North America in 1961 and the development of the parallel-path wet-dry hybrid cooling tower in 1971. www.marleyct.com Marley MCW Cooling Tower http://spxcooling.com/en/library/detail/marley-mcw-cooling Marley NC Class Cooling Tower http://spxcooling.com/en/products/detail/marley-nc-class-cooling- 5