TENDER DOCUMENTS FOR ELECTRICAL WORKS STATE BANK OF INDIA RURAL SELF EMPLOYMENT TRAINING INSTITUTE BASTI (ELECTRICAL WORKS) PRICE BID-VOLUME - II Tender Issued to: Tender Received on: Issued by, ASSTT. GENERAL MANAGER PREMISES & ESTATE DEPTT STATE BANK OF INDIA. LOCAL HEAD OFFICE LUCKNOW ARCHITECT GUPTA & ASSOCIATES 9B-42 MOHANKUNJ, VRINDAVAN COLONY RAEBARELI ROAD LUCKNOW-226029 1
SUMMARY OF COST (ELECTRICAL WORKS) S.N. DESCRIPTION OF ITEM AMOUNT (RS.) 1. Cost of Work Sub Total Unconditional Discount offered ( if any ) (-) TOTAL 2
BOQ - Electrical Works. Rural Self Employment Training Institute Basti. S.No Item of Works Unit Quantity Rate Amount 1 ELECTRIC PANEL : Supply, installation, testing and commissioning of floor / wall mounting, totally enclosed, dust & vermin proof, dead back, fully compartmentalized cubicle type new electric panel made of 2mm thick sheet steel suitable for use on 500V, 3PH, 4 wire 50 Hz A.C. system, incoming ACB/MCCB/Changeover Switch, high conductivity TP&N electrolytic grade aluminium busbars (INDAL /HINDALCO /BALCO/ NALCO), outgoing MCCBs,/MCBs, instrumentation, C.Ts, outgoing feeder terminals and incoming cable compartment having detachable gland plate at top and bottom. The incoming and outgoing functional units shall be arranged in multi tier formation to provide a compact electric panel. Each unit shall be accommodated in a totally separate compartment having hinged door with neoprene gasket and locking arrangement, louvers with brass mesh inside for ventilation. The panel will be complete with switches/ circuit breakers of the following ratings, inter connections to main bus bar with inter connecting bus bars of adequate current carrying capacity, 1x50mmx6mm G.I. earth busbars along the total length of the panel with G.Ibolts, nuts, washers, etc. The cubicle shall be painted with final two coats of steel grey synthetic enamel paint or powder coated including requisite pre finish treatment like cleansing, de greasing, de rusting, phosphadising, two coats of primer. The complete fabrication,construction shall be done as per detailed specification and conforming to relevant I.S. All MCB should be of 10 KA breaking capacity and of C curve characteristics. Control/instruments wiring to be done by 1100V grade PVC insulated, multistrand copper conductor wire of 2.5 mm2 for current circuits and 1.5 sq. mm for potential circuits. Protecting MCBs to be provided for each control/instrumentation circuit. DMC/SMC insulators to be provided for support of main busbar, interconnecting busbar and extension terminals of switchgear for adequate electrical and mechanical strength. MCB s to also be provided with separator sheets and spreader terminals. Minimum clearance for busbars shall be 32 mm(phase to phase) and 26mm (phase to neutral and phase to earth).. Danger plate and name plates for designation and ampere rating of Set 1 3
ACB/MCCB/MCB/Swithchgear etc are to be fixed on front of the panel as directed. Approval of general layout, manufacturing and single line diagram drawings from consultant is required before commencing manufacture and the panel should be tested in the presence ofconsultant/bank s Engineer at manufacturer s premises before dispatch to site along with HV withstand and insulation resistance test reports. MAIN POWER CONTROL PANEL : Incoming:1 No. 160 Amp, 4 pole, Moulded Circuit Breaker having short circuit breaking capacity of 25 KA with adjustable overload, and short circuit tripping mechanism,led indicating lamps for RYB and following metering arrangement.1 set 3 phase analog ammeter with CT set and selector switch.1 set 3 phase analog voltmeter with selector switch 1 set 1 phase digital frequency meter with CTMain Busbar set comprising 4Nos 25x10 (phase and neutral) electrolytic grade Aluminium with colour coded heat shrinkable PVC sleeve. Main Bulbar set comprising 4Nos 25x10 (phase and neutral) electrolytic grade Aluminium with colour coded heat shrinkable PVC sleeve. Outgoing 3 Pole, 63 A, 8 nos. Moulded Case Circuit Breaker having short circuit breaking capacity of 16 KA, fixed S/C and adjustable O/L release, LED type indicating lamp for ON/OFF. 2 Supply installation testing & commissioning (SITC) OF 160A, 4P, 25 KA breaking capacity MCCB with adjustable overload and fixed short circuit tripping device. MCCB to be fixed on suitable angle Iron frame. 3 SITC of 160 A 4 P onload change over switch in sheet steel enclosure change over switch in sheet steel enclosure. Change over to be fixed on suitable angle Iron frame 4 SITC of TPN phase isolation (PPI) double door (2+8) MCB DB with 40 A, 4 P MCB Incomer 3 x 40 A DP, 100 ma sensitivity ELCB sub incomer 15 nos. 6-32 SP MCB outgoing Blanking, plates to be provided and all MCBs to be of 10 KA Breaking Capacity 5 SITC of TPN phase isolation (PPI) double door (2+8) MCB DB with i) 32 A, 4 P MCB Incomer ii) 3 x 25 A DP, 100 ma sensitivity ELCB sub incomer.iii) 15 nos. of 6-32 SP MCB outgoing Blanking plates to be provided and all MCBs to be of 10 KA Breaking Capacity. No 1 4
6 SITC of TPN double door 4 way MCB DB with 40 A, 4P 100 ma sensitivity RCBO incomer 2x6-32 A TP MCB and 4 x 6-32A SP MCB outgoing. Blanking plate to be provided and all MCBs to be of 10 KA Breaking Capacity. 7 Kit Kat fuse unit (03 No) and 01 No copper neutral link of 125 Amp near main energy meter & near generator set on suitable wooden board (porcelain kit Kat fuse unit with connection etc. ) Set 1 8 SITC of single door SPN consumer MCB DB with incomer 25 Amp DP, 100 ma sensitivity ELCB incoming and 6 no (6-32 Amp SPMCB) outgoing all MCB to be of 10 KA breaking capacity. 9 Supply & installation of 63 Amp 2 pole MCB in manufacturers sheet steel enclosure MCB to be of 10 KA breaking capacity C curve No 1 10 Supply & installation of 25 Amp 4 pole MCB in manufacturers sheet steel enclosure MCB to be of 10 KA breaking capacity C curve. 11 Wiring from MCB to Isolation Transformer to UPS with 3X10 sq. mm 1100 V grade FRLS PVC insulated multi strand copper wire in medium duty rigid or flexible PVC conduit as requires preferably concealed in floor/wall including chase cutting and making good of damages or on surface. 12 Supply & laying 1100 V aluminium conductor XLPE/PVC insulated, sheathed armored cable on surface with MS saddle and clamp on underground (as required ) two runs of 8 SWG GI wire along with cable of following size No 1 rmt 5 a. 3 1/2 x 35 mm2 Rmt 70 b. 3 ½ x 25 mm2 Rmt 70 c. 4 x 16 mm2 Rmt 100 13 End termination of cable of following size using dowels make copper cable lugs /cable sockets as required. a. 3 1/2 x 35 mm2 Sets 6 b. 3 ½ x 25 mm2 Sets 12 c. 4x 25 mm2 Sets 12 14 Wiring for air conditioners - power points with 2 wire of size 4 mm2 FOR PHASE & neutral and one wire of 2.5 mm2 FOR EARTH IN 20 MM Rmt 100 5
PVC conduit wire to be of 1100 V grade insulated with copper conductor concealed on wall complete commissioning etc. 15 Wiring with 2 wire of size 6 mm2 FOR PHASE & neutral and one wire of 4 mm2 FOR EARTH IN 20 MM PVC conduit. Wire to be of 1100 V grade insulated with copper conductor concealed on wall complete commissioning etc. (TPN to SPN DB ) Rmt 30 16 Point wiring with 3 x 1.5 sqmm pvc copper wire in PVC conduit for light /fan socket on boards wiring to commence and including circuit wiring, also in PVC conduits from TPN MCB DB Located in stair hall to point switch boards and their after to the points including provision of 3 phase ceiling rose and junction box as required of light /fan points would be either individual or in group up to a max of 2 points item include supply & installation of piano type switches, socket and regulator, face plates and manufacturer s boxes. Enough loose wire to be left at point end / ceiling rose for connection to fixture etc. (One point in the quantity given against this item means either or individual point or a group point to control up to 2 point one switch = one point @ as per requirement only. 17 Supply installation testing and commissioning of power point having one no 15 A switch & 15 A 5 pin socket (Non modular type complete item including plate, boxes etc) with 4 sq mm cu wire for phase and neutral and 2.5 sq mm cu wire for earth in pvc conduit including all accessories boxes as required maximum Point on one circuit should not exceed Two. For water cooler, glow sign, TV, hooter, music system, pantry, flood light pt, out side entrance, rec. room as required by institute at suitable place Circuit to be connected from institute TPN DB controlled by each point with each switch testing / commissioning in all respect.cu wire of PVC 1100 V grade insulated for phase, neutral and earth concealed properly. Wiring to commence from branch TPNDB / Fuse unit to switch board and then to points complete connection testing etc in all respect as per branch requirement in pvc conduit (concealed on wall /floor and making good the same ) item include supply & installation of Piano type board, 15/20 A switches, Sockets complete for power board.( As per requirement only) No No 155 20 18 Providing & Installations on angle iron frame of manufacturers sheet steel 20 A socket board with No 6 6
cover & 2 pole & earth metal plug and socket and 25/32 Amp SPMCB complete in all respect for air conditioners. 19 Supply & installation of 6A swicth, socket point at suitable place as required by the institute, complete testing, commissioning in all respect with 1.5 sqmm pvc 1100 V grade copper insulated wire for phase, Neutral and earth in PVC conduit (concealed on wall / floor and making the same). Item include non-modular switch socket board, front plate etc. 20 Laying of ISI mark PVC conduit on floor / wall As required 1.8-2 mm thick concealed make as approved with Ms saddle screw etc. Size 25 mm / 32 mm. including making surface good No 16 a Size 25 mm mtr 30 b Size 32 mm mtr 30 21 S & I of lighting/ fixtures as per the details given below including necessary hardware such as, clamps, nuts, bolts, nails, screws and suspension chains as required for fixing the fixtures in position as directed by architect / Consultant. a b Supply and fixing of 56"Ceiling fan with fan regulator. Wall bracket oscillating type fan 400mm with inbuilt regulator with connection, testing, commissioning at suitable place in all respect. c Supply & fixing of exhaust fan heavy duty 300 mm swipe and 1400 RPM with lovers and making of hole on wall of proper size with nut bolts /brackets complete installation testing / commissioning & connection, complete in all respect in UPS, Toilets etc. d Supply and fixing of 1 x 20 W LED batten type tubelight fittings complete in all respect with suitable, tube, driver etc. e Supply and fixing of bulk head fitting with bulb 40 W with glass dome with wire guard. f g Supply and fixing of LED down lighter fitting with bulb surface mounted 10-12 W. Supply and fixing of LED Street light fitting with bulb 20-24 W suitable for outdoor installation complete in all respects with LED Drivers etc. 22 Supply & Laying of 10 pair Telephone wire with PVC pipe From Telephone Co. Tag block to E No 32 No 8 No 55 Each 5 Each 35 Each 4 Rmt 30 23 Supply & Installation of 20 pair Krone type Each 1 7
telephone tag block. 24 Supply & Laying of 4 pair Telephone wire with PVC pipe 25 Supply & Installation of RJ-11 Telephone Socket with box. 26 Supply, installation, testing and commissioning (SITC) of 2X4+1X4 sq. mm, 1100 V grade,frls, multi strand copper conductor PVC insulated wire in existing PVC conduit including connections, complete in all respects from TPN MCB DB to SPN DB for UPS powered sockets. 27 SITC of wiring from SPN MCB DB to UPS powered sockets at work stations either in raceway of furniture or away in medium duty PVC conduit of size as per number of wires being drawn (CPWD specs) with wire of of size 2.5 sq. mm for phase and neutral and 1.5 sq. mm for earth, all wires of 1100 V grade, FR, multi strand copper conductor, each work station to be provided with 3, 10 A modular type switches and 3, modular type 10 A sockets with modular type accessories like face cover, base plate, box as required. Each set of this item to include 3 switches and 3 sockets at one work station and related wiring. Maximum three work stations to be wired on one circuit. 28 SITC of RYB phase indicating lamps indicator in duly painted MS box, pre wired, including connection to mains 29 Wiring from TPN MCB DB/MCCB to Isolation Transformer to UPS with 3X10 sq. mm 1100 V grade FR PVS insulated multi strand copper wire in medium duty rigid or flexible PVC conduit as requires preferably concealed in floor/wall including chase cutting and making good of damages or on surface. 30 Supply, installation, testing and commissioning(sitc) of earthing station with copper plate 600mm x 600mm x 3 mm thick, top of the plate placed at 3 M dia below ground level with 20 mm Class-B, G.I pipe for watering as per IS 3043 with salt and charcoal including earth lead of 32X6 mm Copper connected to plate with passivated 2 mm dia x 80 mm long brass bolt, nut and double washers and laid in 50 mm B Class GI pipe up to masonry chamber and with masonry inspection pit having dimension when completed approx 0.56 M (1'-10" x 1'-10") outside dimensions and 0.45 M (1'-6") deep having 125 mm thick brick wall 75 mm brick Rmt 200 Each 8 Mtr 50 Set 20 Set 1 Mtr 5 Set 2 8
soling at the bottoms including inside, outside and top plastering and neat cementing including supplying & fixing cast iron with lockable pit cover (300mm x 300mm). including restoring the surface duly rammed as per specification mm thick brick wall 75 mm brick soling at the bottoms including inside, outside and top plastering and neat cementing including supplying & fixing cast iron with lockable pit cover (300mm x 300mm). including restoring the surface duly rammed as per specification. 31 SITC of earthing station with G.I plate 600mm x 600mm x 6 mm thick, top of the plate placed at 3 mt. dia below ground level with 20 mm Class-B, G.I pipe for watering as per IS 3043, with salt and charcoal including earth lead of 25X3 mm mm GI strip connected to plate with 12 mm dia x 80 mm long GI bolt, nut and double washers nut and double washers and laid in 40 mm B Class GI pipe up to masonry chamber and with masonry inspection pit having dimension when completed approx 0.56 M (1'-10" x 1'-10") outside dimensions and 0.45 M (1'-6") deep having 125 mm thick brick wall 75 mm brick soling at the bottoms including inside, outside and top plastering and neat cementing including supplying & fixing cast iron with lockable pit cover (300mm x 300mm). including restoring the surface duly rammed as per specification 32 Supply and laying of 32 mm x 6 mm Cu earth strip in and with 50 mm B class GI pipe underground at average depth of 450 mm below ground level including digging, refilling, ramming and making good of surface, pipe to be filled with bituminous compound. 33 Supply and laying of 32 mm x 6 mm copper earth strip on surface using Copper bar saddle and clamp or bare elsewhere as per CPWD specifications including making end connections 34 Supply and laying of 25 mm x 3 mm GI earth strip in and with 40 mm B class GI pipe underground at average depth of 450 mm below ground level including digging, refilling, ramming and making good of surface, pipe to be filled with bituminous compound 35 Supply and laying of 25 mm x 3 mm GI earth strip on surface using GI bar saddle and clamp including making end connections Set 2 Mtr 30 Mtr 30 Mtr 15 Mtr 15 36 Supply and laying of 8 swg GI wire on surface Mtr 30 37 Supply & fixing shock treatment chart in English 9
and Hindi duly framed with glass on wall with necessary screws. 38 Supply & fixing first aid box complete with all items as required by rule on M.S Bracket including mending good the damages 39 Supply & fixing 250 mm x 250 mm x 2 mm thick Danger Boards for 440 V with screws 40 Charges for liaising with UPPCL and Directorate of Electrical Safety and other statutory authorities for obtaining sanction/release of electricity connection, clearance of installation, preparation and submission of drawings, drawing approval etc. All statutory expenditure for which the aforesaid offices will issue receipts will be borne by the Bank. 41 Supply & erection of 4 Mtrs long GI pole made of 40 mm dia GI pipe 'B' class with MS welded base plate 6 mm thick size 300mm X 300mm to be installed 1.3 Mtrs below ground level in suitable designed CC foundation with footings including above ground cylindrical muffing of 100 mm thickness all around the pole (i.e. dimension at any point from outside of the pole to the edge of the muffing without plaster should be 100mm) and of height 300mm from ground level, neatly cement plastered (12 mm thick) and painted including supplying and fixing 2 Nos suitable polyethylene pipes in foundation/muffing for cable entry/exit to cable looping junction box (item s. no.2) as necessary including providing necessary earth stud/ bolts in pole, making of hole for wire entry and painting with red oxide primer and two coats of outdoor synthetic enamel paint(berger,j&n) and numbering the poles as required complete in all respect. 42 Supply & fixing of MS weather proof loop - in junction box including necessary clamps / saddles made of 6 mm thick MS strip, box fabricated from 16 swg, MS sheet and of dimension 175 mm X 125 mm X 65 mm with hinged cover, neoprene rubber gasket, locking arrangement, 1 No 10 Amp SP (10 KA) MCB, copper neutral link on porcelain insulator, 6 way copper terminal strip, internal earthing studs(2) to be fixed above muffing on pole and concealed in gate pillar for gate pillar top light, painted inside and outside with red oxide primer and two coats of outdoor synthetic enamel paint(berger,j&n) complete in all respects. No 1 Lum Sum Lum Sum No 4 No 6 10
43 Handling, fixing, installation, testing & commissioning of factory wired /LED luminaries on Pole at pole/on gate pillar complete in all respects as per standard catalogue item, including reducer, nipple, pipe bracket for gate pillar light including its fixing etc that may be required and wiring from cable looping junction box(item s. no.2) to luminaire including end termination with 3 Nos, 1.5 sq mm 1100V PVC insulated FR stranded copper conductor wire complete in all respects. 44 Supply and laying of 1100 V grade, PVC/XLPE insulated, armoured aluminum conductor cable of size 3X6 sq. mm., mostly underground ( as per CPWD specifications), partly on surface/ partly in in pre laid pipes, 45 End termination of 1100 V grade, PVC/XLPE insulated, armoured aluminum conductor cable of size 3X6 sq. mm using Dowell make Cu lugs and double compression brass cable glands as per requirement 46 SITC of earthing station with B class GI earthing pipe,4.5 M long as per IS 3043, with salt and charcoal including earth lead of 2 nos. 8 swg GI wire in underground 15 mm B class GI pipe to nearest external light pole post ( earthing station to be at least 2 M away from the pole post), with masonry inspection pit having dimension when completed approx 0.56 M (1'-10" x 1'-10") outside dimensions and 0.45 M (1'-6") deep having 125 mm thick brick wall 75 mm brick soling at the bottoms including inside, outside and top plastering and neat cementing including supplying & fixing cast iron with lockable pit cover (300mm x 300mm). including restoring the surface duly rammed as per specification 47 SITC OF 40 mm dia, B class GI pipe for suitable pole post light fitting on gate pillar. 48 Earthing interconnection between earthling stud of pole/gate pillar bracket to earthling stud of cable looping junction box with 2X8 swg GI wire No 6 Mtr 100 Set 20 Set 1 Set 4 Total NOTE: i ) Expenditure for obtaining electrical supply from UPPCL shall be as per actual. 11