PRODUCT DATA SHEET Metacaulk BOX GUARD Classified under Wall Opening Protective Material as found in UL's Fire Resistance Directory

Similar documents
Fire Barrier. Moldable Putty+ Pads Protecting Metallic and Non-Metallic Electrical Boxes

3M Fire Barrier Moldable Putty Pads MPP+ Product Data Sheet

Firestopping Submittal Package

System No. C-AJ-8133

Hilti. Outperform. Outlast. Hilti, Inc. (U.S.) en español Hilti Firestop Systems Guide 2007

Firestopping Submittal Package

System No. C-AJ-8048

CAJ. Combos. C-AJ of 5. Through Penetrations Series. Concrete. 3Fire Protection Products

RSIC-1-INSTALALTION GUIDE RSIC-1 SOUND ISOLATION CLIP

Fire Protection Products. Firestop Submittal Package FIP 1-Step Firestop Foam. Electrical Trade

3M Fire Barrier Pass-Through Device Product Description

SECTION GYPSUM BOARD

System No. HW-D-0119

TECHNICAL DATA SHEET ASMACO INTUMESCENT ACRYLIC SEALANT

FIRESTOP TECHNICAL PACK TEL: (888) 721-SEAL (7325) FAX: (888) 921-SEAL (7325)

PARKING PLAZA MEXICO COVERED GAS PUMP ISLAND PARKING BUS PARKING AREA. The Evans Group COVERD AREA TACO STAND COVERD AREA AREA FREEZER EXIT EXIT

3M Fire Protection Products 3M Interam Endothermic Mat For Commercial Buildings

Firestopping Submittal Package

JB ENGINEERING AND CODE CONSULTING, P.C Cardinal Drive Munster, IN Phone: Fax:

SLOTTED STUD WIND-LOAD & NON-LOAD BEARING DEFLECTION WALL SYSTEM. U.L. FIRE RATED Head-of-Wall Joint Systems

Firestopping Submittal Package

RSIC-V RSIC-V INSTALLATION GUIDE RSIC-V SOUND ISOLATION CLIP

RSIC-V INSTALLATION GUIDE RSIC-V SOUND ISOLATION CLIP. PAC International, Inc. Tel: (866) Fax: (866) Web Site:

FIRESTOP SUBMITTAL PACKAGE

The System U.S. Patent No. 5,913,788

3M Fire Barrier Pillows Product Description

System No. C-AJ-8096

SECTION THROUGH-PENETRATION FIRESTOP SYSTEMS

FIRESTOP SUBMITTAL PACKAGE

3M Fire Barrier Mouldable Putty

INSTALLATION MANUAL. FOOTWALL/SINKWALL (floor mount)

BXUV.V481. Fire Resistance Ratings - ANSI/UL 263. Design/System/Construction/Assembly Usage Disclaimer. Fire Resistance Ratings - ANSI/UL 263

DECEMBER Phone: Fax:

RSIC-1 SOUND ISOLATION SYSTEMS RSIC-1 INSTALLATION GUIDE

DIVISION 7 THERMAL AND MOISTURE PROTECTION SECTION PENETRATION FIRESTOPPING

St. Monica Food Pantry

Firestopping Submittal Package

Installation Guide and Safety Manual Resilmount A237R (Resilient Sound Isolation Clips)

SPECIFICATION SECTION : FIRE RATED GLASS PYRAN Platinum min. Fire Rated Ceramic Glass

SUBMITTAL INDEX. Product Datasheets: Product Approvals:

Technical Data Sheet

Fire Protection Products

3M CS-195+ Composite Sheet Product Description

RAY-CORE Structural Insulated Roof and Wall Panels

AUTHORIZATION TO MARK

SOUND SEAL 90 DRAFT / SMOKE / ACOUSTICAL SOUND SEALANT

XHBN.HW-D Joint Systems. Design/System/Construction/Assembly Usage Disclaimer. Joint Systems. System No. HW-D-0631

Installation Guide and Safety Manual QuietClip (Resilient Sound Isolation Clips)

EXCEL Medical Waste - Equipment Installation Section SECTION GYPSUM BOARD

Duct Wrap Flexible Wraps

GC-X360S-W GC-X360S-B

SECTION 3. Sec 3 TECHNICAL DATA SHEET. Cleaners / Strippers. Citrus Cleaner J Green Bean Clean

Fire Protection Products

Installation Guide and Safety Manual Resilient Sound Isolation Clips (SIC Clips)

Installation Guide and Safety Manual

OUTLET PUTTY PADS SPECIFICATIONS

LISTING INFORMATION OF Mitek Design No. MCI/WI SPEC ID: MiTek Canada, Inc. 100 Industrial Road Bradford, ON L3Z 3G7 Canada

RSIC-1. RSIC-1, the Low Cost, High Performance, Noise control Solution. RSIC-1 specifications:

LISTING INFORMATION OF International Fireproof Technology Inc. - Joint Systems SPEC ID: 43848

FORM FOOTWALL. FORM FOOTWALL (floating) (floating) Installation Manual

BXUV.U415 - Fire Resistance Ratings - ANSI/UL 263. Fire Resistance Ratings - ANSI/UL 263

EPV Pellet Vent Pellet Stove Venting System Installation Instructions

research report Fire Resistance Ratings of Load Bearing Steel Stud Walls With Gypsum Wallboard Protection RESEARCH REPORT RP REVISION 2007

UL Design System HW-D-1012 continued

SECTION GYPSUM BOARD

FIRESTOP JOINT SPRAY CFS-SP WB. 2mm (0.079") WET FILM ± 7.5 ± 5

SPECIFICATION SECTION : FIRE RATED GLASS & FRAMING PYRAN Platinum F min. Fire Rated Filmed Ceramic Glass

INSTALLATION MANUAL SURFACE-MOUNTED HEADWALL

Fire Barrier Duct Wrap 615+

Design No. HI/BP PERIMETER FIRE BARRIER SYSTEM Hilti, Inc. ASTM E 2307 Table 1

installation instructions Combination Fire & Smoke Damper

SUBMITTAL INDEX. Product Datasheets: Product Approvals:

Instruction and Safety Manual Resilient Sound Isolation Clips (SIC Clips)

SPECIFICATION DIVISION 7 NUMBER SECTION DESCRIPTION DIVISION 07 THERMAL AND MOISTURE PROTECTION SECTION THROUGH-PENETRATION FIRESTOP SYSTEMS

FIRE RESISTANCE TESTS OF BRICK VENEER / WOOD FRAME WALLS J. GREGG BORCHELT

XHBN.FF-D Joint Systems. Joint Systems. System No. FF-D-3008

LISTING INFORMATION OF International Beams - IB Series Joists SPEC ID: 27316

Gypsum Board Systems Manual

Firestopping Submittal Package

THERMAL AND MOISTURE PROTECTION

Monolithic Isolation Fittings

SECTION STRUCTURAL INSULATED PANELS

SECTION FIRESTOPPING

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: DEMILEC (USA) INC.

SECTION WALL AND DOOR PROTECTION

Following contains common verbiage found in major model building codes and has been edited for the purpose of inclusion on this CD.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: PARKLEX USA

BROADCAST: M BLOCKS, PLUGS, PLANKS NEW PRODUCT LAUNCH Date: June 16, 2016 Issued by: George Yoshida, Ted Colwell

Session: Firestop - Let s Walk a Project and Look at Firestop Together

Protecting Penetrations in Fire Rated Construction

INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS UNIFORM EVALUATION SERVICES

Joint Systems. System No. FF-D-0044

Fire Protection Products

System No. HW-D-0548

Firestopping Submittal Package

Ultralane 781A/B. Product Datasheet. Polyurethane Encapsulation System

Triton BK Backer Board & Tile Underlayment

Transcription:

PRODUCT DATA SHEET Metacaulk BOX GUARD Classified under Wall Opening Protective Material as found in UL's Fire Resistance Directory January 2011 1. Product Description Metacaulk BOX GUARD is a one component fire rated pad for use in electrical boxes. It is inserted on the inside back wall of an electrical box, and is a highly intumescent firestop material. When exposed to fire, Metacaulk BOX GUARD will expand forming a char that will seal off the opening and prevent the spread of flames and limit the temperature rise on the unexposed surfaces. Metacaulk BOX GUARD is applied by hand, and must comply with NEC 314.16 (formerly 370.16) or other applicable codes. U.S. Patent No. 6,207,085 & 6,252,167. Metacaulk BOX GUARD Features * Easy to Install * Cost Effective * Highly Intumescent * Adheres to Back of Electrical Box * Non-Conductive * Dielectric Breakdown Voltage 22V/mil (ASTM D 149) 2. Material Properties Asbestos Fillers Solvents Hazardous Ingredients None None None Sizes (Approx.) Single box: 1 13/16" x 2 13/16" x 1/4" 47 mm X 71 mm x 6 mm Double box (two sizes) 1) 3 11/16" x 3 3/4" x 1/4" 94 mm x 95 mm x 6 mm 2) 4 3/8" x 4 3/8" x 1/4" 111 mm x 111 mm x 6 mm Color Black ASTM E 84, UL 723 Tunnel Test Flame Spread 5 Smoke Index 5 Sound Transmission Class STC Rating 55* *Tested in a UL 411 wall assembly/section to ASTM E90 3. Applications Use Metacaulk BOX GUARD on inside back panel of electrical boxes to maintain the integrity of fire rated wall assemblies restricting the passage of flames and limiting the temperature rise on the unexposed surfaces. When Metacaulk Box GUARD is used as directed, the horizontal separation between outlet boxes on opposite sides of the wall may be less than 24 inches. 4. Installation Instructions Metacaulk BOX GUARD is easy to install. Make sure rear surface is clean, dry and not contaminated. Remove protective paper from tape and stick pad to inside back wall of electrical box*. Center pad from top and bottom of box. Install switch, or outlet. Use the single pad for a single box (2" x 4"), and double pad for double box 4" x 4", and 4 3/8" x 4 3/8" pad for 4 11/16" x 4 11/16"box. Make sure installation complies with NEC 314.16 (formerly 370.16) or other applicable codes. Consult UL Directory for complete instructions and system listings. *If necessary, a maximum 3/8" hole may be created or the pad may be slit from one edge to allow easier access to the electrical box ground screw. 5. Testing Data Metacaulk BOX GUARD is classified by Underwriters Laboratories, Inc. under Wall Opening Protective Material as found in the Fire Resistance Directory. For specific test criteria see UL Fire Resistance Directory or call REC- TORSEAL.

METACAULK BOX GUARD Metacaulk BOX GUARD was tested at positive pressure for a minimum.01 inches of water. The basic standard used to investigate products is UL 263/ ASTM E-119, "Fire Tests of Building Construction and Materials". Complies to Required Environmental Exposure Testing of Accelerated Aging and High Humidity as per UL 1479 Fire Test of Through-Penetration Firestops. 6. Storage & Handling Metacaulk BOX GUARD should be stored in a cool, dry place. Keep products stored under protective cover, in their original containers. A stock rotation program is recommended. 7. Availability Metacaulk BOX GUARD is available as pads measuring, single 1 13/16" x 2 13/16" x 1/4" (47 mm x 71 mm x 6 mm) and two double pads, one measuring 3 3/4" x 3 11/16" x 1/4" (94 mm x 95 mm x 6 mm) and one measuring 4 3/8" x 4 3/8" x 1/4" (111 mm x 111 mm x 6 mm). 8. Limitations To be used only in the tested configurations or as recommended by RectorSeal. 9. CAUTIONS FOR CHEMICAL EMERGEN- CY, SPILL, LEAK, FIRE, EX- POSURE OR ACCIDENT, CALL CHEMTREC - DAY OR NIGHT 1-800- 424-9300. PRECAUTIONS: Do not take internally. May be harmful if swallowed. May cause eye and skin irritation if prolonged or repeated contact occurs. Wash after handling. FIRST AID: For any overexposure, get immediate medical attention after first aid is given. Eyes- Flush 15 minutes with clean water. Skin-Wash with soap and water. Ingestion-Only if conscious, give large amounts of water and call physician. FIRE AND SPILLS: Use water fog, CO 2, foam, or dry chemicals. Wipe up spills to prevent footing hazard. Clean up with scrapers and water. STORAGE AND HANDLING: Store away from heat sources. KEEP OUT OF REACH OF CHILDREN. For additional information, refer to Material Safety Data Sheet. For additional technical service, call: 1-800-231-3345 Fax: 1-800-452-2824 RECTORSEAL 2601 Spenwick Drive Houston, Texas 77055 WWW.RECTORSEAL.COM WWW.METACAULK.COM NOTE: Not to be used on plastic boxes. For additional information refer to UL Directory. Retain a copy of the Product Data Sheet for review by the Inspector. 10. LIMITED WARRANTY RectorSeal makes the Limited Express Warranty that when the instructions for storage and handling of our products are followed we warrant our products to be free from defects. THIS LIMITED EXPRESS WARRANTY IS EXPRESSLY IN LIEU OF ANY OTHER EXPRESS OR IMPLIED WARRANTIES, INCLUDING ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, AND OF ANY OTHER OBLIGATION ON THE PART OF RECTORSEAL. The sole remedy for breach of the Limited Express Warranty shall be the refund of the purchase price. All other liability is negated and disclaimed, and RectorSeal shall not be liable for incidental or consequential damages. Suggestions and recommendations covering the use of our products are based on our past experience and laboratory findings. However, as we have no control as to the methods and conditions of application, we only assume responsibility for the uniformity of our products within manufacturing tolerances. A-11

Issued to: RECTORSEAL 2601 SPENWICK DR HOUSTON, TX 77055 USA This is to certify that representative samples of Wall-opening Protective Materials Metacaulk Fire Rated Putty Pads, Metacaulk Box Guard Inserts and Metacaulk Cover Guard Gaskets. See Addendum Page Have been investigated by UL in accordance with the Standard(s) indicated on this Certificate. Standard(s) for Safety: Additional Information: ANSI/UL 263, "Fire Tests of Building Construction and Materials." See the UL Online Certifications Directory at www.ul.com/database for additional information Only those products bearing the UL Classification Mark should be considered as being covered by UL s Classification and Follow-Up Service. The UL Classification Mark includes: UL in a circle: with the word CLASSIFIED (as shown); a control number (may be alphanumeric) assigned by UL; a statement to indicate the extent of UL s evaluation of the product; and the product category name (product identity) as indicated in the appropriate UL Directory. Look for the UL Classification Mark on the product. Any information and documentation involving UL Mark services are provided on behalf of (UL) or any authorized licensee of UL. For questions, please Page 1 of 8

Metacaulk Box Guard Inserts for use with max 2-1/8 by 4 by 2-1/8 in deep. flush device UL Listed Metallic Outlet Boxes without internal clamps in 2 h fire rated gypsum board wall assemblies framed with min 3-1/2 in. deep steel studs and constructed of the materials and in the manner specified in the individual U400 Series Wall and Partition Designs in the Fire Resistance Directory. One 47 mm wide by 71 mm high insert adhered to the interior back wall of the outlet box in accordance with the installation instructions supplied with the product. Installation to comply with the National Electrical code, (NFPA 70). Outlet boxes installed with steel cover plates. When protective material is used within outlet boxes on both sides of wall as directed, the horizontal separation between outlet boxes on opposite sides of the wall may be less than 24 in. provided that the boxes are not installed back-to-back. Metacaulk Box Guard Inserts for use with max 4 by 4 by 2-1/8 in deep flush device UL Listed Metallic Outlet Boxes without internal clamps in 2 hr fire rated gypsum board wall assemblies framed individual U400 Series Wall and Partition Designs in the Fire Resistance Directory. One 94 mm wide by 95 mm high insert adhered to the interior back wall of the outlet box in accordance with the installation instructions supplied with the product. Installation to comply with the National Electrical Code, (NFPA 70). Outlet boxes installed with steel cover plates. When protective material is used within outlet boxes on both sides of wall as directed, the horizontal separation between outlet boxes on opposite sides of the wall may be less than 24 in. provided that the boxes are not installed back-to-back. Metacaulk Box Guard Inserts for use with max 4-1/2 by 8-1/2 by 1-5/8 in deep. flush device UL Listed Metallic Outlet Boxes without internal clamps in 2 hr fire rated gypsum board wall assemblies framed with min 3-1/2 in.deep steel studs and constructed of the materials and in the manner specified in the individual U400 Series Wall and Partition Designs in the Fire Resistance Directory. Two 94 mm wide by 95 mm high inserts are evenly spaced and adhered to the interior back wall of the outlet box in accordance with the installation instructions supplied with the product. Installation to comply with the National Electrical Code, (NFPA 70). Min 3/4 in. deep plaster rings installed over outlet box. After installation of gypsum board, nom 1/4 in. thickness of RectorSeal Metacaulk 1000 or Biostop 500+ Sealant, bearing the UL Classification Marking for Fill, Void or Cavity Materials, applied between the base layer of wallboard and the plaster ring. Outlet boxes installed with steel cover plates. When protective material is used within and around outlet boxes on both sides of wall as directed, the horizontal separation between outlet boxes on opposite sides of the wall may be less than 24 in. provided that the boxes are not installed back-to-back. Metacaulk Box Guard Inserts for use with max 4 by 4 by 1-1/2 in. deep flush device UL Listed Metallic Outlet Boxes without internal clamps in 1 hr fire rated gypsum board wall assemblies framed with min 3-1/2 in.deep wood studs and with max 4 by 4 by 2-1/8 in. deep flush device UL Listed Metallic Outlet Boxes without internal clamps in 1 hr fire rated gypsum board wall assemblies framed with min 3-1/2 in.deep steel studs and constructed of the materials and in the manner specified in the individual U300 or U400 Series Wall and Partition Designs in the Fire Resistance Directory. One 94 mm wide by 95 mm high insert adhered to the interior back wall of the outlet box in accordance with the installation instructions supplied with the product. Installation to comply with the National Electrical Code, (NFPA 70). Outlet boxes installed with plastic cover plates. When protective material is used within outlet boxes on both sides of wall as directed, the horizontal separation between outlet boxes on opposite sides of the wall may be less than 24 in. provided that the boxes are not installed back-to-back. Metacaulk Box Guard Inserts for use with 4-11/16 by 4-11/16 by 2-1/8 in. deep flush device UL Listed Metallic Outlet Boxes without internal clamps in 1 hr fire rated gypsum board wall assemblies framed with min 3-1/2 in.deep steel studs and constructed of the materials and in the manner specified in the individual U400 Series Wall and Partition Designs in the Fire Resistance Directory. One 111 mm wide by 111 mm high insert adhered to the interior back wall of the outlet box in accordance with the installation instructions supplied with the product. Smaller sized inserts may be cut and combined to achieve the 111 mm by 111 mm coverage and adhered to the interior back wall of the outlet box. Installation to comply with the National Electrical Code, (NFPA 70). Outlet boxes installed with plastic or steel cover plates. When protective material is used within outlet boxes on both sides of wall as directed, the horizontal separation between outlet boxes on opposite sides of the wall may be less than 24 in. provided that the boxes are not installed back-to-back. Metacaulk Box Guard Inserts for use with 4-11/16 by 4-11/16 by 2-1/8 in. deep flush device UL Listed Metallic Outlet Boxes without internal clamps in 2 hr fire rated gypsum board wall assemblies framed with min 3-1/2 in. deep steel studs and constructed of the materials and in the manner specified in the individual U400 Series Wall and Partition Designs in the Fire Resistance Directory. One 111 mm wide by 111 mm high insert adhered to the interior back wall of the outlet box in accordance with the installation instructions supplied with the product. Smaller sized inserts may be cut and combined to achieve the 111 mm by 111 mm coverage and adhered to the interior back wall of the outlet box. Installation to comply with the National Electrical Code, (NFPA 70). Outlet boxes installed with steel cover plates. When protective material is used within outlet boxes on both sides of wall as directed, the horizontal separation between outlet boxes on opposite sides of the wall may be less than 24 in. provided that the boxes are not installed back-to-back. Metacaulk Box Guard Inserts for use with max 3-3/4 by 5-1/2 by 2-1/2 in deep flush device UL Listed Metallic Outlet Boxes without internal clamps in 1 hr fire rated gypsum board wall assemblies framed with min 3-1/2 in. deep steel or wood studs and constructed of the materials and in the manner specified in the individual U300 or U400 Series Wall and Partition Designs in the Fire Resistance Directory. One 94 mm wide by 95 mm high and one 47 mm wide by 71 mm high inserts adhered to the interior back wall of the outlet box in accordance with the installation instructions supplied with the product. Installation to comply with the National Electrical Code, (NFPA 70). Outlet boxes installed with steel cover plates. When protective material is used within outlet boxes on both sides of wall as directed, the horizontal separation between outlet boxes on opposite sides of the wall may be less than 24 in. provided that the boxes are not installed back-to-back. Metacaulk Box Guard Inserts for use with 4-3/8 by 4-7/8 by 2-1/4 in. deep flush device UL Listed Metallic Outlet Boxes without internal clamps in 1 hr fire rated gypsum board wall assemblies framed with min 3-1/2 in. deep steel studs and constructed of the materials and in the manner specified in the individual U400 Series Wall and Partition Designs in the Fire Resistance Directory. One 111 mm wide by 111 mm high insert adhered to the interior back wall of the outlet box in accordance with the installation instructions supplied with the product. Smaller sized inserts may be cut and

combined to achieve the 111 mm by 111 mm coverage and adhered to the interior back wall of the outlet box. Installation to comply with the National Electrical Code, (NFPA 70). Outlet boxes installed with plastic or steel cover plates. When protective material is used within outlet boxes on both sides of wall as directed, the horizontal separation between outlet boxes on opposite sides of the wall may be less than 24 in. provided that the boxes are not installed back-to-back. Metacaulk Box Guard Inserts, for use with 4-3/8 by 4-7/8 by 2-1/4 in. deep flush device UL Listed Metallic Outlet Boxes without internal clamps in 2 hr fire rated gypsum board wall assemblies framed with min 3-1/2 in. deep steel studs and constructed of the materials and in the manner specified in the individual U400 Series Wall and Partition Designs in the Fire Resistance Directory. One 111 mm wide by 111 mm high insert adhered to the interior back wall of the outlet box in accordance with the installation instructions supplied with the product. Smaller sized inserts may be cut and combined to achieve the 111 mm by 111 mm coverage and adhered to the interior back wall of the outlet box. Installation to comply with the National Electrical Code, (NFPA 70). Outlet boxes installed with steel cover plates. When protective material is used within outlet boxes on both sides of wall as directed, the horizontal separation between outlet boxes on opposite sides of the wall may be less than 24 in. provided that the boxes are not installed back-to-back. Metacaulk Box Guard Inserts for use with max 4-11/16 by 4-11/16 by 2-1/8 in. flush device UL Listed Metallic Outlet Boxes installed with steel mud rings and plastic or steel cover plates in 1 h or 2 h fire rated gypsum board wall assemblies framed with min 3-1/2 in. deep wood or steel studs and constructed of the materials and in the manner specified in the individual U300, U400 or V400 Series Wall and Partition Designs in the Fire Resistance Directory. Min 3-1/2 in. thick fiberglass (min 0.5 pcf) or mineral wool (min 4.0 pcf) batt insulation is to be installed within the wall cavity. One 4-3/8 by 4-3/8 in. insert adhered to the interior back wall of the outlet box in accordance with the instructions supplied with the product. Installation to comply with the National Electrical Code (NFPA 70). When protective material is used within outlet boxes on both sides of the wall as directed, the horizontal separation between outlet boxes on opposite sides of the wall may be less than 24 in. provided that the boxes are not installed back-to-back. Metacaulk Box Guard Inserts for use with max 4-11/16 by 4-11/16 by 2-1/8 in. flush device UL Listed Metallic Outlet Boxes installed with steel mud rings and plastic or steel cover plates in 1 h fire rated gypsum board wall assemblies framed with min 6 in. deep wood or steel studs and constructed of the materials and in the manner specified in the individual U300, U400 or V400 Series Wall and Partition Designs in the Fire Resistance Directory. Nom 6-1/2 in. thick fiberglass insulation (min 0.5 pcf) is to be installed within the wall cavity. One 4-3/8 by 4-3/8 in. insert adhered to the interior back wall of the outlet box in accordance with the instructions supplied with the product. Installation to comply with the National Electrical Code (NFPA 70). When back to back boxes are inter connected a 1/4 in. depth of Metacaulk 1000 in the open end of each conduit of the box. UL does not furnish a detail drawing for these listings

This is to certify that representative samples of the product as specified on this certificate were tested according to the current UL requirements. Metacaulk Fire Rated Putty Pads for use with max 4 by 4 in. flush device UL Listed Metallic Outlet Boxes installed with steel cover plates in 1 and 2 h fire rated gypsum board wall assemblies framed with min 3-1/2 in. deep wood or steel studs and constructed of the materials and in the manner specified in the individual U300 or U400 Series Wall and Partition Designs in the Fire Resistance Directory. Min 1/8 in. thick moldable putty pads are to be installed to completely cover the exterior surfaces of the outlet box (except for the side of the outlet box against the stud) and completely seal against the stud within the stud cavity. When moldable putty pad outlet box protective material is used on boxes on both sides of wall as directed, the horizontal separation between outlet boxes on opposite sides of the wall may be less than 24 in. provided that the boxes are not installed back-to-back. Metacaulk Fire Rated Putty Pads for use with max 2-3/16 by 3-3/4 by 2-11/32 in. deep UL Listed Nonmetallic Outlet Boxes manufactured by Pass & Seymour Inc. under the tradename Slater, made from polyvinyl chloride and bearing a 2 h rating under the "Outlet Boxes and Fittings Classified for Fire Resistance" category in the Fire Resistance Directory. Putty pads and boxes for use in 2 h fire rated gypsum board wall assemblies framed with min 3-1/2 in. deep wood or steel studs and constructed of the materials and in the manner specified in the individual U300 or U400 Series Wall and Partition Designs in the Fire Resistance Directory. Outlet box secured to studs by means of mounting tab supplied with the outlet box. Min 1/8 in. thick moldable putty pads are to be installed to completely cover the exterior surfaces of the outlet box including the side of the outlet box against the stud. Outlet boxes installed with steel or plastic cover plates. When moldable putty pad outlet box protective material is used on boxes on both sides of wall as directed, the horizontal separation between outlet boxes on opposite sides of the wall may be less than 24 in. provided that the boxes are not installed back-to-back. Metacaulk fire Rated Putty Pads for use with max 4 by 4 in. flush device UL Listed Metallic Outlet Boxes Installed with steel or plastic cover plates in 1 h fire rated gypsum board wall assemblies framed individual U400 Series Wall and Partition Designs in the Fire Resistance Directory. Two layers of min 1/8 in. thick moldable putty pads are to be installed to completely cover the exterior surfaces of the outlet box including the side of the outlet box against the stud. Nom 1/2 in. plaster rings installed over outlet boxes. After installation of gypsum board, nom 1/4 in. thickness of RectorSeal Metacaulk 1000 or Biostop 500+ Sealant, bearing the UL Classification Marking for Fill, Void or Cavity Materials, applied between gypsum board and the plaster ring. When moldable putty pad outlet box protective material and fill material are used on boxes on both sides of wall as directed, the horizontal separation between outlet boxes on opposite sides of the wall may be less than 24 in. provided that the boxes are not installed back-to-back. Any information and documentation involving UL Mark services are provided on behalf of (UL) or any authorized licensee of UL. For questions, please Page 2 of 8

Metacaulk Box Guard Inserts for use with max 2-1/8 by 4 by 2-1/8 in deep. flush device UL Listed Metallic Outlet Boxes without internal clamps in 2 h fire rated gypsum board wall assemblies framed individual U400 Series Wall and Partition Designs in the Fire Resistance Directory. One 47 mm wide by 71 mm high insert adhered to the interior back wall of the outlet box in accordance with the installation instructions supplied with the product. Installation to comply with the National Electrical code, (NFPA 70). Outlet boxes installed with steel cover plates. A max 3/8 in. diam opening at one edge may be provided to permit access to the electrical box ground screw. When protective material is used within outlet boxes on both sides of wall as directed, the horizontal separation between outlet boxes on opposite sides of the wall may be less than 24 in. provided that the boxes are not installed back-to-back. Metacaulk Box Guard Inserts for use with max 4 by 4 by 2-1/8 in deep flush device UL Listed Metallic Outlet Boxes without internal clamps in 2 hr fire rated gypsum board wall assemblies framed with min 3-1/2 in. deep steel studs and constructed of the materials and in the manner specified in the individual U400 Series Wall and Partition Designs in the Fire Resistance Directory. One 94 mm wide by 95 mm high insert adhered to the interior back wall of the outlet box in accordance with the installation instructions supplied with the product. Installation to comply with the National Electrical Code, (NFPA 70). Outlet boxes installed with steel cover plates. A max 3/8 in. diam opening at one edge may be provided to permit access to the electrical box ground screw. When protective material is used within outlet boxes on both sides of wall as directed, the horizontal separation between outlet boxes on opposite sides of the wall may be less than 24 in. provided that the boxes are not installed back-to-back. Metacaulk Fire Rated Putty Pads for use with max 4 by 3-3/4 by 3 in. deep UL Listed Nonmetallic Outlet Boxes manufactured by Carlon Electrical Products, made from polyvinyl chloride, and bearing a 2 hr rating under the "Outlet Boxes and Fittings Classified for Fire Resistance" category in the Fire Resistance Directory. Putty pads and boxes for use in 1 and 2 hr fire rated gypsum board wall assemblies framed with min 3-1/2 in. deep wood studs and constructed of the materials and in the manner specified in the individual U300 Series Wall and Partition Designs in the Fire Resistance Directory. Outlet box secured to wood stud by means of two nailing tabs in conjunction wit nails supplied with the outlet box. Min 1/8 in. thick moldable putty pads are to be installed to completely cover the exterior surfaces of the outlet box (except for the side of the outlet box against the stud) including the nailing tab and completely seal against the stud within the stud cavity. Outlet boxes installed with steel or plastic cover plates. When moldable putty pad outlet box protective material is used on boxes on both sides of wall as directed, the horizontal separation between outlet boxes on opposite sides of the wall may be less than 24 in. provided that the boxes are not installed back-to-back. Any information and documentation involving UL Mark services are provided on behalf of (UL) or any authorized licensee of UL. For questions, please Page 3 of 8

Metacaulk Box Guard Inserts for use with max 4-1/2 by 8-1/2 by 1-5/8 in deep flush device UL Listed Metallic Outlet Boxes without internal clamps in 2 hr fire rated gypsum board wall assemblies framed individual U400 Series Wall and Partition Designs in the Fire Resistance Directory. Two 94 mm wide by 95 mm high inserts are evenly spaced and adhered to the interior back wall of the outlet box in accordance with the installation instructions supplied with the product. Installation to comply with the National Electrical Code, (NFPA 70). Min 3/4 in. deep plaster rings installed over outlet box. After installation of gypsum board, nom 1/4 in. thickness of RectorSeal Metacaulk 1000 or Biostop 500+ Sealant, bearing the UL Classification Marking for Fill, Void or Cavity Materials, applied between the base layer of wallboard and the plaster ring. Outlet boxes installed with steel cover plates. A max 3/8 in. diam opening at one edge may be provided to permit access to the electrical box ground screw. When protective material is used within and around outlet boxes on both sides of wall as directed, the horizontal separation between outlet boxes on opposite sides of the wall may be less than 24 in. provided that the boxes are not installed back-to-back. Metacaulk Box Guard Inserts for use with max 4 by 4 by 1-1/2 in. deep flush device UL Listed Metallic Outlet Boxes without internal clamps in 1 hr fire rated gypsum board wall assemblies framed with min 3-1/2 in. deep wood studs and with max 4 by 4 by 2-1/8 in. deep flush device UL Listed Metallic Outlet Boxes without internal clamps in 1 hr fire rated gypsum board wall assemblies framed with min 3-1/2 in. deep steel studs and constructed of the materials and in the manner specified in the individual U300 or U400 Series Wall and Partition Designs in the Fire Resistance Directory. One 94 mm wide by 95 mm high insert adhered to the interior back wall of the outlet box in accordance with the installation instructions supplied with the product. Installation to comply with the National Electrical Code, (NFPA 70). Outlet boxes installed with plastic cover plates. A max 3/8 in. diam opening at one edge may be provided to permit access to the electrical box ground screw. When protective material is used within outlet boxes on both sides of wall as directed, the horizontal separation between outlet boxes on opposite sides of the wall may be less than 24 in. provided that the boxes are not installed back-to-back. Metacaulk Cover Guard Gaskets for use with max 4-11/16 by 4-11/16 in. flush device UL Listed Metallic Outlet Boxes installed with steel or plastic cover plates in 2 h fire rated gypsum board wall assemblies framed with min 3-1/2 in. deep steel studs and constructed of the materials and in the manner specified in the individual U400 Series Wall and Partition Designs in the Fire Resistance Directory. Nom 2 by 4 in. or 4 by 4 in. gaskets to be installed on the inside of single gang or double gang cover plates, respectively, prior to attachment to device. Installation to comply with the National Electrical Code, (NFPA 70). When protective material is used within cover plates on outlet boxes on each sides of wall as directed, the horizontal separation between outlet boxes on opposite sides of the wall may be less than 24 in. provided the boxes are not installed back-to-back. Any information and documentation involving UL Mark services are provided on behalf of (UL) or any authorized licensee of UL. For questions, please Page 4 of 8

Metacaulk Cover Guard Gaskets for use with max 4-11/16 by 4-11/16 in. flush device UL Listed Metallic Outlet Boxes installed with steel or plastic cover plates in 1 h fire rated gypsum board wall assemblies framed with min 3-1/2 in. deep wood or steel studs and constructed of the materials and in the manner specified in the individual U300, U400 or V400 Series Wall and Partition Designs in the Fire Resistance Directory. Min 4 in. thick fiberglass (min 0.5 pcf) or mineral wool (min 4.0 pcf) batt insulation is to be installed within the wall cavity. Nom 2 by 4 in. or 4 by 4 in. gaskets to be installed on the inside of single gang or double gang cover plates, respectively, prior to attachment to device. Installation to comply with the National Electrical Code, (NFPA 70). When protective material is used within cover plates on outlet boxes on each sides of wall as directed, the horizontal separation between outlet boxes on opposite sides of the wall may be less than 24 in. provided the boxes are not installed back-to-back. Metacaulk Cover Guard Gaskets for use with max 4-11/16 by 4-11/16 in. flush device UL Listed Metallic Outlet Boxes installed with Decora style steel or plastic cover plates in 1 h fire rated gypsum board wall assemblies framed with min 3-1/2 in. deep wood or steel studs and constructed of the materials and in the manner specified in the individual U300, U400 or V400 Series Wall and Partition Designs in the Fire Resistance Directory. Min 4 in. thick fiberglass (min 0.5 pcf) or mineral wool (min 4.0 pcf) batt insulation is to be installed within the wall cavity. Nom 4 by 4 in. gaskets to be installed on the inside of double gang cover plates prior to attachment to device. Installation to comply with the National Electrical Code, (NFPA 70). When protective material is used within cover plates on outlet boxes on each sides of wall as directed, the horizontal separation between outlet boxes on opposite sides of the wall may be less than 24 in. provided the boxes are not installed back-to-back. Metacaulk Box Guard Inserts for use with 4-11/16 by 4-11/16 by 2-1/8 in. deep flush device UL Listed Metallic Outlet Boxes without internal clamps in 1 hr fire rated gypsum board wall assemblies framed individual U400 Series Wall and Partition Designs in the Fire Resistance Directory. One 111 mm wide by 111 mm high insert adhered to the interior back wall of the outlet box in accordance with the installation instructions supplied with the product. Smaller sized inserts may be cut and combined to achieve the 111 mm by 111 mm coverage and adhered to the interior back wall of the outlet box. Installation to comply with the National Electrical Code, (NFPA 70). Outlet boxes installed with plastic or steel cover plates. A max 3/8 in. diam opening at one edge may be provided to permit access to the electrical box ground screw. When protective material is used within outlet boxes on both sides of wall as directed, the horizontal separation between outlet boxes on opposite sides of the wall may be less than 24 in. provided that the boxes are not installed back-to-back. Any information and documentation involving UL Mark services are provided on behalf of (UL) or any authorized licensee of UL. For questions, please Page 5 of 8

Metacaulk Box Guard Inserts for use with 4-11/16 by 4-11/16 by 2-1/8 in. deep flush device UL Listed Metallic Outlet Boxes without internal clamps in 2 hr fire rated gypsum board wall assemblies framed individual U400 Series Wall and Partition Designs in the Fire Resistance Directory. One 111 mm wide by 111 mm high insert adhered to the interior back wall of the outlet box in accordance with the installation instructions supplied with the product. Smaller sized inserts may be cut and combined to achieve the 111 mm by 111 mm coverage and adhered to the interior back wall of the outlet box. A max 3/8 in. diam opening at one edge may be provided to permit access to the electrical box ground screw. Installation to comply with the National Electrical Code, (NFPA 70). Outlet boxes installed with steel cover plates. When protective material is used within outlet boxes on both sides of wall as directed, the horizontal separation between outlet boxes on opposite sides of the wall may be less than 24 in. provided that the boxes are not installed back-to-back. Metacaulk Box Guard Inserts for use with max 3-3/4 by 5-1/2 by 2-1/2 in deep flush device UL Listed Metallic Outlet Boxes without internal clamps in 1 hr fire rated gypsum board wall assemblies framed with min 3-1/2 in. deep steel or wood studs and constructed of the materials and in the manner specified in the individual U300 or U400 Series Wall and Partition Designs in the Fire Resistance Directory. One 94 mm wide by 95 mm high and one 47 mm wide by 71 mm high inserts adhered to the interior back wall of the outlet box in accordance with the installation instructions supplied with the product. Installation to comply with the National Electrical Code, (NFPA 70). Outlet boxes installed with steel cover plates. A max 3/8 in. diam opening at one edge may be provided to permit access to the electrical box ground screw. When protective material is used within outlet boxes on both sides of wall as directed, the horizontal separation between outlet boxes on opposite sides of the wall may be less than 24 in. provided that the boxes are not installed back-to-back. Metacaulk Box Guard Inserts for use with 4-3/8 by 4-7/8 by 2-1/4 in. deep flush device UL Listed Metallic Outlet Boxes without internal clamps in 1 hr fire rated gypsum board wall assemblies framed individual U400 Series Wall and Partition Designs in the Fire Resistance Directory. One 111 mm wide by 111 mm high insert adhered to the interior back wall of the outlet box in accordance with the installation instructions supplied with the product. Smaller sized inserts may be cut and combined to achieve the 111 mm by 111 mm coverage and adhered to the interior back wall of the outlet box. Installation to comply with the National Electrical Code, (NFPA 70). Outlet boxes installed with plastic or steel cover plates. A max 3/8 in. diam opening at one edge may be provided to permit access to the electrical box ground screw. When protective material is used within outlet boxes on both sides of wall as directed, the horizontal separation between outlet boxes on opposite sides of the wall may be less than 24 in. provided that the boxes are not installed back-to-back. Any information and documentation involving UL Mark services are provided on behalf of (UL) or any authorized licensee of UL. For questions, please Page 6 of 8

Metacaulk Box Guard Inserts for use with 4-3/8 by 4-7/8 by 2-1/4 in. deep flush device UL Listed Metallic Outlet Boxes without internal clamps in 2 hr fire rated gypsum board wall assemblies framed individual U400 Series Wall and Partition Designs in the Fire Resistance Directory. One 111 mm wide by 111 mm high insert adhered to the interior back wall of the outlet box in accordance with the installation instructions supplied with the product. Smaller sized inserts may be cut and combined to achieve the 111 mm by 111 mm coverage and adhered to the interior back wall of the outlet box. Installation to comply with the National Electrical Code, (NFPA 70). Outlet boxes installed with steel cover plates. A max 3/8 in. diam opening at one edge may be provided to permit access to the electrical box ground screw. When protective material is used within outlet boxes on both sides of wall as directed, the horizontal separation between outlet boxes on opposite sides of the wall may be less than 24 in. provided that the boxes are not installed back-to-back. Metacaulk Box Guard Inserts for use with max 4-11/16 by 4-11/16 by 2-1/8 in. flush device UL Listed Metallic Outlet Boxes installed with steel mud rings and plastic or steel cover plates in 1 h or 2 h fire rated gypsum board wall assemblies framed with min 3-1/2 in. deep wood or steel studs and constructed of the materials and in the manner specified in the individual U300, U400 or V400 Series Wall and Partition Designs in the Fire Resistance Directory. Min 3-1/2 in. thick fiberglass (min 0.5 pcf) or mineral wool (min 4.0 pcf) batt insulation is to be installed within the wall cavity. One 4-3/8 by 4-3/8 in. insert adhered to the interior back wall of the outlet box in accordance with the instructions supplied with the product. Installation to comply with the National Electrical Code (NFPA 70). A max 3/8 in. diam opening at one edge may be provided to permit access to the electrical box ground screw. When protective material is used within outlet boxes on both sides of the wall as directed, the horizontal separation between outlet boxes on opposite sides of the wall may be less than 24 in. provided that the boxes are not installed back-to-back. Metacaulk Box Guard Inserts for use with max 4-11/16 by 4-11/16 by 2-1/8 in. flush device UL Listed Metallic Outlet Boxes installed with steel mud rings and plastic or steel cover plates in 1 h fire rated gypsum board wall assemblies framed with min 6 in. deep wood or steel studs and constructed of the materials and in the manner specified in the individual U300, U400 or V400 Series Wall and Partition Designs in the Fire Resistance Directory. Nom 6-1/2 in. thick fiberglass insulation (min 0.5 pcf) is to be installed within the wall cavity. One 4-3/8 by 4-3/8 in. insert adhered to the interior back wall of the outlet box in accordance with the instructions supplied with the product. Installation to comply with the National Electrical Code (NFPA 70). A max 3/8 in. diam opening at one edge may be provided to permit access to the electrical box ground screw. When back to back boxes are inter connected a 1/4 in. depth of Metacaulk 1000 in the open end of each conduit of the box. Any information and documentation involving UL Mark services are provided on behalf of (UL) or any authorized licensee of UL. For questions, please Page 7 of 8

Metacaulk Box Guard Inserts for use with max 4-11/16 by 4-11/16 by 2 1/8 in. flush device UL Listed Metallic Outlet Boxes installed with steel mud rings and plastic or steel cover plates in 1 h or 2 h fire rated gypsum board wall assemblies framed with min 5-1/2 in. deep steel studs and constructed of the materials and in the manner specified in the individual U400 or V400 Series Wall and Partition Designs in the Fire Resistance Directory. One 4-3/8 by 4-3/8 in. insert adhered to the interior back wall of the outlet box in accordance with the instructions supplied with the product. Installation to comply with the National Electrical Code (NFPA 70). A max 3/8 in. diam opening at one edge may be provided to permit access to the electrical box ground screw. Boxes may be installed within the same stud cavity, back-toback. When back-to-back boxes are inter connected, a min 1/4 in. thickness formed plug of Putty Pad or Metacaulk 1000 shall be installed in the open end of each conduit of the box. Metacaulk Fire Rated Putty Pads for use with max 4-11/16 by 4-11/16 by 2-1/8 in. flush device UL Listed Metallic Outlet Boxes installed with steel mud rings and plastic or steel cover plates in 2 h fire rated gypsum board wall assemblies framed with min 5-1/2 in. deep steel studs and constructed of the materials and in the manner specified in the individual U400 or V400 Series Wall and Partition Designs in the Fire Resistance Directory. Min 1/8 in. thick moldable putty pads are to be installed to completely cover the exterior surfaces of the outlet box including the side of the outlet box against the stud. Installation to comply with the National Electrical Code (NFPA 70). Boxes may be installed within the same stud cavity, back-to-back. When back-to-back boxes are inter connected, a min 1/4 in. thickness formed plug of Putty Pad or Metacaulk 1000 shall be installed in the open end of each conduit of the box. Metacaulk Fire Rated Putty Pads for use with max 4-11/16 by 4-11/16 by 2-1/8 in. flush device UL Listed Metallic Outlet Boxes installed with steel mud rings and plastic or steel cover plates in 1 h fire rated gypsum board wall assemblies framed with min 6 in. deep wood or steel studs and constructed of the materials and in the manner specified in the individual U300, U400 or V400 Series Wall and Partition Designs in the Fire Resistance Directory. Nom 6-1/2 in. thick fiberglass insulation (Min 0.5 pcf) is to be installed within the wall cavity. Min 1/8 in. thick moldable putty pads are to be installed to completely cover the exterior surfaces of the outlet box including the side of the outlet box against the stud. Installation to comply with the National Electrical Code (NFPA 70). When back to back boxes are inter connected a 1/4 in. thickness formed plug of Putty Pad or Metacaulk 1000 in the open end of each conduit of the box. Any information and documentation involving UL Mark services are provided on behalf of (UL) or any authorized licensee of UL. For questions, please Page 8 of 8