SECTION FIRESTOPPING

Similar documents
UNIFIED FACILITIES GUIDE SPECIFICATIONS

SECTION THROUGH-PENETRATION FIRESTOP SYSTEMS

SECTION APPLIED FIREPROOFING

FIRESTOPPING & SMOKE SEALS

PHYSICAL FACILITIES Consultant s Handbook Specifications Division 07 Thermal and Moisture Protection 8400 Firestopping

DIVISION 7 THERMAL AND MOISTURE PROTECTION SECTION PENETRATION FIRESTOPPING

SECTION THROUGH-PENETRATION FIRE STOP SYSTEMS

OUTLET PUTTY PADS SPECIFICATIONS

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 07 THERMAL AND MOISTURE PROTECTION

St. Monica Food Pantry

SPECIFICATION DIVISION 7 NUMBER SECTION DESCRIPTION DIVISION 07 THERMAL AND MOISTURE PROTECTION SECTION THROUGH-PENETRATION FIRESTOP SYSTEMS

SECTION FIRESTOP SYSTEMS

Following contains common verbiage found in major model building codes and has been edited for the purpose of inclusion on this CD.

B. American Society for Testing and Materials: 1. ASTM F708 - Standard Practice for Design and Installation of Rigid Pipe Hangers.

SECTION ACOUSTICAL CEILINGS

SECTION THERMAL INSULATION

SECTION COMPOSITE METAL DECKING

SECTION FIRE RESISTIVE JOINT SYSTEMS

SECTION STRUCTURAL STEEL FRAMING

NEW CONSTRUCTION (digital copy available Firestop Solutions Inc.) FIRESTOPPING SPECIFICATION SECTION FIRESTOPPING

Normal, Medium And High Density Fireproofing Materials

A. Section includes Sprayed Fire-Resistive Materials: (SFRM) A. Pre-Installation Conference: Conduct conference at Project Site.

SECTION APPLIED FIREPROOFING

SECTION FIRE RESISTIVE JOINT SYSTEMS Display hidden notes to specifier. (Don't know how? Click Here)

SECTION INTUMESCENT MASTIC FIREPROOFING

SECTION GYPSUM BOARD

RAMAPO COLLEGE OF NEW JERSEY PHASE II HOUSING REHABILITATION C 2012

Jean Vaillancourt Fire Protection Specialist Hilti (Canada) Corp.

SECTION RESINOUS FLOORING

SECTION TERRAZZO FLOOR TILE

SECTION STEEL JOIST FRAMING

FIRESTOP SUBMITTAL PACKAGE

SECTION (07810) - APPLIED FIREPROOFING

RECOMMENDED DESIGN SPECIFICATION

SECTION CONVECTORS

Life Hall Renovation Issued: July 9, 2014 Montclair State University Addendum No. 1 Owner's Project No Cannon Design Project No

SECTION ROOFING AND SIDING PANELS

SECTION CEMENTITIOUS WOOD FIBER DECKS

FIRESTOP SUBMITTAL PACKAGE

SECTION THROUGH-PENETRATION FIRESTOPPING

SECTION FLUID-APPLIED MEMBRANE AIR BARRIERS, VAPOR PERMEABLE

International Fireproof Technology Inc.

SECTION WALL AND DOOR PROTECTION

Protecting Penetrations in Fire Rated Construction

Enthusiastic customers We create success for our customers by Identifying their needs and providing Innovative and value adding solutions.

SOUND SEAL 90 DRAFT / SMOKE / ACOUSTICAL SOUND SEALANT

SECTION MODIFIED BITUMINOUS SHEET WATERPROOFING

Recommended Design Considerations. and. Guide Specifications For. Commercial Building Insulation

SECTION ACCORDION FOLDING PARTITIONS

Building Codes and Ordinances ARC 227

SECTION STANDING SEAM METAL ROOFING

International Fireproof Technology Inc.

Request for Information (RFI) - 52

SECTION RESILIENT SHEET FLOORING

SECTION RESILIENT TILE FLOORING

/ADF BuyLine 1632 FIREBARRIER FIRESTOP SYSTEMS

SECTION COMMON WORK RESULTS FOR FIRE SUPPRESSION

SECTION COMPOSITE METAL DECKING

SECTION INTUMESCENT FIREPROOFING

SECTION PATHWAYS FOR COMMUNICATIONS SYSTEMS

SECTION ENCLOSED BUS ASSEMBLIES

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION DIVISION: AIR BARRIERS REPORT HOLDER:

DIIM & Firestopping. Firestopping Joints FCIA 2018

FIRESTOP 101: An Introduction to Firestopping

SECTION ROOF ACCESSORIES

A. Source Limitations: Obtain each type of building insulation through one source.

EXCEL Medical Waste - Equipment Installation Section SECTION GYPSUM BOARD

SECTION HVAC AIR CLEANING DEVICES

FCIA Education Standards L - Ratings ASTM Movement Standard DRAFT. Eric Keeton, Tracy Smith, Luke Woods. May 2, 2013

SECTION BUILT-UP BITUMINOUS WATERPROOFING

SECTION CONCRETE ABOVE GROUND FUEL STORAGE

PAVING SLABS ON AGGREGATE BED FOR ROOF PLAZA DECKS

SECTION JOINT SEALANTS

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION SECTION: AIR BARRIERS REPORT HOLDER: DAP FOAM, INC.

SECTION RESILIENT BASE AND ACCESSORIES

Session: Firestop - Let s Walk a Project and Look at Firestop Together

Over 98% of our products meet the requirements of the Buy American Act. Below is a list of our product categories that comply with this act.

SECTION FLAGPOLES

SECTION PENETRATION FIRESTOPPING PART 1- GENERAL PART 2- PRODUCTS 1.1 RELATED DOCUMENTS

FireX Fire Stopping Mastic FM

SECTION VINYL-COATED FABRIC WALL COVERINGS

SECTION ALUMINUM STORM WINDOWS

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION SECTION: AIR BARRIERS REPORT HOLDER:

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: ELASTOCHEM SPECIALTY CHEMICALS, INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: RHINO LININGS CORPORATION

Common Firestop Issues in Wood Framed Commercial Construction

ARCHITECTURAL SPECIFICATION

Bid Opportunity Pacific Avenue, Winnipeg, Manitoba Page 1..1 CGSB 51-GP-23M-[78] Thermal Insulation, Urethane, Spray in Place.

1. Division 15 Sections specifying duct and piping penetrations. 2. Division 16 Sections specifying cable and conduit penetrations.

SECTION MULTICOLOR INTERIOR FINISHING

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: APPLIED FIREPROOFING REPORT HOLDER: CARBOLINE COMPANY

Code Change No: FS43-06/07

PRODUCT SPECIFICATIONS

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: NATURAL POLYMERS, LLC

SECTION POLYPROPYLENE FABRIC WALL COVERING

SECTION COMMON WORK RESULTS FOR ELECTRICAL

ROXUL Blanket (and Batt) Insulation Section Master Guide Specification (AFB) Page 1 April 2015

SECTION NON-STRUCTURAL METAL FRAMING

Transcription:

PART 1 - GENERAL 1.1 DESCRIPTION SECTION 07 84 00 SPEC WRITER NOTES: 1. Use this section only for NCA projects. 2. Delete between // // if not applicable to project. Also delete any other item or paragraph not applicable in the section and renumber the paragraphs. 3. Indicate locations of fire resistance rated walls, partitions, floors, ceiling-floor assemblies and other locations requiring firestopping, on the drawings; rating of walls and partitions being penetrated must be shown on the drawings. 4. If smoke barrier walls are required in the project, show them on the drawings. A. Tested and listed firestopping systems, combination of materials, or devices to form an effective barrier against the spread of flame, smoke and gases, and maintain the integrity of fire resistance rated walls, partitions, floors, and ceiling-floor assemblies, including throughpenetrations and construction joints and gaps. 1. Through-penetrations include the annular space around pipes, tubes, conduit, wires, cables and vents. 2. Construction joints include those used to accommodate expansion, contraction, wind, or seismic movement; firestopping material cannot interfere with the required movement of the joint. 3. Gaps requiring firestopping include gaps between the top of the fire-rated walls and the roof or floor deck above and at the intersection of shaft assemblies and adjoining fire resistance rated assemblies. B. Closure of openings in walls against penetration of gases or smoke in smoke partitions. 1.2 RELATED WORK A. Expansion and seismic joint firestopping: Section 07 95 13, EXPANSION JOINT COVER ASSEMBLIES. B. Spray applied fireproofing: Section 07 81 00, APPLIED FIREPROOFING C. Sealants and application: Section 07 92 00, JOINT SEALANTS. 07 84 00-1

D. Fire and smoke damper assemblies in ductwork: Section 23 31 00, HVAC DUCTS AND CASINGS // Section 23 37 00, AIR OUTLETS AND INLETS. 1.3 SUSTAINABILITY REQUIREMENTS A. Materials in this section may contribute towards contract compliance with sustainability requirements. See Section 01 81 11, SUSTAINABLE DESIGN REQUIRMENTS, for project // local/regional materials, // lowemitting materials, // recycled content, // // requirements. 1.4 SUBMITTALS A. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES. B. Submit detail drawings including manufacturer's descriptive data, typical details conforming to UL Fire Resistance or other details certified by another nationally recognized testing laboratory, installation instructions or UL listing details for a firestopping assembly instead of fire-test data or report. For those firestop applications for which no UL tested system is available through a manufacturer, submit a manufacturer's engineering judgment, derived from similar UL system designs or other tests, for review and approval prior to installation. Submittal must indicate the firestopping material to be provided for each type of application; when more than a total of 5 penetrations and/or construction joints are to receive firestopping, provide drawings that indicate location, "F", "T" and "L" ratings, and type of application. C. Submit certificates attesting that firestopping material complies with the specified requirements. For all intumescent firestop materials used in through penetration systems, manufacturer must provide certification from UL of passing the "Aging and Environmental Exposure Testing" portion of UL 1479. D. Submit manufacturer's representative certification stating that firestopping work has been inspected and found to be applied according to the manufacturer's recommendations and the specified requirements. Manufacturer s representative must be a direct employee of the manufacturer (not a distributor or an agent) and be qualified to perform the specified inspections and certify the firestopping installation. 1.5 DELIVERY AND STORAGE A. Deliver materials in their original unopened containers with manufacturer s name and product identification. 07 84 00-2

B. Store in a location providing protection from damage and exposure to 1.6 WARRANTY the elements. A. Firestopping work subject to the terms of the Article Warranty of Construction, FAR clause 52.246-21, except extend the warranty period to five years. 1.7 QUALITY ASSURANCE A. FM, UL, or WH or other approved laboratory tested products will be acceptable. 1.8 APPLICABLE PUBLICATIONS A. Publications listed below form a part of this specification to extent referenced. Publications are referenced in text by the basic designation only. Comply with applicable provisions and recommendations of the following, except as otherwise shown or specified. B. American Society for Testing and Materials (ASTM): E84-12c E814-11a E2174-10ae1 E2393-10a C. FM Global (FM): SPEC WRITER NOTES: 1. Remove reference citations that do not remain in Part 2 or Part 3 of edited specification. 2. Verify and make dates indicated for remaining citations the most current at date of submittal; determine changes from date indicated on the TIL download of the section and modify requirements impacted by the changes. Surface Burning Characteristics of Building Materials D. Underwriters Laboratories, Inc. (UL): Fire Tests of Penetration Firestop Systems On-Site Inspection of Installed Fire Stops On-Site Inspection of Installed Fire Resistive Joint Systems and Perimeter Fire Barriers Approval Guide Building Materials Building Materials Directory Fire Resistance Directory 1479 Fire Tests of Through-Penetration Firestops E. Warnock Hersey (WH): 1.9 SEQUENCING Certification Listings A. Coordinate the specified work with other trades. 07 84 00-3

B. Apply firestopping materials, at penetrations of pipes and ducts, prior to insulating, unless insulation meets requirements specified for firestopping. C. Apply firestopping materials at building joints and construction gaps, prior to completion of enclosing walls or assemblies. D. Locate and install cast-in-place firestop devices in place before concrete placement. Install pipe, conduit or cable bundles through cast-in-place device after concrete placement but before area is concealed or made inaccessible. E. Inspect and receive approval for firestop material prior to final completion and enclosing of any assemblies that may conceal installed firestop. PART 2 - PRODUCTS 2.1 FIRESTOP SYSTEMS A. Use factory built (Firestop Devices) or field erected (through- Penetration Firestop Systems) to form a specific building system maintaining required integrity of the fire barrier and stop the passage of gases or smoke. B. Through-penetration firestop systems and firestop devices tested in accordance with ASTM E814 or UL 1479 using the "F" or "T" rating must maintain the same rating and integrity as the fire barrier being sealed. "T" ratings are not required for penetrations smaller than or equal to 100 mm (4 in) nominal pipe or 0.01 m 2 (16 sq. in.) in overall cross sectional area. C. Products requiring heat activation that seal an opening by its intumescence must exhibit a demonstrated ability to function as designed to maintain the fire barrier. D. Provide firestop sealants used for firestopping or smoke sealing with the following properties: 1. Contain no flammable or toxic solvents. 2. Have no dangerous or flammable out gassing during the drying or curing of products. 3. Water-resistant after drying or curing and unaffected by high humidity, condensation or transient water exposure. 4. When used in exposed areas, firestop sealant can be sanded and finished with similar surface treatments as used on the surrounding wall or floor surface. 07 84 00-4

E. Provide firestopping system or devices used for penetrations by glass pipe, plastic pipe or conduits, unenclosed cables, or other nonmetallic materials with following properties: 1. Classified for use with the particular type of penetrating material used. 2. Penetrations containing loose electrical cables, computer data cables, and communications cables protected using firestopping systems that allow unrestricted cable changes without damage to the seal. 3. Intumescent products which would expand to seal the opening and act as fire, smoke, toxic fumes, and, water sealant. F. Provide products with maximum flame spread of 25 and smoke development of 50 when tested in accordance with ASTM E84. G. Provide products FM, UL, or WH rated or tested by an approved laboratory in accordance with ASTM E814. H. Materials must be asbestos free. 2.2 SMOKE STOPPING IN SMOKE PARTITIONS A. Use silicone sealant in smoke partitions as specified in Section 07 92 00, JOINT SEALANTS. B. Use mineral fiber filler and bond breaker behind sealant. C. Sealants must have a maximum flame spread of 25 and smoke developed of 50 when tested in accordance with E84. D. When used in exposed areas capable of being sanded and finished with similar surface treatments as used on the surrounding wall or floor surface. PART 3 - EXECUTION 3.1 EXAMINATION A. Submit product data and installation instructions, as required by article, submittals, after an on-site examination of areas to receive firestopping. 3.2 PREPARATION A. Remove dirt, grease, oil, loose materials, or other substances that prevent adherence and bonding or application of the firestopping or smoke stopping materials. B. Remove insulation on insulated pipe for a distance of 150 mm (6 inches) on either side of the fire rated assembly prior to applying the firestopping materials unless the firestopping materials are tested and approved for use on insulated pipes. 07 84 00-5

3.3 INSTALLATION A. Do not begin work until the specified material data and installation instructions of the proposed firestopping systems have been submitted and approved. B. Install firestopping systems with smoke stopping in accordance with FM, UL, WH, or other approved system details and installation instructions. C. Install smoke stopping seals in smoke partitions. 3.4 INSPECTIONS A. Manufacturer s technical representative to inspect all firestopping in accordance to ASTM standards for firestop inspection, and document inspection results; ASTM E2174 and E2393. 3.5 CLEAN-UP AND ACCEPTANCE OF WORK A. As work on each floor is completed, remove materials, litter, and debris. B. Do not move materials and equipment to the next-scheduled work area until completed work is inspected and accepted by the RE/COR; RE/COR inspection does not supersede requirement for inspection by manufacturer's representative or requirements of local jurisdiction. C. Clean up spills of liquid type materials. - - - E N D - - - 07 84 00-6