3 MODIFICATIONS TO EXISTING STANDARDS

15 kv EPR Insulated, Jacketed, URD Cable

SOUTH CAROLINA ELECTRIC COOPERATIVES' PRIMARY UNDERGROUND POWER CABLE SPECIFICATION

*** Supercedes: BECO E and COM , , & ***

The Contractor shall furnish and install all shielded power cable suitable for use on this project.

STANDARD FOR EXTRUDED INSULATION POWER CABLES RATED ABOVE 46 THROUGH 345 KV. Approved by AMERICAN NATIONAL STANDARDS INSTITUTE.

SECTION MEDIUM-VOLTAGE CABLES PART 1 GENERAL

WESTERN UNDERGROUND COMMITTEE GUIDE 2.14 (2.14/01/0990)

STANDARD SPECIFICATION FOR SIGNAL CABLE. A. This Specification provides for single and multi-conductor insulated and jacketed cable for

HDPE Conduit Specification 2011

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

Section ARMORED MEDIUM VOLTAGE CABLES SHIELDED 3 CONDUCTOR POWER CABLE - INTERLOCKED ARMOR

MATERIAL STANDARD FOR CABLES AND WIRES

PV Solar Wiring Solutions

STANDARD FOR CONCENTRIC NEUTRAL CABLES RATED 5 THROUGH 46 KV

11-SDMS-01 REV. 02 SPECIFICATIONS FOR LOW VOLTAGE POWER AND CONTROL CABLES

10-SDMS-02 SPECIFICATIONS FOR BARE COPPER CONDUCTORS

MAST ARMS: ALUMINUM, TRUSS TYPE AND DAVIT TYPE

NUCLEAR POWER CORPORATION OF INDIA LTD. (A GOVT. OF INDIA ENTERPRISE) SPECIFICATION NO.PB-E-542/REV. No.0

SECTION GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY

NORMAS DE REFERENCIA AEIC CS 1: ASTM B

11-SDMS-01 REV. 03 ( )

NPS/002/023 Technical Specification for 132kV Power Cables.

IEEE 1580 Type P MOR Polyrad XT-125 Multi Conductor

Specification FOR. 12.7/22KV AL-CV/WS 12.7/22KV Aluminum Conductor XLPE Insulated Copper Wire Screened PVC Sheathed Power Cable.

SPECIFICATION FOR FRLS POWER CABLES

Conductor Shield A combination of semi-conducting tape and extruded thermosetting semi-conducting material meeting UL 1309, IEEE 1580 and UL1072.

TECHNICAL SPECIFICATION FOR L. T. XLPE POWER CABLE

PO Box 1081 Monticello, MN Ph Fax

UNIFIED FACILITIES GUIDE SPECIFICATIONS

SECTION WIRE, CABLE AND BUSWAYS. A. This section specifies providing wire, cable and busways.

DRAFT TANZANIA STANDARD. Part 7: Underground Power Cables for rated voltages 0.6kV/1kV (Um 1.2kV)

SECTION A. ASTM B3 - Standard Specification for Soft or Annealed Copper Wire; 2013.

Single Core, Aluminum Conductor Extruded Cross - Linked Polyethylene (XLPE) Insulated Power Cable

SPECIAL SPECIFICATION 6623 Multi-Duct Conduit System

Four Core, Aluminum Conductor Extruded Cross - Linked Polyethylene (XLPE) Insulated Power Cable


SECTION GROUNDING

SPECIFICATION FOR 600 VOLT CONTROL AND POWER CABLE SPECIFICATION NO. 557

City of Jacksonville Beach

ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD. ANSI/SCTE (Formerly IPS SP 100)

NPS/002/020 Technical Specification for 11 & 20kV Power Cables

All definitions are defined according to ANSI/AWWA C

This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update.

Four Core, Copper Conductor Extruded Cross - Linked Polyethylene (XLPE) Insulated Power Cable

SECTION METAL FRAMED SKYLIGHT. A. Engineering, preparation of fabrication drawings and structural calculations for the entire skylight system.

SECTION METAL-ENCLOSED BUS MEDIUM VOLTAGE

Kaf-Tech Product Specification

SECTION EZ-SLIDE 80 AND 180 HEAVY GLASS TOP HUNG SLIDING DOOR SYSTEMS

SCHEDULE ' A ' TECHNICAL SPECIFICATION FOR L.T.PVC POWER AND CONTROL CABLES FOR DISTRIBUTION NETWORK IN MAHARASHTRA

Standard of Practice - Campus Electrical Distribution System

L1-CHE-SPE-171 TECHNICAL SPECIFICATION FOR ELECTRIC CABLE

CLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS SINGLE-PHASE PADMOUNTED TRANSFORMERS

All definitions are defined according to ANSI/AWWA C b. Flanged Joint: The flanged and bolted joint as described in ANSI/AWWA C110/A21.10.

SECTION CRL70 HEAVY GLASS TOP HUNG SLIDING DOOR SYSTEMS

Tele-Fonika Cable Americas

1.2 REFERENCES.1 CSA C22.2 No.0.3, Test Methods for Electrical Wires and Cables.

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

Glossary Of Terms M-1

P.V.C. INSULATED ALUMINIUM SERVICE MAIN WIRE-FINISHED PRODUCT

SECTION CRL50 AND CRL51 HEAVY GLASS TOP HUNG SLIDING DOOR SYSTEMS

Single Core, Copper Conductor Extruded Cross - Linked Polyethylene (XLPE) Insulated Power Cable

SPECIFICATION FOR ZIRCONIUM AND ZIRCONIUM ALLOY BAR AND WIRE

DESIGN GUIDELINES WIRING AND CONDUITS PAGE 1 of 7

SECTION PARK NON-SEGREGATED BUS SPECIFICATION

Purchase Now ANSI/ICEA S STANDARD FOR 600 VOLT SINGLE LAYER THERMOSET INSULATED UTILITY UNDERGROUND DISTRIBUTION CABLES

United Window & Door - Series 5500 New Construction Double Hung Windows Specifications

2003 International Residential Code ELECTRICAL PROVISIONS ONLY October 2005 EDITORIAL CHANGES SEVENTH PRINTING

SECTION 7.3 TECHNICAL SPECIFICATION OF POWER CABLES & CONDUCTOR

Standard Specification for Niobium-Hafnium Alloy Foil, Sheet, Strip, and Plate 1

MEDIUM VOLTAGE XLPE INSULATED POWER CABLES [6.35/11kV Copper XLPE Three-Core HDPE Sheathed]

8.1.2 Under no circumstances shall a service entrance be left unmetered. Notify the Company if an unmetered service is encountered.

SPECIFICATION FOR THHN/THWN-2/THW/THWN/TW ARROW ROUTE, FONTANA CA

05510: TAPERED STEEL TROLLEY POLES AND ACCESSORIES

SPECIFICATION FOR SIMPLEX SWITCHBOARDS

MESP TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 70mm 2 FLEXIBLE TINNED COPPER CONDUCTOR 3.3kV EPR INSULATED WITHOUT METALLIC SCREEN

12-SDMS-01 Rev.02 SPECIFICATIONS FOR

A. Product Data: Identify thermal conductivity, thickness, and jackets (both factory and field applied, if any), for each type of product indicated.

Test Report No.: Page 2 of 35

Heavy Wall Heat Shrinkable Tubing 5-7. Flame Retardant Heavy Wall Heat Shrinkable Tubing 8. Heat Shrinkable Ends Caps 9

Prepared By: Engineering Staff Approved By: Jerome T. Schmitz

KANSAS DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION TO THE STANDARD SPECIFICATIONS, 1990 EDITION

DISTRIBUTION TRANSFORMER SPECIFICATION #

RESIN FILLING TYPE JOINTING KITS FOR LOW VOLTAGE UNDERGROUND CABLES

SPECIAL SPECIFICATION 4703 Repair Of Impact Damaged Prestressed Concrete Bridge Beams

THERMOFIT ADHESIVE S-1125 Epoxy, Flexible

DETAIL SPECIFICATION SHEET CABLE, ELECTRICAL, -20 C TO +90 C, TYPE LS3SWU (INCLUDING VARIATION LS3SWUS)

N06600, N06601, N06603, N06690, N06693, N06025, N06045,

NEMA Standards Publication No. WC ICEA Publication No. S

8. REVENUE METERING. Operational Excellence Model. 8.1 Introduction

TECHNICAL SPECIFICATION FOR 1.1KV XLPE POWER CABLE SECTION-1

Power Electronics, Inc. Packaged Equipment Center Standard Construction and Design Features

137-1: 2015 CEB SPECIFICATION. XLPE INSULATED SINGLE CORE UNDERGROUND CABLES OF 11 kv RATED VOLTAGE

SILVER LINE BUILDING PRODUCTS. Series 1700 Heavy Commercial Aluminum Double Hung. HC65 48 x84 / HC50 60 x96 Replacement Window

ITEM 435 ELASTOMERIC MATERIALS

138-1: 2015 CEB SPECIFICATION. AERIAL BUNDLE CONDUCTORS - 33 kv (95mm 2 and 150mm 2 )

INDUSTRIAL ATTACK 800

SECTION 1043 FENCE MATERIAL

CONSTRUCTION SPECIFICATION FOR CABLE INSTALLATION

Transcription:

Clark Public Utilities TECHNICAL SPECIFICATIONS 15KV MEDIUM VOLTAGE 1000 MCM AL URD CABLE 175 MIL EPR FEBRUARY 1994 REVISED MAY 1996 REVISED JUNE 2001 REVISED MARCH 2002 REVISED MARCH 2005 REVISED MAY 2007

TECHNICAL SPECIFICATIONS INDEX 1.0 GENERAL 2.0 REFERENCE STANDARDS 3.0 DEFINITION OF TERMS 4.0 MANUFACTURING METHOD 5.0 CONSTRUCTION 6.0 CABLE IDENTIFICATION 7.0 QUALITY ASSURANCE 8.0 TESTING AND TEST METHODS 9.0 ACCEPTANCE TESTS 10.0 SHIPMENT AND REELS 11.0 WARRANTY 12.0 BID QUOTE REQUIREMENTS 13.0 BIDDER S DATA SHEET 2

MEDIUM VOLTAGE 15KV 1000 MCM AL 175 MIL URD CABLE EPR 1.0 GENERAL 1.1 Description This specification covers the technical requirements for 15KV medium voltage 1000 MCM, Al, 175 mil, jacketed, concentric-neutral, URD cable. The cable shall consist of one ethylene propylene rubber (EPR) insulated central conductor with helically applied copper concentric neutral conductors over the insulation shielding, and an overall jacket of black, linear low density polyethylene. 1.2 Applications The cable shall be suitable for use in three-phase primary underground 15KV distribution systems in main feeder and commercial applications. 1.3 Service Environment & Operating Requirements 1.3.1 The cable shall be suitable for aerial, direct burial, and conduit installations in wet and dry locations with maximum normal operating temperatures to 105 C. The cable shall be suitable for a minimum installation temperature of -10 C without special handling. 1.3.2 The cable shall be designed and constructed such that it will operate satisfactorily at emergency operating temperatures to 140 C and short circuit operating temperatures to 250 C as defined by ICEA S-94-649. 1.4 Language All dimensions and specifications communicated to CPU shall be in the English language and shall be in customary English units. Metric units and/or other languages are not acceptable. 2.0 REFERENCE STANDARDS Reference is made in this specification to the following standards, the latest editions, amendments, and supplements of which shall apply, unless otherwise stated in this specification or in associated purchasing documents: 2.1 AEIC CS-8: Specifications for Extruded Dielectric Shielded Power Cables Rated 5 through 46kV. 2.2 ANSI C2: National Electrical Safety Code. 2.3 ASTM Standards: As referenced. 2.4 ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5 through 46kV. 2.5 ISO-9002 (ANSI/ASQC Q92): Quality Systems - Model for Quality Assurance in Production and Installation or CPU approved equivalent. 2.6 NEMA WC 26: Wire and Cable Packaging. 3.0 DEFINITIONS OF TERMS 3

The following definitions pertain to this specification: 3.1 AEIC: Association of Edison Illuminating Companies. 3.2 ANSI: American National Standards Institute. 3.3 ASQC: American Society for Quality Control. 3.4 ASTM: American Society for Testing and Materials. 3.5 Cable Core: The conductor, conductor shielding, insulation and insulation shielding layers of a cable. 3.6 CPU: Clark Public Utilities 3.7 CTR: Manufacturer's Certified Test Report. 3.8 CV: Continuous vulcanization. 3.9 Delta: For any one wafer sample, the delta is the maximum dimension minus the corresponding minimum dimension. 3.10 ICEA: Insulated Cable Engineers Association. 3.11 ISO: International Organization for Standardization. 3.12 MIL(s): One thousandth of an inch. 3.13 Production Run: Includes all of the cable produced by the core extruder line from the first shipping reel of the first master reel through the last shipping reel of the last master reel off the core extruder line. This includes the cable that is shipped to the purchaser, scrapped cable, and cable not-to-beshipped to the purchaser. If the core extruder or jacket line run is shut down and during re-establishing start-up, scrap is produced, then this shall be noted and considered as two production runs. 4.0 MANUFACTURING METHOD 4.1 Extrusion 4.3 Curing 4.1.1 The conductor shielding, insulation, and insulation shielding shall be applied in a triple extrusion process or a two plus one process. 4.1.2 All changes or alterations to the critical process parameters of the extrusion line shall be logged in the production log. The curing system during extrusion shall be either a nitrogen, inert gas or steam system. 4.4 Cooling 5.0 CONSTRUCTION A moisture-free or water cooling process is acceptable. The compound supplied shall be the same as that qualified in the AEIC-ICEA qualification tests. 5.1 Central Conductor 4

The central conductor shall be uncoated aluminum 1350 or 8000 series, stranded as specified by CPU. Aluminum rod from which conductor is drawn shall be free of defects and corrosion, cleaned of oil and contaminants, and purged of cleaning solvents prior to the drawing process. The conductor surface shall be smooth. 5.1.1 Stranded Conductor 5.2 Conductor Shielding Stranded conductor shall be 8000 series or 1350-H19 or less hard, class B concentric lay, and compressed 3% maximum, in accordance with ASTM B609 and ASTM B231. 5.2.1 The conductor shielding shall be a black, extruded, thermosetting, semiconducting or stress-grading material which is compatible with all the materials coming in contact with it. The outer surface of the conductor shielding shall be firmly bonded to the overlying insulation. The shielding shall be easily removable from the conductor. 5.2.2 The physical and electrical properties of the conductor shield shall be in accordance with the requirements of ICEA S-94-649. 5.3 Insulation 5.3.1 The insulation compound shall be ethylene propylene rubber based material and contain no more than 72% ethylene by weight. 5.3.2 The insulation shall be extruded directly over and firmly bonded to the conductor shielding. 5.3.3 The minimum point insulation thickness shall be 165 mils and the maximum point insulation thickness shall be 205 mils. 5.4 Insulation Shielding 5.4.1 The insulation shielding shall consist of a black, extruded, thermosetting, semiconducting, or stress control layer of polymeric material extruded directly over the insulation. The material shall be completely compatible with the insulation. 5.4.2 The insulation shielding shall be readily distinguishable from the insulation and shall be legibly identified as semiconducting or stress control layer by means other than indent printing. 5.4.3 The minimum and maximum thickness of the insulation shielding shall be in accordance with ICEA S-94-649. 5.4.4 The physical and electrical properties of the insulation shield shall be in accordance with ICEA S-94-649. 5.5 Copper 1/3 Concentric Neutral The shielding system shall contain twenty (20) - #10 AWG bare solid copper wires. These neutral wires shall be equally spaced over the insulation shielding layer and helically applied with a lay of 6 to 10 times the diameter over the concentric neutral wires per ICEA S-94-649. 5.6 Overall Outer Jacket 5

The overall outer jacket shall consist of a black, linear low density polyethylene compound. The jacket shall be nonconducting. The jacket shall be an extruded-to-fill type. 5.6.1 The nonconducting jacket shall meet the physical and aging requirements of ICEA S-94-649. 5.6.2 The cable shall be manufactured such that the concentric neutral wires are equally spaced and remain in contact with the underlying extruded insulation shielding after application of the overall jacket. 6.0 CABLE IDENTIFICATION 6.1 The center strand of stranded conductor cable shall be indent printed with the manufacturer's name and year of manufacturer at regular intervals with unindented surfaces not exceeding 12 inches. 6.2 The outer surface of the jacket of each cable shall be durably and legibly marked throughout its length in accordance with ICEA S-94-649, and additionally, a lightning bolt symbol (in accordance with the latest edition of ANSI C2). Identification marking shall be of the indent-printing type. The depth of the indentation shall not result in the violation of the minimum jacket thickness as required by ICEA S-94-649. 6.3 Sequential footage numbers shall be clearly printed throughout the cable length at 2-foot intervals. Sequential footage numbers shall not be repeated on any single order. Sequential footage numbers shall be of the indent-printing type with the indentation highlighted with white or silver colored ink or surface printed. The depth of the indentation shall not result in the violation of the minimum jacket thickness as required by ICEA S-94-649. 6.4 The outer surface of the jacket of each cable shall be marked with three (3) extruded, continuous, longitudinal, highly visible opaque red stripes spaced 120 apart. The nominal dimensions of the stripes shall be in accordance with ICEA S-94-649. 7.0 QUALITY ASSURANCE 7.1 Quality System The cable manufacturer shall have a quality system in place that meets the requirements of ISO-9002 (ANSI/ASQC Q92) or a CPU approved equivalent. 7.2 Plant Certification To qualify as a bidder, the following information shall be submitted for the specific cable manufacturing plant where the cable will be made: 7.2.1 Plant location. 7.2.2 Description of the extrusion equipment used, including positioning of extruders. 7.2.3 Description of the curing process and equipment used. 7.2.4 Description of the cooling down process used. 7.2.5 Description of the compound inspection process used. 6

7.2.6 Description of the compound handling system used from the shipping vehicle to the extruder. 7.2.7 Description of the statistical quality control method used. 7.2.8 List of previous customers supplied from this plant. 8.0 TESTING AND TEST METHODS 8.1 Qualification Tests 8.1.1 One certified copy of the results of ICEA S-94-649/AEIC CS8, qualification tests on specified cable shall be provided. Cable with a number 1/0 conductor size is the preferred size for the qualification tests. 8.1.2 Alternate qualification tests must be approved prior to submitting a bid. 8.2 Production Sampling Tests 8.2.1 Production sampling tests shall be made in accordance with ICEA S-94-649. 8.2.2 Alternate production tests shall be approved prior to submitting a bid. 8.3 Production Run Certified Test Reports (CTR) 8.3.1 General Requirements The following general information shall be included in the CTR: plant identification, process description, CTR number, purchase order number, manufacturer shipment number, reel count, shipment footage, cable core extruder/cv line identifier, and jacket line identifier. The CTR shall list the compound, and the facility where the compound was manufactured and where it was mixed. Any changes or modifications made to the compounds shall be noted in the CTR. 8.3.2 Measurement Data 8.4 Tests on Completed Cables The following CTR production run data shall be provided for all cable produced: minimum point thickness for the conductor shield; the minimum and maximum point thickness for the insulation, insulation shield and jacket; minimum diameter and maximum diameter for the insulation and insulation shielding. This production run data shall be provided for each shipping reel. Tests on completed cable and partial discharge test shall be made in accordance with ICEA S-94-649, if a more stringent test is not possible. 9.0 ACCEPTANCE TESTS 9.1 Shipping and Labeling Requirements 9.1.1 The cable manufacturer shall submit the reports identified in Section 9.2 to the following address: 7

Clark Public Utilities Purchasing Department P.O. Box 8900 Vancouver, WA 98668 9.1.2 All reports shall be shipped in separate packages with the cable shipment. 9.2 Report and Sample Requirements 9.2.1 One certified copy of the reports of all test data and dimensional measurements, including X-Y plots when appropriate, shall be furnished for each master reel of cable to be shipped. 9.3 Sampling by the Utility 9.3.1 A twenty-four inch sample shall be available on the inner end of each cable reel. The sample shall be an extension of the cable through the reel flange and stapled to the flange. 9.4 Performance Acceptance Tests Performance acceptance tests may be conducted on samples from each reel of cable to be accepted based on the procedures contained in this specification. The testing and examinations of cable samples may be performed by the utility or its authorized agent. All test procedures, examinations, and their results shall conform to ICEA S-94-649 except as specifically noted. Failure of a sample to satisfy the requirements of any section of this specification may be cause for rejection of that shipping reel of cable. Clark Public Utilities reserves the right to return, freight collect, any cable not meeting the requirements of this specification. 9.5 Tests that May be Performed on 24 Inch Cable Samples 9.5.1 The cable jacket may be visually inspected for correct markings and any surface damage to the cable jacket. 9.5.2 The cable jacket may be measured to determine the minimum and maximum thickness. 9.5.3 With the jacket removed, the copper concentric neutral wires may be examined for defects. Uniformity of spacing around the cable, lay, the number of straps and the size will be evaluated. 9.5.4 With the copper concentric neutral wires removed, the insulation shield may be visually inspected for correct markings and surface damage. The volume resistivity and the bond strength (or stripping tension) may be measured if applicable. 9.5.5 With the insulation shield removed, the insulation may be visually inspected for contaminants, voids, and protrusions. Any questionable areas may have wafer samples taken which may be examined. 9.5.6 The volume resistivity of the semiconducting conductor shield may be measured. 9.5.7 The conductor may be inspected for lay, protrusions, and defects. The outside diameter of the conductor may be measured. The number of strands may be counted and measured for wire size. 10.0 SHIPMENT AND REELS 10.1 Packing and Sealing 10.1.1 Cable shall be supplied in one continuous length for each reel. 8

10.1.2 Each end of the cable shall be firmly and properly secured to the reel. Care shall be taken to prevent looseness of reeled cable. The cable end attached through the interior of the reel shall be fastened in such a manner that it remains attached as the cable is dispensed from the reel and does not interfere with other reels or waste cable. 10.1.3 There shall be a minimum 2-inch clearance between the outer edge of the reel flange and the surface of the outermost layer of cable. 10.1.4 Watertight seals shall be applied to all cable ends to prevent entry of moisture during transit and outside storage. All reels shall have Class 2 protection over the outer layer of cable in accordance with NEMA WC 26. 10.2 Reels Unless otherwise specified on the bid schedule, all reels shall: Be NEMA Standard non-returnable wood reels free of damaging protrusions, e.g., nails, staples, etc. Use steel bushings to line reel arbor holes. Have a minimum drum diameter of 14 cable diameters. Have a maximum inside traverse of 72 inches. Have a maximum flange diameter of 72 inches. Have a maximum gross weight of 6000 pounds. Have a minimum 1900 feet and a maximum 2000 feet of cable length. 10.3 Marking on Reels Reel information shall be embossed on stainless steel or aluminum tags permanently attached to the outside of the reel. The manufacturer shall label each reel as follows: Manufacturer's name, shipping reel number, factory reel number, and/or any other information to determine the origin of the cable. CPU s purchase order number Net weight, gross weight, and tare weight Length of cable Beginning and ending sequential footage numbers Type of cable Type, size, and stranding of conductor Thickness and type of insulation Voltage rating of cable Date of manufacturer and location DO NOT UPEND. Minimum 2 inches high, bright red or orange. An appropriate symbol such as a reel on its side with a red circle around it and a diagonal line through it is acceptable. 10.4 Shipping Instructions The cable shall be shipped on flat bed vehicles. Enclosed vans will be rejected. The cable shall be shipped with the reel flanges vertically oriented. The reels must be secured to prevent flanges of one reel from damaging the cable on another reel. Reels shipped in enclosed trucks, lying horizontally on the flange, or stacked more than one high will be rejected. 11.0 WARRANTY The vendor warrants that the cable furnished is free from defects in material and workmanship for a period of not less than 5 years and agrees to replace any material that is unsuitable for operation or fails in operation during normal and proper use. The minimum warranty shall be defined by the manufacturer. Any cost for an 9

extended warranty, in addition to the manufacturer's standard warranty, shall be shown separately on all quotations. 12.0 BID QUOTE REQUIREMENTS 12.1 The bid quote shall clearly identify all compounds, the supplier name, plant location, and any modifications to the compounds. 12.2 The bid quote shall include a history of in-service records and a history of the proposed compound. 12.3 The bid quote shall include the manufacturer's most current written copies of the following: (a) (b) (c) (d) The certified copy of the AEIC - ICEA Qualification Test report for the compounds, materials, design, and processes which are to be used in manufacturing the specified cable. Procedures covering repair or rework of the layers outside of the cable core. Procedures, including examples, of production run sample selection, wafer selection, and wafer dimensional data recording. Procedures for re-sampling, hold tagging, and scrapping of portions of the cable run. 12.4 The proposal shall include a bid data sheet for each item and any alternate bids. 12.5 ANY BID QUOTE THAT DOES NOT CONTAIN ALL OF THE INFORMATION REQUESTED IN 12.1 THROUGH 12.4 WILL NOT BE EVALUATED. 10

PART 13 15 KV 1000 MCM URD EPR CABLE BIDDER S DATA SHEET Manufacturer Phase conductor size Bid Number Bid Item Number Neutral Wire Size and Quantity Item Description Guaranteed Values 1. Outside diameter range of cable (complete). 2. Diameter range over insulator shield 3. Diameter range over insulation. 4. Type of stranding. 5. Nominal weight of completed cable. (lbs/ft) 6. Type of insulation. 7. Thickness range of insulation. 8. Thickness range of insulation shield. 9. Thickness range of conductor shield. 10. Reel size (Flange x Traverse x Drum Max Width outside flange) (in inches) x x x - 11. Length of cable on reel. 12. Metal Content in LBS/1000 FT ALUMINUM COPPER 13. Insulation shield (see 5.4). Stripping tensions at room temperature. Stripping tensions at 32 F. Stripping tensions at 100 F. 14. Conductor shield compound. 15. Insulation shield compound. 16. Conductor alloy and temper. 17. Polyethylene content, % by weight. 18. Warranty (include the entire warranty on separate sheets.) 11

CLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS 15kV MEDIUM VOLTAGE 1/0 AL URD CABLE 175 MIL EPR FEBRUARY 1995 REVISED MARCH 1996 REVISED MARCH 2005 REVISED MAY 2007 12

15kV MEDIUM VOLTAGE 1/0 AL 175 MIL URD CABLE EPR 1.0 GENERAL 1.1 Description This specification covers the technical requirements for 15 kv medium voltage, 1/0, Al, 175 mil, jacketed, concentric-neutral URD cable. The cable shall consist of one ethylene propylene rubber (EPR) insulated central conductor with helically applied copper concentric neutral conductors over the insulation shielding, and an overall jacket of black, linear low density polyethylene. 1.2 Applications The cable shall be suitable for use in single, two, and three-phase 15kV underground distribution systems in residential and commercial applications. 1.3 Service Environment & Operating Requirements 1.3.1 The cable shall be suitable for aerial, direct burial, and conduit installations in wet and dry locations with maximum normal operating temperatures to 105 C. The cable shall be suitable for a minimum installation temperature of -10 C without special handling. 1.3.2 The cable shall be designed and constructed such that it will operate satisfactorily at emergency operating temperatures to 140 C and short circuit operating temperatures to 250 C as defined by ICEA S-94-649. 1.4 Language All dimensions and specifications communicated to CPU shall be in the English language and shall be in customary English units. Metric units and/or other languages are not acceptable. 2.0 REFERENCE STANDARDS Reference is made in this specification to the following standards, the latest editions, amendments, and supplements of which shall apply, unless otherwise stated in this specification or in associated purchasing documents: 2.1 AEIC CS-8: Specifications for Extruded Dielectric Shielded Power Cables Rated 5 through 46kV. 2.2 ANSI C2: National Electrical Safety Code. 2.3 ASTM Standards: As referenced. 2.4 ICEA S-94-649: Standard for Concentric Neutral Cables Rated 5 through 46kV. 2.5 ISO-9002 (ANSI/ASQC Q92): Quality Systems - Model for Quality Assurance in Production and Installation or CPU approved equivalent. 2.6 NEMA WC 26: Wire and Cable Packaging. 3.0 DEFINITIONS OF TERMS 13

The following definitions pertain to this specification: 3.1 AEIC: Association of Edison Illuminating Companies. 3.2 ANSI: American National Standards Institute. 3.3 ASQC: American Society for Quality Control. 3.4 ASTM: American Society for Testing and Materials. 3.5 Cable Core: The conductor, conductor shielding, insulation and insulation shielding layers of a cable. 3.6 CPU: Clark Public Utilities 3.7 CTR: Manufacturer's Certified Test Report. 3.8 CV: Continuous vulcanization. 3.9 Delta: For any one wafer sample, the delta is the maximum dimension minus the corresponding minimum dimension. 3.10 ICEA: Insulated Cable Engineers Association. 3.11 ISO: International Organization for Standardization. 3.12 MIL(s): One thousandth of an inch. 3.13 Production Run: Includes all of the cable produced by the core extruder line from the first shipping reel of the first master reel through the last shipping reel of the last master reel off the core extruder line. This includes the cable that is shipped to the purchaser, scrapped cable, and cable not-to-beshipped to the purchaser. If the core extruder or jacket line run is shut down and during reestablishing start-up, scrap is produced, then this shall be noted and considered as two production runs. 4.0 MANUFACTURING METHOD 4.1 Extrusion 4.3 Curing 4.1.1 The conductor shielding, insulation, and insulation shielding shall be applied in a triple extrusion process or a two plus one process. 4.1.2 All changes or alterations to the critical process parameters of the extrusion line shall be logged in the production log. The curing system during extrusion shall be either a nitrogen, inert gas or steam system. 4.4 Cooling 5.0 CONSTRUCTION A moisture-free or water cooling process is acceptable. The compound supplied shall be the same as that qualified in the AEIC-ICEA qualification tests. 5.1 Central Conductor 14

The central conductor shall be uncoated aluminum 1350 or 8000 series, stranded as specified by CPU. Aluminum rod from which conductor is drawn shall be free of defects and corrosion, cleaned of oil and contaminants, and purged of cleaning solvents prior to the drawing process. The conductor surface shall be smooth. 5.1.1 Stranded Conductor 5.2 Conductor Shielding Stranded conductor shall be 8000 series or 1350-H19 or less hard, class B concentric lay, and compressed 3% maximum, in accordance with ASTM B609 and ASTM B231. 5.2.1 The conductor shielding shall be a black, extruded, thermosetting, semiconducting or stress grading material which is compatible with all the materials coming in contact with it. The outer surface of the conductor shielding shall be firmly bonded to the overlying insulation. The shielding shall be easily removable from the conductor. The shielding shall not penetrate past the center of the outside strand layer. 5.2.2 The physical and electrical properties of the conductor shield shall be in accordance with the requirements of ICEA S-94-649. 5.3 Insulation 5.3.1 The insulation compound shall be ethylene propylene rubber based material and contain no more than 72% ethylene by weight. 5.3.2 The insulation shall be extruded directly over and firmly bonded to the conductor shielding. 5.3.3 The minimum point insulation thickness shall be 165 mils. The maximum point insulation thickness shall be 205 mils. 5.4 Insulation Shielding 5.4.1 The insulation shielding shall consist of a black, extruded, thermosetting, semiconducting, or stress control layer of polymeric material extruded directly over the insulation. The material shall be completely compatible with the insulation. 5.4.2 The insulation shielding shall be readily distinguishable from the insulation and shall be legibly identified as semiconducting or stress control layer by means other than indent printing. 5.4.3 The minimum and maximum thickness of the insulation shielding shall be in accordance with ICEA S-94-649. 5.4.4 The physical and electrical properties of the insulation shield shall be in accordance with ICEA S-94-649. 5.5 Concentric Neutral Conductor 5.5.1 A concentric neutral conductor consisting of round annealed, uncoated copper wires in accordance with ICEA S-94-649, shall be applied helically over and in contact with the insulation shielding. 5.5.2 The conductivity of the concentric neutral shall be a full neutral. The number and size of concentric neutral wires shall be as shown in ICEA S-94-649, Table 6-2. 15

5.6 Overall Outer Jacket The overall outer jacket shall consist of a black, linear low density polyethylene compound. The jacket shall be nonconducting. The jacket shall be an extruded-to-fill type. 5.6.1 The nonconducting jacket shall meet the physical and aging requirements of ICEA S-94-649. 5.6.2 The cable shall be manufactured such that the concentric neutral wires are equally spaced and remain in contact with the underlying extruded insulation shielding after application of the overall jacket. 6.0 CABLE IDENTIFICATION 6.1 The center strand of stranded conductor cable shall be indent printed with the manufacturer's name and year of manufacturer at regular intervals with unindented surfaces not exceeding 12 inches. 6.2 The outer surface of the jacket of each cable shall be durably and legibly marked throughout its length in accordance with ICEA S-94-649 including month and year of manufacturing, and additionally, a lightning bolt symbol (in accordance with ANSI C2). Identification marking shall be of the indent-printing type. The depth of the indentation shall not result in the violation of the minimum jacket thickness as required by ICEA S-94-649. 6.3 Sequential footage numbers shall be clearly printed throughout the cable length at 2-foot intervals. Sequential footage numbers shall not be repeated on any single order. Sequential footage numbers may be of the indent-printing type with the indentation highlighted with white or silver colored ink or surface printed. The depth of the indentation shall not result in the violation of the minimum jacket thickness as required by ICEA S-94-649. 6.4 The outer surface of the jacket of each cable shall be marked with three (3) extruded, continuous, longitudinal, highly visible opaque red stripes spaced 120 apart. The nominal dimensions of the stripes shall be in accordance with ICEA S-94-649. 7.0 QUALITY ASSURANCE 7.1 Quality System The cable manufacturer shall have a quality system in place that meets the requirements of ISO-9002 (ANSI/ASQC Q92) or a CPU approved equivalent. 7.2 Plant Certification To qualify as a bidder, the following information shall be submitted for the specific cable manufacturing plant where the cable will be made: 7.2.1 Plant location. 7.2.2 Description of the extrusion equipment used, including positioning of extruders. 7.2.3 Description of the curing process and equipment used. 7.2.4 Description of the cooling down process used. 16

7.2.5 Description of the compound inspection process used. 7.2.6 Description of the compound handling system used from the shipping vehicle to the extruder. 7.2.7 Description of the statistical quality control method used. 7.2.8 List of previous customers supplied from this plant. 8.0 TESTING AND TEST METHODS 8.1 Qualification Tests 8.1.1 One certified copy of the results of ICEA S-94-649, and AEIC CS8 qualification tests on specified cable shall be provided. Cable with a number 1/0 conductor size is the preferred size for the qualification tests. 8.1.2 Qualification tests must be approved by Clark Public Utilities prior to acceptance as a supplier. 8.2 Production Sampling Tests 8.2.1 Production sampling tests shall be made in accordance with ICEA S-94-649. 8.2.2 Alternate production tests shall be approved by Clark Public Utilities prior to acceptance as a supplier. 8.3 Production Run Certified Test Reports (CTR) 8.3.1 General Requirements The following general information shall be included in the CTR: plant identification, process description, CTR number, purchase order number, manufacturer shipment number, reel count, shipment footage, cable core extruder/cv line identifier, and jacket line identifier. The CTR shall list the compound, and the facility where the compound was manufactured and where it was mixed. Any changes or modifications made to the compounds shall be noted in the CTR. 8.3.2 Measurement Data 8.4 Tests on Completed Cables 9.0 ACCEPTANCE TESTS The following CTR production run data shall be provided for all cable produced: minimum point thickness for the conductor shield; the minimum and maximum point thickness for the insulation, insulation shield and jacket; minimum diameter and maximum diameter for the insulation and insulation shielding. This production run data shall be provided for each shipping reel and shall be traceable to the production log. Tests on completed cable and partial discharge test shall be made in accordance with ICEA S-94-649, if a more stringent test is not possible. 9.1 Shipping and Labeling Requirements 17

9.1.1 The cable manufacturer shall submit the reports identified in Section 9.2 to the following address: Clark Public Utilities Purchasing Department P.O. Box 8900 Vancouver, WA 98668 9.1.2 All reports shall be shipped in separate packages with the cable shipment. 9.2 Report and Sample Requirements 9.2.1 One certified copy of the reports of all test data and dimensional measurements, including X-Y plots when appropriate, shall be furnished for each master reel of cable to be shipped. 9.3 Sampling by the Utility Clark Public Utilities, or its designated agent, will take additional cable samples from each shipping reel of received cable as deemed necessary. 9.3.1 A twenty-four inch sample shall be available on the inner end of each cable reel. The sample shall be an extension of the cable through the reel flange and stapled to the flange. 9.4 Performance Acceptance Tests Performance acceptance tests may be conducted on samples from each reel of cable to be accepted based on the procedures contained in this specification. The testing and examinations of cable samples may be performed by the utility or its authorized agent. All test procedures, examinations, and their results shall conform to ICEA S-94-649 except as specifically noted. Failure of a sample to satisfy the requirements of any section of this specification may be cause for rejection of that shipping reel of cable. Clark Public Utilities or its authorized representative reserves the right to refuse installation of any cable not meeting the requirements of this specification. 9.5 Tests that May be Performed on 24 Inch Cable Samples 9.5.1 The cable jacket may be visually inspected for correct markings and any surface damage to the cable jacket. 9.5.2 The cable jacket may be measured to determine the minimum and maximum thickness. 9.5.3 With the jacket removed, the copper concentric neutral wires may be examined for defects, uniformity of spacing around the cable, and lay. The number of strands may be counted and the wire size measured. 9.5.4 With the copper concentric neutral wires removed, the insulation shield may be visually inspected for correct markings and surface damage. The volume resistivity and the bond strength (or stripping tension) may be measured. 9.5.5 With the insulation shield removed, the insulation may be visually inspected for contaminants, voids, and protrusions. Any questionable areas may have wafer samples taken which may be examined. 9.5.6 The volume resistivity of the semiconducting conductor shield may be measured. 18

9.5.7 The conductor may be inspected for manufacturer identification, lay, protrusions, and defects. The outside diameter of the conductor may be measured. The number of strands may be counted and measured for wire size. 10.0 SHIPMENT AND REELS 10.1 Packing and Sealing 10.2 Reels 10.1.1 Cable shall be supplied in one continuous length for each reel. Length shall be +5% to -0% of the length specified for each reel. 10.1.2 Each end of the cable shall be firmly and properly secured to the reel. Care shall be taken to prevent looseness of reeled cable. The cable end attached through the interior of the reel shall be fastened in such a manner that it remains attached as the cable is dispensed from the reel and does not interfere with other reels or waste cable. 10.1.3 There shall be a minimum 2-inch clearance between the outer edge of the reel flange and the surface of the outermost layer of cable. 10.1.4 Watertight seals shall be applied to all cable ends to prevent entry of moisture during transit and outside storage prior to installation. All reels shall have Class 2 protection over the outer layer of cable in accordance with NEMA WC 26. Unless otherwise specified, all reels shall: Be NEMA Standard non-returnable wood reels free of damaging protrusions, e.g., nails, staples, etc. Use steel bushings to line reel arbor holes. Have a minimum drum diameter of 24 cable diameters. Have a maximum flange diameter of 58 inches. 10.3 Marking on Reels Reel information shall be embossed on stainless steel or aluminum tags permanently attached to the outside of the reel. The manufacturer shall label each reel as follows: Manufacturer's name, shipping reel number, factory reel number, and/or any other information to determine the origin of the cable. Purchaser s purchase order number Net weight, gross weight, and tare weight Length of cable Beginning and ending sequential footage numbers Type of cable Type, size, and stranding of conductor Thickness and type of insulation Voltage rating of cable Date of manufacturer and location DO NOT UPEND. Minimum 2 inches high, bright red or orange. An appropriate symbol such as a reel on its side with a red circle around it and a diagonal line through it is acceptable. All reels shall be traceable to the production log. 10.4 Shipping Instructions 19

11.0 WARRANTY The cable shall be shipped on flat bed vehicles. Enclosed vans will be rejected. The cable shall be shipped with the reel flanges vertically oriented. The reels must be secured to prevent flanges of one reel from damaging the cable on another reel. Reels shipped in enclosed trucks, lying horizontally on the flange, or stacked more than one high will be rejected. The vendor warrants that the cable furnished is free from defects in material and workmanship for a period of not less than 5 years and agrees to replace any material that is unsuitable for operation or fails in operation during normal and proper use. The minimum warranty shall be defined by the manufacturer. Any cost for an extended warranty, in addition to the manufacturer's standard warranty, shall be shown separately on all bids. 12.0 BID REQUIREMENTS 12.1 The bid shall clearly identify all compounds, the supplier name, plant location, and any modifications to the compounds. 12.2 The bid shall include a history of in-service records and a history of the proposed compound. 12.3 The bid shall include the manufacturer's most current written copies of the following: (a) (b) (c) (d) The certified copy of the AEIC - ICEA Qualification Test report for the compounds, materials, design, and processes which are to be used in manufacturing the specified cable. Procedures covering repair or rework of the layers outside of the cable core. Procedures, including examples, of production run sample selection, wafer selection, and wafer dimensional data recording. Procedures for re-sampling, hold tagging, and scrapping of portions of the cable run. 12.4 The bid shall include a bid data sheet for each item and any alternates. 12.5 Any bid that does not contain all of the information requested in 12.1 through 12.4 will not be evaluated. 20

PART 13 15kV 1/0 EPR CABLE DATA SHEET Manufacturer Phase Conductor size Bid Number Item Number Neutral Wire Size & Quantity Item Description Guaranteed Values 1. Outside diameter range of cable (complete). 2. Diameter range over insulator shield. 3. Diameter range over insulation. 4. Type of stranding. 5. Nominal weight of completed cable. Lbs/ft 6. Type of insulation. 7. Thickness range of insulation. 8. Thickness range of insulation shield. 9. Thickness range of conductor shield. 10. Reel Size (Flange x Traverse x Drum Max width outside flange in inches) x x - 11. Length of cable on reel. 12. Metal Content in lbs/1000 ft. Aluminum 13. Insulation shield (see 5.4) Copper Stripping tensions at room temperature. / Stripping tensions at 32 F. / Stripping tensions at 100 F. / Material manufacturer and identification. 14. Conductor shield manufacturer and identification. 15. Conductor alloy and temper. 16. Polyethylene content, % by weight. 17. Dissipation Factor at 20 C, at 50 C, at 90 C 18. S.I.C. at 20 C, at 50 C, at 90 C 19. Warranty (include the entire warranty on separate sheets). 21