DRAFT Version 1.2 of Installed Capacity Manual Attachment D For Discussion at Installed Capacity WG Meeting on January 27, 2005

Similar documents
Rules and Procedures for Determination of Generating Capability

Resource Capability Testing

PJM Manual 21: Rules and Procedures for Determination of Generating Capability Revision: 12 Effective Date: January 1, 2017

Expanding Capacity Eligibility

Rules and Procedures for Determination of Generating Capability

Comparison of Installed Capacity (ICAP) & Unforced Capacity (UCAP) Capacity Value Calculation Methods. Eligibility WG Meeting #3 July 4, 2017

Concepts for Changes to ACL for SCRs

Load Forecasting Manual

Installed Capacity Manual. August 2017

Manual 21- Revision 13 Rules and Procedures for Determination of Generating Capability Changes

Behind the Meter Net Generation Initiative: Energy Supplier Participation Requirements

NPCC Regional Reliability Reference Directory # 9 Verification of Generator Gross and Net Real Power Capability

UCAP Calculation Comparison

Wind Workshop. Technical Characterization: Dependable Capacity & Firm Energy 10:00-10:30am

Installed Capacity Market

Capacity Performance Training. June 24, 2015

Concepts for Behind-the- Meter Net Generation

Participation in the monthly auction and the capability period auction shall consist of:

Solar Integration Study

Deliverability Requirements for Capacity Imports

Capacity Performance FAQ Response

Applicable New York Wholesale Electricity Supplier Emissions

RPM 301 Performance in Reliability Pricing Model

4 Calculation of Demand Curve Parameters

PJM Manual 18B: Energy Efficiency Measurement & Verification Revision: 03 Effective Date: November 17, Prepared by PJM Forward Market Operations

ROCKY MOUNTAIN POWER Second Revision of Sheet No Canceling First Revision of Sheet No. 37-1

Criteria Revision Request. Revise SPP Criteria Section 12.1 for EIA_411 reporting purposes. Normal Expedited Urgent Action

2018/2019 NYSRC RELIABILITY RULE A.2 REQUIREMENTS R1, R2, R3 COMPLIANCE SUBMITTAL

7. Electrical Facility Ratings

Reliability Pricing Model (RPM) DRAFT Business Rules

LOLE is expressed as hours per year with the usual target criteria being (0.1 days/year) or 1- day in 10-years MISO Tariff: Module E-1 - The

Special Case Resources: Evaluation of the Performance and Contribution to Resource Adequacy

Requirements for Real and Reactive Power Testing

PJM Manual M36 System Restoration. A.1 Critical Black Start Criteria

Capacity Resource Performance in NYISO Markets

Mothball Outages in Capacity Markets

Winter 2015 Cold Weather Operations

Current Rules Related Energy Storage in PJM Markets V1: May 10, 2018

the Real-Time Market will be based on the system marginal costs produced by the Real-Time

Ancillary Services Matrix

PJM Generator Verification Test Correction Calculations Temperature Correction Calculations and Example: Combustion Turbines

Renewables and Self Supply Compliance Filing

California Independent System Operator Corporation. California ISO. Import resource adequacy. Department of Market Monitoring

Hydro Coalition Briefing Paper in Response to the PJM Capacity Performance Proposal

the Real-Time Market will be based on the system marginal costs produced by the Real-Time

Capacity Performance Training. March 16, 2015

Outage Types and Entering Tickets PJM State & Member Training Dept.

Load Forecasting Manual

LOAD SERVING ENTITIES PJM REGION


New England States Committee on Electricity

2010 RTO Metrics Report: NESCOE Data Summary

Energy Efficiency in RPM. Adam Keech Director, Market Operations PJM January 13, 2015

Planning Committee Recommendations for Summer Capability Verification Tests

PJM Manual 15: Cost Development Guidelines Revision: 30 Effective Date: December 4, Prepared by Cost Development Subcommittee

Highlights from the Quarterly Report on the New York ISO Electricity Markets Third Quarter of 2017

Market Design Concepts to Prepare for Significant Renewable Generation

Article 5. Electricity Generation Source Disclosure

Gas-Electric Coordination in PJM: Trends, Issues, Interactions, and Looking Ahead

RELIABILITY AND SECURITY ISSUES OF MODERN ELECTRIC POWER SYSTEMS WITH HIGH PENETRATION OF RENEWABLE ENERGY SOURCES

CO 2 Emissions from Electricity Generation and Imports in the Regional Greenhouse Gas Initiative: 2011 Monitoring Report

Cost Development Guidelines

Market Impact Assessment: Preliminary DAM Results Overview

PJM Generator Verification Test Correction Calculations Temperature and Relative Humidity Correction Calculations and Example: Combustion Turbines

New York CES: Renewable Energy Standard Underlying Fundamentals

Cost Development Guidelines

15.3 Rate Schedule 3 - Payments for Regulation Service. This Rate Schedule applies to Suppliers that provide Regulation Service to the ISO.

Introduction to the PJM Markets

Who should calculate the UCAP. Eligibility WG September 12, 2017

Progress Report Study Approach and Assumptions

Internal NYISO HVDC Controllable Line Scheduling. Concept of Operation. LECG Staff

ISO New England s 2011 Natural Gas Study

ConOp. Internal NYISO Controllable Lines. Concept of Operation. Scott Harvey, LECG. Document Locator:

2011/2012 RPM Base Residual Auction Results

Locational Export Capacity Proposal

Intermittent Resources in RPM. Sept 21, 2015

Cost Development Guidelines

MANITOBA HYDRO Power Smart Load Displacement Program. Engineering Cost Estimate Study Guide (Version 3)

PJM Manual 15: Cost Development Guidelines Revision: 2930 Effective Date: May 15, 2017April 9, Prepared by Cost Development Subcommittee

Schedule 2 TECHNICAL INFORMATION

ERCOT Public LTRA Probabilistic Reliability Assessment. Final Report

Cost Development Guidelines

Demand Side Ancillary Services Program (DSASP)

Cost Development Guidelines

PJM Manual 15: Cost Development Guidelines Revision: 2930 Effective Date: May 15, 2017July 31, Prepared by Cost Development Subcommittee

Beacon Power, LLC Response to the New York Energy Highway Request for Information (RFI) May 30, 2012

Capacity Performance Proposal. Summary of Key Design Elements

Climate Change Vulnerabilities of and Adaptation Strategies for New York State s Future Electric System

Comprehensive Shortage Pricing

Potential Methodology to Account for OFO Penalties Incurred due to Real-time Energy Dispatches

3.2 Market Settlements.

3.2 Market Buyers Spot Market Energy Charges.

Numerical Example of Net Short Threshold for Self Supply Exemption

PJM Interconnection, L.L.C. ( PJM ) submits hereby submits its responses to the United

Stakeholder Meeting Installed Capacity Demand Curves

Day-Ahead Market Enhancements Phase 1: Fifteen-Minute Granularity. Second Revised Straw Proposal

California Independent System Operator Corporation Fifth Replacement Electronic Tariff

NYISO 2015/2016 ICAP Demand Curve Reset

Transcription:

Attachment D: Dependable Maximum Net Capability, Audit Forms, the Procedure to Adjust a Resource s Proven Maximum Production Capability and the Procedure to Weather Adjust DMNC Test Data 1.0 Introduction All NYISO Resources are required to establish DMNC ratings to be eligible to become Installed Capacity Suppliers. They are also required to retest during each DMNC Test Period within each Capability Period in which it has committed Unforced Capacity. This Attachment establishes the requirements that must be met by such Resources to establish a uniform rating. It provides guidelines for how capability should be established, and how Resources will be audited by the ISO. PMPC and DMNC test data must be submitted to the NYISO s Resource Reliability Department. Documentation submitted via e-mail is preferred, however, delivery by regular mail, courier service or fax is also acceptable. Documentation should be addressed as follows: Email: generator_test_data@nyiso.com FAX: (518) 356-6208 Manager, Resource Reliability c/o New York Independent System Operator 290 Washington Ave. Extension Albany, NY 12203 For the purposes of rating and auditing Resources, as described in this Attachment, the following classification of Resources is used and thethe following forms are included in this attachment:? Steam Generation? Hydro Generation? Internal Combustion and Combustion Turbine Generation? Combined Cycle Generation? Other (Includes Intermittents) 1.1 Procedure to Adjust a Resource s Proven Maximum Production Capability D-1

A Resource s Proven Maximum Production Capability (PMPC) may be adjusted at any time. Five (5) business days are required to process the PMPC request and to be made available in the Market In formation System.? Provide the appropriate Dependable Maximum Net Capability Audit Form for the type of Resource being reported.? Check the PMPC box at top left of form. If only the PMPC box is checked, then DMNC information is not required with this submission. 1.2 Procedure to Weather Adjust DMNC Test Data All DMNC tests on internal combustion, combustion units and combined cycles units must be temperature adjusted. The temperature to be used for the temperature adjustment is the average ambient and cooling system temperature at the generator location experienced at the time of the TD peak during the previous four (4) relevant Capability Periods. The previous four (4) relevant Capability Periods do not include the Capability Period in which the DMNC test was performed. The dates and times of the TD peak in each Capability Period are posted on the ISO website at: www.nyiso.com/markets/icapinfo.html under General Information.? Determine the weather adjusted DMNC rating for the generator using the manufacturer s provided temperature adjustment curves and generator specific curves (if applicable) produced from historical experience.? Provide both sets of ratings and temperature adjustment curves.? The higher of the two values may be claimed. The ISO may lower the value claimed for the weather-adjusted DMNC, if the provided temperature adjustment curves are significantly different. Data should be submitted in accordance with the timeline as posted on the NYISO website at www.nyiso.com/markets/icapinfo.html and Section 4.2 of this Installed Capacity Manual. 2.0 Standard Generat ing Resources Standard generating Resources include all Resources registered with the ISO represented in the MIS except as noted below. Standard generating units must regularly achieve DMNC capability when called upon to do so. Capabilities must reflect, with reasonable accuracy, a unit's physical characteristics, the interdependence of common elements and auxiliaries located within a multi-unit generating station, and the deployment of operating personnel required for unit and/or station achievement D-2

of DMNC rating. Details pertaining to establishing and auditing of DMNC values for standard generating units are included below. 2.1 Intermittent Power Resources Intermittent Power Resources are capacity resources that depend on wind or solar energy for their fuel, and whose output amount and availability are not subject to the control of the ISO or the plant operator because of the source of fuel (e.g., wind, solar). 2.2 Run-of-River Hydro Units Run-of-river hydro units will be subject to the DMNC test procedures as delineated in Section X, below. 2.3 Energy Limited Resources Resources that, due to design considerations, environment restrictions on operations, cyclical requirements, such as the need to recharge or refill, or other non-economic reasons, are unable to operate continuously on a daily basis but are able to operate for at least four (4) consecutive hours each day. These include pumped storage hydro units that must be able to be dispatched by NYISO. 2.4 External Resources The ISO will honor the capability tests as applicable in the PJM or ISO-NE control area provided they are reasonably consistent with testing requirements for similar units in the NYCA. In addition to bidding, scheduling and notification requirements of any Installed Capacity resource, these units must demonstrate deliverability to the NYCA when scheduled in the DAM and when called on during an SRE or an emergency condition, in accordance with the Market Services Tariff. 2.5 Special Case Resources Special Case Resources must comply with the testing and reporting requirements in Section 4.12 of this Installed Capacity Manual as well as this Attachment D and Attachment K. 2.2 DMNC Test Periods The DMNC Test Demonstration Periods are defined as subsets of the respective Summer and Winter Capability Periods. DMNC rating for all Resources must be demonstrated in each of these DMNC Test Periods unless they were not a committed Installed Capacity Resource during any part of the applicable Capability Period. The Summer Demonstration Period begins on June 1 and ends on August 31. The Winter Demonstration Period begins on December 1 and ends on the last day of the immediately following February. In addition, the DMNC test period or the equivalent production data is more specifically defined as being limited to the time period beginning in hour 0800 and ending hour 2200, excluding NERC Holidays. D-3

3.1 DMNC Ratings DRAFT Version 1.2 of Installed Capacity Manual Attachment D DMNC ratings represent the Summer and Winter Capability of a generating unit or a combination of units. DMNCs are the maximum dependable load carrying ability, in megawatts truncated to one decimal place (full 100kW blocks), of such unit or units, excluding capacity required for station use. These ratings are the base Installed Capacity values that will be used to calculate Unforced Capacity values in accordance with Attachment J. To ensure a consistent basis for establishing the capability for generating units, Market Participants should follow the guidelines provided in Section Y of this Attachment. 3.2 DMNC Audits The ISO has the right to conduct audits for the purpose of establishing, restoring or verifying the DMNC rating of all generating units. 4.0 General Requiremenst for DMNC testing of all Resources 4.1 [Test requirements for Fossil or Nuclear Steam, Internal Combustion or Combustion Turbine, and Comined Cycle plants are largely unchanged except as noted above un Section 2.0, above] The forms (Excel Workbook) for submitting DMNC and/or PMPC test results information are posted on the ISO website at: http://www.nyiso.com/markets/icapinfo.html 4.2 DMNC for Hydroelectric generating Stations Hydroelectric generating stations shall have DMNC ratings that reflect variations in stream flow over the course of each Capability Period. DMNC capability calculations will utilize hourly river flow rate data over the applicable DMNC Test Period for each Capability Period. The DMNC rating for hydroelectric generators will be the average of the highest 4-hour production period for each month in the DMNC Test Period between 1400 and 1800 hours. The forms (Excel Workbook) for submitting this information are posted on the ISO website at: http://www.nyiso.com/markets/icapinfo.html 4.3 DMNC for Intermittent Generators This section describes the general procedure for calculating UCAP values for all intermittent capacity resources. It is intended to be the basis upon which to create capacity value calculation procedures for specific types of intermittent generators such as wind farms and photovoltaic generators. The forms (Excel Workbook) for submitting DMNC and/or PMPC test results information are posted on the ISO website at: http://www.nyiso.com/markets/icapinfo.html D-4

DEFINITIONS 1. Unforced Capacity value for an Intermittent Power Resource represents that amount of generating capacity, expressed in MW, that it can reliably contribute during peak hours and which can be traded as Unforced Capacity in the NYCA capacity markets. 2. Capacity Factor for an Intermittent Power Resource is a factor based on historical operating data and/or the Class Average Capacity Factor, and is used in calculating that Intermittent Power Resource s Unforced Capacity value. 3. The intermittent capacity resource s DMNC is the manufacturer s output rating less the Station Load where Station Load refers to the amount of energy that is consumed to operate all auxiliary equipment and control systems. 4. Intermittent Power Resources with three or more years of applicable operational data are referred to as Mature. Those with fewer than three years of data are Immature. [may not need this distinction] 5. Class Average Capacity Factor is a factor that is used only in the calculations for Unforced Capacity rating of an immature intermittent capacity resource. Initially, the Class Average Capacity Factor for Wind Generators is set at 15% [just a placeholder for now] but is subject to change upon the emergence of operating data from additional wind farms upon which to base the analysis. 6. Hourly output is the average of the metered outputs, in MW, integrated over a onehour period. 7. Summer Day is defined as any day from June 1 through August 31, inclusive. 8. Winter Day is defined as any d ay from December 1 through the last day in February, inclusive. 9. Peak Hours are those ending at 3, 4, 5, and 6 PM. 10. Summer Peak Hours means all Peak Hours for all of the Summer Days. CALCULATION PROCEDURE General Approach - Calculating an Unforced Capacity value for a particular Intermittent Power Resource for a particular year is performed by first computing its unique capacity factor. That capacity factor is based upon operating data for each Capability Period, or in the case of an immature Intermittent Power Resource, the capacity factor is assigned the value of the Class Average Capacity Factor for the Capability Period where there is no or incomplete data. The Capacity Factor, when multiplied by the current DMNC yields the current Unforced Capacity value for that Intermittent Power Resource. This process accommodates any changes in the DMNC capacity that may have occurred over time and is as follows: A. Sum all of the hourly outputs for each of the peak hours in the most recent Capability Period. B. Then, for each of those same peak hours sum the DMNC values. D-5

C. The quotient of the summed peak hour outputs (a) divided by the summed peak hour DMNC values (b) will yield a capacity factor for that year. D. If there is either no, or incomplete, operating data for one or more of the Capability Periods summers (immature Intermittent capacity resource) then the single year capacity factor for each of those years is assigned the value of the Class Average Capacity Factor. E. The current Unforced Capacity value is then calculated by multiplying this Capacity Factor by the current DMNC of the Intermittent Capacity Resource. Simplified Method (Constant Net Maximum Capacity Factor) - The calculation for a capacity factor (steps (A) through (D) above) is simplified sign ificantly if the DMNC is constant during each Capability Period for which it is being calculated. In this case the process is merely to average the Hourly Outputs for the Peak Hours and divide that by the DMNC for that Capability Period. The result will be the capacity factor for that Capability period. Again, the capacity factor for each Capability Period in which there is no or incomplete operating data is the current Class Average Capacity Factor. The process for calculating the Capacity Value is then as described in steps (E) above. 1. General Approach - The calculation of a Capacity Value for a particular wind farm for a particular year is performed by first computing the unique single year capacity factors for each of the prior three summers. Those single year capacity factors are based upon operating data for each of those summers, or in the case of an immature wind farm, the single year capacity factor is assigned the value of the Wind Class Average Capacity Factor for each summer where there is no or incomplete operating data. The mean of single year capacity factors for each of the prior three years results in a Capacity Factor representative of the three prior years. That Capacity Factor, when multiplied by the current Net Maximum Capacity yields the current capacity value for that wind farm. This two-step process accommodates any changes in the Net Maximum Capacity that may have occurred during the prior three summers of operation or the current year of operation. A detailed outline of this approach (addressing both mature and immature wind farms) is as follows: a. Sum all of the hourly outputs for each of the summer peak hours in the year that is three years prior to the current year. b. Then, for each of those same summer peak hours sum the Net Maximum Capacity values. c. The quotient of the summed summer peak hour outputs (a) divided by the summed summer peak hour Net Maximum Capacities (b) will yield a single year capacity factor for that year. d. If there is no or incomplete operatin g data for one or more of the summers (immature wind farm) then the single year capacity factor for each of those years is assigned the value of the Wind Class Average Capacity Factor. e. Repeating steps (a) through (d) above for each of the two intervening years (current year minus 2, and current year minus 1) will generate two more single year capacity factors, one for each of those years. f. The Capacity Factor to be used in the current year is the mean (arithmetic average) of the three single year capacity factors calculated in steps (c) and (d) above. D-6

g. The current Capacity Value is then calculated by multiplying this Capacity Factor from (f) above by the current Net Maximum Capacity of the wind farm. 2. Simplified Method (Constant Net Maximum Capacity Factor) - The calculation for a single year capacity factor (steps (a) through (e) above) is simplified significantly if the Net Maximum Capacity is constant during the Summer Period for which it is being calculated. In this case the process is merely to average the Hourly Outputs for the Summer Peak Hours and divide that by the Net Maximum Capacity for that summer. The result will be the single year capacity factor for that year. Again, the single year capacity factor for each year in which there is no or incomplete Summer Period operating data is the current Wind Class Average Capacity Factor. The process for calculating the Capacity Value is then as described in steps (f) and (g) above. D-7