A. ASTM E84 Standard Test Method for Surface Burning Characteristics of Building Materials

D. Provide UL-approved assemblies for pipes and ducts passing through fire-rated floors, walls, or partitions as required.

B. Refer to Section : Air Distribution for lined ductwork requirements.

This Design guideline contained herein includes the requirements for mechanical insulation at The University of Texas at Austin

University of Delaware

A. Section Fire Procection, HVAC & Plumbing Penetration Firestopping. B. Section Interior Painting: Painting insulation jacket.

HVAC INSULATION. A. General Requirements for Flexible Elastomeric Insulation: 3. Use pre-molded roll on pipe sizes 3.5" and below.

SECTION HVAC INSULATION

FIRE STATION 55 June 14, 2010

SECTION MECHANICAL INSULATION

UBC Technical Guidelines Section Edition Thermal Insulation for Piping Page 1 of 5

SECTION MECHANICAL INSULATION. A. Types of insulation specified in this section include the following:

PRESTON HEALTH SERVICES ARCHITECT S NO. 2700

1. Division 23 Section "Hangers and Supports for HVAC Piping and Equipment" for pipe insulation shields and protection saddles.

A. Deliver material to job site in original, nonbroken, factory packaging, labeled with manufacturer's density and thickness.

MECHANICAL INSULATION

A. This Section includes duct and plenum insulation; accessories and attachments; and sealing compounds.

DSC BUILDING 1200 ALTERATIONS OCTOBER 2011 SECTION DUCT INSULATION

SECTION HVAC INSULATION

SECTION PIPING INSULATION

SECTION MECHANICAL INSULATION

A. Product Data: Identify thermal conductivity, thickness, and jackets (both factory and field applied, if any), for each type of product indicated.

SECTION PLUMBING INSULATION

UBC Technical Guidelines Section Edition Insulation of Tanks, Steam and Condensate Piping Page 1 of 6

SECTION IDENTIFICATION FOR PLUMBING PIPING AND EQUIPMENT

State of Alaska Section State Office Building HVAC Fan Replacement MECHANICAL INSULATION

PROJ. NO SECTION HVAC DUCT INSULATION

HVAC INSULATION

SECTION (15081) - HVAC INSULATION

University of Houston Master Construction Specifications Insert Project Name

DIVISION 23 HEATING, VENTILATING, AND AIR CONDITIONING (HVAC) SECTION HVAC INSULATION

SECTION PROJECTED SCHEDULE

PRESTON HEALTH SERVICES ARCHITECT S NO. 2700

BuildingName The Description of the Project P DOCUMENTS

Revision May 2017 SECTION INSULATION SYSTEMS

.1 The following is a list of standards which may be referenced in this Section:

SECTION DUCT INSULATION

.1 Thermal insulation for insulated piping and piping accessories affected by construction and new pipe sections as indicated on drawings.

SECTION MECHANICAL SYSTEMS INSULATION

*************************************************************************************************************

NORTH HARRIS COUNTY REGIONAL WATER AUTHORITY. Section PIPE AND EQUIPMENT INSULATION

HVAC Piping Insulation FIBERGLAS Insulation. General Specification Guide SECTION

Addendum to Specifications

INSULATION SECTION 15250

SECTION HANGERS AND SUPPORTS FOR PLUMBING

This specification describes the minimum requirements for industrial thermal insulation.

Division 15 INSULATION Section 15100

ACOUSTICAL INSULATION (LAGGING) FOR PIPING AND EQUIPMENT

SUPERIOR CAL-SHIELDS Features & Benefits FAST

NCCER Progress Blvd, Alachua, Florida Tel: (888)

SECTION THERMAL INSULATION GENERAL THERMAL INSULATION PART RELATED DOCUMENTS

1. ARI 410 Standard for chilled water, hot water and steam coils. 2. ARI 430 Central Station Air Handling Units

HVAC Piping Insulation- FIBERGLAS Insulation

Addendum 1 Section THERMAL INSULATION FOR PIPING Burrow Avenue Pumping Station Upgrades Page 1 of 5

DUKE UNIVERSITY CONSTRUCTION STANDARDS

5. AMCA 301 Method of Publishing Sound Ratings for Air Moving Devices. 6. AMCA 500 Test Methods for Louver, Dampers, and Shutters

K. All mechanical rooms shall be designed with a minimum 3-1/2 dropped floor.

GUIDE SPECIFICATION: DUCT LINER

TENOCHCA HALL - PROJECT NO FAN COIL UNITS, RESTROOM AND FINISH RENOVATION

SECTION HVAC PIPING INSULATION Updated 8/2018

SECTION HVAC PIPING INSULATION

SECTION HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT

Knauf Data Sheet AH-DS-5E Friendly Feel. Duct Wrap. with ECOSE Technology

SECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT. A. ASME B31.1 (American Society of Mechanical Engineers) - Power Piping

SECTION PLUMBING INSULATION

B. American Society for Testing and Materials: 1. ASTM F708 - Standard Practice for Design and Installation of Rigid Pipe Hangers.

SECTION DUCTWORK INSULATION

Mechanical Insulation for Refrigeration Systems

. SECTION HANGERS AND SUPPORTS

10.1 APPLICATION 1 A. HOT PIPING 1 B. ANTI SWEAT PIPING 1 C. COLD PIPING FINISHES 2

SECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT

Daytona Beach Pier Building Renovation Jun 2010

EcoTouch Insulation with PureFiber Technology

SECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT

CHAPTER 26 PLASTIC SECTION BC 2601 SECTION BC 2603 GENERAL FOAM PLASTIC INSULATION

TENOCHCA HALL - PROJECT NO FAN COIL UNITS, RESTROOM AND FINISH RENOVATION

SECTION HVAC PIPING INSULATION

D-10 OUTLINE SPECIFICATION FOR PRE FAB Undergrd Piping System

GUIDE SPECIFICATION: MECHANICAL SYSTEMS

SECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT

Friendly Feel Duct Wrap with KwikStretch Markings. Knauf Data Sheet AH-DS

SECTION AIR DISTRIBUTION

Price High Performance Horizontal Fan Coil Units

Section Roof/Ceiling Thermal Insulation

PRODUCT SELECTION GUIDE

SECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT

STATE UNIVERPROGRAM DIRECTIVES

SECTION AIR TERMINAL UNITS

A. Thermal Conductivity: Thicknesses indicated are for thermal conductivity (k-value at 75 degrees F) specified for each material.

NORTH HARRIS COUNTY REGIONAL WATER AUTHORITY PIPE HANGERS, Section PIPE HANGERS, SUPPORTS, AND RESTRAINTS

SECTION CEMENTITIOUS WOOD FIBER DECKS

A. This section is intended to provide design guidelines for Utility Direct Buried Piping and Conduit Systems.

SECTION PLUMBING PIPING SYSTEM

RLGA. Gypsum Board Construction 2012 International Building Code. By Ronald L. Geren, AIA, CSI, CCS, CCCA, SCIP

Updated 6/4/2012. Table Of Contents SECTION PLUMBING INSULATION

CHAPTER 26 PLASTIC SECTION 2601 SECTION 2603 GENERAL FOAM PLASTIC INSULATION

UNIFIED FACILITIES GUIDE SPECIFICATIONS

Insulation Board. Knauf Data Sheet PE-DS

SECTION HANGERS AND SUPPORTS PART 1 - GENERAL. A. Drawings and Division 1 Specification Sections, apply to this Section.

Transcription:

PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is to apply the principles of this section such that the University may achieve a level of quality and consistency in the design and construction of their facilities. Deviations from these guidelines must be justified through LCC analysis and submitted to the University for approval. 1.02 References: A. ASTM E 84 - Standard Test Method for Surface Burning Characteristics of Building Materials B. ASTM C 533 Block and Pipe Thermal Insulation C. ASTM C 547 Mineral Fiber Preformed Insulation D. ASTM C 552 Cellular Glass Block and Pipe Thermal Insulation E. ASTM C 553 Mineral Fiber Blanket and Felt Insulation F. ASTM C 612 Mineral Fiber Block and Board Thermal Insulation G. ASTM C 1126 Rigid Cellular Phenolic Thermal Insulation H. ASTM C 921 Standard Practice for Determining the Properties of Jacketing Materials for Thermal Insulation I. MSS SP-69 Pipe Hangers and Supports Selection and Application 1.03 Requirements: A. Provide insulation and associated accessories with flame-spread index of 25 or less, and smoke-developed index of 50 or less, as tested by ASTM E 84 (NFPA 255) method. B. Provide piping and ductwork insulation thickness and thermal conductivity in conformance with the latest edition of ASHRAE 90.1. C. Provide duct and pipe insulation continuous through walls, partitions, ceiling openings and sleeves. D. Provide UL-approved assemblies for pipes and ducts passing through fire-rated floors, walls, or partitions as required. Design and Construction Standards, Revised January 2013 5.23.07-1

E. Provide a continuous, unbroken, vapor seal on all cold pipe surfaces. Guides and anchors secured directly to cold surfaces shall be adequately insulated and vapor sealed to prevent condensation. F. Provide aluminum jackets, 0.016 thick, for exterior pipe, ductwork, and equipment insulation covers, as well as for exposed piping in mechanical rooms subject to wear or abuse. Locate seams on bottom side of horizontal pipe G. Jackets for Piping Insulation shall conform to requirements of ASTM C 921, Type II for piping with temperatures above ambient. H. Provide insulation protection shields fabricated from galvanized steel at all pipe hangers in accordance with MSS SP-69. I. Encase pipe fittings insulation with one-piece pre-molded PVC fitting covers, fastened as per manufacturer's recommendations. J. Provide staples, bands, wires, cement, adhesives, sealers, and protective finishes as recommended by insulation manufacturer for applications indicated. i. [LEED EQ Credit 4.1 Low-Emitting Materials Specify materials that qualify as low-emitting VOC compounds as defined in the LEED Reference Guide] K. Provide flexible reusable insulation blankets for equipment requiring access such as pumps, strainers, etc. L. Insulate valves, fittings and similar items in each piping system with equivalent thickness and composition of insulation as applied to adjoining pipe run. Install factory molded, precut units. PART 2 - PRODUCTS 2.01 Piping Insulation Materials: A. Rigid Phenolic Insulation: Shall be CFC free and meet or exceed requirements of ASTM C 1126, Type III, Grade 1 to 250 deg F service. Provide with factory-applied jacket suitable for the installation location. B. : Shall meet or exceed the requirements of ASTM C533, Type I. Provide insulation with manufacturer s recommended jacket. C. Fiberglass Piping Insulation: Shall meet or exceed requirements of ASTM C 547, Class 1, noncombustible, with factory applied white kraft foil vapor barrier unless otherwise indicated. D. Flexible Elastomeric Closed Cell: Shall meet or exceed requirements of ASTM C 534, Type I, tubular grade. Provide finish coating. Design and Construction Standards, Revised January 2013 5.23.07-2

E. Foam Glass: Shall meet or exceed requirements of ASTM C 552, Type II. Provide factory cover and vapor retarder finish. 2.02 Equipment Insulation Materials: A. Mineral Fiber: Shall meet or exceed requirements of ASTM C 547, Types I, II or III. Provide with factory-applied jacket. B. : Shall meet or exceed the requirements of ASTM C 533, Type I or II. Provide insulation with manufacturer s recommended jacket. C. Flexible Elastomeric Cellular: Shall meet or exceed the requirements of ASTM C 534, Grade 1, Type I or II. Provide type II with vapor retarder skin on one or both sides of insulation. 2.03 Ductwork Insulation Materials: A. Flexible Fiberglass: Shall meet or exceed requirements of ASTM C 553. Provide insulation with a density of 1 pound per cubic foot and thermal conductivity (k value) of 0.29 @ 75oF mean temperature. Provide with vapor barrier facing of an aluminum foil and kraft paper lamination sandwiching a fiberglass scrim for reinforcing. B. Flexible Closed-Cell Elastomeric: Shall meet or exceed requirements of ASTM C 534, Type II. Provide with finish protective coating. PART 3: EXECUTION 3.01 Piping System Insulation: A. HVAC Piping System Omissions: Omit insulation on hot piping within radiation enclosures or unit cabinets; on cold piping within unit cabinets provided piping is located over drain pan; on heating piping beyond control valve, located within heated space; on condensate piping between steam trap and union; and on unions, flanges, strainers, flexible connections, and expansion joints. B. Steel piping insulated with rigid phenolic shall be coated with epoxy finish prior to insulation installation. C. Insulate piping systems per table 23.07.1 Design and Construction Standards, Revised January 2013 5.23.07-3

Table 23.07.1 SERVICE MATERIAL VAPOR BARRIER CHW supply/return, Fin water Rigid Phenolic Yes Existing wet pipe (tunnel piping) Foam Glass Yes Heating Hot Water supply/return (max 250 F), Condensate Mineral Fiber / Calcium Silicate Low Pressure Steam (max 250 F) Potable Cold Water, makeup water, drinking fountain drain Potable Hot Water supply/recirculating (max 200 F) Refrigerant Suction Flexible Elastomeric Closed Cell Flexible Elastomeric Closed Cell Yes 3.02 Equipment Insulation: A. Do not insulate over nameplate or ASME stamps. Bevel and seal insulation around nameplates. B. Insulate the following equipment per Table 23.07.2: Cold refrigeration equipment not factory insulated, drip pans under chilled equipment, cold and hot water storage tanks, water softeners, duct mounted coils, cold and chilled water pumps, air handling equipment not factory insulated, expansion and air separator tanks, heat exchangers, hot water generators, and pumps handling media above 130 degrees F. Design and Construction Standards, Revised January 2013 5.23.07-4

Table 23.07.2 Table 23.07.2 EQUIPMENT HANDLING MEDIA AT INDICATED TEMPERATURE INSULATION MATERIAL THICKNESS 1 to 34 degrees F Flexible Elastomeric 1.5 inches Cellular 35 to 60 degrees F Flexible Elastomeric 1.0 inches Cellular 61 to 250 degrees F Mineral Fiber 2.0 inches 2.0 inches 251 to 400 degrees F Mineral Fiber 3.0 inches 4.0 inches 401 to 600 degrees F Mineral Fiber 4.0 inches 6.0 inches > 600 degrees F Thickness necessary to limit external insulation temperature to 120 degrees F. 3.03 Duct System Insulation: A. Except as otherwise indicated, omit external insulation on ductwork where internal insulation or sound absorbing linings have been provided. B. Hot and cold interior ductwork shall be insulated with Flexible Fiberglass insulation. Provide thickness to achieve minimum R-value requirements per ASHRAE 90.1. C. Exterior ductwork shall be insulated with Flexible Closed-Cell Elastomeric insulation. Provide with aluminum jacketing sealed water tight. Cant insulation on top of ductwork to promote drainage. D. Fiberous glass insulation shall not be installed as internal insulation in contact with the air stream in supply, return, transfer, or outside air ducts. END OF STANDARD Design and Construction Standards, Revised January 2013 5.23.07-5