SECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES PART 1 - GENERAL 1.1 SUMMARY. A Section Includes: 1.2 ACTION SUBMITTALS

Similar documents
A. Product Data: For surface pathways, wireways and fittings, floor boxes, hinged-cover enclosures, and cabinets.

SECTION PATHWAYS FOR ELECTRONIC SAFETY AND SECURITY

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 26 ELECTRICAL SECTION RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS

SECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

Student Services & Classroom Addition

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

SECTION GROUNDING AND BONDING

SECTION GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS

B. Insulated Conductors: Stranded copper wire, green or green with yellow stripe insulation, insulated for 600 V, and complying with UL 83.

Youngstown State University

Essex County College - West Essex Campus Addition And Renovations dlb # / 11-14

SECTION PART 1 GENERAL

SECTION GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY

A. Coordinate arrangement, mounting, and support of electrical equipment:

SECTION GROUNDING

NYULMC AMBULATORY CARE CENTER FIT-OUT PHASE 1 Perkins & Will Architects PC 222 E 41st ST, NYC Project: Issued for GMP March 15, 2017

Procurement Services SVC East Fowler Avenue Tampa, Florida (813)

SECTION GROUNDING AND BONDING

DESIGN GUIDELINES WIRING AND CONDUITS PAGE 1 of 7

DIVISION 26 RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS PART 1 - GENERAL RELATED DOCUMENTS

SECTION RACEWAYS AND BOXES

1. Telecommunications mounting elements. 2. Backboards. 3. Telecommunications equipment racks and cabinets. 4. Grounding.

A. Basket Cable Tray: A fabricated structure consisting of wire mesh bottom and side rails.

SECTION A. Underwriters Laboratories, Inc., listed and NEC approved

SECTION GROUNDING AND BONDING

SECTION (Master Template Final-05) ELECTRICAL BOXES. A. Provide boxes for electrical equipment and wiring devices as follows:

SECTION CONDUITS AND BACKBOXES FOR COMMUNICATIONS SYSTEMS

B. Provide a complete conduit system with associated couplings, connectors, and fittings.

This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update.

3. Intermediate metal conduit (IMC). 4. Electric metallic tubing (EMT). 5. Flexible metal conduit (FLEX). 6. Polyvinyl chloride conduit (PVC).

SECTION GROUNDING AND BONDING

ELECTRICAL SECTION 2

A. All materials shall be tested and listed by an OSHA approved Nationally Recognized Testing Laboratory (NRTL).

SECTION A. ASTM B3 - Standard Specification for Soft or Annealed Copper Wire; 2013.

Design Standard Conduit for Electrical Systems

GLENWOOD PLACE 2 MAR 2015

This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update.

A. Basket Cable Tray: A fabricated structure consisting of wire mesh bottom and side rails.

SECTION PATHWAYS FOR COMMUNICATIONS SYSTEMS

Kaf-Tech Product Specification

ADDENDUM 2. Lockwood Hall Renovation Project. July 9, The bidders are to take notice and acknowledge the following:

2003 International Residential Code ELECTRICAL PROVISIONS ONLY October 2005 EDITORIAL CHANGES SEVENTH PRINTING

SECTION WIRE, CABLE AND BUSWAYS. A. This section specifies providing wire, cable and busways.

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

NEC 2014 Code Changes

SECTION RACEWAYS

1510 RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS

WIRING METHODS CHAPTER 38

1. Section "Underground Ducts and Raceways for Electrical Systems" for exterior DEFINITIONS

Essex County College - West Essex Campus Addition And Renovations dlb # / SECTION CABLE TRAYS FOR COMMUNICATIONS SYSTEMS

CONTENTS. B. System Design and Performance Requirements

SECTION CONDUIT AND FITTINGS

A. Section includes busway and fittings including plug-in units.

A. This Section includes steel cable trays and accessories.

UNDERGROUND SERVICES SECONDARY

CONDUITS AND FITTINGS

SECTION PATHWAYS FOR COMMUNICATIONS SYSTEMS

CHAPTER 11 CONDUITS AND FITTINGS

SECTION RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS

SECTION WIRE AND CABLE Raceways and Conduit Motor Power and Control Wiring.

SERVICES CHAPTER 35. wire. For all other installations, the rating of the ungrounded conductors shall be not less than 60 amperes.

SECTION CONDUITS AND BOXES

SECTION RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS. A. ANSI C Electrical Rigid Steel Conduit, Zinc Coated.

BASIC ELECTRICAL MATERIALS AND METHODS

WIRE AND CABLE Raceways and Conduit Motor Power and Control Wiring.

SECTION CHAIN-LINK FENCES AND GATES 02821/1

1. Hangers and supports for electrical equipment and systems.

1. Building wires and cables rated 600 V and less. 2. Connectors, splices, and terminations rated 600 V and less.

SECTION MINOR ELECTRICAL DEMOLITION

PHYSICAL FACILITIES Consultant s Handbook Specifications Division 27 Communication 0528 Pathways. Page 1 of 6

SECTION RACEWAYS AND BOXES FOR ELECTRONIC SAFETY AND SECURITY

EFFECTIVE DATE: November 1, 2011, unless a later date is cited at the end of a section. [ NMAC - Rp,

NORTHEASTERN REMC ELECTRIC STANDARDS MANUAL

SECTION UNDERGROUND ELECTRICAL CONSTRUCTION

SECTION CONDUIT AND BOXES

Police/Emergency Service Center PSGP Grant #2007-GB-T CN

SECTION ELECTRICAL SYSTEM RACEWAY and BOXES

SECTION CONDUI T

SECTION CONDUITS AND BOXES PART 1- GENERAL. A. Work covered by this section includes the furnishing and installation of conduits and boxes.

SECTION BASIC ELECTRICAL MATERIALS AND METHODS

SECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES (24 Volt AC/DC or Less)

SECTION OUTLET, PULL, AND JUNCTION BOXES

SECTION FACILITY LIGHTNING PROTECTION

A. Section Includes: Electrical site utilities and coordination of requirements with the utility company and service specifications.

A. Product Data shall be provided for each type of product indicated.

SECTION ELECTRICAL SITE UTILITIES

SECTION COMMON WORK RESULTS FOR FIRE SUPPRESSION

A. American Society for Testing and Materials (ASTM): Specification for Concentric-Lay-Stranded Copper Conductors, Hard, Medium-Hard or Soft.

NORTHWESTERN UNIVERSITY PROJECT NAME JOB #

SECTION CONDUITS AND BACKBOXES FOR COMMUNICATIONS SYSTEMS

6. SECONDARY SERVICES (under 600 volts) 6.1 AVAILABILITY For the electrical characteristics of available secondary services see Section 3.4.

2008 NEC Guide Lines for Home Owner Doing Electrical Work on their Property

NORTHEASTERN REMC ELECTRIC STANDARDS MANUAL

SECTION GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS

CITY OF OCEANSIDE. Electrical Lines, Plumbing and Mechanical Burial & Support Requirements. Informational Bulletin

1. Section COVER PAGE: remove and replace with new Cover Page, Attached.

The General Provisions of the Contract, including General, Supplementary and Special Conditions, apply to the work specified in this Section.

SECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES

Transcription:

SECTION 260519- LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES PART 1 - GENERAL 1.1 SUMMARY A Section Includes: 1. Building wires and cables rated 600 V and less. 2. Connectors, splices, and terminations rated 600 V and less. Related Requirements: 1. Section 260523 "Control-Voltage Electrical Power Cables" for control systems communications cables and Classes 1, 2 and 3 control cables. 1.2 ACTION SUBMITTALS Product Data: For each type of product. 1.3 INFORMATIONAL SUBMITTALS Field quality-control reports. PART 2 -PRODUCTS 2.1 CONDUCTORS AND CABLES c. Copper Conductors: Comply with NEMA WC 70/ICEA S-95-658. Conductor Insulation: Comply with NEMA WC 70/ICEA S-95-658 for Type THW-2, Type THHN/THWN-2 and Type XHHW-2. Multi-conductor Cable: Comply with NEMA WC 70/ICEA S-95-658 for metal-clad cable, Type M C with ground wire. 2.2 CONNECTORS AND SPLICES Description: Factory-fabricated connectors and splices of size, ampacity rating, material, type, and class for application and service indicated. 2.3 SYSTEM DESCRIPTION Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFP A 70, by a qualified testing agency, and marked for intended location and application. Comply with NFPA 70. LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES 260519-1

PART 3 - EXECUTION 3.1 CONDUCTOR MATERIAL APPLICATIONS Feeders: Copper. Solid for No. 10 AWG and smaller; stranded for No.8 AWG and larger. Branch Circuits: Copper. Solid for No. 12 AWG and smaller; stranded for No. 10 AWG and larger. 3.2 CONDUCTOR INSULATION AND MULTICONDUCTOR CABLE APPLICATIONS AND WIRING METHODS c. Exposed Feeders: Type THHN/THWN-2, single conductors in raceway and Type XHHW-2, single conductors in raceway. Feeders Concealed in Ceilings, Walls, Partitions, and Crawlspaces: Type THHN/THWN-2, single conductors in raceway. Exposed Branch Circuits, Including in Crawlspaces: Type THHN/THWN-2, single conductors in raceway. D. Branch Circuits Concealed in Ceilings, Walls, and Partitions: Type THHN/THWN-2, single conductors in raceway metal-clad cable, Type MC. 3.3 INSTALLATION OF CONDUCTORS AND CABLES Conceal cables in fmished walls, ceilings, and floors unless otherwise indicated. Complete raceway installation between conductor and cable termination points according to Section 260533 "Raceways and Boxes for Electrical Systems" prior to pulling conductors and cables. C. Use manufacturer-approved pulling compound or lubricant where necessary; compound used must not deteriorate conductor or insulation. Do not exceed manufacturer's recommended maximum pulling tensions and sidewall pressure values. D. Use pulling means, including fish tape, cable, rope, and basket-weave wire/cable grips, that will not damage cables or raceway. E. Install exposed cables parallel and perpendicular to surfaces of exposed structural members, and follow surface contours where possible. 3.4 CONNECTIONS Tighten electrical connectors and terminals according to manufacturer's published torquetightening values. If manufacturer's torque values are not indicated, use those specified in UL 486A-486 Make splices, terminations, and taps that are compatible with conductor material and that possess equivalent or better mechanical strength and insulation ratings than unspliced conductors. C. Wiring at Outlets: Install conductor at each outlet, with at least 12 inches of slack. LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES 260519-2

3.5 IDENTIFICATION Identify and color-code conductors and cables. Identify each spare conductor at each end with identity number and location of other end of conductor, and identify as spare conductor. 3.6 SLEEVE AND PENETRATIONS SLEEVE-SEAL INSTALLATION FOR ELECTRICAL Install sleeves and sleeve seals at penetrations of exterior floor and wall assemblies. Comply with requirements in Section 260544 "Sleeves and Sleeve Seals for Electrical Raceways and Cabling." 3.7 FIRES TOPPING c. Apply firestopping to electrical penetrations of fire-rated floor and wall assemblies to restore original fire-resistance rating of assembly. Install penetration frrestopping systems to comply with manufacturer's written installation instructions and published drawings for products and applications. Penetration Firestopping Systems: Systems that resist spread of fire, passage of smoke and other gases, and maintain original fire-resistance rating of construction penetrated. Penetration firestopping systems shall be compatible with one another, with the substrates forming openings, and with penetrating items if any. Penetrations in Fire-Resistance-Rated Walls: Penetration firestopping systems with ratings determined per ASTM E 814 or UL 1479, based on testing at a positive pressure differential of 0.01-inch wg. 1. F-Rating: Not less than the fire-resistance rating of constructions penetrated. 3.8 FIELD QUALITY CONTROL A Perform the following tests and inspections: 1. After installing conductors and cables and before electrical circuitry has been energized, test for compliance with requirements. Delete first subparagraph below if deleting options in subparagraph above. 2. Perform each visual and mechanical inspection and electrical test stated in NET A Acceptance Testing Specification. Certify compliance with test parameters. Cables will be considered defective if they do not pass tests and inspections. END OF SECTION 260519 LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES 260519-3

THIS PAGE INTENTIONALLY LEFT BLANK

SECTION 260523 ~CONTROL~ VOLTAGE ELECTRICAL POWER CABLES PART 1 ~GENERAL 1.1 SUMMARY Section Includes: 1. RS-485 cabling. 2. Low-voltage control cabling. 3. Control-circuit conductors. 4. Identification products. 1.2 ACTION SUBMITTALS Product Data: For each type of product. 1.3 INFORMATIONAL SUBMITTALS Source quality-control reports. Field quality-control reports. PART 2 -PRODUCTS 2.1 SYSTEM DESCRIPTION Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFP A 70, by a qualified testing agency, and marked for intended location and application. 2.2 PERFORMANCE REQUIREMENTS Flame Travel and Smoke Density in Plenums: As determined by testing identical products according to NFP A 262 by a qualified testing agency. Identify products for installation in plenums with appropriate markings of applicable testing agency. 1. Flame Travel Distance: 60 inches or less. 2. Peak Optical Smoke Density: 0.5 or less. 3. Average Optical Smoke Density: 0.15 or less. Flame Travel and Smoke Density for Riser Cables in Non-Plenum Building Spaces: As determined by testing identical products according to UL 1666. C. Flame Travel and Smoke Density for Cables in Non-Riser Applications and Non-Plenum Building Spaces: As determined by testing identical products according to UL 1685. 2.3 RS-485 CABLE Plenum-Rated Cable: NFPA 70, Type CMP. 1. Paired, One Pair, No. 22 AWG, stranded (7x30) tinned-copper conductors. 2. Fluorinated ethylene propylene insulation. 3. Unshielded. CONTROL-VOLTAGE ELECTRICAL POWER CABLES 260523-1

4. Fluorinated ethylene propylene jacket. 5. Flame Resistance: NFPA 262. 2.4 LOW-VOLTAGE CONTROL CABLE Plenum-Rated, Paired Cable: NFPA 70, Type CMP. 1. One pair, twisted, No. 16 A WG, stranded (19x29) tinned-copper conductors. 2. PVC insulation. 3. Unshielded. 4. PVC jacket. 5. Flame Resistance: Comply with NFPA 262. 2.5 CONTROL-CIRCIDT CONDUCTORS Class 1 Control Circuits: Stranded copper, Type THHN-2-THWN-2. Class 2 Control Circuits: Stranded copper, Type THHN-2-THWN-2, in raceway. C. Class 3 Remote-Control and Signal Circuits: Stranded copper, Type THHN-2-THWN-2, in raceway. PART 3 -EXECUTION 3.1 INSTALLATION OF RACEWAYS AND BOXES Comply with requirements in Section 260533 "Raceways and Boxes for Electrical Systems" for raceway selection and installation requirements for boxes, conduits, and wireways as supplemented or modified in this Section. 1. Outlet boxes shall be no smaller than 2 inches wide, 3 inches high, and 2-1/2 inches deep. 2. Flexible metal conduit shall not be used. Comply with TIA-569-B for pull-box sizing and length of conduit and number of bends between pull points. C. Install manufactured conduit sweeps and long-radius elbows if possible. D. Raceway Installation in Equipment Rooms: 1. Position conduit ends adjacent to a comer on backboard if a single piece of plywood is installed, or in the comer of the room if multiple sheets of plywood are installed around perimeter walls of the room. 2. Install cable trays to route cables if conduits cannot be located in these positions. 3. Secure conduits to backboard if entering the room from overhead. 4. Install metal conduits with grounding bushings and connect with grounding conductor to grounding system. 3.2 INSTALLATION OF CONDUCTORS AND CABLES Comply with NECA 1 and NFPA 70. General Requirements for Cabling: CONTROL-VOLTAGE ELECTRICAL POWER CABLES 260523-2

1. Comply with TIA-568-C Series of standards. 2. Comply with BICSI ITSIMM, Ch. 5, "Copper Structured Cabling Systems" and Ch. 6, "Optical Fiber Structured Cabling Systems." 3. Tetminate all conductors and optical fibers; no cable shall contain unterminated elements. Make terminations only at indicated outlets, terminals, and patch panels. 4. Cables may not be spliced. 5. Secure and support cables at intervals not exceeding 30 inches and not more than 6 inches from cabinets, boxes, fittings, outlets, racks, frames, and terminals. 6. Bundle, lace, and train conductors to terminal points without exceeding manufacturer's limitations on bending radii, but not less than radii specified in BICSI ITSIMM, Ch. 5, "Copper Structured Cabling Systems" and Ch. 6, "Optical Fiber Structured Cabling Systems." Install lacing bars and distribution spools. 7. Do not install bruised, kinked, scored, deformed, or abraded cable. Do not splice cable between termination, tap, or junction points. Remove and discard cable if damaged during installation and replace it with new cable. 8. Cold-Weather Installation: Bring cable to room temperature before dereeling. Do not use heat lamps for heating. 9. Pulling Cable: Comply with BICSI ITSIMM, Ch. 5, "Copper Structured Cabling Systems." Monitor cable pull tensions. 10. Support: Do not allow cables to lie on removable ceiling tiles. 11. Secure: Fasten securely in place with hardware specifically designed and installed so as to not damage cables. C. Open-Cable Installation: 1. Install cabling with horizontal and vertical cable guides in telecommunications spaces with terminating hardware and interconnection equipment. 2. Suspend copper cable not in a wireway or pathway a minimum of 8 inches above ceilings by cable supports not more than 30 inches apart. 3. Cable shall not be run through or on structural members or in contact with pipes, ducts, or other potentially damaging items. Do not run cables between structural members and corrugated panels. D. Separation from EMI Sources: 1. Comply with BICSI TDMM and TIA-569-B recommendations for separating unshielded copper voice and data communications cable from potential EMI sources including electrical power lines and equipment. 3.3 3.4 REMOVAL OF CONDUCTORS AND CABLES Remove abandoned conductors and cables. Abandoned conductors and cables are those installed that are not terminated at equipment and are not identified for future use with a tag. CONTROL-CIRCUIT CONDUCTORS Minimum Conductor Sizes: 1. Class 1 remote-control and signal circuits; No 14 A WG. 2. Class 2low-energy, remote-control, and signal circuits; No. 16 AWG. 3. Class 3low-energy, remote-control, alarm, and signal circuits; No 12 AWG. CONTROL-VOLT AGE ELECTRICAL POWER CABLES 260523-3

3.5 3.6 3.7 3.8 FIRESTOPPING Comply with requirements in Section 078413 "Penetration Firestopping." Comply with TIA-569-B, Annex A, "Firestopping." GROUNDING For data communication wiring, comply with ANSI-J-STD-607-A and with BICSI TDMM, "Bonding and Grounding (Earthing)" Chapter. For low-voltage control wiring and cabling, comply with all NEC requirements for grounding. IDENTIFICATION Identify all circuits in coordination with facility owner. Identify data and communications system components, wiring, and cabling according to TIA- 606-A; label printers shall use label stocks, laminating adhesives, and inks complying with UL969. FIELD QUALITY CONTROL Perform the following tests and inspections: 1. Visually inspect UTP and optical-fiber cable jacket materials for UL or third-party certification markings. Inspect cabling terminations to confirm color-coding for pin assignments, and inspect cabling connections to confirm compliance with TIA-568-C.l. 2. Visually inspect cable placement, cable termination, grounding and bonding, equipment and patch cords, and labeling of all components. 3. Test UTP cabling for direct-current loop resistance, shorts, opens, intermittent faults, and polarity between conductors. Test operation of shorting bars in connection blocks. Test cables after termination but not after cross-connection. a. Test instruments shall meet or exceed applicable requirements in TIA-568-C.2. Perform tests with a tester that complies with performance requirements in "Test Instruments (Normative)" Annex, complying with measurement accuracy specified in "Measurement Accuracy (Informative)" Annex. Use only test cords and adapters that are qualified by test equipment manufacturer for channel or link test configuration. End-to-end cabling will be considered defective if it does not pass tests and inspections. END OF SECTION 260523 CONTROL-VOLTAGE ELECTRICAL POWER CABLES 260523-4

SECTION 260526- GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS PART 1- GENERAL 1.1 SUMMARY Section includes grounding and bonding systems and equipment. 1.2 ACTION SUBMITTALS Product Data: For each type of product indicated. PART 2 -PRODUCTS 2.1 SYSTEM DESCRIPTION Electrical Components, Devices, and Accessories: Listed and labeled as defmed in NFP A 70, by a qualified testing agency, and marked for intended location and application. Comply with UL 467 for grounding and bonding materials and equipment. 2.2 CONDUCTORS fusulated Conductors: Copper wire or cable insulated for 600 V unless otherwise required by applicable Code or authorities having jurisdiction. Bare Copper Conductors: 1. Solid Conductors: ASTM B 3. 2. Stranded Conductors: ASTM B 8. 3. Bonding Cable: 28 kcmil, 14 strands ofno. 17 AWG conductor, 114 inch in diameter. 4. Bonding Conductor: No. 4 or No. 6 A WG, stranded conductor. 5. Bonding Jumper: Copper tape, braided conductors terminated with copper ferrules; 1-5/8 2.3 CONNECTORS inches wide and 1/16 inch thick. Listed and labeled by an NRTL acceptable to authorities having jurisdiction for applications in which used and for specific types, sizes, and combinations of conductors and other items connected. Bolted Connectors for Conductors and Pipes: Copper or copper alloy. C. Welded Connectors: Exothermic-welding kits of types recommended by kit manufacturer for materials being joined and installation conditions. D. Bus-Bar Connectors: Mechanical type, cast silicon bronze, solderless compression-type wire terminals, and long-barrel, two-bolt connection to ground bus bar. 2.4 GROUNDING ELECTRODES Ground Rods: Copper-clad steel; 3/4 inch by 10 feet. GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS 260526-1

PART 3 ~ EXECUTION APPLICATIONS Conductors: Install solid conductor for No. 8 A WG and smaller, and stranded conductors for No. 6 A WG and larger unless otherwise indicated. Underground Grounding Conductors: Install bare copper conductor, 4/0 A WG minimum. 1. Bury at least 24 inches below grade. C. Conductor Terminations and Connections: 1. Pipe and Equipment Grounding Conductor Terminations: Bolted connectors. 2. Underground Connections: Welded connectors except at test wells and as otherwise indicated. 3. Connections to Ground Rods at Test Wells: Bolted connectors. 4. Connections to Structural Steel: Welded connectors. 3.2 EQUIPMENT GROUNDING Install insulated equipment grounding conductors with all feeders and branch circuits. Install insulated equipment grounding conductors with the following items, in addition to those required by NFPA 70: 1. Feeders and branch circuits. 2. Single-phase motor and appliance branch circuits. 3. Three-phase motor and appliance branch circuits. 4. Flexible raceway runs. c. D. Water Heater, Heat-Tracing, and Antifrost Heating Cables: Install a separate insulated equipment grounding conductor to each electric water heater and heat-tracing cable. Bond conductor to heater units, piping, connected equipment, and components. Propane Tank: Drive one (1) ground rod on either end of tank and connect to 4/0 ground ring around the tank with exothermic welds. Bond tank structure to ground ring in two locations. 3.3 INSTALLATION c. Grounding Conductors: Route along shortest and straightest paths possible unless otherwise indicated or required by Code. Avoid obstructing access or placing conductors where they may be subjected to strain, impact, or damage. Ground Bonding Common with Lightning Protection System: Comply with NFP A 780 and UL 96 when interconnecting with lightning protection system. Bond electrical power system ground directly to lightning protection system grounding conductor at closest point to electrical service grounding electrode. Use bonding conductor sized same as system grounding electrode conductor, and install in conduit. Ground Rods: Drive rods until tops are 2 inches below finished floor or final grade unless otherwise indicated. GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS 260526-2

1. Interconnect ground rods with grounding electrode conductor below grade and as otherwise indicated. Make com1ections without exposing steel or damaging coating if any. 2. For grounding electrode system, install at least three rods spaced at least one-rod length from each other and located at least the same distance from other grounding electrodes, and connect to the service grounding electrode conductor. D. Bonding Straps and Jumpers: Install in locations accessible for inspection and maintenance except where routed through short lengths of conduit. 1. Bonding to Structure: Bond straps directly to basic structure, taking care not to penetrate any adjacent parts. 2. Bonding to Equipment Mounted on Vibration Isolation Hangers and Supports: Install bonding so vibration is not transmitted to rigidly mounted equipment. 3. Use exothermic-welded connectors for outdoor locations; if a disconnect-type connection is required, use a bolted clamp. E. Grounding and Bonding for Piping: 1. Metal Water Service Pipe: Install insulated copper grounding conductors, in conduit, from building's main service equipment, or grounding bus, to main metal water service entrances to building. Connect grounding conductors to main metal water service pipes; use a bolted clamp connector or bolt a lug-type connector to a pipe flange by using one of the lug bolts of the flange. Where a dielectric main water fitting is installed, connect grounding conductor on street side of fitting. Bond metal grounding conductor conduit or sleeve to conductor at each end. 2. Water Meter Piping: Use braided-type bonding jumpers to electrically bypass water meters. Connect to pipe with a bolted connector. 3. Bond each aboveground portion of gas piping system downstream from equipment shutoff valve. 3.4 FIELD QUALITY CONTROL Perform tests and inspections. Inspect physical and mechanical condition. Verify tightness of accessible, bolted, electrical connections with a calibrated torque wrench according to manufacturer's written instructions. END OF SECTION 260526 GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS 260526-3

THIS PAGE INTENTIONALLY LEFT BLANK

SECTION 260533- RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS PART 1- GENERAL 1.1 SUMMARY Section Includes: 1. Metal conduits, tubing, and fittings. 2. Boxes, enclosures, and cabinets. 1.2 ACTION SUBMITTALS Product Data: None required. PART 2 -PRODUCTS 2.1 METAL CONDUITS, TUBING, AND FITTINGS c. D. E. F. Listing and Labeling: Metal conduits, tubing, and fittings shall be listed and labeled as defined in NFP A 70, by a qualified testing agency, and marked for intended location and application. GRC: Comply with ANSI C80.1 and UL 6. IMC: Comply with ANSI C80.6 and UL 1242. EMT: Comply with ANSI C80.3 and UL 797. LFMC: Flexible steel conduit with PVC jacket and complying with UL 360. Fittings for Metal Conduit: Comply with NEMA FB 1 and UL 514 1. Conduit Fittings for Hazardous (Classified) Locations: Comply with UL 886 and NFPA 70. 2. Fittings for EMT: a. Material: Steel. b. Type: Compression. 3. Expansion Fittings: Match conduit type, complying with UL 651, rated for environmental conditions where installed, and including flexible external bonding jumper. G. Joint Compound for IMC, GRC, or ARC: Approved, as defined in NFPA 70, by authorities having jurisdiction for use in conduit assemblies, and compounded for use to lubricate and protect threaded conduit joints from corrosion and to enhance their conductivity. 2.2 BOXES, ENCLOSURES, AND CABINETS General Requirements for Boxes, Enclosures, and Cabinets: Boxes, enclosures, and cabinets installed in wet locations shall be listed for use in wet locations. Sheet Metal Outlet and Device Boxes: Comply with NEMA OS 1 and UL 514 RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS 260533-1

C. Cast-Metal Outlet and Device Boxes: Comply with NEMA FB 1, ferrous alloy, Type FD, with gasketed cover. D. Small Sheet Metal Pull and Junction Boxes: NEMA OS 1. E. Cast-Metal Access, Pull, and Junction Boxes: Comply with NEMA FB 1 and UL 1773, galvanized, cast iron with gasketed cover. F. Box extensions used to accommodate new building finishes shall be of same material as recessed box. G. Device Box Dimensions: 4 inches square by 2-1/8 inches deep. H. Gangable boxes are prohibited. I. Hinged-Cover Enclosures: Comply with UL 50 and NEMA 250, Type 1 with continuoushinge cover with flush latch unless otherwise indicated. 1. Metal Enclosures: Steel, fmished inside and out with manufacturer's standard enamel. 2. Interior Panels: Steel; all sides finished with manufacturer's standard enamel. J. Cabinets: 1. NEMA 250, Type 1 galvanized-steel box with removable interior panel and removable front, finished inside and out with manufacturer's standard enamel. 2. Hinged door in front cover with flush latch and concealed hinge. 3. Key latch to match panel boards. 4. Metal barriers to separate wiring of different systems and voltage. 5. Accessory feet where required for freestanding equipment. 6. Nonmetallic cabinets shall be listed and labeled as defined in NFP A 70, by a qualified testing agency, and marked for intended location and application. PART 3 -EXECUTION 3.1 RACEWAY APPLICATION Outdoors: Apply raceway products as specified below unless otherwise indicated: 1. Exposed Conduit: GRC. 2. Concealed Conduit, Aboveground: GRC. 3. Underground Conduit: RNC, Type EPC-40-PVC. 4. Connection to Vibrating Equipment (Including Transformers and Hydraulic, Pneumatic, Electric Solenoid, or Motor-Driven Equipment): LFMC. 5. Boxes and Enclosures, Aboveground: NEMA 250, Type 4. Indoors: Apply raceway products as specified below unless otherwise indicated. 1. Exposed Conduit: GRC. 2. Connection to Vibrating Equipment (Including Transformers and Hydraulic, Pneumatic, Electric Solenoid, or Motor-Driven Equipment): LFMC. 3. Concealed in Ceilings and Interior Walls and Partitions: EMT. 4. Damp or Wet Locations: IMC. RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS 260533-2

5. Boxes and Enclosures: NEMA 250, Type 1. C. Minimum Raceway Size: 3/4-inch trade size. D. Raceway Fittings: Compatible with raceways and suitable for use and location. 1. Rigid and Intermediate Steel Conduit: Use threaded rigid steel conduit fittings unless otherwise indicated. Comply with NEMA FB 2.10. 2. EMT: Use compression fittings. Comply with NEMA FB 2.10. 3. Flexible Conduit: Use only fittings listed for use with flexible conduit. Comply with NEMA FB 2.20. 3.2 INSTALLATION Comply with NECA 1 and NECA 101 for installation requirements except where requirements on Drawings or in this article are stricter. Comply with NFPA 70 limitations for types of raceways allowed in specific occupancies and number of floors. Keep raceways at least 6 inches away from parallel runs of flues and steam or hot-water pipes. Install horizontal raceway runs above water and steam piping. C. Install no more than the equivalent of three 90-degree bends in any conduit run except for control wiring conduits, for which fewer bends are allowed. Support within 12 inches of changes in direction. D. Conceal conduit finished walls, ceilings, and floors unless otherwise indicated. Install conduits parallel or perpendicular to building lines. E. Support conduit within 12 inches of enclosures to which attached. F. Threaded Conduit Joints, Exposed to Wet, Damp, Corrosive, or Outdoor Conditions: Apply listed compound to threads of raceway and fittings before making up joints. Follow compound manufacturer's written instructions. G. Coat field-cut threads on PVC-coated raceway with a corrosion-preventing conductive compound prior to assembly. H. Raceway Terminations at Locations Subject to Moisture or Vibration: Use insulating bushings to protect conductors including conductors smaller than No. 4 A WG. I. Terminate threaded conduits into threaded hubs or with locknuts on inside and outside of boxes or cabinets. Install bushings on conduits up to 1-1/4-inch trade size and insulated throat metal bushings on 1-1/2-inch trade size and larger conduits terminated with locknuts. Install insulated throat metal grounding bushings on service conduits. J. Install pull wires in empty raceways. Use polypropylene or monofilament plastic line with not less than 200-lb tensile strength. Leave at least 12 inches of slack at each end of pull wire. Cap underground raceways designated as spare above grade alongside raceways in use. K. Install raceway sealing fittings at accessible locations according to NFP A 70 and fill them with listed sealing compound. For concealed raceways, install each fitting in a flush steel box with a blank cover plate having a finish similar to that of adjacent plates or surfaces. RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS 260533-3

L. Flexible Conduit Cmmections: Comply with NEMA RV 3. Use a maximum of 72 inches of flexible conduit equipment subject to vibration, noise transmission, or movement; and for transformers and motors. M. Install devices to seal raceway interiors at accessible locations. Locate seals so no fittings or boxes are between the seal and the following changes of environments. Seal the interior of all raceways at the following points: 1. Where conduits pass from warm to cold locations, such as boundaries of refrigerated spaces. 2. Where an underground service raceway enters a building or structure. 3. Where otherwise required by NFPA 70. N. Expansion-Joint Fittings: 1. Install in each run of aboveground RNC that is located where environmental temperature change may exceed 30 deg F and that has straight-run length that exceeds 25 feet. 2. Install expansion fittings at all locations where conduits cross building or structure expansion joints. 3. Install each expansion-joint fitting with position, mounting, and piston setting selected according to manufacturer's written instructions for conditions at specific location at time of installation. Install conduit supports to allow for expansion movement. 0. P. Q. R. s. T. Mount boxes at heights indicated on Drawings Horizontally separate boxes mounted on opposite sides of walls so they are not in the same vertical channel. Locate boxes so that cover or plate will not span different building finishes. Support boxes of three gangs or more from more than one side by spanning two framing members or mounting on brackets specifically designed for the purpose. Fasten junction and pull boxes to or support from building structure. Do not support boxes by conduits. Set metal floor boxes level and flush with finished floor surface. 3.3 INSTALLATION OF UNDERGROUND CONDIDT Direct-Buried Conduit: 1. Excavate trench bottom to provide firm and uniform support for conduit. Prepare trench bottom as specified in Section 312000 "Earth Moving" for pipe less than 6 inches in nominal diameter. 2. Install backfill as specified in Section 312000 "Earth Moving." 3. After installing conduit, backfill and compact. Start at tie-in point, and work toward end of conduit run, leaving conduit at end of run free to move with expansion and contraction as temperature changes during this process. Firmly hand tamp backfill around conduit to provide maximum supporting strength. After placing controlled backfill to within 12 inches of fmished grade, make final conduit connection at end of run and complete backfilling with normal compaction as specified in Section 312000 "Earth Moving." RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS 260533-4

4. Install manufactured duct elbows for stub-up at poles and equipment and at building entrances through floor unless otherwise indicated. Encase elbows for stub-up ducts throughout length of elbow. 5. Install manufactured rigid steel conduit elbows for stub-ups at poles and equipment and at building entrances through floor. a. Couple steel conduits to ducts with adapters designed for this purpose, and encase coupling with 3 inches of concrete for a minimum of 12 inches on each side of the coupling. b. For stub-ups at equipment mounted on outdoor concrete bases and where conduits penetrate building foundations, extend steel conduit horizontally a minimum of 60 inches from edge of foundation or equipment base. Install insulated grounding bushings on terminations at equipment. 6. Underground Warning Tape: a. Recommended by manufacturer for the method of installation and suitable to identify and locate underground electrical utility lines. b. Printing on tape shall be permanent and shall not be damaged by burial operations. c. Tape material and ink shall be chemically inert and not subject to degradation when exposed to acids, alkalis, and other destructive substances commonly found in soils. d. Comply with ANSI Z535.1, ANSI Z535.2, ANSI Z535.3, ANSI Z535.4, and ANSI Z535.5. e. Inscriptions for Red-Colored Tapes: "ELECTRIC LINE, HIGH VOLTAGE" 3.4 3.5 C. D. E. INSTALLATION OF UNDERGROUND HANDHOLES AND BOXES Install handholes and boxes level and plumb and with orientation and depth coordinated with connecting conduits to minimize bends and deflections required for proper entrances. Unless otherwise indicated, support units on a level bed of crushed stone or gravel, graded from 1/2-inch sieve to No.4 sieve and compacted to same density as adjacent undisturbed earth. Elevation: In paved areas, set so cover surface will be flush with finished grade. Set covers of other enclosures 1 inch above finished grade. Install handholes with bottom below frost line. Field-cut openings for conduits according to enclosure manufacturer's written instructions. Cut wall of enclosure with a tool designed for material to be cut. Size holes for terminating fittings to be used, and seal around penetrations after fittings are installed. FIRES TOPPING Apply firestopping to electrical penetrations of fire-rated floor and wall assemblies to restore original fire-resistance rating of assembly. Install penetration frrestopping systems to comply with manufacturer's written installation instructions and published drawings for products and applications. Penetration Firestopping Systems: Systems that resist spread of fire, passage of smoke and other gases, and maintain original fire-resistance rating of construction penetrated. Penetration RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS 260533-5

firestopping systems shall be compatible with one another, with the substrates forming openings, and with penetrating items if any. C. Penetrations in Fire-Resistance-Rated Walls: Penetration firestopping systems with ratings determined per ASTM E 814 or UL 1479, based on testing at a positive pressure differential of 0.01-inch wg. 1. F -Rating: Not less than the fire-resistance rating of constructions penetrated. 3.6 PROTECTION Protect coatings, finishes, and cabinets from damage and deterioration. 1. Repair damage to galvanized finishes with zinc-rich paint recommended by manufacturer. END OF SECTION 260533 RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS 260533-6

SECTION 262726- WIRING DEVICES PART 1- GENERAL 1.1 SUMMARY Section Includes: 1. Shutdown Buttons 1.2 ACTION SUBMITTALS Product Data: For each type of product. PART 2 -PRODUCTS 2.1 MANUFACTURERS Source Limitations: Obtain each type of wiring device and associated wall plate from single source from single manufacturer. 2.2 GENERAL WIRING-DEVICE REQUIREMENTS Wiring Devices, Components, and Accessories: Listed and labeled as defmed in NFP A 70, by a qualified testing agency, and marked for intended location and application. Comply with NFPA 70. C. Devices that are manufactured for use with modular plug-in connectors may be substituted under the following conditions: 1. Connectors shall comply with UL 2459 and shall be made with stranding building wire. 2. Devices shall comply with the requirements in this Section. 2.3 SHUTDOWN BUTTONS One manually operated remote shutdown button for the water heaters with a hinged cover installed near the room exit as shown on drawings. PART 3 -EXECUTION 3.1 INSTALLATION Comply with NECA 1, including mounting heights listed in that standard, unless otherwise indicated. Coordination with Other Trades: 1. Install device boxes in brick or block walls so that the cover plate does not cross a joint unless the joint is troweled flush with the face ofthe wall. 2. Install wiring devices after all wall preparation, including painting, is complete. WIRING DEVICES 262726-1

C. Conductors: 1. Do not strip insulation from conductors until right before they are spliced or terminated on devices. 2. Strip insulation evenly around the conductor using tools designed for the purpose. A void scoring or nicking of solid wire or cutting strands from stranded wire. 3. The length of free conductors at outlets for devices shall meet provisions of NFPA 70, Article 300, without pigtails. 4. Existing Conductors: D. Device Installation: a. Cut back and pigtail, or replace all damaged conductors. b. Straighten conductors that remain and remove corrosion and foreign matter. c. Pigtailing existing conductors is permitted, provided the outlet box is large enough. 1. Replace devices that have been in temporary use during construction and that were installed before building finishing operations were complete. 2. Keep each wiring device in its package or otherwise protected until it is time to connect conductors. 3. Do not remove surface protection, such as plastic film and smudge covers, until the last possible moment. 4. Connect devices to branch circuits using pigtails that are not less than 6 inches in length. 5. When there is a choice, use side wiring with binding-head screw terminals. Wrap solid conductor tightly clockwise, two-thirds to three-fourths of the way around terminal screw. 6. Use a torque screwdriver when a torque is recommended or required by manufacturer. 7. When conductors larger than No. 12 A WG are installed on 15- or 20-A circuits, splice No. 12 AWG pigtails for device connections. 8. Tighten unused terminal screws on the device. 9. When mounting into metal boxes, remove the fiber or plastic washers used to hold device-mounting screws in yokes, allowing metal-to-metal contact. 3.2 FIELD QUALITY CONTROL c. Verify the performance and function of the shutdown buttons. Wiring device will be considered defective if it does not pass tests and inspections. Prepare test and inspection reports. END OF SECTION 262726 WIRING DEVICES 262726-2