Experimental Validation of a Computational Fluid Dynamics Model for IAQ applications in Ice Rink Arenas

Similar documents
An experimental method for contaminant dispersal characterization in large industrial buildings for IAQ applications.

A study on the effect of the airflow rate of the ceiling type air-conditioner on the ventilation performance

Validation of a Coupled Multizone and CFD Program for Building Airflow and Contaminant Transport Simulations

ENERGY EFFICIENT AIR QUALITY CONTROL IN LABORATORIES USING BENCH EXHAUSTS

Floor-Supply Displacement Ventilation in a Small Office

CFD Modelling of an Aerosol Exposure Chamber for Medical Studies G. Manenti, M. Derudi, G. Nano, R. Rota

Current Studies on Air Distributions in Commercial Airliner Cabins

Vipac Engineers & Scientists Ltd

Numerical Modeling of Buoyancy-driven Natural Ventilation in a Simple Three Storey Atrium Building

Riccardo Buccolieri 1, Mats Sandberg 2

Prediction of Pollutant Emissions from Industrial Furnaces Using Large Eddy Simulation

Thermal and Fluid-dynamical Optimisation of Passengers Comfort in a Touring Bus Cabin

MODELLING COMBUSTION AND THERMAL NO X FORMATION IN ELECTRIC ARC FURNACES FOR THE PRODUCTION OF FERRO-SILICON AND SILICON-METAL

Numerical analysis of eccentric orifice plate using ANSYS Fluent software

On the performance of the Stravent ventilation system in an office space Numerical and experimental investigations

Numerical Analysis of Ventilation Effectiveness in Occupied Zones for Various Industrial Ventilation Systems

Sensitivity Analysis of Personal Exposure Assessment Using a Computer Simulated Person Brohus, Henrik; Jensen, H. K.

Numerical analysis of CO concentration distribution on extraction ventilation type tunnel Tao Guo 1,a, Jun Zhou 2,b, Xiaonan Liu 3,c and Bo Shang 4

Thermal Management of Densely-packed EV Battery Set

XVII th World Congress of the International Commission of Agricultural and Biosystems Engineering (CIGR)

APPLYING COMPUTATIONAL FLUID DYNAMICS TO ARCHITEC- TURAL DESIGN DEVELOPMENT

CFD Modelling and Analysis of Different Plate Heat Exchangers

Fluctuating Inlet Flow Conditions for Use in Urban Air Quality CFD Studies

REDUCTION IN FUME EMISSION FROM A SLAG FUMER CHARGE PORT USING CFD MODELLING

Carbon Monoxide Dispersion in Enclosed Car Parks: Pollutant Source Modelling Methods. Jason Gaekwad 1 1. Mott MacDonald, Melbourne, Australia

Performance Improvement Analysis for a Negative-pressurized Biosafety Level Laboratory

Air distribution in indoor ice skating rinks

Investigation of air quality, comfort parameters and effectiveness for two floor level air supply systems in classrooms

Indoor Air 2005, Beijing, China Effectiveness of confluent jets ventilation system for classrooms

Comparison of Standards Requirements with CFD Simulations for Determining Sizes of Hazardous Locations in Hydrogen Energy Station

A three-dimensional numerical model of air pollutant dispersion

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

CFD and Wind Tunnel Study of the Performance of a Multi- Directional Wind Tower with Heat Transfer Devices

A Sensitivity Analysis on Mixing Energy Loss in Air-Conditioned Rooms by Using CFD

COOLING EFFECT ENHANCEMENT IN MAGNETRON SPUTTERING SYSTEM

EXPERIMENTAL AND NUMERICAL STUDY OF SMOKE CONDITIONS IN AN ATRIUM WITH MECHANICAL EXHAUST

Piotr Ciuman, Barbara Lipska

Theory Comparison between Propane and Methane Combustion inside the Furnace

Numerical Modelling of Air Distribution in the Natatorium Supported by the Experiment

A STUDY OF CROSS CONTAMINATION OF IN-SUITE VENTILATION SYSTEMS USED IN MULTI-UNIT RESIDENTIAL BUILDINGS

Flow and heat distribution analysis of different transformer sub-stations

Application of CFD to Predict and Control Chemical and Biological Agent Dispersion in Buildings

The Pennsylvania State University. The Graduate School. Department or Architectural Engineering THERMAL AND VENTILATION PERFORMANCE

Air Distribution and Microenvironment Evaluation of a Desktop Task. Conditioning System 1

IDENTIFICATION OF VENTILATION PROBLEMS IN AN UNDERGROUND BUS TERMINAL IN KOREA

Volume 2, Issue 2 (2014) ISSN International Journal of Advance Research and Innovation

Numerical simulation of inter-flat pollutant dispersion routes and cross-contamination risk in high-rise residential buildings Di Mu, Naiping Gao* Ins

Investigating Two Configurations of a Heat Exchanger in an Indirect Heating Integrated Collector Storage Solar Water Heating System

Combustion conditions and design control of a two-stage pilot scale starved air incinerator by CFD

On-Site Experimental Validation of a Coupled Multizone and CFD Model for Building Contaminant Transport Simulations PROOF

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress volume 5 Heiselberg, Per Kvols. Publication date: 2016

Numerical and Experimental Modeling of Producer Gas Carburettor

CFD SIMULATION OF HEAVY GAS DISPERSION IN VENTILATED ROOMS AND VALIDATION BY TRACING EXPERIMENTS

ADVANCES in NATURAL and APPLIED SCIENCES

Optimization of a Dual-Fuel Low-NOx Combustion System for a Tangentially-Fired Utility Boiler Operating at a High Elevation.

H POLLUTANT DISPERSION OVER TWO-DIMENSIONAL IDEALIZED STREET CANYONS: A LARGE-EDDY SIMULATION APPROACH. Colman C.C. Wong and Chun-Ho Liu*

Computational Analysis of Blast Furnace Pulverized Coal Injection For Iron Making

CFD Modeling of Reactive Pollutants in an Urban Street Canyon using Different Chemical Mechanisms

Indoor Airflow Modeling and Data Assimilation. Hengye Yang Ph.D. Student, LISC Dec. 21, 2018

Computational Modelling and Scale Model Validation of Airflow Patterns in Naturally Ventilated Barns

Numerical modelling of shielding gas flow and heat transfer in laser welding process

CFD Study on Inter-Action between NonIsothermal Airflow and Buoyancy Plume in an AirConditioned Space

NUTC R203. Safety Risks of Hydrogen Fuel for Applications in Transportation Vehicles. Shravan K. Vudumu

CFD modeling of airflows and contaminant transport in an aircraft cabin

Investigating two configurations of a heat exchanger in an Indirect Heating Integrated Collector Storage Solar Water Heating System (IHICSSWHS)

NUMERICAL SIMULATION OF AIR NATURAL CIRCULATION AND THERMAL RADIATION IN PASSIVE CONTAINMENT COOLING SYSTEM

Dr. J. Wolters. FZJ-ZAT-379 January Forschungszentrum Jülich GmbH, FZJ

Energy Consumption and Indoor Environment Predicted by a Combination of Computational Fluid Dynamics and Building Energy Performance Simulation

An Evaluation of Heat Transfer Coefficient in an Independent Zonal Temperature Controls with CFD

CFD Analysis of a Mixture Flow in a Producer Gas Carburetor for optimizing the design configuration

INVESTIGATION ON THE RELATIONSHIP BETWEEN FLOW PATTERN AND AIR AGE

Numerical Investigation on Ventilation Strategy for Laboratories: A Novel Approach to Control Thermal Comfort Using Cooling Panels

NUMERICAL STUDY ON AIRFLOW IN AN OFFICE ROOM WITH A DISPLACEMENT VENTILATION SYSTEM Yukihiro Hashimoto 1 1

Numerical thermal analysis of helical-shaped heat exchanger to improve thermal stratification inside solar storage tank

Analysis of Uniformity and Energy Consumption in. Supermarket installed DurkeeSox Air Dispersion System. with PE Air Dispersion Model

Available online at ScienceDirect. Procedia Engineering 105 (2015 )

THERMAL ENVIRONMENT OF OUTDOOR UNITS OF VRV SYSTEM IN HIGH- RISE BUILDING. Gang Wang, Yafeng Hu, and Songtao Hu

NUMERICAL SIMULATION AND OPTIMIZATION OF SOLID-LIQUID TWO-PHASE FLOW IN A BACK-SWEPT AXIAL FLOW PUMP

EFFECT OF PLENUM CHAMBER DEPTH IN A SWIRLING FLUIDIZED BED

Numerical Investigation of the Air Flow in a Novel PV-Trombe Wall Based on CFD Method

ADVANCED CO 2 OCEAN SEQUESTRATION TECHNOLOGY FOR GLOBAL WARMING

PERFORMANCE ANALYSIS OF NATURAL DRAFT WET COOLING TOWER AT OPTIMIZED INJECTION HEIGHT

An Analytical Solution for Steady Temperature Profiles in a Vertically Stratified Environment

The Air Distribution Around Nozzles Based On Active Chilled Beam System

DEVELOPMENT OF THE STREAM RECOGNITION MODEL OF TRANSPORTED PROBABILITIES FOR TURBULENT FLAMES. by S.V. Zhubrin

CFD-BASED INVESTIGATION OF HEAT TRANSFER CHARACTERISTICS OF FLUE GAS-WATER HEAT EXCHANGER PANELS PRODUCED WITH A NOVEL MANUFACTURING PROCESS

PERFORMANCE EVALUATION OF TWO AIR DISTRIBUTION SYSTEMS. T Karimipanah 1 and H B Awbi 2

CFD ANALYSIS OF CONVECTIVE FLOW IN A SOLAR DOMESTIC HOT WATER STORAGE TANK

Evaluation of UV dose of upper-room UVGI system in a ward using CFD simulation

3D Simulation of a fire inside a river tunnel and optimisation of the ventilation using Computational Fluid Dynamics

Numerical Simulation of the Flue Gas Desulfurization in the Sieve Tray Tower

Comparison of airflow and contaminant distributions in rooms with traditional displacement ventilation and under-floor air distribution systems

FLUID STRUCTURE INTERACTION MODELLING OF WIND TURBINE BLADES BASED ON COMPUTATIONAL FLUID DYNAMICS AND FINITE ELEMENT METHOD

Investigation on conformal cooling system design in injection molding

ASSESSMENT OF AIR CHANGE RATE AND CONTRIBUTION RATIO IN IDEALIZED URBAN CANOPY LAYERS BY TRACER GAS SIMULATIONS

DETERMINATION OF CLEARANCE DISTANCES FOR VENTING OF HYDROGEN STORAGE

A Test Chamber for the Assessment of Human Exposure to Fine Particles

Optimization and control of working parameters of hot blast furnace

Numerical Simulation of Airflow Organization and Temperature Distribution in Bulk Curing Barn Yong-qiao WANG, Yan-qiong LI, Yan ZHAO

A Numerical Investigation on bubble formation in Coolant channel with various Ethylene Glycol and water compositions and change in contact angle

Transcription:

Yang, C., Demokritou, P., Chen Q., and Spengler, J. 2001. Experimental validation of a computational fluid dynamics model for IAQ applications in ice rink arenas, Indoor Air, 11(2), 120-126. Experimental Validation of a Computational Fluid Dynamics Model for IAQ applications in Ice Rink Arenas Chunxin Yang 1, Philip Demokritou 2*, Qingyan Chen 1 and John Spengler 2 1 Building Technology Program, Department of Architecture, Massachusetts Institute of Technology, MIT Room 5-418,77 Massachusetts Avenue, Cambridge, MA 02139, USA. Fax: (617) 253-6152 2 Environmental Science and Engineering Program, School of Public Health, Harvard University. SPH1-B23, 665 Huntington Avenue, Boston, MA 02115, USA, Fax: 617-432-4122, Abstract Many ice rink arenas have ice resurfacing equipment that uses fossil fuel as power. The combustion byproducts are a major source of contamination. Ventilation along with other pollution source control measures is the most widely applied strategy to lower the contaminant level below the threshold limit and maintain acceptable indoor air quality. A computational fluid dynamics (CFD) model has been used to predict the contaminant concentrations, air velocity, and air temperature distributions in ice rinks. The numerical results agree reasonably with the corresponding experimental data for both steady state and transient conditions. The CFD model is a useful and inexpensive tool to investigate ventilation parameters, such as air distribution methods, ventilation effectiveness, air exchange rates, and various ventilation control strategies. Keywords: Indoor Air Quality, Ice Rink, Numerical Simulation, CFD Practical Implications: Compromised indoor air quality in ice skating arenas due to the combustion byproducts from the fossil powered resurfacing equipment, poses a health risk for both athletes and spectators. Advanced computational fluid dynamics (CFD) modeling can be used effectively to predict the indoor environmental quality in such a unique built environment. A CFD model was developed and validated experimentally for both steady state and transient conditions and used to evaluate IAQ in ice rink arenas. The results show that the CFD model is sufficiently good to predict the air velocity, air temperature, and contaminant concentrations in ice rink arenas. INTRODUCTION There are thousands of ice rink arenas worldwide, and many cases with compromised indoor air quality have been reported in such a building environment. A major source of air pollution is the combustion byproducts emitted from the fossil fuel resurfacing equipment. The pollutants include hydrocarbons (HC), carbon monoxide(co), and NO x. In many studies, CO and NO X concentrations in ice rink arenas have been measured up to 100 times as high as usual urban air concentrations (Spengler et al. 1978; Lee et al. 1994; Brauer and Spengler 1994) imposing serious health risks to both spectators and athletes. Characterizing the contaminant distribution in such a large open space is considered a difficult technical task, taking into consideration the non-uniformity of the indoor air flow created by local heat sources, geometrical obstructions and the air distribution method. The sensitivity of concentration to various flow non-uniformity is identified in many studies (Hangstrom et al, 1

1999). Therefore, a significant number of data points is required in order to get a reliable contaminant spatial distribution in the space Two popular approaches are available to determine the distribution of indoor air quality and airflow in such a built environment: experimental measurements and numerical simulation. The experimental approach uses tracer gas methods to study the contamination dispersal and ventilation effectiveness. One example of such an application for ice rink arenas is by Demokritou et al. (1999). The numerical simulation applies the computational fluid dynamics (CFD) technique to study airflow and IAQ in buildings with a turbulence model (Chen 1997). Despite the fact that numerical simulation has been used extensively in studying airflow and IAQ in buildings to the knowledge of the authors, there has no utilization of CFD for ice rink arenas. The drawback of the experimental methods is the time and the complicated equipment needed for the measurements. A CFD model, on the other hand, can be a powerful tool not only to characterize the existing conditions but also to modify scenarios related to the ventilation system. In the present study, a CFD model has been developed and validated for both steady-state and transient conditions. The distributions of air velocity, air temperature, CO concentration, and tracer gas concentration measured in an ice rink are used to validate the numerical results. The results have demonstrated that the CFD model can be used with good accuracy to analyze and design such a complicated indoor air environment. NUMERICAL SIMULATION The CFD model The CFD model consists of the conservation equations of mass, momentum, energy, and species concentrations that govern the transport phenomena in ice rinks. The CFD approach numerically solves these equations together with the corresponding boundary conditions for airflow, temperature, and species concentration in ice rink. Most airflows in buildings are turbulent. With an eddy-viscosity turbulence model, the airflow, temperature, and species transport phenomena can be described by the following timeaveraged Navier-Stokes equations: ( ρφ) + div( ρvφ Γ t Φ gradφ) = S (1), eff Φ Where: ρ = Air density, kg/m 3 Φ =1 for mass continuity; = V j (j=1, 2, 3) for three components of momentum; = k for turbulent energy; = ε for the dissipation rate of k; = T for energy transport equation; 2

V Γ Φ, eff S Φ = C i for containment concentrations; = τ for age of air; = velocity vector = effective diffusion coefficient = source term The effective diffusion coefficient and source term for the differential equations are listed in Table 1. The effective viscosity, μ eff, is the sum of molecular viscosity, μ, and turbulent viscosity, μ t : μ eff = μ + μ t (2) where μ is a fluid property while μ t depends on flow conditions. The effective diffusivity for mass transfer of contamination is: D eff = μ/( ρ Sc)+ μ t /( ρ Sc t ) (3) where Sc and Sc t are the molecular and turbulent Schmidt numbers for the species. The CFD model uses approximations in calculating the turbulence quantities, such as isotropic turbulence and the Buossinesq eddy viscosity concept. Chen (1997) has detailed the pros and cons as well as the limitation of the CFD model. Boundary conditions The governing equations can be closed with appropriate boundary conditions at all the boundaries such as air inlets, outlets and wall surfaces. The values of velocity, temperature, kinetic energy and its dissipation rate and species concentration should be set at the boundaries. External walls and obstructions: A non-slip condition at all solid walls is applied to the velocities. The logarithmic law or wall function has been used (Launder and Spalding, 1974) for the near wall boundary layer because the turbulence model does not work for the low Reynolds number flow near a wall. The present study uses the measured temperatures of the wall and ice surface from the survey as the boundary values for each arena. Air Inlets: The measured air temperature, airflow rate, concentration levels at every inlet constitute the corresponding boundary conditions. Velocity, kinetic energy, and its dissipation are estimated as follows: M U in = ρa (4) 2 k in = 0.05U in (5) ε 1.5 0.09k / D (6) in = in Where k in = kinetic energy, m 2 /s 2 ; 3

ε in = dissipate rate of kinetic energy, m 2 /s 3 ; U in = inlet air velocity, m/s; D = characteristic scale of inlet, m. M = air flow rate (kg/s) Steady-state and transient conditions: The simulations have been performed for both steady-state and transient conditions. Under the steady-state conditions, the ventilation system is assumed on all the time and the pollution source from an ice resurfacer is uniformly distributed on the ice surface. In order to evaluate the CO emissions from the ice resurfacer, the CO emissions were measured for the propane fueled resurfacer and found to be 200mg/s. This CO emission level is typical for an ice resurfacer and was verified in many other similar propane type resurfacers, investigated in our survey. The emphasis of steady-state simulation is placed on the prediction of air velocity, temperature and contaminant profile in the arena. The CO should be considered as a normalized contaminant source. Normalized means the value presented is normalized by the source strength. This study does not consider any sink effects for the air contaminant. Concentrations of other gaseous pollutants such as NO x and HC can be calculated by scaling, even though they have a different molecular weights than CO. This was possible because the magnitude of the pollution sources was small and the resulting concentrations were so low as to have a negligible effect on the density of the mixture of air and pollutants. The transient condition has been used to investigate the dynamic contamination dispersal in an ice resurfacing cycle. Under transient conditions, the basic assumption is that the resurfacer moves in circles around the ice surface for a certain period of time while the ventilation system is on all the time. In order to simulate the circular motion of the ice resurfacer, a number of contamination sources have been distributed over the ice surface. The contamination sources are activated sequentially for a brief period of time to simulate the movement of the resurfacer. Therefore, the boundary condition for the contaminant source was a moving one. The activation time of each source is determined by the moving speed of the resurfacer and the distance between two successively active sources. Initial conditions for transient conditions The initial values must also be set for all the variables in the simulation of transient conditions. The investigation uses the steady-state solutions as the initial conditions for pressure, velocity, energy, kinetic energy, and its dissipation rate. However, the initial condition for CO concentration is assumed to be zero. Numerical procedure A CFD program, PHOENICS 3.1 (CHAM, 1998), was used to solve the time-dependent conservation equations together with the standard k-ε model (Launder and Spalding, 1974) and the corresponding boundary conditions. The program divided the space of the ice rink into nonuniform computational cells, and the discrete equations were solved with the SIMPLE algorithm (Patankar, 1980). The convergence criteria used at each time step ensured that the total normalized residuals were less than 1% for flow and 3% for CO concentration. 4

VALIDATION EXPERIMENTS CASE STUDIES Air velocity and temperature distribution under steady state conditions: In this case, numerical simulations and validation tests have been conducted to verify the ability of CFD to predict air velocity and temperature distributions in an arena located in the Boston area. Figure 1 shows the configuration of the ventilation system and the building geometry of the arena. Fresh air is supplied from a side wall through an inlet and is exhausted from four outlets on the opposite wall. The size of the inlet and outlets is 3.6 m by 1.2m and 0.9m by 0.9m, respectively. The air velocity and temperature profiles in front of the inlet were measured and used as boundary conditions in the simulations. The air velocity and temperature vertical profiles were also measured at six locations, as shown on Figure 1. At each location, air velocity and temperature were measured at seven different heights from the ice surface: 1.0m, 2.0m, 3.0m, 3.5m, 4.0m, 4.5m, and 5.0 m, respectively. The air velocity was measured by using a digital hot wire anemometer. We recorded ten readings every 90 seconds, the ten readings were averaged to give the time-averaged air velocity. The typical standard error is 10 to 30 percent, where the standard error is defined as: 10 1 1 2 s.e. = (U i (t) U). (7) U 10 i= 1 Figure 2 shows both experimental and numerical air velocity and temperature profiles at the six locations. The agreement between computed and measured temperature is good. However, there are discrepancies between the computed and measured velocity profiles. In such a large space, it is difficult to measure the velocity profile with a single anemometer. It took two days to complete the measurements. It is clear to see from the measured data that the velocity may not be the same because the velocity in the upper part of the arena (measured in the second day) is very different from that in the lower part (measured in the first day). Since the flow boundary condition at the inlet was measured in the first day, the agreement between the computed velocity and the measured data is much better in the first day. Due to the uncertainty in the measurements, the numerical results are acceptable. CO concentration levels under steady state conditions In order to evaluate the ability of the CFD model to predict the contaminant dispersal under steady state conditions a passive perfluorocarbon tracer gas (PFT) was used. This passive tracer gas method is presented in detail in another publication (Demokritou et al., 1999) Thirty PFT sources were distributed around the glass shielding of the ice arena at a height of 1.4 m, as shown on Figure 3. Tracer gas source characteristics are shown on Table 3. The HVAC system was operated continuously for 24 hours after the PFT sources were distributed in order to reach an equilibrium - steady state condition. Then absorption based passive samplers were deployed in selected locations (Figure 3) and remained in place for approximately an additional 48 hours. The samplers were located to measure the concentrations in a horizontal x-y plane at a 5.7 m height over the ice arena. The PFT vapor collected by the passive samplers was extracted in the laboratory and analyzed by a gas chromatography to determine the concentration levels. 5

The comparison of experimental and numerical concentration data are shown for various locations in the arena in Figure 4. The agreement between the computed and measured results is acceptable for the study of indoor air quality in ice rink arenas. CO concentration levels during an ice-resurfacing cycle (transient conditions) The validation has also been conducted in order to test the ability of the CFD technique to predict the concentration levels during and after an ice resurfacing cycle under transient conditions. Figure 5 shows the ventilation system and the building characteristics of the arena. The ventilation system consists of six inlets at ceiling height and two outlets located at both sides of the spectator s area. Each inlet is has an air supply area of 0.5m 2 while the size of each outlet is 1.0m 2. The supplied airflow rate was measured and found to be 22,000 m 3 /hr. An ice resurfacing cycle lasts approximately fifteen minutes. During ice resurfacing, the propane fueled ice resurfacer moves in circles around the ice arena while the ventilation system is on all the time. In order to simulate the circular motion of the ice resurfacer, a number of contamination sources have been distributed over the ice surface. The contamination sources are activated sequentially for a period of time to simulate the movement of the resurfacer. (moving boundary source) as shown in Figure 5, where Sn stands the number of source. Table 2 shows the emission rate of each source and the duration time of activation. The average speed of the resurfacer is about 1.0 to 2.0 m/s and the distance between two CO sequential sources is 10 m. CO concentration levels were measured at one minute intervals over approximately a 12 hour period on March 13 th and a 5 hour period on March 16 th, 1999. The instrument used was mounted 1.1 m above the ice surface at the center of the ice arena. Figure 6 shows the experimental and simulated CO concentrations. The computed results are in good agreement with the experimental data. Note that the technique used to simulate the moving CO source is crucial to obtain the best numerical results. A uniform distribution of CO source on the ice surface cannot produce satisfactory results. Discussion The CFD model is a useful and economical tool to investigate how ventilation parameters such as air exchange rates, air distribution methods and control strategies affect the IAQ in ice rink arenas. The model can also be used to develop guidelines for ventilation system design. Although the simulation process requires significant effort to input the building geometrical features and the boundary conditions, the personnel effort is much less than conducting actual measurements in an arena. The CFD results are much more informative. They contain detailed information such as contaminant concentrations, temperature, velocity, etc. at every location of an arena simulated. However, the measurements can only be done in a few locations. The flow and thermal boundary conditions in an arena are impossible to control and that leads to a great uncertainty in data quality. The computing effort has become smaller and smaller due to the fast development in computer speed and capacity. For example, the transient simulations can be performed on a Pentium II, 400 MHZ personal computer. 6

CONCLUSIONS The paper presents the validation of a CFD model for the investigation of ventilation and IAQ in ice rink arenas. Validation tests included air velocity and temperature spatial distributions under steady-state conditions and contaminant dispersion under both steady-state and transient conditions. The contaminant is from the fossil powered resurfacing equipment. The results show that the CFD model is sufficiently good to predict the air velocity, air temperature, and contaminant concentrations in ice rink arenas. The CFD model is a powerful tool to study ventilation and indoor air quality in an ice rink. The validated CFD model will be used to develop engineering design guidelines for the ventilation system of such a built environment. The impact of fundamental ventilation parameters such as air exchange rate, air distribution methods and control strategies on IAQ will be numerically investigated. ACKNOWLEDGMENT The authors thank Mr. Shiping Hu, Mr. Jui-Chen R. Chang, and Ms. Beth A. Manoogian for they assistance in the field survey and experimental measurements. The project is sponsored jointly by Frank J. Zamboni & Co., Inc., New England Ice Skating Managers Association, the Ice Skating Institute, and Nova Scotia Sport and Recreation Commission. REFERENCES Brauer, M. and Spengler, J.D. (1994) Nitrogen dioxide exposures inside ice skating rinks, Am. J. Publ. Health 84: 429-433. CHAM (1998). PHOENICS Version 3.1, CHAM Ltd, UK. Chen, Q., (1997). Computational fluid dynamics for HVAC: success and failures, ASHRAE Transactions. 103(1), 178-187. Demokritou, P., Yang, C., Spengler, J.D. and Chen, Q. (1999) An experimental method for contaminant dispersal characterization in large scale buildings for IAQ applications, Submitted to journal Building & Environment. Hangstrom, K.(1999). The influence of heat and contaminant Source nonuniformity on the performance of three different room air distribution methods ASHRAE transactions 1999, vol. 105. Int-Hout, D. and Kloostra, L. (1999) Air distribution for large spaces, ASHRAE Journal., 57-64. April. Launder, B.E. and Spalding, D.B. (1974). The numerical computation of turbulent flows, Computer Methods in Applied Mechanics and Energy, 3, 269-289. Lee, K., Yangisawa, Y., Spengler, J.D., and Nakai, S. (1994) Carbon monoxide and nitrogen dioxide levels in indoor ice skating rinks, Journal of sports Science. 12:279-283. Nielsen, P. (1994) Prospects for computational fluid dynamics in room air contaminant control, Proceedings of the4 th international Symposium on Ventilation for Contaminant control, Stockholm. Patankar, S.V. (1980) Numerical Heat Transfer and Fluid Flow, New York, Hemisphere Publishing Corp. 7

Spengler, J.D., Stone, K.R., and Lilley, F. W. (1978). High carbon monoxide levels measured in enclosed skating rinks, Journal of Air Pollution. Control Association. 28: 776-779. 8

Table 1: Values of Φ, Γ Φ, eff and S Φ for PDE equations. Φ Γ Φ, eff S Φ Continuity 1 0 0 x-momentum V 1 μ+ μ t - P/ x y-momentum V 2 μ+ μ t - P/ y z-momentum V 3 μ+ μ t - P/ z-ρgβ(t-t 0 ) T-equation T μ/σ l + μ t /σ t S T k-equation k (μ+ μ t )/σ k G-ρε +G B ε-equation ε (μ+ μ t )/σ ε [ε (C ε1 G-C ε2 ρε)/k] +C ε3 G B (ε/k) Species C (μ+ μ t )/σ c S C Age of air τ μ+ μ t ρ μ t =ρc μ k 2 /ε G=μ t ( U i / x j + U j / x i ) U i / x j G B =-g(β/c P )( μ t /σ T,t ) T/ x I C ε1 =1.44, C ε2 =1.92, C ε3 =1.44, C μ =0.09 σ t =0.9, σ k =1.0, σ ε =1.3, σ C =1.0 9

Table 2: Moving CO boundary source for transient state conditions. Time step Time (s) Source No. Time step Time (s) Source No. 1 0 10 S1 16 150 160 S16 2 10 20 S2 17 160 170 S17 3 20 30 S3 18 170 180 S18 4 30 40 S4 19 180 190 S19 5 40 50 S5 20 190 200 S20 6 50 60 S6 21 200 210 S21 7 60 70 S7 22 210 220 S22 8 70 80 S8 23 220 230 S23 9 80 90 S9 24 230 240 S24 10 90 100 S10 25 240 250 S25 11 100 110 S11 26 250 260 S26 12 110 120 S12 27 260 270 S27 13 120 130 S13 28 270 280 S28 14 130 140 S14 29 280 290 S29 15 140 150 S15 10

Table 3 : Tracer gas (PFT) source characteristics Source Permeation Rate Permeation Rate Source Permeation Rate Permeation Rate No. at 24 o C (ng/min) at 9 o C (ng/min) No. at 24 o C (ng/min) at 9 o C (ng/min) S1 1932.5 1062.9 S16 1876.4 1032.0 S2 1839.1 1011.5 S17 1812.2 996.7 S3 1803.7 992.0 S18 1980.6 1089.3 S4 1927.5 1060.1 S19 1892.4 1040.8 S5 1715.3 943.4 S20 1874.4 1030.9 S6 1741.8 958.0 S21 1892.4 1040.8 S7 1865.6 1026.1 S22 1788.1 983.5 S8 1913.4 1052.4 S23 1750.7 962.9 S9 1860.3 1023.3 S24 1916.4 1054.0 S10 1780.1 979.1 S25 1780.1 979.1 S11 1844.3 1014.4 S26 1716.0 943.8 S12 1996.6 1098.1 S27 1796.2 987.9 S13 2004.7 1102.6 S28 1772.1 974.7 S14 2060.1 1133.1 S29 1956.5 1076.1 S15 2051.3 1128.2 S30 1828.2 1005.5 a. Permeation rates were measured at 24 C. b. Temperature correction was based on 9 C source temperature. 11

Outlet Inlet (a) Plan view 1 Measurement position 2 3 4 5 6 X Outlet Asymmetric Section Outlet (b) Section view Inlet Figure 1: Ventilation system and measurement locations for the steady-state case. Y Shielding Outlet Shielding Outlet 6 2.5m/s 5 HEIGHT (m) 4 3 2 1 0 0 4 8 12 16 20 24 28 x (m) Simulation (a) Velocity profiles Experimental 5.0 C 6 5 Inlet 12 Outlet (m) 4 Z Shielding

(b) Temperature profiles Figure 2 Comparison of the computed and measured air velocity and temperature profiles for the steady-state case. Exhaust Air ICE SURFACE Glass Screen PFT Source Sampler X C12 Glass screen Air Supply C1 duct Spectators C6 Figure 3: Location of tracer gas sources and passive samplers to measure PFT concentrations C11 C7 C13 under steady state conditions. Vertical riser C8 C9 (a) Tracer gas concentrations at spectators zone(height z=5.7 m) (b) Tracer gas concentrations at height 150 z=5.7 m PFT Concentrationmg/m3 PFT Concentrationmg/m3 C2 350 300 250 200 150 100 50 0 C3 C4 C5 C10 200 100 50 0 Supply air Duct Exhaust air outlet C14 Spectators 13 012345678910 Sampler Number Simulation Experim. C17 C16 C15 C18 C19 C15 C16 C17 C18 C19 PFT Sampler Number Simulation Experim. Y

Figure 4: Experimental and numerical tracer gas concentrations under steady state conditions. 14

Y Outlet S2 S29 S17 S28 S16 S15 S3 S4 S5 S18 S27 S19 S26 Ice surface S20 S25 S14 S13 S12 S24 S6 S7 S21 S8 S22 S23 S9 S11 S10 Outlet X (a) Plan view of the ice rink Z Shielding (b) Front-section view of the ice rink Inlet Figure 5: Moving CO source used in the CFD simulation for the CO emissions from a 18 16 CO concentration (ppm) 14 12 10 8 6 4 Simulation Test 2 0 0 60 120 180 240 300 Time (minute) resurfacer. Figure 6: The measured and computed CO concentrations for transient conditions 15