Addendum to Specifications

Similar documents
DSC BUILDING 1200 ALTERATIONS OCTOBER 2011 SECTION DUCT INSULATION

A. This Section includes duct and plenum insulation; accessories and attachments; and sealing compounds.

FIRE STATION 55 June 14, 2010

A. Product Data: Identify thermal conductivity, thickness, and jackets (both factory and field applied, if any), for each type of product indicated.

PROJ. NO SECTION HVAC DUCT INSULATION

B. Refer to Section : Air Distribution for lined ductwork requirements.

ACOUSTICAL INSULATION (LAGGING) FOR PIPING AND EQUIPMENT

SECTION HVAC INSULATION

SECTION MECHANICAL INSULATION. A. Types of insulation specified in this section include the following:

SECTION (15081) - HVAC INSULATION

INSTALLATION GUIDELINES for ISO-C1 POLYISOCYANURATE MECHANICAL INSULATION for CHILLED WATER SYSTEMS

INSTALLATION GUIDELINES for ISO-C1 POLYISOCYANURATE MECHANICAL INSULATION for CHILLED WATER SYSTEMS

Design & Construction Standards, Revised January

A. ASTM E84 Standard Test Method for Surface Burning Characteristics of Building Materials

D. Provide UL-approved assemblies for pipes and ducts passing through fire-rated floors, walls, or partitions as required.

ITW INSULATION SYSTEMS

This specification describes the minimum requirements for industrial thermal insulation.

ITW INSULATION SYSTEMS

A. Section Fire Procection, HVAC & Plumbing Penetration Firestopping. B. Section Interior Painting: Painting insulation jacket.

This Design guideline contained herein includes the requirements for mechanical insulation at The University of Texas at Austin

INSTALLATION GUIDELINES FOR CHILL WATER PIPE INSULATION

PRESTON HEALTH SERVICES ARCHITECT S NO. 2700

1. Division 23 Section "Hangers and Supports for HVAC Piping and Equipment" for pipe insulation shields and protection saddles.

INSTALLATION GUIDELINES FOR COLD/CRYOGENIC PIPE INSULATION

INSTALLATION GUIDELINES for ISO-C1 POLYISOCYANURATE MECHANICAL INSULATION for LIQUEFIED NATURAL GAS (LNG) CRYOGENIC REFRIGERATION CHILLED WATER

MECHANICAL INSULATION

State of Alaska Section State Office Building HVAC Fan Replacement MECHANICAL INSULATION

SECTION MECHANICAL INSULATION

SECTION PLUMBING INSULATION

Division 15 INSULATION Section 15100

ITW INSULATION SYSTEMS

SECTION MECHANICAL SYSTEMS INSULATION

INSTALLATION GUIDELINE FOR TRYMER INSULATION ITW INSULATION SYSTEMS

University of Delaware

DIVISION 23 HEATING, VENTILATING, AND AIR CONDITIONING (HVAC) SECTION HVAC INSULATION

INSTALLATION GUIDELINE FOR TRYMER INSULATION ITW INSULATION SYSTEMS

SECTION MECHANICAL INSULATION

UBC Technical Guidelines Section Edition Insulation of Tanks, Steam and Condensate Piping Page 1 of 6

SECTION IDENTIFICATION FOR PLUMBING PIPING AND EQUIPMENT

A. Deliver material to job site in original, nonbroken, factory packaging, labeled with manufacturer's density and thickness.

INSTALLATION GUIDELINE FOR TRYMER INSULATION ITW INSULATION SYSTEMS

PRESTON HEALTH SERVICES ARCHITECT S NO. 2700

SECTION PIPING INSULATION

SECTION HVAC PIPING INSULATION

Mechanical Insulation for Refrigeration Systems

A. ASTM E 84 - Standard Test Method for Surface Burning Characteristics of Building Materials

10.1 APPLICATION 1 A. HOT PIPING 1 B. ANTI SWEAT PIPING 1 C. COLD PIPING FINISHES 2

TENOCHCA HALL - PROJECT NO FAN COIL UNITS, RESTROOM AND FINISH RENOVATION

INSTALLATION GUIDELINE FOR TRYMER INSULATION

Installation Guidelines for ITW Insulation Systems Metal Jacketing Used on Insulated Pipe

UBC Technical Guidelines Section Edition Thermal Insulation for Piping Page 1 of 5

INSULATION SECTION 15250

SUPERIOR CAL-SHIELDS Features & Benefits FAST

SPECIFICATION FOR COLD INSULATION

.1 Thermal insulation for insulated piping and piping accessories affected by construction and new pipe sections as indicated on drawings.

BuildingName The Description of the Project P DOCUMENTS

SECTION HVAC INSULATION

PERMATHERM, INC. SPECIFICATION FOR COLD/CRYO PIPE INSULATION

PERMATHERM, INC. SPECIFICATION FOR COLD/CRYO PIPE INSULATION

PERMATHERM PIPE INSULATION PRODUCTS

NORTH HARRIS COUNTY REGIONAL WATER AUTHORITY. Section PIPE AND EQUIPMENT INSULATION

University of Houston Master Construction Specifications Insert Project Name

SPECIFICATION GUIDELINES FOR THE USE OF CRYOGEL Z ON COLD PIPING AND EQUIPMENT

SECTION THERMAL INSULATION GENERAL THERMAL INSULATION PART RELATED DOCUMENTS

Design No. HI/BP PERIMETER FIRE BARRIER SYSTEM Hilti, Inc. ASTM E 2307 Table 1

PIPEWORK INSULATION. 14/ Page 1 of 10 Pipework Insulation Rev D

Architectural Roof and Wall Products Guide Specifications

PERMATHERM, INC. SPECIFICATION FOR CHILLED WATER PIPE INSULATION

079 Quick Installation Guide

SECTION HVAC DUCTS AND CASINGS

Architectural Roof and Wall Products Guide Specifications

Revision:C Pipework Insulation Issued:14/11/2012 PIPEWORK INSULATION CU14. 14/11/2012 Page 1 of 10 Pipework Insulation - RevC

TENOCHCA HALL - PROJECT NO FAN COIL UNITS, RESTROOM AND FINISH RENOVATION

Pipe and Equipment Insulations. Zeston. PVC Insulated Fitting Covers Installation Instructions for Hot, Cold and USDA Piping Systems

BNIM ARCHITECTS 2460 PERSHING ROAD, SUITE 100 KANSAS CITY, MO

Architectural Wall Products Guide Specifications

A. Source Limitations: Obtain each type of building insulation through one source.

FOAMGLAS INSULATION SPECIFICATION

Duct Wrap Flexible Wraps

INSTALLATION GUIDELINE FOR TRYMER SUPERCEL PHENOLIC INSULATION

EcoTouch Insulation with PureFiber Technology

379 Quick Installation Guide

Division 07 Thermal and Moisture Protection Thermal Protection Blanket Insulation Page 1 of 17

FIRESTOP JOINT SPRAY CFS-SP WB. 2mm (0.079") WET FILM ± 7.5 ± 5

1 of 17. PO Box Bellevue Rd, Newark, DE V F

STANDARD SPECIFICATIONS. Followings have been covered in this section. The work is to be carried based on the standard specifications:

SECTION DUCT INSULATION

SECTION PRE-ENGINEERED BUILDING INSULATION

SECTION COMMON WORK RESULTS FOR FIRE SUPPRESSION

Insulation Board. Knauf Data Sheet PE-DS

Addendum 1 Section THERMAL INSULATION FOR PIPING Burrow Avenue Pumping Station Upgrades Page 1 of 5

Friendly Feel Duct Wrap with KwikStretch Markings. Knauf Data Sheet AH-DS

Fire Barrier Duct Wrap 615+

HOLLOW METAL DOORS AND FRAMES SECTION HOLLOW METAL DOORS AND FRAMES PART 1 - GENERAL

GOWANDA, NEW YORK SEPTEMBER 18, 2008 ARCH PROJECT NO

NCCER Progress Blvd, Alachua, Florida Tel: (888)

SECTION PLUMBING PIPING INSULATION

SECTION CEMENTITIOUS WOOD FIBER DECKS

Transcription:

Addendum to Specifications SOW #: Construction Specification #: Date: Additions to Specifications: Deletions to Specifications: Engineer Date Design Engineering Manager Date Page 2 of 7

PART 1 - GENERAL 1.1 PURPOSE Provide requirements for thermal insulation for mechanical equipment and tanks. 1.2 REFERENCE STANDARDS A. MANUFACTURERS RECOMMENDATIONS: Manufacturers current published recommendation unless otherwise specified. B. ASTM E84: Surface burning characteristics of building material. C. NFPA: Standard number 220. 1.3 SUBMITTALS A. MATERIAL DATA: Provide for approval B. SAMPLES: Provide for approval. PART 2 - MATERIALS 2.1 COMBUSTIBILITY: Thermal insulation system materials shall be "noncombustible" where possible or "limitedcombustible" otherwise as defined by NFPA Standard No. 220. Provide insulation and appurtenances with a Flame Spread Index of 0-25, Fuel Contributed 0-35 and a maximum Smoke Developed Index of 50 as defined by ASTM E84. 2.2 ASBESTOS: The use of asbestos or asbestos containing materials is prohibited. 2.3 INSULATION 70F to 450F: OWENS CORNING industrial insulation 700 SERIES type 701, Type 703, or Type 705 or Equal. Insulation shall be plain or faced with a factory-applied vapor barrier material as indicated in the schedules. 2.4 ADHESIVES AND MASTICS: Equivalents to those listed below as manufactured by BENJAMIN FOSTER, INSUL-COUSTICS, or LION are subject to approval by the Owner s Representative. Page 3 of 7

Breather Mastic Vapor Barrier Mastic Vapor Barrier Lab Adhesive Lagging Adhesive Bonding Adhesive Weather Proof Mastic CHILDERS CP-10 CHILDERS CP-30 CHILDERS CP-82 CHILDERS CP-50 CHILDERS CP-88 CHILDERS CP-10 2.5 INSULATING CEMENTS: Shall be as manufactured by RYDER, P.K. INSULATING COMPANY or equivalent as approved by the Owner s Representative. 2.6 GLASS CLOTH FABRIC: Shall be as manufactured by J. P. STEVENS, ALPHA, CHILDERS or equivalent as approved by the Owner s Representative. 2.7 JACKETING MATERIAL: Of the thickness specified, shall be as manufactured by CHILDERS, PABCO, QUALITY SERVICE METALS or equivalent as approved by FBP s Representative. Moisture barrier on jackets, where specified, shall consist of one layer of one mil polyethylene film with a protective layer of 40 pound virgin kraft paper continuously laminated across the full width of the jacket. 2.8 STAPLES: DUO-FAST or equivalent as approved by the Owners Representative. The stapler shall have a flaring attachment. PART 3 - EXECUTION 3.1 GENERAL: Insulation, adhesives, mastics, cements, vapor barrier coatings and other coatings or materials applied to the insulation shall be uniformly applied in strict accordance with Manufacturer's recommendations. A. SURFACE PREPARATION: Surfaces to be insulated shall be dry and free of oil, dirt, and other foreign material prior to the application of insulation. B. MOISTURE: Insulation materials shall be dry when installed. C. OUTDOOR INSTALLATIONS: No more insulation shall be applied in one day than can be weatherproofed during the same day. Exposed edges of unfinished insulation shall be protected against weather damage. D. GALVANIC CORROSION: Insulation components of dissimilar metals subject to galvanic corrosion shall not be brought into contact with each other. E. PAINT: Equipment shall have one prime coat of paint (by others) or a manufacturer's standard finish coat before insulation is installed. Covering material must be pre-sized or otherwise compatible with the finish PAINT material. Finish painting over insulation, where required, will be by others. F. END DETAILS: Wherever insulation terminates, trowel insulation cement to a neat bevel and cover. Allow room to remove flange bolts. Openings in insulation at manholes, nozzles, taps, supports or other attachments shall be sealed against the entrance of water. Page 4 of 7

G. NAMEPLATES: Insulation around nameplates and code stamps shall be beveled away from such markings and sealed against entrance of water. H. VESSEL ACCESS COVERS: Insulate in such a manner that the bolting may be removed without disturbing the insulation. I. CEMENT AND MASTIC: Coating shall be applied in 1/8 inch coats. J. VOIDS: Fill voids with insulating cement before applying finish cover. Joints shall be butted tight and finished smooth. K. JOINTS: Insulation shall be installed with sections closely butted together. The outer layer of a multiple layer insulation system shall be installed with longitudinal and end joints staggered over the joints of the inner layer. Longitudinal joints shall be on least conspicuous side. L. LAPS: Laps on longitudinal and butt joints of outer layer of insulation shall be pasted down. M. STAPLES: Staples may be used, as additional joint fastening, only on tanks and equipment operating above 70F. Staples shall NOT be used to fasten insulation to items requiring a vapor barrier such as chillers, dehumidifiers and evaporator coolers operating below 70F. N. WALL PENETRATIONS: Insulation of duct and equipment shall be unbroken through wall sleeves or other openings. O. INSULATION ANCHORS: Provide support, lugs, or anchorages required for fastening insulation in place. P. INSULATION SUPPORT: Provide insulation support steel at the base of equipment such as Boilers, Vertical Tanks, etc. Q. TEMPERATURE LIMITATIONS FOR PRESSURE-SENSITIVE TAPES: Pressuresensitive sealing tapes or patches shall only be applied when the ambient temperature is between 35F and 110F. R. WELD PINS: Space weld pins 12 inches on center and 3 inches from edge, unless noted otherwise. S. PATCHING: Whenever patching is done to existing insulation work, materials and finish of patched area shall match existing. T. DOUBLE LAYER INSULATION: Where insulation is specified in thickness greater than 2 inches or operating temperature shall exceed 600F, it shall be applied in multiple layers. Each layer shall be separately vapor sealed. U. EXPANSION JOINTS: One inch wide joints, packed with light density Fiberglas shall be provided on tanks, towers, or heat exchangers at every reinforcing ring on vertical equipment and every 16 feet on horizontal equipment. Page 5 of 7

3.2 ITEMS NOT INSULATED A. Insulation shall be omitted on the following components unless indicated otherwise on the drawings. A) Vent to atmosphere, discharges from safety devices and relief valves b) Nameplates and Code Stamps c) Man ways and Access Doors 3.3 INSTALLATION - ROUND VESSELS 36 INCHES AND LESS IN DIAMETER A. FIT: Insulation shall be cut or scored to fit the contour of the equipment without voids between equipment surface and insulation. Voids around edges shall be stuffed with like type insulation pieces. B. FASTENERS: Secure insulation to vessel with 1/2 inch stainless steel bands around circumference spaced 12 inches apart. C. JOINTS/VOIDS: Point up voids with insulating cement. Seal all breaks and joints with matching seal tape and vapor barrier mastic on faced insulation. D. SUPPORT RING: On vessels taller than 10 feet provide insulation support ring vertically every 10 feet. Support ring to be 1/2 inch less in width than insulation thickness. 3.4 INSTALLATION - IRREGULAR AND FLAT SURFACES - AND VESSELS GREATER THAN 36 INCHES DIAMETER A. FIT: Insulation shall be cut or scored to fit the contour of the equipment without voids between equipment surface and insulation. Voids around edges shall be stuffed with like type insulation pieces. B. FASTENERS, VERTICAL SURFACES: Insulation shall be impaled on weld pins 12 inches on center, a minimum of 3 inches from edge of insulation, and secured in place with 1-1/2_inch speed washers. If a corrugated metal jacket is specified as the finish, shoulder studs shall replace welded pins and be used to anchor metal jacket as well as insulation. C. FASTENERS, FLAT HORIZONTAL SURFACES: Insulation shall be impaled over weld pins spaced 18 inches apart. D. JOINTS/VOIDS: Point up all voids with insulating cement. Seal all breaks and joints with matching seal tape and vapor barrier mastic on faced insulation. Coat all speed washers with insulating cement unless aluminum jacket is to be applied. 3.5 FINISHES A. INDOOR EQUIPMENT WITH IRREGULAR SURFACES: Finish with two coats of vapor barrier mastic, reinforced with glass fabric. Lap all joints a minimum of 2 inches. Page 6 of 7

B. OUTDOOR EQUIPMENT WITH IRREGULAR SURFACES: Apply two 1/8 inch coats of outdoor weatherproof mastic, reinforced with glass fabric. Lap all joints a minimum of 2 inches. C. TANKS AND ROUND EQUIPMENT - 36 INCH DIAMETER AND LESS: Finish with.024 inch thick aluminum jacket held in place with 1/2 inch stainless steel horizontal bands on 12 inch vertical centers. Overlap all joints 3 inches minimum. Horizontal joints to have "S" clips or stainless steel sheet metal screws on 6 inch centers. Tank and vessel ends and tops to be finished as in 3.5.1 or 3.5.2. D. FLAT SURFACES, TANKS AND ROUND EQUIPMENT 36 INCH DIAMETER AND LARGER: Finish with.024 inch thick corrugated aluminum jacket. Overlap all horizontal joints a minimum of 4 inches and vertical joints a minimum of 1-1/2 corrugations. Secure by shoulder studs. All seams to be further fastened with stainless steel screws on 8 inch centers. Tank and vessel ends and tops to be finished as in 3.5.1 or 3.5.2. E. MANHOLES, NOZZLES AND COUPLINGS: Aluminum sheets shall be carefully fitted around all manholes, nozzles and couplings on shell of tanks in order to make a weather- tight covering. Outdoor Breather Mastic shall be applied on overlapping metal surfaces and on areas adjacent to the appurtenance so joints and seams are weatherproof. On equipment subject to mechanical abuse, 24 gauge sheet metal shall be substituted for the aluminum jacket. Application per 3.5.C or 3.5.D. ++ END OF SECTION ++ Page 7 of 7