NFPA 285 Assemblies. Table of Contents

Similar documents
NFPA 285 Assemblies. Table of Contents

Henry NFPA 285 Air Barrier Assemblies

NFPA 285 Compliant Wall Assemblies with Perm-A-Barrier Air Barriers Walls Containing Mineral Wool Insulation

CommercialComplete Wall System

NFPA 285 Compliant Wall Systems and Assemblies

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: WATER RESISTIVE BARRIERS/WEATHER BARRIERS SECTION: AIR BARRIERS

Deer Ridge Consulting, Inc.

Exterior Wall Analysis Use of Gypsum Sheathing Over XPS Insulation in NFPA 285 Complying Wall Assemblies JENSEN HUGHES Project No. 1JJB05306.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: WATER RESISTIVE BARRIERS/WEATHER BARRIERS SECTION: AIR BARRIERS

Originally Issued: 12/12/2014 Revised: 12/29/2017 Valid Through: 12/29/2018

October 15, Dow Building Solutions The Dow Chemical Company 1605 Joseph Drive Midland, MI 48642

RE: Exterior Wall Analysis Use of Gypsum Sheathing Over Dow Thermax Insulation in NFPA 285 Complying Wall Assemblies No. 1JJB05306.

SECTION CONTINUOUS INSULATION XCI 286 WALL/CEILING PANELS

Originally Issued: 03/28/2014 Revised: 05/19/2017 Valid Through: 03/31/ General

Originally Issued: 03/28/2014 Revised: 05/19/2017 Valid Through: 03/31/ General

December 8, Dow Building Solutions The Dow Chemical Company 1605 Joseph Drive Midland, MI 48642

UL Evaluation Report UL ER Issued: October 30, Revised: September 12, UL Category Code: ULEX.

O82018 Hunter Panels XCI Foil

Originally Issued: 03/28/2014 Revised: 05/25/2017 Valid Through: 03/31/2018

ICC-ES Evaluation Report. ESR-3398* Reissued October 2013 This report is subject to renewal November 1, 2015.

NFPA 285 Wall Assemblies

ENGINEERING EVALUATION

REPORT HOLDER: JOHNS MANVILLE TH STREET DENVER, COLORADO EVALUATION SUBJECT:

ESR-2072 Reissued September 1, 2013 This report is subject to renewal September 1, 2015.

SECTION CONTINUOUS INSULATION XCI FOIL (CLASS A) WALL PANELS

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION SECTION: WATER-RESISTIVE BARRIERS/WEATHER BARRIERS

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: CERTAINTEED CORPORATION

ESR-1655 Reissued April 2014 This report is subject to renewal April 1, 2016.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION SECTION: WATER-RESISTIVE BARRIERS REPORT HOLDER:

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: ICYNENE, INC.

Code Compliance Research Report CCRR-1043

Design No. HI/BP PERIMETER FIRE BARRIER SYSTEM Hilti, Inc. ASTM E 2307 Table 1

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: LAPOLLA INDUSTRIES, INC. EVALUATION SUBJECT:

calibrated gas flows from the room burner.

TSX Insulation for Exposed Use ROOF WALL SPECIALTY

SECTION CONTINUOUS INSULATION XCI CG WALL PANELS

NFPA 285: Assembly Test of Exterior Walls with Combustible Components. Herman Lopez DuPont Commercial Account Manager

Impact of NFPA 285 on Air Barrier Specification and Design

NFPA 285 Tested Wall Assemblies Using

Ultra Wall System. CAD Detail Sets

APPENDIX DETAIL (1) INSULATION HAS 3-INCH TOP INSPECTION GAP AND EXTENDS 24 INCHES BELOW GRADE

NFPA 285 Tested Wall Assemblies Using

FIRESTOP JOINT SPRAY CFS-SP WB. 2mm (0.079") WET FILM ± 7.5 ± 5

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION SECTION: WATER RESISTIVE BARRIERS/WEATHER BARRIERS

R-Value and Densities Chart

Originally Issued: 07/06/2009 Revised: 04/07/2017 Valid Through: 07/31/2017

OCS ONE COAT STUCCO A custom blend of Portland cement, sand, extenders, fiber reinforcement and modifiers.

Incorporating Insulating Sheathing into the Design of the Thermal and Moisture Management System of the Building Enclosure

Continuous Insulation and Air Barriers for High Performance Walls

Intertek Research Report IRR-1011

Originally Issued: 07/31/2015 Revised: 07/31/2017 Valid Through: 07/31/ General

R-Matte Plus-3: Insulation for the Building Envelope

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: ARCONIC ARCHITECTURAL PRODUCTS, LLC

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: ICYNENE, INC. EVALUATION SUBJECT:

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: ICYNENE, INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: BAYER MATERIALSCIENCE, LLC

Insulation. First Revison October DC14 Drainage Mat INSTALLATION GUIDE FOR RESIDENTIAL & COMMERCIAL APPLICATIONS

Continuous Insulation: Code Compliance and the NFPA 285 in Commercial Wall Assemblies. Hunter Panels Provider No. K169 Course Number HP 105

Technical Data Sheet

SUBJECT: NEW 2000 INTERNATIONAL RESIDENTIAL CODE (IRC) DATE:

ProGUARD Guide Specification

Insulated Concrete Forms (ICFs)

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: DEMILEC (USA) INC.

INSTALLATION INSTRUCTIONS ENERGYSHIELD AND RBOARD USE IN CANADA

Thermasheath -3. Insulation for the Building Envelope ROOF WALL SPECIALTY

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: JOHNS MANVILLE

Trusted ICC ES DIVISION: ATLANTA, CGF PRO, ENERGYS. Look. Conformity! Evaluation. ICC-ES Evaluation

Thermasheath -3. Insulation for the Building Envelope ROOF WALL SPECIALTY

REPORT HOLDER: STAR R FOAM MANUFACTURING, INC. EVALUATION SUBJECT: STAR R FOAM INSULATION BOARDS

WEIGHT PER PIECE (LBS.)

Johns Manville MinWool Water & Fire Block Mineral Wool Insulation

Thermasheath -3. Insulation for the Building Envelope ROOF WALL SPECIALTY

Session: Foam Plastic Insulation Exterior Wall Fire Safety

A. Source Limitations: Obtain each type of building insulation through one source.

Stone and Masonry Veneer

SECTION THERMAL INSULATION

Beginning of the Course

ICC-ES Evaluation Report Reissued April 1, 2010 This report is subject to re-examination in two years.

OWENS CORNING ENCLOSURE SOLUTIONS:

ICC-ES Evaluation Report. ESR-1154 Reissued July 1, 2012 This report is subject to renewal September 1, 2014.

August 28, Mr. Jason Roy Plant Manager Advanced Building Products, Inc. 95 Cyro Drive Sanford, ME 04073

THERMAL AND AIR BARRIER WALL SYSTEM

Code Compliance Research Report CCRR-0231

ProGUARD DP The Game-changing Wall System

C. Product Test Reports: Based on evaluation of comprehensive tests performed by a qualified testing agency, for each product.

SCIENCE. SERVICE. SOLUTIONS. AIR & VAPOR BARRIER. Fire Resist Product Line

MID-RISE DESIGN & CONSTRUCTION

ESR-1826 Reissued February 1, 2013 This report is subject to renewal February 1, 2015.

REPORT HOLDER: ATLAS EPS, A DIVISION OF ATLAS ROOFING CORPORATION 8240 BYRON CENTER SOUTHWEST BYRON CENTER, MICHIGAN EVALUATION SUBJECT:

REPORT HOLDER: THE DOW CHEMICAL COMPANY 1501 LARKIN CENTER DRIVE MIDLAND, MICHIGAN EVALUATION SUBJECT:

Installation Guidelines

ELEVATION FOR DETAIL REFERENCE ONLY

Originally Issued: 07/2009 Revised: 09/30/2014 Valid Through: 07/2015

INSTALLATION MANUAL. ZIP System R12 Sheathing. Contents. 07 ZIP System R12 Sheathing Window Installation 08 ZIP System R12 Sheathing Siding Guidelines

ENGINEERING EVALUATION

Fire Testing Laboratory

INSTALLATION INSTRUCTIONS

ICC-ES Evaluation Report Reissued February 1, 2012 This report is subject to renewal February 1, 2013.

Transcription:

Effective 12/16/2014 Supersedes all previous versions NFPA 285 Assemblies The following Henry assemblies meet the performance requirements of NFPA 285 as required by the International Building Code (2003, 2006, 2009, 2012 and 2015 editions). These assemblies are based on the specific construction materials installed in the manner described in the tables shown. Changes or modifications to the construction and/or materials used in the tested assembly may result in a different fire performance and not meet the performance requirements of NFPA 285. All Air Barriers to be installed at recommended application rates as per Henry installation instructions. This document will be updated periodically. Therefore, it is important to refer to the most up to date version as found on the Henry website: www.henry.com. Table of Contents Henry Assemblies Table 1 XPS Insulation with Non-Combustible Veneers Figure 1 XPS Window Detail 1 Figure 2 XPS Window Detail 2 Figure 3 XPS Window Detail 3 Table 2 Permax with Non-Combustible Veneers Table 3 Polyisocyanurate with Non-Combustible and Combustible Veneers Table 4 Mineral Wool with Non-Combustible and Combustible Veneers Table 5 Walls excluding Exterior Insulation Table 6 Extruded Polystyrene with Non-Combustible Veneers Flow Chart Quick Reference NFPA 285 Flow Chart Third Party Assemblies Laminators Inc. Hunter Panels

Henry Assemblies Table 1. Walls Containing XPS Insulation and Henry Air Barrier membranes as Noted Wall Component Base wall system Use either 1, 2 or 3 Floor-line Fire-stopping Cavity Insulation Use either 1, 2, 3, 4 or 6 Interior vapor membrane (optional) Use either 1 or 2 Exterior sheathing Use either 1 or 2 Air barrier membrane applied to gypsum sheathing Select from list Exterior insulation Exterior Veneer Use either 1, 2, 3, 4, 5 or 6 Continued on next page Materials 1 Concrete wall 2 Concrete Masonry wall 3 1 layer ⅝-inch thick, Type X, Gypsum wallboard on interior, installed over steel studs: minimum 3⅝-inch depth, minimum 20-gauge at a maximum of 24-inch OC with lateral bracing every 4-ft vertically 4 lb/cu ft. mineral wool (e.g. Thermafiber or Roxul) in each stud cavity at each floorline attached with Z-clips or equivalent 2 Any noncombustible insulation (faced or unfaced) per ASTM E136 3 Any Mineral Fiber (Board type Class A, ASTM E84 faced or unfaced) 4 Any Fiberglass (Batt type Class A, ASTM E84 faced or unfaced) 5 Items 2-4 may incorporate a Class A vapor barrier film 6 Henry Permax SPF maximum thickness 6-inch 2 One layer of maximum 6-mil thick polyethylene film 1 ½-inch thick, exterior type gypsum sheathing 2 ⅝-inch thick, Type X, exterior type gypsum sheathing 2 Air-Bloc 17MR 3 Air-Bloc 21FR or 21S 4 Air-Bloc 31MR 5 Air-Bloc 32MR 6 Air-Bloc 33MR 7 Blueskin VP160 8 Blueskin SA or SA LT 9 Metal Clad 10 FoilSkin Extruded Polystyrene Foam Insulation (XPS) - Type IV per ASTM C578 Maximum of 3-inch thickness on insulation joints, flashing tape such as Henry Blueskin SA or Butyl Flash max. 12-inch width can be used. 1 Brick - Standard nominal 4-inch thick, clay brick. Brick installed with standard type veneer anchors at maximum 24-inch OC vertically on each stud. Maximum 2-inch air gap between exterior insulation and brick 2 Concrete 2-inch thick or greater. Maximum 2-inch air gap between exterior insulation and concrete. 3 Concrete masonry units 4-inch thick or greater. Maximum 2-inch air gap between exterior insulation and CMU. 4 Stone veneer Minimum 2-inch thick, Limestone or natural stone veneer or minimum 1½-inch thick cast artificial stone veneer. Any standard non-open-joint installation technique such as ship-lap, etc. can be used.

Table 1 (Continued) Exterior Veneer (continued) Special Conditions Flashing of window, door and other exterior wall penetrations. 5 Terracotta cladding Use any terracotta cladding system in which terracotta is minimum 1¼-inch thick. Any non-open-joint installation technique such as shiplap, etc. can be used. 6 Stucco Minimum ¾-inch thick, exterior cement plaster and lath. This exterior veneer cannot be used with the exterior insulation described above. Use header treatment shown in Figure 1, 2 or 3 for all window and door openings in walls utilizing XPS insulation. As an option, flash window, door and other exterior penetrations with limited amounts of asphalt, acrylic or butyl-based flashing tape such as Henry Blueskin SA or Butyl Flash max. 12-inch width. Figure 1 Window / Door Opening Detail

Figure 2 Window / Door Opening Detail

Figure 3 Window / Door Opening Detail

Table 2. Walls Containing Henry Permax 2.0 or Permax 1.8 SPF Wall Component Base wall system Cavity Insulation Use either 1 or 2 Interior vapor membrane (optional) Use either 1 or 2 Exterior sheathing Air barrier membrane applied to gypsum sheathing Exterior insulation Exterior Veneer Special Conditions Materials 1 layer ⅝-inch thick, Type X, Gypsum wallboard on interior, installed over steel studs: 6-inch depth, minimum 16-gauge at a maximum of 16-inch OC 2 Any noncombustible insulation (faced or unfaced) per ASTM E136 2 One layer of maximum 6-mil thick polyethylene film ½-inch thick, exterior type gypsum sheathing DensGlass Gold Exterior Sheathing (Georgia Pacific) None Permax 2.0 or Permax 1.8 Closed Cell Sprayed Polyurethane Foam Insulation (nominal density of 2.0 lb/ft 3 or 1.8 lb/ft 3 ), spray applied to a nominal 4-inch thickness on the outside of the exterior gypsum sheathing. Brick - Standard nominal 4-inch thick, clay brick with Type S masonry cement. Brick installed with 3½-inch X-seal HD6 Hohmann & Barnard, Inc. Anchors, installed in the insulation, over the DensGlass Gold Exterior Sheathing at 16-inch OC using #14 x 5- inch polymer-coated screws with washer creating a minimum 2-inch air space between the insulation and brick. The window lintel 4-inch x 4-inch x ¼-inch steel angle, 94-inch long (8-inch coverage on both sides of the window). The window header, jambs and sill constructed of 2 overlapping pieces of 2-inch x 9-inch, 16-gauge steel installed using #12 x 1-1.2 TEKS self-tapping screws spaced a nominal 24-inch OC on the window header, sill and jambs. The steel is to be attached to the interior of the wall using #12 x 1-1/2 TEKS self-tapping screws spaced a nominal 24-inch OC through the 2- inch leg, and to the brick facing using ¼-inch x 1¼-inch TITEN Simpson Strong Ties spaced a nominal 24-inch OC through the 2-inch leg.

Table 2.5 Walls Containing Henry Permax 2.0X or Permax 2.0X Fast SPF Wall Component Base wall system Use either 1, 2 or 3 Floorline Firestopping Cavity Insulation Use either 1, 2 or 3 Interior vapor membrane (optional) Use either 1 or 2 Exterior sheathing Exterior insulation Exterior Veneer Materials 1 Concrete wall 2 Concrete masonry wall 3 1 layer ⅝-inch thick Type X gypsum wallboard complying with ASTM C36 or C1396 on the interior, installed over minimum 3⅝-inch, no. 20 gage C-shaped steel studs, spaced a maximum of 24-inch on center with lateral bracing every 4-ft vertically. 4 pcf mineral wool in each stud cavity at each floorline, attached with z-clips 2 Fiberglass batt insulation (faced or unfaced) 3 Permax 2.0X or Permax 2.0X Fast closed cell insulation 2 One layer of maximum 6-mil thick polyethylene film ½-inch or ⅝-inch thick, exterior type gypsum sheathing Permax 2.0X or Permax 2.0X Fast Closed Cell Sprayed Polyurethane Foam Insulation (nominal density of 2.0 lb/ft 3 ), spray applied to a maximum nominal 3- inch thickness on the outside of the exterior gypsum sheathing. 1 Brick - Standard nominal 4-inch thick clay brick with Type S masonry cement. Brick veneer anchors installed at a maximum of 24-inch OC creating a minimum 2-inch air space between the insulation and brick. 2 Stucco minimum ¾-inch thick exterior cement plaster and lath. 3 Minimum 2-inch thick limestone. Any standard non-open jointed installation technique such as ship-lap, etc. may be used.

Table 3. Walls Containing Polyisocyanurate Insulations and Henry Air Barrier Membranes as Noted Wall Component Base wall system Use either 1, 2 or 3 Floorline Firestopping Cavity Insulation Use either 1, 2, 3, 4 or 6 Interior vapor membrane (optional) Use either 1 or 2 Exterior sheathing Henry Air Barrier membrane applied to gypsum sheathing Select from list. Exterior insulation Use either 1 or 2 Continued on next page Materials 1 Concrete wall 2 Concrete Masonry wall 3 Steel Stud Framed Wall (24-inch OC max.) Minimum 16-gauge, 3⅝-inch studs, with lateral bracing every 4-ft vertically, with a minimum of 1 layer of ⅝-inch Type X gypsum wallboard on interior face of studs. With Base wall system No. 3 above, 4 lb/cu ft. mineral wool (e.g. Thermafiber) in each stud cavity and at each floorline attached with Z-clips or equivalent 2 Any noncombustible insulation (faced or unfaced) per ASTM E136 3 Any Mineral Fiber (Board type Class A, ASTM E84 faced or unfaced) 4 Any Fiberglass (Batt type Class A, ASTM E84 faced or unfaced) 5 Items 2-4 may incorporate a Class A vapor barrier film 6 Henry Permax SPF maximum thickness 6-inch 2 One layer of maximum 6-mil thick polyethylene film ⅝-inch thick, Type X, exterior type gypsum sheathing 2 Air-Bloc 17MR 3 Air-Bloc 21FR & 21S 4 Air-Bloc 31MR 5 Air-Bloc 32MR 6 Air-Bloc 33MR 7 Blueskin VP160 8 Blueskin SA or SA LT 9 Metal Clad 10 FoilSkin 2 Atlas Energy Shield Pro Rigid Insulation, Atlas Energy Shield Pro2 Rigid Insulation or Atlas Rboard Rigid Insulation with 4-inch maximum thickness using joint tape tested per ASTM E1354

Table 3 (Continued) Exterior Veneer Use either 1, 2, 3, 4, 5, 6, 7, 8, 9 or 10 1 Brick Brick veneer anchors standard types installed maximum 24-inch OC vertically on each stud Maximum 2-inch air gap between exterior insulation and brick Standard nominal 4-inch thick, clay brick 2 Stucco Minimum ¾-inch thick, exterior cement plaster and lath. A secondary water-resistive barrier can be installed between the exterior insulation and the lath. The secondary water-resistive barrier shall not be full-coverage asphalt or butylbased self- adhered membranes. 3 Stone veneer Minimum 2-inch thick, Limestone or natural stone veneer or minimum 1½-inch thick cast artificial stone veneer. Any standard installation technique can be used. 4 Terracotta cladding Use any terracotta cladding system in which terracotta is minimum 1¼-inch thick. Any standard installation technique can be used. 5 Metal veneer such as steel, aluminum, copper, etc. Any standard installation technique can be used. 6 Fiber cement siding or fiber cement panels. Any standard installation technique can be used. 7 MCM System Use any Metal Composite Panel that has been successfully tested by the panel manufacturer via NFPA 285 test method. Note: Only steel window framing shall be used. 8 Concrete Masonry Units (CMU) Minimum 4-inch thick CMU, with a 2-inch maximum air gap between exterior insulation and CMU. 9 Concrete Panels Minimum 2-inch thick panel, with a 2-inch maximum air gap between exterior insulation and concrete panel. 10 Insulated Concrete Sandwich Panels Minimum 2-inch thick outer and inner faces. Maximum 2-inch air gap between inner face and wall system. Note: All exterior veneer/cladding systems must be installed in accordance with manufacturer s recommended installation instructions and with applicable building codes. Flashing of window, door and other exterior wall penetrations. As an option, flash window, door and other exterior penetrations with limited amounts of asphalt, acrylic or butyl-based flashing tape such as Henry Blueskin SA or Butyl Flash max. 12-inch width.

Table 4. Walls Containing Mineral Wool Insulation and Henry Air Barriers as Noted Wall Component Base wall system Cavity Insulation Use either 1, 2, 3, 4 or 6 Interior vapor membrane (optional) Use either 1 or 2 Exterior sheathing Use either 1 or 2 Air barrier membrane applied to gypsum sheathing Select from list. Exterior insulation Continued on next page Materials Steel studs with Interior wall membrane (typically gypsum) on the interior 2 Any noncombustible insulation (faced or unfaced) per ASTM E136 3 Any Mineral Fiber (Board type Class A, ASTM E84 faced or unfaced) 4 Any Fiberglass (Batt type Class A, ASTM E84 faced or unfaced) 5 Items 2-4 may incorporate a Class A vapor barrier film 6 Henry Permax SPF maximum thickness 6-inch 2 One layer of maximum 6-mil thick polyethylene film 1 ½-inch thick, exterior type gypsum sheathing 2 ⅝-inch thick, Type X, exterior type gypsum sheathing 2 Air-Bloc 06WB 3 Air-Bloc 17MR 4 Air-Bloc 21FR or 21S 5 Air-Bloc 31MR 6 Air-Bloc 32MR 7 Air-Bloc 33MR 8 Blueskin VP160 9 Blueskin SA or SA LT 10 MetalClad 11 FoilSkin Mineral wool insulation as per ASTM C612 and meeting the following conditions: The mineral wool shall be a minimum of 2-inch thick The mineral wool shall not have any type of facer (foil, etc.) on either side The mineral wool shall be noncombustible via ASTM E136 testing The density of the mineral wool shall range from 4.0 to 9.0 lbs/ft 3 The R-value/inch of the mineral wool shall range from 3.5 to 4.5 The mineral wool insulation must be mechanically attached, and The mineral wool must completely cover the Air Barrier membrane

Table 4 (Continued) Exterior Veneer Use either 1, 2, 3, 4, 5, 6, 7 or 8 1 Brick Standard nominal 4-inch thick, clay brick. Brick installed with standard type veneer anchors at maximum 24-inch OC vertically on each stud. Maximum 2-inch air gap between exterior insulation and brick 2 Concrete 2-inch thick or greater. Maximum 2-inch air gap between exterior insulation and concrete. 3 Concrete masonry units 4-inch thick or greater. Maximum 2-inch air gap between exterior insulation and CMU. 4 Stone veneer Minimum 2-inch thick, limestone or natural stone veneer or minimum 1½-inch thick cast artificial stone veneer. Any standard non-open-joint installation technique such as ship-lap, etc. can be used. 5 Terracotta cladding Use any terracotta cladding system in which terracotta is minimum 1¼-inch thick. Any non-open-joint installation technique such as shiplap, etc. can be used. 6 Stucco Minimum ¾-inch thick, exterior cement plaster and lath. This exterior veneer cannot be used with the exterior insulation described above. 7 Metal veneer such as steel, aluminum, copper, etc. Any standard installation technique can be used. 8 NFPA 285 complying Combustible Veneer Special Conditions Any combustible NFPA 285 complying exterior veneer is identical to that tested The use of the Air Barrier membranes is limited to applications behind the mineral wool insulation and not on the exterior face of the insulation. No other combustibles such as foam plastic insulations, etc. are used in the wall system. Cavity wall space is optional. Flashing of window, door and other exterior wall penetrations. As an option, flash window, door and other exterior penetrations with limited amounts of asphalt, acrylic or butyl-based flashing tape such as Henry Blueskin SA or Butyl Flash max. 12-inch width.

Table 5. Walls Excluding Exterior Insulation and Henry Air Barriers as Noted Wall Component Base wall system Use either 1, 2 or 3 Floorline Firestopping Cavity Insulation Use either 1 or 2 Interior vapor membrane (optional) Use either 1 or 2 Exterior sheathing Air barrier membrane applied to gypsum sheathing Select from list Exterior insulation Continued on next page Materials 1 Concrete wall 2 Concrete Masonry wall 3 Steel Stud Framed Wall (24-inch OC max.) Minimum 16-gauge, 3⅝-inch studs with lateral bracing every 4 ft vertically, with a minimum of 1 layer of ⅝-inch Type X gypsum wallboard on interior face of studs. With Base wall system No. 3 above, 4 lb/cu ft. mineral wool (e.g. Thermafiber) in each stud cavity and at each floorline attached with Z-clips or equivalent 2 Any noncombustible insulation (faced or unfaced) per ASTM E136 2 One layer of maximum 6-mil thick polyethylene film ⅝-inch thick, Type X, exterior type gypsum sheathing 1 Metal Clad 2 Air-Bloc 17MR None

Table 5 (Continued) Exterior Veneer Use either 1, 2, 3, 4, 5, 6, 7, 8, 9 or 10 1 Brick Brick veneer anchors standard types installed maximum 24-inch OC vertically on each stud Maximum 2-inch air gap between exterior insulation and brick Standard nominal 4-inch thick, clay brick 2 Stucco Minimum ¾-inch thick, exterior cement plaster and lath. A secondary water-resistive barrier can be installed between the exterior insulation and the lath. The secondary water-resistive barrier shall not be full-coverage asphalt or butyl-based self- adhered membranes. 3 Stone veneer - Minimum 2-inch thick, Limestone or natural stone veneer or minimum 1½-inch thick cast artificial stone veneer. Any standard installation technique can be used. 4 Terracotta cladding Use any terracotta cladding system in which terracotta is minimum 1¼-inch thick. Any standard installation technique can be used. 5 Metal veneer such as steel, aluminum, copper, etc. Any standard installation technique can be used. 6 Fiber cement siding or fiber cement panels. Any standard installation technique can be used. 7 MCM System Use any Metal Composite Material system that has been successfully tested by the panel manufacturer via NFPA 285 test method. Note: Only steel window framing shall be used. 8 Concrete Masonry Units (CMU) Minimum 4-inch thick CMU, with a 2-inch maximum air gap between exterior insulation and CMU. 9 Concrete Panels Minimum 2-inch thick panel, with a 2-inch maximum air gap between exterior insulation and concrete panel. 10 Insulated Concrete Sandwich Panels Minimum 2-inch thick outer and inner faces. Maximum 2-inch air gap between inner face and wall system. Note: All exterior veneer/cladding systems must be installed in accordance with manufacturer s recommended installation instructions and with applicable building codes. Flashing of window, door and other exterior wall penetrations. As an option, flash window, door and other exterior penetrations with limited amounts of asphalt, acrylic or butyl-based flashing tape such as Henry Blueskin SA or Butyl Flash max. 12-inch width.

Table 6. Walls Containing Expanded Polystyrene Insulation and Henry Air Barrier membranes as Noted Wall Component Base wall system Use either 1, 2 or 3 Floor-line Fire-stopping Cavity Insulation Use either 1, 2, 3, 4 or 6 Interior vapor membrane (optional) Use either 1 or 2 Exterior sheathing Use either 1 or 2 Air barrier membrane applied to gypsum sheathing Select from list Exterior insulation Continued on next page Materials 1 Concrete wall 2 Concrete Masonry wall 3 1 layer ⅝-inch thick, Type X, Gypsum wallboard on interior, installed over steel studs: minimum 3⅝-inch depth, minimum 20-gauge at a maximum of 24-inch OC with lateral bracing every 4-ft vertically 4 lb/cu ft. mineral wool (e.g. Thermafiber or Roxul) in each stud cavity at each floorline attached with Z-clips or equivalent 2 Any noncombustible insulation (faced or unfaced) per ASTM E136 3 Any Mineral Fiber (Board type Class A, ASTM E84 faced or unfaced) 4 Any Fiberglass (Batt type Class A, ASTM E84 faced or unfaced) 5 Items 2-4 may incorporate a Class A vapor barrier film 6 Henry Permax SPF maximum thickness 6-inch 2 One layer of maximum 6-mil thick polyethylene film 1 ½-inch thick, exterior type gypsum sheathing 2 ⅝-inch thick, Type X, exterior type gypsum sheathing 2 Air-Bloc 17MR 3 Air-Bloc 21FR or 21S 4 Air-Bloc 31MR 5 Air-Bloc 33MR 6 Blueskin VP160 7 Blueskin SA or SA LT 8 Metal Clad 9 FoilSkin 1 Atlas ThermalStar CVT 25 maximum 5.4-inch thick 2 Atlas ThermalStar CVT 15 maximum 7.2-inch thick 3 Atlas ThermalStar LCi 25 maximum 5.4-inch thick 4 Atlas ThermalStar LCi 15 maximum 7.2-inch thick 5 Atlas ThermalStar CHROME 15 maximum 7.2-inch thick 6 Atlas ThermalStar CHROME 25 maximum 5.4-inch thick 7 AFM Foam Control EPS Type I 10.75-inch 8 AFM Foam Control EPS Type VIII 8.25-inch 9 AFM Foam Control EPS Type II 7-inch 10 AFM Foam Control EPS Type IX 5.25-inch 11 AFM Foam Control EPS Type XIV 4-inch 12 AFM Foam Control EPS Type XV 3.25-inch

Table 6 (Continued) Exterior Veneer Use either 1, 2, 3, or 4 Special Conditions Flashing of window, door and other exterior wall penetrations. 1 Brick - Standard nominal 4-inch thick, clay brick. Brick installed with standard type veneer anchors at maximum 24-inch OC vertically on each stud. Maximum 2-inch air gap between exterior insulation and brick 2 Stone veneer Minimum 2-inch thick, Limestone or natural stone veneer or minimum 1½-inch thick cast artificial stone veneer. Any standard non-open-joint installation technique such as ship-lap, etc. can be used. 3 Terracotta cladding Use any terracotta cladding system in which terracotta is minimum 1¼-inch thick. Any non-open-joint installation technique such as shiplap, etc. can be used. 4 Stucco Minimum ¾-inch thick, exterior cement plaster and lath. Use header treatment shown in Figure 1 for all window and door openings in walls utilizing EPS insulation. Flash window, door and other exterior penetrations with limited amounts of asphalt, acrylic or butyl-based flashing tape such as Henry Blueskin SA or Butyl Flash max. 12-inch width. Figure 1 Header Detail Source: AFM Technologies

NFPA 285 Approved Assemblies by Third Party Certification of NFPA 285 test results or extension by engineering analysis was provided by the listed manufacturers. Henry did not participate in their testing or certification processes and therefore assumes no responsibility for their results. Contact the manufacturer for more information. Laminators Inc. - Omega-Lite Dry Seal System The assemblies below are the property of Laminators Inc. For additional information, clarification or installation questions please contact Laminators Inc. at 877-OMEGA77 or fax them at 215-721- 1239. You may also visit their website at www.laminatorsinc.com Wall Component Base wall system Materials 1 layer ⅝-inch thick, Type X, Gypsum wallboard on interior, installed over steel studs: minimum 6-inch depth, minimum 20-gauge at a maximum of 16-inch OC Floor-line Fire-stopping 4 lb/cu ft. mineral wool (e.g. Thermafiber or Roxul) in each stud cavity at floor-line attached with Z-clips or equivalent Cavity Insulation Use either 1 or 2 Exterior sheathing 2 Any noncombustible insulation (unfaced) per ASTM E136 ⅝-inch thick, Densglass Gold Sheathing Air barrier membrane applied to gypsum sheathing Exterior insulation Use either 1 or 2 Exterior Veneer Flashing of window, door and other exterior wall penetrations. 1 Henry Air-Bloc 31MR (For ext. veneer option 1 or 2 only) 2 Henry Air-Bloc 33MR (For ext. veneer option 3 only) 2 Mineral Wool non-combustible insulation 1 Omega-Lite 1 Piece, Tight-fit Molding System 2 Omega-Lite Dry Seal System 3 Omega-Lite Rout & Return System In accordance with Laminators Inc. installation procedures. Contact Laminators Inc. at www.laminatorsinc.com for more details. As an option, flash window, door and other exterior penetrations with limited amounts of asphalt flashing tape such as Henry Blueskin SA or Butyl Flash max. 12-inch width.

Hunter Panels Hunter Xci CG The assemblies below are the property of Hunter Panels. For additional information, clarification or installation questions please contact Hunter Panels at 888-746-1114. You may also visit their website at http://www.hunterxci.com/ Wall Component Base wall system Materials 1 Steel Stud 1 layer ⅝-inch thick Type X or ½-inch thick Type C Gypsum wallboard on interior, installed over steel studs: minimum 3 5/8" depth, minimum 22-gauge at a maximum of 24-inch OC with lateral bracing every 4 ft vertically 2 Concrete Wall (cast in place or precast) 3 Concrete Masonry Wall Floor-line Fire-stopping 4 lb/cu ft. mineral wool (e.g. Thermafiber or Roxul) in each stud cavity at floor-line attached with Z-clips or equivalent Cavity Insulation Use either 1 or 2 Exterior sheathing Air barrier membrane applied to gypsum sheathing Exterior insulation Use either 1 or 2 Exterior Veneer - Use either 1, 2, 3, 4, 5, 6, 7 or 8 2 Any noncombustible insulation (unfaced) per ASTM E136 ½-inch or ⅝-inch thick exterior type gypsum sheathing Henry Air-Bloc 32MR 3½-inch maximum thickness of Hunter Xci CG, 4x8 panels or cut to size 1 Masonry Brick veneer anchors, standard types, installed maximum 24-inch OC vertically on each stud. Maximum 2-inch air gap between exterior insulation and brick. Standard nominal 4-inch thick or greater, clay brick. 2 Stucco - Minimum ¾-inch thick, exterior cement plaster and lath 3 Limestone or Natural Stone Minimum 2-inch thick, limestone or natural stone veneer or minimum 1½-inch thick cast artificial stone veneer. Any standard installation technique can be used. 4 Terracotta Cladding - Use any terracotta cladding system in which terracotta is minimum 1¼-inch. Any standard installation technique can be used. 5 MCM System Use any Metal Composite Material system that has been successfully tested by the panel manufacturer via the NFPA 285 test method. Any standard installation technique can be used. 6 Metal Exterior wall coverings such as Steel, Aluminum, Copper, etc. Any standard installation technique can be used. 7 Fiber Cement Board Siding - Any standard installation technique can be used. 8 Stone Aluminum Honeycomb Composite Panels that have been successfully tested by the panel manufacturer via the NFPA 285 test method. Any standard installation technique can be used.

NFPA 285 Performance Requirements and Code References NFPA 285 (previously UBC 26-9) is the standard fire test method for evaluation of fire propagation characteristics of exterior non-load-bearing wall assemblies containing combustible components. Meeting the performance requirements of NFPA 285 is determined by the analysis of NFPA 285 tests and additional small scale tests. Analysis is provided by accredited testing facilities and outside Fire Protection engineers as referenced in AC12 6.6. The relevant sections of the International Building Code that address NFPA 285 are as follows. Foam Plastics 2603.5.5 (~1988 edition) Combustible Veneers Use over 40ft above grade MCMs & ACMs 1407.10 (2000 edition) HPLs 1409.10 (2009 edition) EIFS 1408.2 (2009 edition) FRPs 2612.5 (2009 edition) Water-resistive barriers 1403.5 (2012 edition) Quick Reference NFPA 285 Flow Chart

Disclaimer Henry Company Tech-Talks are updated on a regular basis; it is the user s responsibility to obtain and to confirm the most recent version. Information contained in this Tech-Talk Bulletin may change without notice. For Additional Information Contact: Henry Product Support 1-800-486-1278 ProductSupport@henry.com