SECTION PARK NON-SEGREGATED BUS SPECIFICATION

Similar documents
SECTION METAL-ENCLOSED BUS MEDIUM VOLTAGE

BUSWAY LOW VOLTAGE (POW-R-WAY III) SECTION SECTION 16466

A. Section includes busway and fittings including plug-in units.

SECTION BUSWAYS

31-SDMS-03 REV. 01 SPECIFICATIONS FOR

SUGGESTED SPECIFICATION for Low Voltage (600V) Generator Paralleling Switchboard

UNIFIED FACILITIES GUIDE SPECIFICATIONS. Use for Southeast projects only **************************************************************************

SERIES 800 / 810 SPECIFICATION 15KV & 25KV PADMOUNTED LIQUID-INSULATED VACUUM LOAD INTERRUPTER ASSEMBLIES

Point Eight Power, Inc. Switchgear Specification Low Voltage UL 1558 Metal-Enclosed Switchgear

SECTION WIRE, CABLE AND BUSWAYS. A. This section specifies providing wire, cable and busways.

SECTION to 5000 AMPERE PLUG-IN AND FEEDER BUSWAYS - SPECTRA. A. Low-Voltage Plug-in Busway to 5000 ampere, 600 VAC

Essex County College - West Essex Campus Addition And Renovations dlb # / SECTION CABLE TRAYS FOR COMMUNICATIONS SYSTEMS

SECTION SECONDARY UNIT SUBSTATIONS

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

Customer Owned Meter Enclosures for Self-Contained Watthour Meters

37-SDMS-01 REV. 03 SPECIFICATIONS FOR

METAL ENCLOSED BUS SOLUTIONS

SECTION HEAT TRACING FOR PLUMBING PIPING

UNIFIED FACILITIES GUIDE SPECIFICATIONS

SECTION MOTOR CONTROL CENTER

33-SDMS-02 SPECIFICATIONS FOR

A. The work consists of furnishing a Chiller Noise Reduction System as listed in the specifications.

SECTION HEAT TRACING FOR PLUMBING PIPING

SECTION CHAIN-LINK FENCES AND GATES 02821/1

30-SDMS-01 SPECIFICATIONS FOR LOAD BREAK SWITCH

SECTION 16496A MTS MANUAL TRANSFER SWITCH (MANUAL CONTROL ONLY) Note to Spec Writer: { } Denotes EATON Feature reference number

SECTION GROUNDING

Important Considerations for Specifying MV Mining Switchgear Western Mining Electrical Association Edmonton, Canada June 13, 2008

SECTION ENCLOSED BUS ASSEMBLIES

MANUFACTURING TECHNICAL INSTRUCTIONS SAFETY Subject: DESIGN, MAINTENANCE AND INSPECTION OF SECONDARY ELECTRICAL DISTRIBUTION SYSTEMS

OVERHEAD SERVICES - SECONDARY

Houston First Corporation Package 1 SECTION MEDIUM VOLTAGE FUSED SWITCH INTERRUPTER

SECTION PART 1 GENERAL

Details of technical leaflets/write-up on various pieces of equipment.

GE EQUIPMENT CENTERS APPLICATION CONSIDERATIONS

SECTION SECONDARY UNIT SUBSTATIONS SECONDARY LESS THAN 1000 V

UNIFIED FACILITIES GUIDE SPECIFICATIONS

SECTION GENERAL MOTOR REQUIREMENTS FOR HVAC AND STEAM GENERATION EQUIPMENT

DESIGN GUIDELINES WIRING AND CONDUITS PAGE 1 of 7

UNDERGROUND SERVICES SECONDARY

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Medium Voltage Switchgear. Basis of Design.

SECTION ENCLOSED BUS ASSEMBLIES

Power Control Distribution Building (PCD) Technical Specification General Purpose (Non-Hazardous) Environment

a) Line and load compartments must be separated by a stable barrier.

PRIMARY UNIT SUBSTATIONS SECONDARY 1000 V AND ABOVE SECTION SECTION

1 29SEP03 ALL General update with miscellaneous changes in entire document.

A. Access doors and frames are part of an access door and frame allowance.

UFGS (August 2010) UNIFIED FACILITIES GUIDE SPECIFICATIONS

SECTION INTEGRATED POWER ASSEMBLY (IPA)

6. SECONDARY SERVICES (under 600 volts) 6.1 AVAILABILITY For the electrical characteristics of available secondary services see Section 3.4.

Power Zone Center. Your solution for power distribution and control systems

N-SERIES: NTH2700 SPECIFICATIONS Tubular Composite Top Hung Sliding Door System

CONTENTS. B. System Design and Performance Requirements

DISTRIBUTION TRANSFORMER SPECIFICATION #

SECTION OUTLET, PULL, AND JUNCTION BOXES

Power Control Distribution Building (PCD) Technical Specification Corrosive Environment

Standard of Practice - Campus Electrical Distribution System

SECTION ROOF ACCESSORIES

OPERATING PROCEDURE NO. 310

56-SDMS-01 REV. 01 SPECIFICATIONS FOR

CONSOLIDATED EDISON COMPANY OF NEW YORK, INC Van Dam Street Long Island City, NY ELECTRIC METER SHOP DEPARTMENT

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

Customer Owned Meter Enclosures for Self-Contained Watthour Meters

SECTION GROUNDING AND BONDING

Power Electronics, Inc. Packaged Equipment Center Standard Construction and Design Features

SPECIFICATION FOR SIMPLEX SWITCHBOARDS

SECTION DECORATIVE METAL RAILINGS

INDEX. Page SECTION 1.0: SCOPE Toronto Hydro Requirements Ontario Electrical Safety Code 1 SECTION 2.0: PURPOSE 1

SECTION GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY

A. All materials shall be tested and listed by an OSHA approved Nationally Recognized Testing Laboratory (NRTL).

42-SDMS-02 SPECIFICATIONS FOR FIBERGLASS REINFORCED LOW VOLTAGE SERVICE CABINET FOR 800A BULK CUSTOMERS

OKLAHOMA DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION FOR BRIDGE NAVIGATION LIGHTING

OVERHEAD SERVICES - RESIDENTIAL & GENERAL SERVICE. See Chapter 3, Section 3.01 for more information about point of entrance (POE).

SECTION HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS

WHITE PAPER The Criticality of Proactive Maintenance on Isolated Phase Bus Duct Systems

SECTION SUBSTATION BUS ASSEMBLIES ERGLE SUBSTATION

Flat Bank SERIES 05FB AND 07FB. Options CONSTRUCTION FEATURES EQUIPMENT OPTIONS PRODUCT DATA CLEAN-LINE TM SERIES 05FB/07FB PD-CLFB-03A JANUARY 2003

MATERIAL SPECIFICATION FOR LUMINAIRE RAISING AND LOWERING EQUIPMENT

Product Guide Specification

PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES

B. Provide liquid-filled secondary substation transformers as indicated on drawings.

SECTION MISCELLANEOUS METALS

LOW-VOLTAGE SERVICE ENTRANCE SWITCHBOARDS SECTION D

N-SERIES: NTH3500 SPECIFICATIONS Hollow Metal Sliding Door System

A. Provide a complete Distribution Panelboard system as indicated on the drawings, and as specified herein.

SECTION FACILITY LIGHTNING PROTECTION

Outdoor + Switchgear, Walk-in Equipment Buildings Low & Medium Voltage NEMA 3R

SECTION GROUNDING AND BONDING

Equipment Specifications Low Voltage. Active Harmonic Filter

*** Supercedes: BECO E and COM , , & ***

SECTION OVERHEAD CONDUCTOR RAIL

MATERIAL SPECIFICATION FOR HIGH PRESSURE SODIUM LUMINAIRES FOR UNDERPASS LIGHTING

Arc Resistant Switchgear & Integrated Factory Assembled Buildings

STANDARD SPECIFICATION FOR SIGNAL CABLE. A. This Specification provides for single and multi-conductor insulated and jacketed cable for

DMS CONDUIT EFFECTIVE DATE: APRIL

SECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES (24 Volt AC/DC or Less)

SECTION LOW-VOLTAGE TRANSFORMERS

A. This Section includes steel cable trays and accessories.

A. Basket Cable Tray: A fabricated structure consisting of wire mesh bottom and side rails.

6. SECONDARY SERVICES (under 600 volts) 6.1 AVAILABILITY For the electrical characteristics of available secondary services see Section 3.4.

Transcription:

Page 1 of 5 SECTION ------- PARK NON-SEGREGATED BUS SPECIFICATION 1.0 SCOPE 1.1. This specification describes assemblies of 600V, 5Kv and 15Kv non-segregated bus duct, which will be installed indoors and outdoors. 1.2. The manufacturer shall have a minimum of 5 years field experience with the equipment proposed. 2.0 CODES and STANDARDS 2.1. All codes and standards referenced in this specification shall be those in effect at the time of Purchase Order award. Permission for deviation from this specification and referenced codes and standards will not be allowed. 2.1.1. American National Standards Institute, Inc. (ANSI) 2.1.2. Institute of Electrical and Electronic Engineers (IEEE) 2.1.3. National Electrical Manufacturers Association (NEMA) 2.1.4. National Electrical Code (NEC) 2.2. It shall be the Seller s and/or Manufacture's responsibility to be, or to become, knowledgeable of the requirements of these Codes and Standards. Any changes or alterations to the equipment to make it meet the Codes and Standards requirements shall be at the expense of the Seller. 2.3. Whenever equipment, proposed by the Seller, cannot fully meet the requirements of this specification, such exceptions must be clearly stated by the Seller. No exceptions shall be allowed. 3.0 DETAILED TECHNICAL REQUIREMENTS 3.1. Basic Construction 3.1.1. The bus duct shall be completely metal-enclosed and weatherproof with pitched roof for outdoor applications. 3.1.2. The bus conductor shall be made of C110 copper. 3.1.3. 5Kv and 15Kv Design: Except at bolted termination's the bus bar shall be insulated with flame retardant, epoxy insulation applied by Park fluidized bed system. All bolted joints; expansion joints; and bus connections, factory or field; shall be insulated with removable boots. Taping is acceptable at transformer and equipment terminations. Removable boots shall be designed to overlap permanent insulation on each conductor in the connection. The length of overlap on each conductor shall not be less than 2 inches at expansion joints, and not less than

Page 2 of 5 1/2 at other connections. The insulation rating of bus joint, connection, and termination insulation shall be not less than the voltage rating of the equipment. 4.1.1. 600V Design: Bare bus is acceptable, but painted black. 4.1.1.a. OPTION for 600V: Except at bolted termination's the bus bar shall be insulated with flame retardant, epoxy insulation applied by Park fluidized bed system. All bolted joints; expansion joints; and bus connections, factory or field; shall be insulated with removable boots. Taping is acceptable at transformer and equipment terminations. Removable boots shall be designed to overlap permanent insulation on each conductor in the connection. The length of overlap on each conductor shall not be less than 2 inches at expansion joints, and not less than 1/2 at other connections. The insulation rating of bus joint, connection, and termination insulation shall be not less than the voltage rating of the equipment. 3.1.5. All bus bar connections shall be bolted, accomplished by bolts passing through the bus bar conductor capable of being torqued and locked in place to provide and maintain full and uniform pressure under all operation conditions. All bolted joints shall have silver to silver or tin to tin contact surfaces with minimum contact resistance. Provisions shall be made for bus expansion, to prevent undesirable or destructive mechanical strains in the bus supports and connections. Expansion joints shall be furnished where required. (Torque requirements in FT-LBS shall be furnished by the manufacturer). 3.1.6. The bus shall be installed with rigid, non-tracking, fire-resistant, and nonhydroscopic insulating supports capable of with standing the mechanical forces imposed by short-circuit currents equal to the momentary current. Park GPO-3 insulators shall be used. (Insulator Part# B1400, 600V Insert Part# B1401, 5Kv & 15Kv Insert Part# B1402 ) 3.1.7. The enclosure shall be aluminum with stainless steel hardware. The enclosure and joints shall be designed and sized to meet all the requirements of an equipment grounding conductor in accordance with NEC. This requires bonding jumpers and/or a separate ground bus be furnished. 3.1.8. The bus duct shall include all necessary Park flexible connectors and hardware to connect the bus duct to the auxiliary transformer and to the switchgear. Insulated cable or hard bus connection is not acceptable. 3.1.9. A fire resistant divider or barrier shall be provided at all points where the bus duct extends through the building wall. The barrier shall have a minimum rating of (3) three hours. 3.1.10. Suitable accessories and fittings shall be furnished on the bus duct to accommodate buyers hangers and supports. Required support point shall be designated on the bus duct drawings. 3.1.11. It shall be the bus duct Seller s responsibility to match the bus duct connection flanges to switchgear and transformers. If necessary, dimensions and details of the connecting equipment flange connections will be supplied to Seller by Buyer. 3.1.12. Space heaters rated 240 volts ac, operating at 120 volts ac, shall be provided in all outdoor bus duct to prevent condensation. The space heaters shall be completely factory wired with no exposed wiring inside the bus housing. Heaters shall be thermostatically controlled. The space heaters shall be supplied from and external source by Buyer. The entire circuit shall be wired to an accessible terminal block providing for a single connection of the external power source. Space heaters shall be accessible from the outside of the bus duct. A drip shield will be provided over the space heater opening to prevent entry of water into the enclosure.

Page 3 of 5 3.2. Finish 3.1.13. The bus enclosure shall be farbricated from aluminum not less than 1/8 inch thick. 3.1.14. Bus hardware shall be stainless steel for outdoor applications and zinc plated for indoor applications. 3.2.1. The bus duct enclosures shall be cleaned, primed and finish-powder coated in accordance with Park standard practice. 3.2.2. The finish coat shall be ANSI No. 61 - light gray. 3.3. Outdoor Bus Duct Supports 3.3.1. Support spans shall be 12 feet or less. 3.3.2. Supports shall be galvanized steel. 3.3.3. Supports over 10 feet tall shall be (Park Prt#DBSJ20) constructed with 12 X12 X3/8 wall steel tubing. Supports under 10 feet tall shall be (Park Prt#DBSJ10) constructed with 6 X6 X3/8 wall steel tubing. Supports may vary with material and size depending on site conditions. 3.3.4. Structures shall be galvanized by the hot dip process in accordance with ASTM A-123 except that all shapes shall receive 3.0 oz. of zinc per square foot of surface area. Structures are to be galvanized both inside and out after all cutting, punching, welding and cleaning have been completed. 3.3.5. Finished galvanized surfaces must be uniform in color, appearance and texture and must be free of excessive roughness, pimples, lumpiness and runs. 3.4. Indoor Bus Supports 4.0. BUS RATINGS 3.4.1. Indoor supports shall be (Park Prt# DBSJ111) constructed of galvanized steel and designed for hanging supports from building overhead steel. Support spans shall be 5 feet or less. 4.1.1. Bus Ratings 4.1.1.a. Bus duct shall be furnished with the following voltage ratings: 1. Nominal voltage: 480V rms 2. Rated maximum voltage: 600V rms 1 minute withstand voltage: 2.2 kv rms 4. Rated impulse withstand voltage: 10 kv peak 4.1.1.b. Bus duct shall be furnished with the following voltage ratings:

Page 4 of 5 1. Nominal voltage: 4.16 kv rms 2. Rated maximum voltage: 4.76 kv rms 1 minute withstand voltage: 19 kv rms 4. Rated impulse withstand voltage: 60 kv peak 4.1.1.c. 1. Nominal voltage: 13.2 kv rms 2. Rated maximum voltage: 15 kv rms 1 minute withstand voltage: 36 kv rms 4. Rated impulse withstand voltage: 95 kv peak 4.1.2. Bus duct shall be furnished with the following current and short circuit ratings: 1. Continuous rated current: 1,200 amps rms 1,600 amps rms 2,000 amps rms 2,500 amps rms 3,000 amps rms 3,200 amps rms 4,000 amps rms 4,500 amps rms 5,000 amps rms Other Sizes Available 2. Short-circuit withstand, Symmetrical: 25,000 amps or greater 5.0. ENGINEERING DATA REQUIREMENTS 5.1. All engineering data provided shall be for the equipment as specified and ordered. Engineering data, as listed below, shall be supplied to the Buyer. 5.2. Copies of factory standard tests shall be provided to Buyer. 5.3. All symbols used on drawings shall be in accordance with applicable ANSI standards. 5.4. Drawing Requirements Typical drawings are not acceptable unless they are revised to show only the equipment being furnished. Reproducible drawings for approval shall be supplied as follows: 5.4.1. Outline and Arrangement Drawings, completely dimensioned, showing:

Page 5 of 5 a. Dimensional Plan and Elevation, front view, other elevation views if pertinent, and shipping sections. b. Bus duct arrangement. c. Cross sectional view of bus bar arrangement, support blocks, and the totally-enclosed housing arrangement. d. Bus termination details. e. Location of space heaters and space heater wiring diagram indicating wiring terminal locations. f. Conductor joint connection details. g. Grounding connections. h. Weight of busway per foot. I. Location, size and of bus duct supports. J. Identification of all terminals, terminal blocks and wires. 5.4.3. Installation, Operating, and Maintenance Instructions Installation, operating, storage and maintenance instructions shall cover all equipment furnished. 6.0. APPROVED MANUFACTURERS 6.1. Park Electric Company, Detroit, MI, David Shillingburg Jr. 313-366-2200 7.0. INSPECTION AND TESTING 7.1. All standard factory tests shall be in full accordance with the latest applicable standards and the results shall be submitted to the Buyer. 7.2. Where any component has failed to pass any test, the Buyer shall be notified in writing of the nature of the failure and the corrective measures applied. 7.3. All equipment covered in this specification shall be subject to inspection and/or witnessed testing by the Buyer or his designated representative.