Performance Evaluation under the Actual Operation Condition of a Ground Source Multiheat Pump System

Similar documents
Measurement of COPs for Ground Source Heat Pump (GSHP) System in Heating and Cooling Mode

Comparative Heating Performances of Ground Source and Air Source Heat. Pump Systems for Residential Buildings in Shanghai

EXPERIMENT FOR VERIFICATION OF GROUND SOURCE HEAT PUMP USING THE DIRECT EXPANSION METHOD

Heating Performance with a Volume Ratio on 2-Stage Compressor

Performance Comparison of Air-source Heat Pumps Using Economizer Vapor Injection and Internal Heat Exchanger in Cold Regions

Heat exchanger performance of ground source heat pump by water cooling method

Thermal Performances Of Three Types Of Ground Heat Exchangers In Short-Time Period Of Operation

Research on Ground Source Heat Pump Design

Conversion Factors for Comparing the Performance of Variable Refrigerant Flow Systems

Performance Mapping for Variable Ductless Heat Pump Systems in Heating, Cooling and Defrost Operation

Investigation on A Ground Source Heat Pump System Integrated With Renewable Sources

Experimental Investigation of a Hermetic Scroll Expander-Generator

A Scroll Expander with Heating Structure and Their Systems

Long-Term Heating Test Using the Semi-open Loop Ground Source Heat Pump System

Experimental Study of a CO2 Thermal Battery for Simultaneous Cooling and Heating Applications

Fundamental Investigation Of Whole-Life Power Plant Performance For Enhanced Geothermal Systems

Using Simulation Model to Reduce System Design Time and Cost

Utilizing Heat Dump Capacity of a Small Pond Attached to Infloor Slab of a Net-Zero Energy House

Study on Ejector - Vapor Compression Hybrid Air Conditioning System Using Solar Energy

Welcome Everyone. Not Quite this kind! Geothermal Heat Pumps are a indirect solar heating system! Introduction to Geothermal

Application Of Oil Flooded Compression With Regeneration To A Packaged Heat Pump System

Introduction to Geothermal Comfort Systems in INDIA

An Integrated Solution for Commercial AC Chillers Using Variable Speed Scroll Compressors

Multi-Variable Optimisation Of Wet Vapour Organic Rankine Cycles With Twin-Screw Expanders

Experimental Investigation of Gas Engine Driven Heat Pump Used in Water Cooling

DEVELOPMENT OF A DESIGN AND PERFORMANCE PREDICTION TOOL FOR THE GROUND SOURCE HEAT PUMP SYSTEM

Performance Evaluation Of Thermally Activated Glass Fibre Reinforced Gypsum Building Equipped With Desiccant System

Solar-Assisted Space Heating of a Highly Insulated Energy Efficient House

Application of Near-Optimal Tower Control and Free Cooling on the Condenser Water Side for Optimization of Central Cooling Systems

Field Performance Measurements of VRF System with Subcooling Heat Exchanger

State of the Art of Air-source Heat Pump for Cold Regions

Enhancement of Heat Exchange Capacity of Ground Heat Exchangers by Injecting Water into Wells

Experimental Results on a New Prototype Packaged Heat Pump System Retrofitted with Oil Flooded Compression and Regeneration Technology

Experimental investigation of a Scroll unit used as a compressor and as an expander in a Heat Pump/ ORC reversible unit

Heat Pump With a Condenser Including Solid- Liquid Phase Change Material

Seasonal Energy Efficiency Rating Improvement Of Residential HVAC Systems Using A Low Power Inverter With A PSC Compressor

Low-Grade Waste Heat Recovery for Power Production using an Absorption-Rankine Cycle

Profile LFR-56 HELIOS. KOREA Republic of. Molten lead-bismuth eutectic

Study on Heat Exchange Characteristics for PHC Energy Piles

Application of Taguchi Robust Design Method for Energy Efficiency Ratio and Noise of Compressors

Temperature Control of Industrial Water Cooler using Hot-gas Bypass

CO 2 Transcritical Cycle for Ground Source Heat Pump

Economic Estimation of Heat Storage Type Geothermal Source Heat Pump System Applied in K-Ward Office Building

Two-Phase Distribution of R-134a in a Header of a Parallel Flow Heat Exchanger

Energy Optimization of an Installation of Reversible Geothermal Heat Pump

Initial Commissioning of a Water to Water GHP system in KIER

Experimental analysis of heat-pump integrated with solar energy

The Benefit of Variable-Speed Turbine Operation for Low Temperature Thermal Energy Power Recovery

Secondary Loop System for Automotiv HVAC Units Under Different Climatic Conditions

Flow Mal-Distribution In Micro-channel Evaporator

Ground Source Heat Pumps

Study of Performance Improvement of Air Conditioning using Various Heat Recovery Techniques

Ground-source Heat Pumps State of the Art

Employment of Multiphase (Two Phase) Thermal Pump in Absorption Refrigeration System

Measurement and Simulation of Startup and Shut Down of Heat Pumps

Performance Characteristics and Mapping for a Variable-Speed Ductless Heat Pump

Characteristics of Energy Consumption by building type of a U.S. Navy Installation in Hot and Humid Climate

HEAT RECOVERY IN MULTI-GHP (GAS-DRIVEN HEAT PUMP) SYSTEM

Design and Experiments of a Solar Low-temperature Hot Water Floor Radiant. Heating System 1

Enhancement of CO2 Refrigeration Cycle Using an Ejector: 1D Analysis

The impact of hot and cold storages on a solar absorption cooling system for an office building

Normalized Effect Of Condenser Fouling And Refrigerant Charge On Performance Of Vapor Compression Air Conditioning Systems

Compressor Performance Comparison When Using R134 and R1234YF as Working Fluids

Recent U. S. R&D results from IEA HPP Annex 41

The Part-Load Efficiency Benefit of Oil-Free, High- Speed, Direct-Drive Centrifugal Compressors

Scientific Journal Impact Factor: (ISRA), Impact Factor: [Son, 3(10): October, 2014] ISSN:

Performance enhancement of a photovoltaic thermal (PVT) and ground-source heat pump system

Opportunities and Limitations of Building Precooling

The Impact of Evaporator Fouling on the Performance of Packaged Air Conditioners

Analysis of Fuel Cell Driven Ground Source Heat Pump Systems in Community Buildings

Modeling and simulation of a reclaimed water source heat pump system based on TRANSYS 1

M. Karagiorgas, M. Tsagouris, K. Galatis BONAIR Meletitiki, Greece. A. Botzios-Valaskakis CRES, Greece ABSTRACT

Experimental Study on Thermal Performance Improvement of Envelop Integrated with Phase Change Material in Air-conditioned Room

Available online at ScienceDirect. Energy Procedia 78 (2015 )

Design And Manufacturing Of An Accelerated Lifetime Tester For Non-Metallic Materials Used For Compressor Valve Sealing Elements

Vapor injected heat pump using non-azeotropic mixture R32/R1234ze(E) for low temperature ambient

Performance investigation of multiple-tube ground heat exchangers for ground-source heat pump

DOE Webinar Residential Geothermal Heat Pump Retrofits

Research on single hole heat transfer power of ground source heat pump system

Mathematical Modeling of Basic Parts of Heating Systems with Alternative Power Sources

A new application of an old idea

*Corresponding authors. Tel.: x415, address: (N. Zhu)

THERMAL ENERGY ANALYSIS OF SOLAR POWERED VAPOUR ABSORPTION COOLING SYSTEM

Geothermal Heat Pump Systems Being Green by using the Ground

Economic Model Predictive Control for Variable Refrigerant Systems

Selection of 3X400 Ton Centrifugal Water Chillers for Central AIC Plant --- A Case Study

Heat Pump Assisted Solar Thermal System

Guide. Heat Pump Boilers. Information. Issue Ten >

Assessing the feasibility of highdensity subsurface heat extraction in urban areas

Two-Phase-Flow Turbines as Stand-Alone Throttle Replacement Units in Large Ton Centrifugal Chiller Installations

Thermodynamic Analysis of Ground Source Heat Pump for Space Heating Using R-22

Modelica-Based Heat Pump Model for Transient and Steady-State Simulation Using Low-GWP Refrigerants Paper 2264

HVAC INTEGRATED CONTROL FOR ENERGY SAVING AND COMFORT ENHANCEMENT vahid Vakiloroaya

A Study on Engineering Application of Solar Heating System Assisted by Heat Pump

Component-Based Vapor Compression Simulation Tool With Integrated Multi-Objective Optimization Routines

Study And Experimental Analysis Of Horizontal Ground Source Heat Pump System

Bifluid Geothermal System New Generation

Introduction to Geothermal Comfort Systems in INDIA

Influencing Factors on Ground Heat Balance of GSHP System Xiaohong Zhang1, a *, Zehua Liu2,b, Chao Zhang3,c and Long Ma4,d

Numerical and analytical analysis of groundwater influence on the pile ground heat exchanger with cast-in spiral coils

Transcription:

Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2010 Performance Evaluation under the Actual Operation Condition of a Ground Source Multiheat Pump System Young-Man Jeong Pusan National University Jaekeun Lee Pusan National University Donghyuk Lee LG Electronics Inkyu Kim LG Electronics Follow this and additional works at: http://docs.lib.purdue.edu/iracc Jeong, Young-Man; Lee, Jaekeun; Lee, Donghyuk; and Kim, Inkyu, "Performance Evaluation under the Actual Operation Condition of a Ground Source Multi-heat Pump System" (2010). International Refrigeration and Air Conditioning Conference. Paper 1051. http://docs.lib.purdue.edu/iracc/1051 This document has been made available through Purdue e-pubs, a service of the Purdue University Libraries. Please contact epubs@purdue.edu for additional information. Complete proceedings may be acquired in print and on CD-ROM directly from the Ray W. Herrick Laboratories at https://engineering.purdue.edu/ Herrick/Events/orderlit.html

2209, Page 1 Performance Evaluation under the Actual Operation Condition of a Ground Source Multi-heat Pump System Youngman Jeong 1, Jaekeun Lee 2 *, Donghyuk Lee 3, Inkyu Kim 4 1 School of Mechanical Engineering, Pusan National University Busan, Korea +82-55-510-3055, jym@pusan.ac.kr 2 School of Mechanical Engineering, Pusan National University Busan, Korea +82-55-510-2455, jklee@pusan.ac.kr 3 Air-conditioning Laboratory, LG Electronics Changwon City, Gyeongnam, Korea +82-55-260-3861, ldhpsm@lge.com 4 CAC Engineering Team, LG Electronics Seoul, Korea +82-2-3777-2939, ikkim@lge.com * Corresponding Author ABSTRACT This paper presents the performance of a water-to-refrigerant type ground source multi-heat pump (GSHP) system installed in a school building in Korea. The evaluation of the performance has been conducted under the actual operating conditions of the GSHP system. Ten units with the capacity of 10 HP each were installed in the building. Also, a closed vertical typed-ground heat exchanger with 24 boreholes of 175 m in depth was constructed for the GSHP system. For analyzing the performance of the GSHP system, we monitored various operating conditions, including the outdoor temperature, the ground temperature, and the water temperature of inlet and outlet of the ground heat exchanger. Simultaneously, the capacity and the input power were evaluated for determining the performance of the GSHP system. The average cooling coefficient of performance (COP) of the heat pump was found to be 8.3 at 65% partial load condition, while the overall system COP was found to be 5.9. The average heating COP of the heat pump was found to be 5.1 at 45% partial load condition, while the overall system COP was found to be 4.2. 1. INTRODUCTION Concerns about application of the GSHP systems increase due to the shortage of fossil fuels and environmental pollution problems all over the world (Zhaho et al., 2002). The GSHP system which consists of ground heat exchangers (GHE) and heat pumps is recognized to be outstanding cooling and heating system. In the heating system, the GSHP absorbs heat from the ground and uses it for heating the house or building. In the cooling system, heat is absorbed from the conditioning space and transferred to the earth through the GHE (Sohn et al., 2005). The

2209, Page 2 merit of this system is less consumption of energy for operating than an source heat pump (ASHP) system. Because the ground temperature that acts heat sink and heat source of heat pump is more stable than outdoor temperature, the GSHP system has superior performance. Main disadvantage of the GSHP is the higher initial capital cost for installation (Hepbasli, A., 2002 and Hwang et al., 2007). Performance of the GSHP system is affected by the thermal conductivity and temperature of ground, the type of the GHE and the heat pump. The GSHP performance is studied by Hepbasli et al. (2003), Zhao (2004), Nagano et al. (2006) and Michopoulos et al. (2007). The water-to-water type heat pump systems are usually adopted for GSHP systems. It supplies energy as cold and hot water made by heat pump to whole building by the fan coil unit (FCU). A water-to-refrigerant type heat pump system has been developed for the GSHP lately. In the water-to-refrigerant type heat pump system, the GHE is the same as the water-to-water type, but the indoor units exchange heat by to refrigerant. In the water-to-water type heat exchanger, it needs for a circulating pump to send water to the FCU, the maintenance is regularly needed due to corrosion of water pipe and leakage problem. However, in the water-torefrigerant type, the circulating pump is not needed to send water to the FCU, so that the cost for the pump input power and its maintenance can be saved. In this study, the GSHP system of the water-to-refrigerant type is installed in a school building. Cooling and heating performance of heat pump itself and the whole system is estimated. And we measure the ground temperature variation when the GSHP system is operating. 2. EXPERIMENTAL 2.1 Experimental apparatus The GSHP system is installed in a building at Pusan National University to analyze its technical and economical aspects under the actually operating condition. The building is constructed with two stories below and six floors above the ground. The GSHP system covers the first and second floors, and the total floor area is 1,193 m 2. 10 units (LRW-N2900D, LG Electronics, Korea) which have the capacity of 29 kw are established in this building for the GSHP system. Figure 1 shows an overview of the water-to-refrigerant type heat pump system with 4 indoor units and the specifications of the components were summarized in Table 1. The GSHP system of the water-to-refrigerant type has higher efficiency with the compressor of inverter type and it has a good performance in partial load. The GHE is the closed vertical type which has 24 boreholes with 175 m in depth. The building where the GSHP was installed has the offices, the seminar rooms and the professor rooms. Water to refrigerant heat exchanger Expansion valve Refrigerant to heat exchanger Thermocouples Circulating pump 1.5 m 2.5 m Compressor 4 way valve Room 1 Room 2 Room 3 Room 4 Ground heat exchanger 24 U-tubes, 175 m in depth Heat pump system Figure 1: System diagram of the ground source multi-heat pump

2209, Page 3 Table 1: Specification of the components consisting of the GSHP system Main circuit Component Specification Ground coupling circuit Heat pump circuit (Manufacturer: LG Electronics; model: LRW-N2900D) Ground heat exchanger Circulating pump Heat exchanger Compressors Indoor unit Vertical-closed U-bend type Borehole diameter: 150 mm Internal diameter of U-bends: 42 mm Borehole depth: 175 m, Material: polyethylene Volumetric flow rate: 45~130 m 3 /h Power:7.5kW, Speed: 1750 rpm Capacity: 32.6 kw Type: Plate heat exchanger Type: Rotary Refrigerant: R-410A 1. Inverter type: 4.2 hp (3.1 kw) 2. Fixed type: 4.2 hp (3.1 kw) Manufacturer: LG Electronics Model:LRD-N725T Cooling capacity: 7.2 kw To analyze the performance of the heat pump, we selected 1 unit of the GSHP which is connected in the office. Figure 1 shows the schematic diagram of the system to analyze the performance of the GSHP system and the ground temperatures. Each office has one indoor unit (LRD-N725T, LG Electronics) for the GSHP system. One office area is 43.2 m 2 and the total office area is 172.8 m 2. The temperatures of the ground corresponding to the depth are measured with T-type thermocouple. The inlet and outlet temperatures of the circulating water through the heat pump are measured with the resistance temperature detector (RTD Pt-100). The indoor temperatures and humidity to evaluate the cooling load are measured with thermocouple and hygrometer (EL-2, LASCAR). The power consumption of the system (i.e. the electric power input to the compressor, water circulating pump and the fan of indoor unit) is measured by a wattmeter (MWT-340S, Hanguk micronics). In addition, the power consumption of the compressor for the performance of the heat pump is measured by another wattmeter (WT1600, Yokogawa). All measured quantities are regularly recorded in every 1 minute with the data acquisition system. 2.2 Data analysis Generally performance of the GSHP is represented by the coefficient of performance (COP). COP of heat pump in the cooling and heating mode is calculated by the following equation (1). COP Q / (1) hp W c Where Q is the space cooling or heating load, W c is the power input to the compressor. The overall coefficient of performance of the system is calculated by COP overall (2) Q/( Wc Wp Wf ) Where W p is the power input to the circulating pump of the GHE, W f is the power input to the fan of indoor unit. Where Q the space cooling or heating load can be calculated as follows Q m h h ) (3) ( o, i,

m 2209, Page 4 V (4) m is the mass flow rate of, V is the volumetric flow rata of, is the density of. Where And h o, is the enthalpy of outlet, h i, is the enthalpy of inlet in the heat exchanger of the indoor unit. 3. RESULTS AND DISCUSION When absorption or extraction of thermal energy from the ground is accomplished by using the GHE, Performance of the GSHP is influenced by the thermal properties of the ground. Therefore, we installed thermocouples under the ground to analyze thermal diffusion property of the GHE in Figure 1. Figure 2 shows the ground temperature variations corresponding to the depth ranging from the surface to 20 m. The ground temperature at 2.5 m in depth is greatly dependent on the outdoor temperature. The ground temperature at 5m in depth is also affected by outdoor temperature. Variation of temperature is stable below 10 m in depth. The average temperature of circulating water is 20.2 during the operating of the system in the cooling mode. And it is 15.3 during the operating of the system in the heating mode. Figure 3 shows the monthly operating load of the heat pump. It is observed that the system was in operation about 9 h/day from May, 2007 to June, 2008. It was cooling season from May to September and cooling load was the highest in August. It was heating season from November to March and heating load was the highest in January. There was no load in April so the heat pumps were not operated. The operating load of the heat pump was average 65% in August when cooling load was the highest during cooling period. And it was average 45% in January when heating load was the highest during heating period. There was a difference according to partial load of the heat pump in performance of heat pump. In general, it is announced that good performance of heat pumps are obtained at low partial load. In this research, we estimated the performance of GSHP in January (heating period) and August (cooling period) when the load of heat pump was the highest. Figure 4 shows performance of cooling and heating. The performance of GSHP is calculated using equation (3) and it is measured from the indoor units. The cooling load of these space is 19.1 kw in average, which is 65% partial load compared to full load (29 kw) of the GSHP. Average COP of heat pump is 8.3, while average COP of whole system is 5.9. The heating load of these space is 14.7 kw in average, which is 45% partial load compared to full load (32.6 kw) of the GSHP. Average COP of heat pump is 5.1, while average COP of whole system is 4.2. Figure 2: The monthly average ground temperature, outdoor temperature and circulating water temperature variations from March, 2007 to December, 2008

2209, Page 5 Figure 3: The monthly average operating load of the ground source multi-heat pump from May, 2007 to June, 2008 Figure 4: The cooling performance (partial load 65%) and the heating performance (partial load 45%) of the ground source multi-heat pump

2209, Page 6 4. CONCLUSIONS In this study, the GSHP system of the water-to-refrigerant type is installed in a school building. Performance of heat pump itself and the whole system is estimated. And we measure the ground temperature variation when the GSHP system is operating. (1) We installed thermocouples under the ground to analyze thermal diffusion property of the GHE. As the result, the ground temperature at 2.5 m in depth is greatly dependent on the outdoor temperature. The ground temperature at 5 m in depth is also affected by outdoor temperature. Variation of temperature is stable below 10 m in depth. (2) We estimated the performance of GSHP in January (heating period) and August (cooling period) when the load of heat pump was the highest. The cooling load of space is 19.1 kw in average, which is 65% partial load compared to full load (29 kw) of the GSHP. Average COP of heat pump is 8.3, while average COP of whole system is 5.9. The heating load of space is 14.7 kw in average, which is 45% partial load compared to full load (32.6 kw) of the GSHP. Average COP of heat pump is 5.1, while average COP of whole system is 4.2. REFERENCES Hepbasli, A., 2002, Performance evaluation of a vertical ground-source heat pump system in Izmir, Turky, Int. J. Energy Res., vol. 26: p.1121-1139. Hepbasli, A., Akdemir, O., Hancioglu, E., 2003, Experimental study of a closed loop vertical ground source heat pump system, Energy Conversion and Management, vol. 44: p.527-548. Hwang, Y., Lee, J., Jeong, Y., Koo, K., Lee, D., Kim, I., Jin, S., Kim, S.H., 2009, Cooling performance of a vertical ground-coupled heat pump system installed in a school building, Renewable Energy, vol. 34: p. 578-582. Michopoulos, A., Bozis, D., Kikidis, K., Kyriakis, N.A., 2007, Three-years operation experience of a ground source heat pump system in Northern Greece, Energy and Building, vol. 39: p.328-334. Nagano, K., Katsura, T., Takeda, S., 2006, Development of a design and performance prediction tool for the ground source heat pump system, Applied Thermal Engineering, vol. 26: p.1578-1592. Sohn, B.H., Cho, C., Shin, H., An, H., 2005, Cooling and heating performance evaluation of a GSHP system, Airconditioning and Refrigeration Engineering, vol. 17, no. 1: p.71-81. Zhaho, P.C., Zhao, G.L., Zhang, C.L., 2002, Experimental research on geothermal heat pump system with nonazeotropic working fluids, App lied Thermal Engineering, vol. 22: p.1749-1761. Zhao, L., 2004, Experimental evaluation of a non-azeotropic working fluid for geothermal heat pump system, Energy Conversion and Management, vol. 44: p.1369-1378. ACKNOWLEDGEMENT This research achieved with under supports of Korea Energy Management Corporation (KEMCO), LG Electronics and Department of Facilities in Pusan National University.