SCHOOL DISTRICT PALM BEACH COUNTY BUILDING DEPARTMENT PLAN REVIEW CHECK LIST -- STRUCTURAL

Similar documents
STRUCTURAL DESIGN CRITERIA TABLE OF CONTENTS

STRUCTURAL DESIGN CRITERIA TABLE OF CONTENTS

STRUCTURAL MASONRY SPECIAL INSPECTOR. Study Guide

Stone and Masonry Veneer

Purpose: The procedure establishes the requirements for Threshold Buildings.

Table 3. Detailed Comparison of Structural Provisions of IRC 2000 and 1997 NEHRP (Continued)

Statement of Special Inspection Requirements

C. SPECIAL INSPECTOR S RESPONSIBILITIES

1 Exam Prep Placing Reinforcing Bars Tabs and Highlights

Mechanical Engineer of Record: (Smoke Control Systems Only) Name & License Company. Others: Responsible Party Name & License Company

Statement of Special Inspections Michigan Building Code 2012 (MBC 2012)

Chapter 2 Notation and Terminology

DESIGN STANDARDS WASHINGTON UNIVERSITY SCHOOL OF MEDICINE

Tolerances for Concrete Construction. Tolerances for Concrete Construction. Tolerance 6/16/2015

THRESHOLD INSPECTION SPECIAL INSPECTION PLAN. Evangel Temple Addition

PLANNING DEPARTMENT 701 OCEAN STREET, 4 TH FLOOR, SANTA CRUZ, CA (831) FAX: (831)

Chapter 2 QUALITY ASSURANCE

SPECIAL INSPECTION AND OBSERVATION PROGRAM City of Walnut Creek Building Division. Project Address:

STATEMENT OF SPECIAL INSPECTION FORM

SPECIAL INSPECTION AND TESTING AGREEMENT

Structural Tests and Special Inspections Form. Inspection of Fabricators (1704.2)

Project Address: Name of Person Completing Form:

Originally Issued: 03/31/2017 Revised: 03/15/2018 Valid Through: 03/31/2018

EXAMPLE STATEMENT OF SPECIAL INSPECTIONS (SSI)

SPECIAL INSPECTION AGREEMENT

Statement of Special Inspections

RETAINING WALL LEVEL BACKFILL

Supplemental Plan Check List for Concrete Special Moment Resisting Frame

Building Department Informational Handout

Lintel Tables Design Notes and Limitations

1. Cast-in-place concrete is specified in Section

WILTON MANORS, Island City 2020 WILTON DRIVE, WILTON MANORS, FLORIDA 33305

Structural System. Design Criteria Fire Resistance Concrete designed for 2 HR rating (worst case) Geotechnical Report Allowable Bearing Capacity

Crossroads at Westfields Building II

SECTION 415 REINFORCING FOR CONCRETE

OVERALL STRUCTURAL SYSTEM

Proposed Revisions to Part 2, Sections 2.13 to Draft DEVELOPMENT AND SPLICES OF REINFORCEMENT SECTION 2.13 DEVELOPMENT REQUIREMENTS

SECTION ORCHESTRA PIT FILLER

1.02 STANDARD REFERENCES: The following standard specifications shall apply to the Work of this Section as indicated:

POST FRAME BUILDING STANDARDS

ORDINANCE NO * * * THE BOARD OF SUPERVISORS OF THE COUNTY OF SAN JOAQUIN, STATE OF CALIFORNIA, DOES ORDAIN AS FOLLOWS:

Anchor bolts ASTM F1554, Gr. 36 Wide flange beams ASTM A992, Fy = 50 ksi Misc. structural steel ASTM A36, Fy = 36 ksi

Supplemental Plan Correction Sheet for LA Residential Code Prescriptive Design (2011 LARC)

REINFORCED CONCRETE MASONRY SECTION

SECTION VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS

CITY OF COOPER CITY BUILDING DEPARTMENT

List of Required Structural Tests & Special Inspections CBC

SECTION UNIT MASONRY

2012 VIRGINIA TECH SCHEDULE OF SPECIAL INSPECTIONS

INSPECTION REQUIREMENTS: FOUNDATIONS

Section REINFORCING STEEL

R CODE CHANGE PROPOSAL FORM (See instructions on page 2)

Statement of Special Inspections

ESR-2036 Reissued May 1, 2013 This report is subject to renewal June 1, 2015.

HYBRID CONCRETE MASONRY CONSTRUCTION DETAILS. TEK 3-3B Construction (2009) Related TEK: 14-9A

GARAGE MAIN FLOOR PLAN

NCMA TEK RESIDENTIAL DETAILS FOR HIGH WIND AREAS. TEK 5-11 Details (2003)

SPECIAL INSPECTION AGREEMENT FORM

HILLSBOROUGH TOWNSHIP CODE ENFORCEMENT

Pulaski County, Virginia

Supplemental Plan Correction Sheet for LA Residential Code Prescriptive Design (2014 LARC)

Work Order Number *************************************************************************** SECTION C20 STAIRS 02/18

SUBJECT: NEW 2000 INTERNATIONAL RESIDENTIAL CODE (IRC) DATE:

SECTION MANUAL FOUR FOLD DOORS MODEL 38 DECORATIVE PANEL DESIGN

SECTION VIBRATION CONTROLS FOR HVAC PIPING AND EQUIPMENT

Table of Contents 2. Structural Systems.4 Foundations.4 Floor System...4 Columns..5 Lateral System...5

SECTION VIBRATION CONTROLS FOR PLUMBING PIPING AND EQUIPMENT

HAMPTON ROADS AREA STATEMENT OF SPECIAL INSPECTIONS

SPECIAL INSPECTION AGREEMENT

ISSUE A Code Change # 2 Class 3 and Class 4 Buildings

Hilton Baltimore Convention Center Hotel Western Podium

STRUCTURAL STEEL FRAMING

CBC SECTION/TABLE NUMBER NEW -CHANGE COMMENTARY. X Flexible and Rigid definitions removed and found in ASCE 7-10

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

DIVISION: CONCRETE SECTION: CONCRETE ACCESSORIES SECTION: REINFORCING STEEL REPORT HOLDER: TENDON SYSTEMS, LLC

Research Evaluation of Single Lift Grouting in Concrete Masonry Wall Panels

DIVISION: METALS SECTION: STEEL DECKING REPORT HOLDER: EPIC METALS CORPORATION 11 TALBOT AVENUE RANKIN, PENNSYLVANIA 15104

TECHNICAL REPORT 1. Structural Concepts / Structural Existing Conditions. Penn State Hershey Medical Center Children s Hospital. Hershey, Pennsylvania

REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT:

Structural Observation Program Based on the 2013 California Building Code (CBC) Chapter 17 Published 2013

SECTION VIBRATION CONTROLS FOR HVAC PIPING AND EQUIPMENT

Supplemental Plan Check List for Unreinforced Masonry (URM) Retrofit

SECTION EXTERIOR ATHLETIC LIGHTING

Statement of Special Inspections

CHAPTER 3 BUILDINGS WITH WOOD FRAMED EXTERIOR WALLS 301 SCOPE

Minimum Requirements For One & Two Family Structures FBC 6 th Edition (2017)

GARAGE MAIN FLOOR PLAN

ICC/NSSA STANDARD FOR THE DESIGN AND CONSTRUCTION OF STORM SHELTERS ICC

Multi-Institutional Academic Health Science & Research Center Evansville, IN

Signage Code. H101.2 Signs exempt from permits. The following signs are exempt from the requirements to obtain a permit before erection:

DIVISION: CONCRETE SECTION: CONCRETE ACCESSORIES SECTION: REINFORCING STEEL REPORT HOLDER: PEIKKO GROUP, INC.

CHAPTER 19 CONCRETE. Italics are used for text within Sections 1903 through 1905 of this code to indicate provisions that differ from ACI 318.

STATE UNIVERSITY CONSTRUCTION FUND. UNIVERSITY CON DIRECTIVE 5-1 Issue date: October 2014

ACCESSORY STRUCTURES (Garages/Sheds) BUILDING AND ZONING REQUIREMENTS (REVISED 4/21/16)

Student Services & Classroom Addition SECTION VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS

Custom 22' x 40' - 16' Tall Garage Plan #g227 By SDS-CAD Specialized Design Systems

SPECIAL INSPECTION PROGRAM GUIDE

Supplemental Plan Check List for Concrete Special Moment Resisting Frame

Simplified Building Schematic for Typical Floor (Levels 9 through 22):

Residential Deck Safety, Construction and Repair. Juneau Permit Center, 4 th Floor Marine View Center,(907) February 2016

Transcription:

SCHOOL DISTRICT PALM BEACH COUNTY BUILDING DEPARTMENT PLAN REVIEW CHECK LIST -- STRUCTURAL 3300 SUMMIT BOULEVARD WEST PALM BEACH, FLORIDA 33406 TEL (561) 688-7687 FAX (561) 688-7654 http://www.palmbeach.k12.fl.us/fm/bd/index.htm PROJECT NAME: DATE PROJECT NUMBER: REVIEWER The intent of this checklist is to act as a tool for the District Plan Reviewers to review construction plans and specification of projects submitted for permitting by the Building Department. Architects and Engineers are encouraged to use this document as a tool to prepare construction plans and specifications for District projects. The codes references in the checklist are Florida Building Code (FBC), District Design Criteria (DDC), District Master Specification (DMS), National Fire Prevention Association Codes (NFPA), American Society of Civil Engineers (ASCE), American Concrete Institute (ACI), Florida Statutes (FS) current editions, and. Occupational Safety and Health Administration (OSHA). Phase I Schematic Design (Not Required) Phase II Design Development (Not Required) STRUCTURAL "Phase III" Plans (Final Construction Documents) General Plans are signed and sealed All documentation submitted Index represents what is submitted Plans match the specifications Plans comply with the District Design Criteria 471.025, FS Structural Plans Submittal Documents submittal. Verify that the structural plans, Phase III, documents are dated, signed and sealed by the professional engineer of record. Verify that the plans are sealed with a metal-type impression seal. The use of a rubber stamp seal is prohibited. Verify that the signature of the professional engineer of record is an original handwritten signature. Copy of signature is not allowed. Verify if any building or the whole facility has been designated as an EHPA, (Enhanced Hurricane Protection Area). FBCB 104.2.2 FAC 61G15-23.001 FAC 61G15-23.002 7/1/04 Structural Page 1 of 1

Verify that two copies of the Geotechnical Engineer s Soil Report was submitted. Verify that the Geotechnical Engineer s Soil Report is dated signed and sealed by the geotechnical engineer in responsible charge. FBCB 104.2.2 Enhanced Hurricane Protection Areas (EHPA) Verify that the EHPAs are being considered as threshold building. 553.71(7), F.S. Threshold Buildings Verify if any buildings classify as a Threshold Building. A Threshold Building as any building satisfying any of the following Greater than 3 stories. 50 feet in height. Has an assembly occupancy classification that exceeds 5,000 SF in area and occupant content greater than 500 persons. Verify that all plans for the building which are required to be signed by the architect or engineer of record contain a statement that To the best of the architect or engineer s knowledge, the plans and specifications comply with the applicable minimum building codes fire-safety standards as determined by the local authority in accordance with this chapter and chapter 633. Verify that all shoring and reshoring procedures, plans and details be submitted to the enforcement agency for recordkeeping. Threshold Inspection Plan. Verify that two copies of the Inspection have been submitted with Phase III documents. Verify that the Inspection Plans have been dated, signed and sealed by the professional engineer in responsible charge. Verify that the Inspection Plan include the name of the facility, project number, and name of building or buildings. A generic, non-specific Inspection Plan shall be revised and submitted to the Building Department. The Inspection Plan shall be made specifically for the building or buildings considered as Threshold Buildings. 553.71(7), F.S. FBCB 202 553.79, F.S. 3.13.2.4.12 FBCB 105.13.4.4 553.7(c), F.S. FBCB 104.2.2 Codes Verify that the structural design comply with the following codes. Florida Building Code FBCB Minimum Design Loads for Buildings and Other Structures, ASCE 7-98, Chapter 6. 7/1/04 Structural Page 2 of 2

Verify that the wind load importance for educational facilities is 1.15. Building Code Requirements for Structural Concrete. ACI 318-02. ACI 530/ASCE 5/TMS 402-02 ACI 533/ASCE 6/TMS 602-02 SPECIAL ASSEMBLY OCCUPANCIES Auditoriums. Verify that the Assumed values for the following loads are clearly noted on construction documents submitted for approval: Head block beams Loft block beams Gridiron, walk-on Loading and fly galleries Railings, channels or similar battens intended for mounting theatrical lighting Pinrails and locking rails FBCB 403.2.3.2 Foundation and Ground Floor Plan Foundation Plan Verify that all footings are marked. Verify that the marked footings are included in the footing Verify that all columns are marked. Verify that the marked columns are included in the column Verify that the marked masonry walls are included in the masonry Footing Schedule. Verify that the scheduled footings are included in the foundation plan.. Verify that the area of the footing reinforcement comply with the ACI 318-99, Section minimum area of steel reinforcement as required by Section 7.12. Verify that the maximum spacing for the footing reinforcement does not exceed the lesser of three times the thickness or 18 in. Column Schedule Concrete Columns Verify that the scheduled columns are identified in the foundation plan. Verify that the longitudinal reinforcement comply with the requirement for minimum area of steel. Verify that the size of the ties comply with the requirement for minimum tie size. 10.5.4 ACI 318-99, Section 10.5.4 7.10.5.1 7/1/04 Structural Page 3 of 3

All nonprestressed bars shall be enclosed by lateral ties, at least: o No. 3 in size for longitudinal bars No. 10 and smaller o No. 4 in size for No.11, No.14, No.18, and bundled longitudinal bars. o Deformed welded wire fabric of equivalent area shall be permitted. Verify that the vertical spacing of ties do not exceed: o 16-longitudinal bar diameter o 48-tie bar or wire reinforcement o The least dimension of the column. Verify that the ties are arranged so that no vertical bar shall be farther than 6 inches clear on each side along the tie from such a laterally supported bar. Verify the length of the lap splices for the column dowels with the 7.10.5.1 7.10.5.2 5.10.5.3 FBCB 01, 2 nd. Ed. 104.2.1 vertical reinforcing steel. Steel Columns. Base Plate and Anchor Bolts Check the anchor bolt size. Check the embedment of the anchor bolts. Masonry Schedule. Verify that the scheduled masonry walls are identified in the foundation plan. Lap splices. Verify the length of the lap splices for the dowels and for the vertical reinforcing steel. The splice shall be a minimum of 48-bar diameter. Dowels. Verify the embedment length for the vertical Joint Verify the gage of the horizontal joint Joint Verify the spacing of the horizontal joint Second Floor Framing Plan Columns. Verify that all columns are marked. Verify that the marked columns are included in the column Concrete Beams. Verify that all beams are marked. Verify that the marked beams are included in the beam schedule or have been individually detailed. Soffit Beams. Verify that all soffit beams are marked. Verify that the marked soffit beams are included in the soffit beam Beam Schedule Verify that all the beams comply with the minimum area of steel required by ACI.318-02 Stirrups: 7/1/04 Structural Page 4 of 4

Verify the spacing of the stirrups. The spacing of shear reinforcement placed perpendicular to axis of member shall not exceed d/2 in nonprestressed members and 0.75h in prestressed members, nor 24 inches. When Vs exceeds 4 times the square root of f c times b w x d, maximum spacings given in 11.5.4. and 11.5.4.2 shall be reduced by one-half. Beam Reinforcing Bar Diagram Verify that the marks for reinforcing steel correspond with the size of the reinforcing steel on the beam schedule. Soffit Beam Schedule Verify the area of steel (reinforcing bars) provided as shear friction ACI 318-02, Section 11.5.4.1 ACI 318-02, Section 11.5.4.3 Verify the load values of the shear friction. Soffit Beam Reinforcing Bar Diagram Verify the length of the shear friction reinforcing bars. Roof Framing Plan Verify that all steel beams are marked. Verify that all steel joists are marked. FBCB. 104.2.104.2.1 Verify that all concrete beams are marked. Verify that all tie beams are marked. Verify that the joist bracing is not continuous through an expansion joint. Sections and Details Fixed Ladders. Verify that the perpendicular clearance between fixed ladder rungs, cleats, and steps, and any obstruction behind the ladder is at least 7 inches. OSHA, Tittle 29, Part 1926.1053(13) Scoreboard Scoreboard design complies with the following. Wind loads shall be as per ASCE 7-98, Chapter 6, and Minimum Design Loads for Buildings and Other Structures. Verify that the size of the poles comply with ASCE 7-98, Chapter 6 wind loads. Note that usually W6x6x15 steel poles are not strong enough to resist the wind loads as per ASC7-98. Verify that the embedment length has been engineered for the actual soil conditions. Note that usually the embedment length has been figured as if the pole will be embedded in rock. District Comment District Comment 7/1/04 Structural Page 5 of 5

Specifications Section 03200 Concrete Reinforcement. Verify that ASTM designation and the Grade of Steel for the reinforcing steel is specified. Usually ASTM A-615, Grade 60. Verify that ASTM designation and the Welded Steel Wire Fabric is specified. Usually it is ASTM A-185. Section 03300 Cast in-place Concrete. Verify that the design complies with ACI 318-02 Building Code Requirements for Reinforced Concrete. Section 04100 Mortar and Grout. Verify that the design complies with ACI 533/ASCE 5/TMS 402-02 Building Code Requirements for Masonry Structures. Verify that the design complies with ACI 533/ASCE 6/TMS 602-02 Specifications for Masonry Structures. Section 04300 Unit Masonry System. Verify that the design complies with ACI 533/ASCE 5/TMS 402-02 Building Code Requirements for Masonry Structures. Verify that the design comply with ACI 533/ASCE 6/TMS 602-02 Specifications for Masonry Structures. Verify that the concrete masonry units comply with ASTM C 90. FBCB 2104.1 Section 4340 Reinforced Unit Masonry System. Verify that the design complies with ACI 533/ASCE 5/TMS 402-02 Building Code Requirements for Masonry Structures. Verify that the design complies with ACI 533/ASCE 6/TMS 602-02 Specifications for Masonry Structures. Verify that the concrete masonry units comply with ASTM C 90. FBCB 2104.1 Section 05120 Structural Steel. Verify that the ASTM designation number for the structural steel is specified. Verify that the ASTM designation number for the structural steel indicated in the plans is the same as the one in the project manual specifications. Section 05400 Cold Formed Metal Framing. Verify that the specifications for the cold formed follows the Master Specifications of the SDPBC. Section 13120 Pre-Engineered Buildings. Verify that the design of the pre-engineered building complies with FBC and the wind loads comply with ASCE 7-98, Minimum Design Loads for Buildings and Other Structures, Chapter 6. Section 10350 Flagpoles. Verify that the design of the metal flagpole complies with NAAMM FP-1001, Specification for Design Loads of Metal Flagpoles. Section 10532 Aluminum Walkway Covers. Verify that the design of the aluminum walkway cover complies with FBCB 01,2 nd Ed. and wind loads comply with ASCE 7-98, Minimum Design Loads for Buildings and Other Structures, Chapter 6. District requirement FBCB 1606.1.1(5) 7/1/04 Structural Page 6 of 6

Specifications Specifications match the District Master Specs Specifications match the plans Specifications follow the District Design Criteria Specification follow the Educational Specifications s s s s Other 7/1/04 Structural Page 7 of 7