Duke Energy Catawba Nuclear Station Solving Cavitation Problems

Similar documents
Fisher Cavitrol III One, Two, and Three Stage Trims

INTRODUCTION. Ringo Válvulas (RV) is located in the industrial city of. Zaragoza, Spain. Since its establishment, RV has designed

CHOKE VALVES. CC-Series, API 6A Certified Severe Service X[iks]-trim Application Choke Valve. API-6A License Number / 6A-1929

Effective solutions for preventing control valve noise.

COMPUTATIONAL FLUID DYNAMICS IN EQUIPMENT DESIGN AND FAILURE ANALYSIS

4.2 DEVELOPMENT OF FUEL TEST LOOP IN HANARO

Observations from Several Condition Assessments of Prestressed Concrete Cylinder Pipe used at Energy Generation Facilities

VALVE SELECTION GUIDE FOR THE HYDROPOWER INDUSTRY

Nuclear Valve Overview

Product of our comprehensive range of valves for the energy & process industries

KEYSTONE RMI DUBEX BUTTERFLY VALVE AWWA FACE-TO-FACE

Water Quality Specification for Power Supplies

DESIGN AND OPERATION OF POROUS METAL CROSSFLOW MICROFILTERS

Module 9 : Sewage And Storm water Pumping Stations. Lecture 11 : Sewage And Storm water Pumping Stations

Power Recovery Turbines

Nuclear Service Valves

Turbine Bypass. Systems

TOP Pre-engineered Fiberglass Pump Station

Wastewater Treatment WHERE VALVES ARE USED

Masoneilan * Series Control Valve

AMCOT COOLING TOWER CORPORATION LRC-H & LRC-LNS CROSS FLOW COOLING TOWER OPERATIONS AND MAINTAINENCE MANUAL

Tube support plate clogging up of French PWR steam generators

COMMERCIAL / INDUSTRIAL COOLING TOWER SIDE STREAM FILTER SYSTEMS

Pump Division MNR MND. Absorber Recirculation Pumps. Bulletin PS (E)

Complete flow control

Advanced Grit Removal Technology

Printing Version: for optimal viewing set the print to A3 and print two pages of the catalogue (including this one) on each sheet.

The Ecopure RL Abatement System

TOPIC: KNOWLEDGE: K1.01 [2.5/2.5]

Engineered Hot Water Systems. For your specific requirements

CHEMICAL INJECTION METHODS Pros & Cons

80 exam difficulty level problems Covers Mechanical PE Thermal & Fluids exam topics Written in exam format Also includes detailed solutions

YOUR VALVE SPECIALIST

Screening, Definition: The unit involved is called a screen.

VLM10 In-line Vortex Mass Flow Meter

OpTB TM Trunnion Ball Valve

Water Well Screens and Well Efficiencies Designing an Efficient Well

Energy Requirements for Drip Irrigation of Tomatoes in North Florida 1

Hygiene Water Temperature Control. Experience is Central to Every Solution. The Brain. Process Water Temperature Control. Emech

Status Update 18MW ILC Beam Dump Design

2. (a) How do you classify water turbines? (b) Define and explain different efficiencies of a water turbine. [8+8]

Selection and Installation of a Full- Flow Condensate Filtration System

Preface to the First Edition Preface to the Second Edition. Acknowledgment

level control gates Waterman Industries of Egypt WATERMAN

Condenser Performance Solutions

Fisher NotchFlo DST Control Valve

SIMPACK - MODEL DEVELOPMENT PACKAGE FOR POWER PLANTS

Our Cyprus strategic alliance associates presentation TAPROGGE

Nessie Pumps type PAH 2/4/6.3, PAH 10/12.5, PAH 20/25/32 and PAH 50/63/70/80/100

SANITARY CONTROL VALVES & REGULATORS

Controlling NOx and other Engine Emissions

The Superior Jet Aeration System

Fluid Mechanics. The Energy Equation [7] Dr. Mohammad N. Almasri

Troubleshooting Piping Systems

Overhaul Issues on Vertical Pumps

FloMax Air Atomizing Nozzles: High Efficiency Nozzles Offer Tight Control of Drop Size and Spray Coverage, Provide Precise Performance.

sanitary control valves & regulators

Pneumatic control and on/off valves for thermoelectric plants

SAF Filters. The automatic self-cleaning filter - suitable for more applications than ever.

vapor control systems Quality, Dependability, Service. Reputation Built on Valve Concepts, Inc. com A Cashco, Inc.

Geothermal Power Plant

G L Pumps. SSV Series. Vertical Multistage Pumps. New!! Expanded Range Capable of Flows up to 650 GPM!! Goulds Pumps.

Filtration and Separation Systems

VENTURI FLOWMETERS. Your First Choice in Intelligent Flow Management...

B. System Design and Performance Requirements

3 Steps to Better Steam Temperature Control Proven Strategies to Minimize Thermal Stress and Tube Leaks

Pump Performance Curves and Matching a Pump to a Piping System

Size Matters: Picking the Right Size of Piping System Components. April 13, 2017

Pump Performance Curves and Matching a Pump to a Piping System

HEATMAX. Mechanical Installation and Commissioning Instructions HEATMAX

Pumping System Vibration

The Prescriptive Promise

Lenntech. Tel Fax / Marley MS Cooling Tower /

ROTARY KILN COMBUSTION SYSTEMS

Rugged, reliable and efficient sump pumps... your assurance of a dry basement!

SPECIFYING PUMPS WHY DO PUMPS FAIL.

Severe Casing and Impeller Erosion : Analysis and Resolution

Wood Products Energy Savings Guide

CHILLED WATER DISTRIBUTION SYSTEM

MA-I & MA-IU. Mechanical Atomizing Desuperheater

25fh DOE/NRC NUCLEAR AIR CLEANING AND TREATMENT CONFERENCE

Nessie Pumps type PAH 2/4/6.3, 10/ /32 and PAH 50/63/70/80

Application of COMSOL Pipe Flow Module to Develop a High Flux Isotope Reactor System Loop Model

Pump System Optimization Checklist

PUMPING SOLUTIONS FOR LANDSCAPE

Turbo Machines Pumps and Turbines ME 268

Specifying Pumps Why Do Pumps Fail.

THE VERY BEST IN HIGH PRESSURE WATER JETTING SYSTEMS INNOVATION THROUGH EXPERIENCE.

u m p a n d u m p i n g y s t e m p e c i a l i s t s i n c e

HYDROPOWER INDUSTRY SOLUTIONS

TECHNICAL MANUAL TEH-375A. Pump & System Curve Data for Centrifugal Pump Selection and Application

COMPRESSED AIR SYSTEM DESIGNS BEGIN WITH THE DEMANDS

Pressure Booster System. Hya-Eco VP. Type Series Booklet

6. Repulp Spray System (Optional) Polyweb Urethane Screen Panels

Pump Division BSV BCV. Concrete Volute Pumps. Bulletin PS-40-1 (E)

Pump Division BSV BCV. Concrete Volute Pumps. Bulletin PS-40-1a (E)

AP1000 The PWR Revisited

Atlas Copco. ZM Oil-free multistage centrifugal pressure and vacuum blowers

flow rates filtration degrees water for cleaning minimum operating pressure micron less than 1% of the total flow

VALVE SOLUTIONS GUIDE FOR THE POWER INDUSTRY

Transcription:

Duke Energy Catawba Nuclear Station Solving Cavitation Problems................................................... By Deane Beck, CCI; John R. Deyton Jr., Duke Energy Presented at AUG January 8-12, 2007 22591 Avenida Empresa Rancho Santa Margarita, CA 92688 949.858.1877 Fax 949.858.1878 ccivalve.com 872 11/06 2006 CCI DRAG is a registered trademark of CCI.

Duke Energy Catawba Nuclear Solving Cavitation Problems By Denae Beck, CCI USA; John Deyton, Jr., Duke Energy Presented at AUG January 8-12, 2007 Catawba Nuclear Station is a two unit 1,145 MWe each PWR nuclear plant located in Clover, South Carolina. The plant design employs forced air Cooling Towers taking make-up service water from Lake Wylie. Cooling Tower basin water level is monitored with a sensor to signal valve position to maintain basin water level. The original plant configuration had make-up water tied from the Low Pressure service water system to Cooling Tower basins through a 2000 ft. long sub-grade 30 in. pipe using two electro-hydraulic operated butterfly valves for isolation and throttling service. Since the 1985 initial start-up, Catawba Unit 1 and subsequently Unit 2 experienced severe cavitation and erosion damage of two each Cooling Tower basin level butterfly control valves when used for make-up flow throttling. These valves trended to produce the highest level of corrective work orders of all valves located in the raw water system and exhibited excessive cost for repair. Cavitation in the butterfly control valves was severe enough to cause easily detected ground vibration. Cavitation induced valve oscillation resulted in mechanical damage of linkage between the valve and actuator which required repair or replacement every outage. Unsuccessful attempts were made to reinforce actuator to valve connection to tolerate vibration. As part of a year 2001 plant design enhancement to address biological formation and fouling in the subject Cooling Tower basin level make-up line, Duke Energy elected to abandon in place, the make-up line and establish a replacement cross tie connection. The new cross tie connection was decided to be located between the existing Condenser Circulating Water system and Low Pressure service water system for Cooling Tower basin level make-up purposes. This new configuration eliminated the high cost of repairing or replacing 2000 ft. of sub-grade level pipe and allowed reduction of basin water level control valve quantity from two to one for each Unit. Existing electro-hydraulic actuated butterfly valves were located adjacent to the Cooling Towers. Relocation of the upgrade motor operated control valves to a convenient, remote area where a new cross tie connection would be established was considered and approved. Raw water supplied from Lake Wylie has above average dissolved solids measuring 53 ppm and suspended solids ranging from 8-175 ppm. Service water pump discharge screens are designed limit particulate by-pass size to less than 1/8 in. A motor operated control valve specifically designed to tolerate Catawba raw water conditions to mitigate clogging and seat damage, and to prevent development of micro biological growth through design elimination of stagnant flow regions was required. Pressure differential across the two systems to be connected, tight shut off and improved system response to compensate for anticipated thermal lag from valve relocation of 1,500 ft. greater distance was also carefully considered. ROOT CAUSE ANALYSIS The service conditions for this application (Table 1) shows that the pressure drop across the valve to be in the range of 25-35 psid, which was not considered too severe. However, the Cavitation Index σ in the range of 2.16 to 1.74 for a butterfly valve is severe enough to cause cavitation. Another cause was the excessive trim exit velocity that peaks at a value of 73 ft/sec, which is quite high in a large service water line. Also, the amount of horsepower available in the exit jet was computed and found to be over 300. This is an enormous energy available to excite the valve and other pipeline components. The solution to this problem is to reduce the amount of trim exit velocity and the available horsepower in the jet exit by an order of magnitude. 2 Duke Energy Catawba Nuclear Station Solving Cavitation Problems 872 2006 CCI. All rights reserved.

Table 1: Service Conditions Fluid Water Critical Pressure psi G 3194 Critical Temperature deg F 705.5 Condition Max Normal Max X-Conn Min Fluid State Water Water Water Liquid Vol Flow Rate gpm(us) 22000 22000 15000 Mass Flow Rate W, lbm/hr 10,959,951 10,959,951 7,472,694 Inlet Pressure psi G 39.6 32.6 47.8 Outlet Pressure psi G 14.8 14.8 12.3 Pressure Differential psi 24.8 17.8 35.5 Inlet Temperature deg F 90.0 90.0 90.0 Density lbm/ft3 62.12 62.12 62.12 Vapor Pressure psi G -14.0-14.0-14.0 Service Cavitation Index 2.16 2.62 1.74 Required Flow Capacity Cv 6354.4 6814.6 4035.1 Trim Exit Velocity of BFV V, ft/sec 60.8 51.5 72.8 Power in Jet Exit hp 318.0 228.2 310.8 With 4 stage DRAG V, ft/sec 19.8 16.8 23.7 Power in Jet Exit hp 33.7 24.3 32.9 2006 CCI. All rights reserved. 872 Duke Energy Catawba Nuclear Station Solving Cavitation Problems 3

SOLUTION After lengthy evaluation of alternative solutions, Duke selected CCI s DRAG control valve with Limitorque brand modulating motor operator to address valve cavitation wear and system response anomalies. To correct conditions of cavitation and erosion, the new control valve was specified as a 24 x 24 angle type with four pressure let down stages in multi-path, radial configuration (Figure 1). The velocity in the jet exit was reduced to a maximum of 24 ft/sec and the jet exit horsepower to 34 which is less by a factor of 10 (Table 1). Valve plug size is 22 in. with large 26 in. stroke that optimizes mechanical rangeability and thus provides fine loop response to compensate for increased distance in control element location. CCI s control valve passages were specifically engineered to accommodate Catawba NPP raw water solids and conditions without clogging. The passages were carefully designed so that any encrustation may be mechanically removed by a rotary tool (Figure 2). All stainless steel construction was specified by the plant for improved environmental compatibility and elimination of coating repair costs (Figure 3). CONCLUSION Since the 2001 installation of DRAG control valves in Catawba NPP s raw water system, no valve related failures or clogging have occurred, dispelling concern that a radial path control valve may not accommodate debris particles suspended in medium. The new configuration has proven to eliminate vibration. Valve life extension is attributed to a decrease in trim exit flow velocities and resulting reduction in jet exit horsepower acting as an aging mechanism on the original valve. Figure 2: Simulated Rotary tool cleaning of disk passages Figure 1: 4 Stage DRAG trim with large passages, complete disk stack 4 Duke Energy Catawba Nuclear Station Solving Cavitation Problems 872 2006 CCI. All rights reserved.

Figure 3: Complete valve undergoing shop test, section view of valve. Note all stainless steel construction. 2006 CCI. All rights reserved. 872 Duke Energy Catawba Nuclear Station Solving Cavitation Problems 5