Fire Testing Laboratory TEST REPORT FOR THERMORY USA, LLC Wilmette Avenue, Suite 208 Wilmette, IL 60091

Similar documents
Fire Testing Laboratory TEST REPORT

REPORT NUMBER: SAT-001A ORIGINAL ISSUE DATE: March 13, 2017 REVISED DATE:

REPORT NUMBER: SAT-002A ORIGINAL ISSUE DATE: August 16, 2017 REVISED DATE:

REPORT NUMBER: SAT-001A ORIGINAL ISSUE DATE: December 29, 2011 REVISED DATE:

ASTM E84-05 SURFACE BURNING CHARACTERISTICS OF BUILDING MATERIALS

REPORT NUMBER: SAT-001D ORIGINAL ISSUE DATE: February 24, 2012 REVISED DATE:

REPORT NUMBER: SAT-001A ORIGINAL ISSUE DATE: December 18, 2012 REVISED DATE:

REPORT NUMBER: SAT-001A ORIGINAL ISSUE DATE: April 30, 2013 REVISED DATE:

REPORT NUMBER: SAT-001A ORIGINAL ISSUE DATE: February 29, 2016 REVISED DATE:

REPORT NUMBER: SAT-001A Rev 1 ORIGINAL ISSUE DATE: November 16, 2010 REVISED DATE: June 20, 2011

REPORT NUMBER: SAT-001A ORIGINAL ISSUE DATE: March 13, 2013 REVISED DATE:

REPORT NUMBER: SAT-001B ORIGINAL ISSUE DATE: October 30, 2014 REVISED DATE:

REPORT NUMBER: SAT-004A ORIGINAL ISSUE DATE: April 13, 2017 REVISED DATE:

TEST REPORT. Acoustical Surfaces, Inc. ASTM E84-04 SURFACE BURNING CHARACTERISTICS OF BUILDING MATERIALS. We Identify and S.T.O.P. Your Noise Problem

TEST REPORT. Acoustical Surfaces, Inc. ASTM E84-04 SURFACE BURNING CHARACTERISTICS OF BUILDING MATERIALS. We Identify and S.T.O.P. Your Noise Problem

TEST REPORT. Acoustical Surfaces, Inc. ASTM E84-03 SURFACE BURNING CHARACTERISTICS. We Identify and S.T.O.P. Your Noise Problem.

TEST REPORT. Acoustical Surfaces, Inc. ASTM E84-03 SURFACE BURNING CHARACTERISTICS. We Identify and S.T.O.P. Your Noise Problems

FUNDERMAX GMBH LETTER OF RESULTS

SouTHwEsT RESEARCH INSTITUTE

ASTM E84-09 SURFACE BURNING CHARACTERISTICS OF BUILDING MATERIALS

Fire Testing Laboratory

SHOWER WALLS S.A. DE C.V. FIRE TEST REPORT

DICKSON COATINGS FIRE TEST REPORT

RENDERED TO. CastleRock Building Products Incorporated P.O. Box 1258 Meridian, ID USA 83680

DICKSON COATINGS FIRE TEST REPORT

REPORT NUMBER: SAT-005 ORIGINAL ISSUE DATE: September 14, 2012 REVISED DATE: N/A

Product Test Summaries

Product Test Summaries

TEST REPORT. Contact No: SAMPLE NOT DRAWN BY OUR LABORATORY. THE RESULTS RELATE ONLY TO THE ITEMS TESTED

FIRE RATINGS. European Oak

REPORT NUMBER: SAT-001 ORIGINAL ISSUE DATE: March 23, 2010 REVISED DATE: NA

calibrated gas flows from the room burner.

Rose Brand Acoustical Test Report for: Rhapsody Fabric Panels

UL 1715 TESTING FOR DURABLIS ON JETBOARD WITH ELFOAM P200 AND MAGNUM BOARD WITH ELFORM P200 VTEC # TESTED: MARCH 11, 2015

ASTM E Fire Tests of Building Construction and Materials* Protective Structures, Ltd. Bullet-Resistant FRP Panel

FIRE RESISTANCE TESTS OF BRICK VENEER / WOOD FRAME WALLS J. GREGG BORCHELT

ASTM E 648 Test Method. 5/8" Walnut Engineered Wood Flooring

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: CHEMICAL BROTHERS INTERNATIONAL, LLC

Product Test Summaries

NFPA Committee on Fire Tests

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: CHEMICAL BROTHERS INTERNATIONAL, LLC

Report to: Plumberex Specialty Products, Inc. Pipe Insulation and Fire Safety

Product Test Summaries Nichiha Fiber Cement Products Sierra Premium Boards

Product Test Summaries

Rose Brand Acoustical Test Report for: 64" IFR 22 oz. Encore. 100% Fullness Pleated Panel

1.0 INTRODUCTION 2.0 DESCRIPTION OF TEST APPARATUS AND PROCEDURE

Flame Spread Performance of Wood Products Used for Interior Finish

Report on First Revision June 2014 NFPA 5000

Combustible Exterior Wall Cladding Systems: An ICC Perspective

Gold Bond BRAND Gypsum Sheathing

Test Summaries: AWP 1818 & 3030

SOUTH AFRICAN NATIONAL STANDARD

High Strength LITE Family Of Products

DRAFT - MOCA STANDARD for Fiber-Reinforced Magnesium Cement Board

REPORT HOLDER: R.L. ADAMS PLASTICS, INC CROSSROADS COMMERCE PARKWAY WYOMING, MICHIGAN EVALUATION SUBJECT: POLYCORE BRAND INSULATION

CODE COMPLIANCE, STRENGTH AND SAVINGS IN ONE PANEL

Non-combustible fiber cement board

Phenolic Exterior Wall Cladding

Burtin Polymer Laboratories 2 SwRI Project No e[1]

The Importance of Building Envelope Performance

Copyright Materials. John Buddy Showalter, PE VP, Technology Transfer American Wood Council

Use of Coatings to Improve Fire Resistance of Wood

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: FIBER-CEMENT SIDING REPORT HOLDER: TAKTL, LLC

PERFORMANCE EVALUATION TEST REPORT. Rendered to: CBT SUPPLY, INC. / D.B.A. SMARTDESKS

Inspecta-Shield Fire Retardant

International Code Council. ICC XX Public Input Agenda based on input received on Initial Draft

MEETING FIRE CODE WITH ORIENTED STRAND BOARD

Guide Specification SECTION DUCT INSULATION

Thermasheath -3. Insulation for the Building Envelope ROOF WALL SPECIALTY

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: BASF CORPORATION (RIGID PU SYSTEMS)

BS :2005 test on a Kingspan Benchmark External Wall Insulation System

Standard Test Method for Surface Burning Characteristics of Building Materials 1

Report on Spread of Flame and Burning Brand Performance of Generic Installations

July 23, 2010 PARTIES INTERESTED IN REFLECTIVE FOIL INSULATION

Trusted ICC ES DIVISION: 07 LTD. PLASTI FAB CANADAA PLASTISPAN. Look. Conformity! Evaluation. ICC-ES Evaluation

Test Report. Prepared For: Mr. Simone Furiato Ebrille S.r.l Strada Canelli, 53/a Nizza Monferrato (Asti)-Italy

Commissioning of a Modular Steiner Tunnel

Section Roof/Ceiling Thermal Insulation

Fire Retardants and Truss Design. Overview

Recent Considerations of New UL1703 Method. Dwayne Sloan

INTERIOR FINISHES CHAPTER 8

Robert S. Kiefer (ext ) James F. Smith (ext )

FM APPROVED. FIRE PERFORMANCE Differences Between Elastomeric and Polyethylene/Polyolefin Insulations

Deer Ridge Consulting, Inc.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: RHINO LININGS CORPORATION

Surface Flammability, Smoke and Toxic Gas Generation of "3M Polyurethane Adhesive Sealant 550 Fast Cure"

PROPOSAL BALLOT DUE BY: Wednesday, September 2, 2009

Surface Flammability, Smoke and Toxic Gas Generation of "3M Scotch-Weld Acrylic Adhesive DP8410NS Green"

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: ELASTOCHEM SPECIALTY CHEMICALS, INC.

SOUTH AFRICAN NATIONAL STANDARD

2007 FLORIDA BUILDING CODE TEST PROTOCOLS HVHZ (TAS)

Polystyrene beads designated Neopor F5 Pro, F2200, F2300, F2400, F5300, F5300 Plus, F5200 Plus, KF2200, KF2300, KF2300S, KF2400

14104 ORANGE AVENUE, PARAMOUNT, CALIFORNIA TELEPHONE (562) FAX (562) Website: AQLramtech.

Image courtesy of KTGY, Inc. ENGINEERED FOR FIRE CODE COMPLIANCE AND DESIGN FLEXIBILITY

Image courtesy of KTGY, Inc. ENGINEERED FOR FIRE CODE COMPLIANCE AND DESIGN FLEXIBILITY

Thermasheath -3. Insulation for the Building Envelope ROOF WALL SPECIALTY

Design No. M507. Design No. M507

Surface Flammability, Smoke and Toxic Gas Generation of "3M Polyurethane Adhesive Sealant 560"

Transcription:

Fire Testing Laboratory Testing Laboratory TL-216 TEST REPORT Page 1 of 5 FOR THERMORY USA, LLC 1213 Wilmette Avenue, Suite 208 Wilmette, IL 60091 Standard Test Method for Surface Burning Characteristics of Building Materials ASTM E84 12a Test Report No: FH-2403 Assignment No: H-977 Test Date: 05/09/2013 Report Date: 05/09/2013 Subject Material: 0.79" x 5.9" T.M. Ash Decking and 1.02" x 5.7" T.M. Ash Decking Prepared by: Michael J. Rizzo Test Engineer Reviewed by: Robert J. Menchetti Director, Laboratory Facilities and Testing Services The results reported in this document apply to specific samples submitted for measurement. No responsibility is assumed for performance of any other specimen. The laboratory s test report in no way constitutes or implies product certification, approval or endorsement by this laboratory. This report may not be reproduced, except in full, without the written approval of the laboratory. 1650 Military Road Buffalo, NY 14217-1198 (716) 873-9750 Fax (716) 873-9753 www.ngctestingservices.com

Page 2 of 5 INTRODUCTION: This report presents the results of specimens tested in accordance with the requirements of ASTM E84-12a Standard Test Method for Surface Burning Characteristics of Building Materials. This test method is also published under the designations ANSI/UL 723, NFPA 255, and UBC 8-1(42-1). The purpose of this test method is to determine the relative behavior of the material by observing the flame spread along the specimen. Flame spread and smoke developed index are reported. However, there is not necessarily a relationship between these two measurements. This standard is used to measure and describe the response of materials, products, or assemblies to heat and flame under controlled laboratory conditions. It should not alone be used for fire hazard or fire risk assessment of the materials, products, or assemblies under actual fire conditions. MATERIAL TESTED: Material submitted by Thermory USA, of Wilmette, IL was identified by the client as: 0.79" x 5.9" T.M. Ash Decking 1.02" x 5.7" T.M. Ash Decking The material was received, in good condition, by NGC Testing Services on April 30, 2013. The material was submitted as nominally 95 in. long boards; twelve (12) boards were submitted for each sample material. From the boards submitted, NGCTS personnel constructed (3) test specimen decks for each sample material, per ASTM Practice E2579. The specimen decks were constructed on May 8, 2013. MOUNTING METHOD: The specimen decks were placed end-to-end, directly on the tunnel ledges, and butted tightly together, to achieve the required 24 ft. length. No additional support was required. Non-combustible, fiber-reinforced cement board (1/4 in. thick) was placed over the specimen decks as lid protection.

Page 3 of 5 TEST RESULTS: The test results, computed on the basis of observed flame front advance and electronic smoke density measurements are presented in the table below. The reported flame spread and smoke developed indices, as presented below, are the computed comparison to the standard calibration materials mineral fiber-reinforced cement board and select grade red oak flooring. The cement board is used to establish relative 0 values for flame spread and smoke developed; red oak decks are used to establish relative 100 values for flame spread and smoke developed. CALCULATED CALCULATED TEST NO. MATERIAL TESTED SIDE EXPOSED SUPPORT FLAME SPREAD SMOKE DEVELOPED 1 0.79" x 5.9" T.M. Ash Decking Symmetrical Self Supporting 36.85 246.91 2 1.02" x 5.7" T.M. Ash Decking Symmetrical Self Supporting 36.83 85.52 FLAME SPREAD SMOKE DEVELOPED MATERIAL TESTED SIDE EXPOSED SUPPORT INDEX * INDEX* RED OAK FLOORING Finished Self Supporting 100 100 REINFORCED CEMENT BOARD Symmetrical Self Supporting 0 0 1 0.79" x 5.9" T.M. Ash Decking Symmetrical Self Supporting 35 250 2 1.02" x 5.7" T.M. Ash Decking Symmetrical Self Supporting 35 85 CLASSIFICATION FSI SDI * Flame Spread / Smoke Developed Index is the result (or the CLASS "A" 0-25 0-450 average of the results of multiple tests), rounded to the nearest CLASS "B" 26-75 0-450 multiple of 5. Smoke developed results in excess of 200 are CLASS "C" 76-200 0-450 rounded to the nearest multiple of 50. 0.79" x 5.9" T.M. Ash Decking 1.02" x 5.7" T.M. Ash Decking FLAME SPREAD INDEX 35 FLAME SPREAD INDEX 35 SMOKE DEVELOPED INDEX 250 SMOKE DEVELOPED INDEX 85 OBSERVATIONS: 0.79" x 5.9" T.M. Ash Decking: The test specimen exhibited steady ignition at 00:32 (min:sec). The flame front reached a maximum distance of 9.08 feet, achieved at 09:54 (min:sec). After the ignition flame was extinguished, the test specimen continued to flame and was manually extinguished. Once the test specimen was cooled and removed from the furnace, it was observed to have a char length of 9 feet and was discolored to 24 feet. 1.02" x 5.7" T.M. Ash Decking: The test specimen exhibited steady ignition at 00:51 (min:sec). The flame front reached a maximum distance of 11.98 feet, achieved at 09:46 (min:sec). After the ignition flame was extinguished, the test specimen briefly continued to flame before self-extinguishing. Once the test specimen was cooled and removed from the furnace, it was observed to have a char length of 10 feet and was discolored to 24 feet.

Page 4 of 5 The following data sheets are actual printouts of the computerized data system which monitors the tunnel furnace. The sheets contain all calibration and specimen data needed to calculate the test results.

Page 5 of 5