596TW kcmil Type 13, 3M Brand Composite Conductor Compression Connector Qualification - Tensile, Sustained Load, and High-temperature Sustained Load

Similar documents
477 kcmil, 3M Brand Composite Conductor Mechanical Properties, Volume 1 Tensile and Stress-Strain Tests

Room-temperature Creep. 3M Company Purchase Order NEETRAC Project Number:

Merrimack and Suwannee ACSS/TW/HS285 Conductor Stress-Strain Tests. Southwire Company

Testing of THERMOLIGN Dead-End. For. Prepared by: Robert Whapham Preformed Line Products, Principal Investigator

CTC Lisbon ACCC Conductor Stress-Strain, Clamp Slip, and Compression Fitting Tensile Tests, Modification 1 Lamifil Comments

Test Report on 3M ACCR 477-T16 Conductor Returned from Xcel Riverside Line after 13 Years of Service in Minneapolis, MN

Kinectrics North America Inc. Report No.: K RC-0001-R01 November 4, 2005

TENSILE TEST SUMMARY- DRAKE ACCC/TW

Composite Conductor. Al-Zr Alloy Wire. Thermal Aging Behavior and Lifetime Modeling for Aluminum- Zirconium Alloy used in ACCR. Technical Information

P A (1.1) load or stress. elongation or strain

Thermo-Mechanical Conductor & Dead-End Testing ACCC Drake

1.103 CIVIL ENGINEERING MATERIALS LABORATORY (1-2-3) Dr. J.T. Germaine Spring 2004 PROPERTIES OF HEAT TREATED STEEL

ACCR. More Amps. More Confidence. Glenmar E. Cambri, REE Senior Applications Engineer

TIME Group Inc. ISO9001 International Quality Certificate. Highway and Bridge Testing Machine

Connectors The Weak Link

TI Typical HDPE raw material and pipe test methods EDITION 0607 PAGE 1/10

Increasing the capacity of existing transmission lines by re-conductoring using ACSS HTLS conductors

POWERTECH LABS INC. CONNECTABILITY TESTING OF COPPER AND ALUMINUM WIRING, PHASE 2: Current Cycling Tests Mechanical Connectors PROJECT PL-00236

Sag-tension Calculations

SERVO-HYDRAULIC UNIVERSAL TESTING MACHINE SERIES A

CHAPTER 4 EXPERIMENTAL ANALYSIS FOR A 2 IN, SCHEDULE 10 PIPE

Electromechanical Creep Testing Machines

SMU 2113 ENGINEERING SCIENCE. PART 1 Introduction to Mechanics of Materials and Structures

Mechanical Testing at UCSB

SHORT CIRCUIT PERFORMANCE TEST ON 1020 kcmil ACCC/TW CONDUCTOR FOR COMPOSITE TECHNOLOGY CORPORATION

Creep testing of AMBEX AAC anchoring capsules

FINAL REPORT: CONNECTION STRENGTH TESTING TENSAR GEOGRIDS WITHIN MESA STANDARD BLOCKS AND MESA STANDARD CONNECTORS

Servo-hydraulic Universal Testing Machine HUT Type B

SECTION PARK NON-SEGREGATED BUS SPECIFICATION

SOLARLOK BREEZE Junction Box

SECTION CHAIN-LINK FENCES AND GATES 02821/1

Cold Shrink EPDM Tubes Connector Insulators 8420 Series

Servo Hydraulic Universal Testing Machine. SHT4000G Series. Configuration

TESTING ELASTOMERIC CONCRETE

ME 354, MECHANICS OF MATERIALS LAB CREEP

CEEN Behavior & Properties of Engineering Materials Laboratory Experiment No. 3 Tension, Shear and Impact Resistance of Metals

ME 354, MECHANICS OF MATERIALS LAB CREEP

Revamped High Ampacity Low Sag Stranded Carbon Fiber Composite Core Aluminium Conductor Fiber Reinforced Conductor (ACFR)

YD6Series. Single Point Load Cell

UNIVERSAL Testing Machines

YD6Series. Single Point Load Cell

Design of a Horizontal Creep Testing Machine

1 29SEP03 ALL General update with miscellaneous changes in entire document.

Page 1 of 46 Exam 1. Exam 1 Past Exam Problems without Solutions NAME: Given Formulae: Law of Cosines: C. Law of Sines:

PROJECT TITLE: Rice Board Laminate BioComposite Development to Rice Straw Based Construction Panels Continuation

High-Temperature Materials Testing.» Dipl.-Ing. Andrej Mahr, Applications Engineer» MTS Systems GmbH

STATNAMIC LOAD TESTING OF HIGH CAPACITY MARINE FOUNDATIONS

Trusted ICC ES TEK USA, Evaluation. report, or as to any. ICC-ES Evaluation

Soil-Structure Interaction (SSI) Testing Facility and Capabilities at Lehigh University

Image Analysis of Kevlar 49 Fabric at High Strain Rate

Engineering Materials

STRENGTH OF MATERIALS laboratory manual

Youngstown State University

SOUTH CAROLINA ELECTRIC COOPERATIVES' PRIMARY UNDERGROUND POWER CABLE SPECIFICATION

Girder-End Cracking in Prestressed I-Girders

TECHNICAL ANALYSIS #2

Standard Test Method for Tensile and Tensile Adhesion Properties of Rigid Cellular Plastics 1

FSEL TESTING STEEL COUPONS WITH MTS C FRAME AND F EXTENSOMETER 1. PROCEDURE OVERVIEW PROCEDURE FOR

SPECIAL SPECIFICATION 4492 Tie Back Anchors

NUMERICAL SIMULATION ON LOCAL BOND-SLIP BETWEEN STEEL AND CONCRETE WITH EXPERIMENTAL VERIFICATION

TORLON Polyamide-Imide Processing and Curing

ZBSeries. S Beam Load Cell

Reinforcing Aluminum Conductors with High Tensile Strength Bezinal Coated Steel

Purchase Now ANSI/ICEA S STANDARD FOR 600 VOLT SINGLE LAYER THERMOSET INSULATED UTILITY UNDERGROUND DISTRIBUTION CABLES

Evaluation of Aluminum Cable Presentation for IEEE OCS September 14, 2011 Breck Booker, Southwire

TEST REPORT ON 26 GA. PBR PANELS AT 5' 0" PANEL SPANS WITH 26 GA. SEALED N SAFE THERMAL BLOCKS IN ACCORDANCE WITH ASTM E AND AISI S907-08

Tensile Properties of Alloy 617 Bar Stock

Calculation accuracy of high-temperature sag for ACSR in existing lines

ECO INSTRUMENT (NS M)

Agilent Technologies 11752D/E Option K01 Connector Gage Kit. User s Guide

Gage Series Stress Analysis Gages

TEST REPORT ON. TESTED FOR: Central States Manufacturing, Inc. 302 Jane Place Lowell, AR Telephone: (800) Fax: (800)

CHAPTER III METHODS AND MATERIALS

The Contractor shall furnish and install all shielded power cable suitable for use on this project.

A. This Section includes the following types of dry-type transformers rated 600 V and less, with capacities up to 1000 kva:

GUIDE SPECIFICATIONS CURA ADJUSTABLE REROOF FRAMING SYSTEMS SECTION REROOFING ADJUSTABLE FRAMING SYSTEM

LUD PRINCIPLE. Figure 1 LUD Detail. Silicone compound squeezed around piston

Report Number: G Date: February 3, 2012 INTRODUCTION

RESEARCH FACILITIES AND EQUIPMENT

A. Product Data shall be provided for each type of product indicated.

RAYCHEM NT-MIL TUBING Modified Chlorinated Polyolefin, Elastomeric, Flexible, Flame Retarded, Heat Shrinkable

Testing of CSS Georgia Casement Rail Preliminary Report

TEST REPORT ON. TESTED FOR: Central States Manufacturing, Inc. 302 Jane Place Lowell, AR Telephone: (800) Fax: (800)

NTPEP. Mill: Name: Physical Address: Mailing Address: SAME AS ABOVE (if different from above) Primary Contact Name: Title: Telephone: Cell:

APPENDIX B. LOAD FRAME. This Appendix will describe the philosophy in the design and operation of the loading system.

SENTRAN. Low Profile Load Cell. For more information call

BASES OF DESIGN OF OVERHEAD ELECTRICAL LINES ACCORDING TO GENERAL REQUIREMENTS OF EUROPEAN STANDARD EN : 2001

EFFECT OF THERMAL CYCLING ON TENSILE AND COMPRESSIVE STRENGTH OF REINFORCED PLASTIC LAMINATES

SECTION COLD-FORMED METAL TRUSSES

Investigation for the Removal of Steel Tie Rods in a Historic Segmental Arch Floor

ESR-2604* Reissued January 1, 2011 This report is subject to renewal in two years.

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: WOOD, PLASTIC, AND COMPOSITE FASTENINGS REPORT HOLDER: MITEK USA, INC.

Aurora Genmounts Install LT Installation Manual

The UK s Leading Supplier LUMINUS

EXPRESSION OF INTREST

Advanced Technology for Large Structural Systems Research Center Lehigh University Bethlehem, PA

AC : STUDENT FEEDBACK AND LESSONS LEARNED FROM ADDING LABORATORY EXPERIENCES TO THE REINFORCED CONCRETE DESIGN COURSE

Hermetically Sealed S Beam Load Cell

Study Committee B2 Technical Advisory Group B2-AG-06

Experiment 4 - Testing of Materials in Tension

Transcription:

596TW kcmil Type 13, 3M Brand Composite Conductor Compression Connector Qualification - Tensile, Sustained Load, and High-temperature Sustained Load 3M Company Purchase Order 88324 NEETRAC Project Number: 3-81 September, 23 A Research Center of The Georgia Institute of Technology Requested by: Mr. Colin McCullough 3M Principal Investigator: Paul Springer III, P.E. Reviewed by: Dale Callaway

596TW kcmil Type 13, 3M Brand Composite Conductor Compression Connector Qualification - Tensile, Sustained Load, and High-temperature Sustained Load 3M Company Purchase Order 88324 NEETRAC Project Number: 3-81 August, 23 Summary: 3M contracted with NEETRAC for a series of qualification tests for Alcoa Conductor Accessories (ACA) full-tension splice connectors and dead-end terminal connectors. One dead-end connector was subjected the ANSI C119.4 sustained load test. All splice and dead end samples exceed the ANSI mechanical requirements for full-tension connectors. A second dead end sample was subjected to a special version of the sustained load test. Conductor temperature was maintained at 24 o C with the tension at 15% RBS. The high-temperature sustained load sample exceeded RBS in the residual strength test following the high-temperature sustained load phase. These test results provide reasonable assurance of reliable service for this connector system in overhead lines. Samples: 1) 596TW, Type 13, 3M Brand Composite Conductor, from reel received from 3M on 3/31/3. 1) Two (2) ACA compression splice connectors (special 3M Composite Conductor design), catalogue number B995-H. 2) Four (4) ACA compression dead end connectors (special 3M Composite Conductor design), catalogue number B985-G. References: 1) Proprietary Information Agreement. Dated 3/27/1, and renewed 3/3. 2) ANSI C119.4 1999, (Connector performance requirements). 3) 3M Purchase Order 88324. 4) PRJ 3-81, NEETRAC Project Plan. Equipment Used: 1) MTS Servo-hydraulic tensile machine, Control # CQ 195. 2) Fowler 42-inch caliper micrometer, Control # CN32. 3) Load frame 25K load cells Control #s CN 356 and CN 357 4) Load frame extensometers, Control #s CN 341 and CN 342 Procedure: 1. Tensile Tests on compression splices and dead-end terminals: NEETRAC 3-81, 596TW Type 13, 3M Composite Conductor, Compression Fittings Qualification Tests Page 2 of 8

Fittings were installed on the conductor by ACA at their factory in South Carolina. NEETRAC installed special cast resin terminations on the free ends of the samples. Two resin terminations are needed for the ends of the splice sample. Dead end samples need only one fitting. All samples were approximately 22 feet long overall, with approximately 2 ft of conductor in the test section. Samples were pulled to destruction at a loading rate of 1, lb/min. ANSI C119.4 requires that a connector hold a minimum of 95% of the conductors rated breaking strength. According to the 3M conductor specifications, the rated breaking strength (RBS) for the 596TW 3M Composite Conductor is 21,263 lbs. Two additional dead end samples were tested to determine residual strength following the sustained load test. See the section on the sustained load test for those results. Initial tensile test results are as follows: Sample Max. load %RBS Failure description (lbs) Splice 1 22,71 17 Tensile break, all strands, 5 ½ inside splice Splice 2 22,61 16 Tensile break, all strands, 8 inside splice Splice 3 23,2 19 Tensile break, all strands, 5 ½ inside splice Dead end 1 21,24 1 Tensile break, all strands, 8 inside dead end Dead end 2 22,21 14 Tensile break, all strands, 8 inside dead end Figures 1 and 2 show the tension versus actuator displacement for the splice and dead end tests, respectively. NEETRAC 3-81, 596TW Type 13, 3M Composite Conductor, Compression Fittings Qualification Tests Page 3 of 8

477/TWD ACCR, Tensile Tests for AFL Compound Compression Splices 25 2 Tension (lb) 15 1 5 Splice 1 Splice 2 Splice 3 95% RBS = 2,2 lb.5 1 1.5 2 2.5 3 Crosshead Displacement (inches) Figure 1, Tensile Test Data for ACA Compression Splices NEETRAC 3-81, 596TW Type 13, 3M Composite Conductor, Compression Fittings Qualification Tests Page 4 of 8

477/TWD ACCR, Tensile Tests for AFL Compound Compression Dead ends 25 2 Dead end 1 Dead end 2 Tension (lb) 15 1 95% RBS = 2,2 lb 5.5 1 1.5 2 2.5 3 Crosshead Displacement (inches) Figure 2, Tensile Test Data for ACA Compression Dead Ends 2. Sustained Load Test Per ANSI C119.4: Dead end terminal fittings were installed by ACA at their factory in South Carolina. Two samples were shipped to NEETRAC with a connector on one end, and bare conductor on the opposite end. NEETRAC installed special cast resin terminations on the free end of each sample. One of the samples was subjected to the standard ANSI C119.4 sustained load test. To qualify under the ANSI standard, a connector must hold 77% of the conductor s rated breaking strength (RBS) for seven days (168 hours). At the end of the sustained load period, the residual strength must exceed 95% of the conductor RBS. The second sample was subjected to a test designed to demonstrate sustained load performance of the connector system at extreme high temperature. AC current was used to raise the conductor temperature to 24 o C for the duration of the 168 hour test. Tension for the high temperature sample was 15% RBS. Lower tension is appropriate for this test because high tension caused by wind and ice loading cannot coincide with extreme conductor temperature. Thermal elongation due to high temperature operation will ensure that tension is below 15% RBS for all normal installed line tensions. Both samples were installed in a load frame. Both samples were fitted with extensometers to monitor conductor creep. The barrel of each dead end connector was marked with a center-punch to provide a reference section to monitor for creep in the connector body. Both samples are maintained at the tension target by computer control. An electric-drive lead screw operates to correct tension whenever the load falls outside of a +/- 2 lb deadband. The high temperature sample was instrumented for temperature in the center surface, center core, and at both ends. A data acquisition system logs tension, elongation, and temperature data. NEETRAC 3-81, 596TW Type 13, 3M Composite Conductor, Compression Fittings Qualification Tests Page 5 of 8

Figure 3 shows the data for the room temperature sample. Figure 4 shows data for the 24 o C sample. The high-temperature sample was cooled slowly to ambient temperature before the tension was removed. Both samples appeared to be in good condition at the end of the sustained load phase. 381 3M 477 ACCR/TDW Dead End Sustained Load @ 77% RBS 5.25 4.2 Temperature ( C), Tension (lb) 3 2 Tension/1 Dead end temperature Free span strain (%) Connector Barrel Strain (%).15.1 Strain (%) 1.5 2 4 6 8 1 12 14 16 Elapsed Time (Hours). Figure 3, Data Recorded during the Room Temperature Sustained Load Test Notes: 1) Temperature (red curve) is warm, and somewhat erratic because the sample was located next to the 24 o C sample. Heat from the high temperature test overloaded the room AC system during high daytime temperatures. 2) Initial creep is high for both the dead end barrel and the conductor. Connector creep is near zero after 5 hours into the test. Conductor creep is leveling off, but still increasing at the end of the test. NEETRAC 3-81, 596TW Type 13, 3M Composite Conductor, Compression Fittings Qualification Tests Page 6 of 8

381 3M 477 ACCR/TDW Dead End Sustained Load @ 77% RBS 25.1 225.9 2.8 Temperature ( C), Tension (lb) 175 15 125 1 Tension/1 (lb) Conductor Core Conductor Surface Connector Temperature Ambient Temperature Strain (%) Connector Barrel Strain.7.6.5.4 Strain (%) 75.3 5.2 25.1. 2 4 6 8 1 12 14 16 18 Elapsed Time (Hours) Figure 4, Data Recorded during the High Temperature Sustained Load Test Notes: 1) Conductor creep is essentially zero (noise) during this test. Gaps in the conductor creep data are due to a loose connector. There is no evidence of problems with any of the data recorded. 2) Small initial creep is evident in the connector barrel, but is essentially zero after 5 hours into the test. 3) The core thermocouple evidently worked its way to the surface during the test. Note there is a 7 o C gradient at the start of the test, but the temperatures converge later in the test. 3. Residual Strength Test: Following the sustained load period, the samples were loaded to destruction at room temperature at a loading rate of 1, lb/min. The room temperature sample ruptured at 22,1 lb, or 14% RBS. The high temperature sample ruptured at 22,84 lb, or 17% RBS. Both samples failed in the middle of the gage section. Figure 5 shows the load versus actuator motion data for the two samples. NEETRAC 3-81, 596TW Type 13, 3M Composite Conductor, Compression Fittings Qualification Tests Page 7 of 8

477/TWD ACCR, Residual Strength Test for Sustained Load Samples 25 2 Room Temp at 77% RBS 24 C at 15% RBS 95% RBS = 2,2 lb 15 Tension (lb) 1 5.5 1 1.5 2 2.5 3 Crosshead Displacement (inches) Figure 5, Tensile Test Data for the Residual Strength Test Notes: 1) Knee point for the 77% RBS sample is likely due to creep during the sustained load phase. 2) Curves are smoother than the initial tensile test results because the resin terminations settled in during the sustained load phase, and therefore did not slide as much during the tensile test. Conclusions: The tests were designed to qualify the ACA dead end connector for the 596TW conductor with an RBS value of 21,263 lb. All samples exceeded RBS, demonstrating good conformance to the 95% RBS minimum requirement of ANSI C119.4. The high temperature sustained load test is not required by ANSI C119.4, but was performed to demonstrate connector performance during extreme high temperature operation. Overall test results demonstrate that the connector system is suitable for service on overhead lines up to the 24 o maximum conductor rating for 3M Composite Conductors. Acknowledgement: This material is based upon work supported by the U.S. Department of Energy under Award No. DE-FC2-2CH11111. Disclaimer: Any opinions, findings, and conclusions or recommendations expressed in this material are those of the author(s) and do not necessarily reflect the views of the Department of Energy. NEETRAC 3-81, 596TW Type 13, 3M Composite Conductor, Compression Fittings Qualification Tests Page 8 of 8