SECTION PRE-ENGINEERED METAL BUILDING

Similar documents
SECTION PRE - ENGINEERED METAL BUILDING MATERIALS

SECTION FABRICATED ENGINEERED STRUCTURES. A. Pre-engineered, shop-fabricated structural steel building with formed purlin framing.

PRE-ENGINEERED METAL BUILDING SYSTEM

Addendum #4 NEW LOW HEAD OXYGEN SYSTEM Contractor EXHIBIT T SPECIAL PROVISIONS SECTION METAL SHADE STRUCTURE

Architectural Roof and Wall Products Guide Specifications

Architectural Roof and Wall Products Guide Specifications

SECTION METAL BUILDING SYSTEMS

SECTION ROOFING AND SIDING PANELS

TATA BLUESCOPE STEEL LIMITED PRODUCT SPECIFICATION LANGUAGE FOR PRE ENGINEERED STEEL BUILDING (BUTLER BUILDING SYSTEM- WITH MR-24 ROOF SYSTEM)

SECTION STEEL BUILDING SYSTEMS

Dugout Covers Specifications

SECTION PRE-ENGINEERED METAL BUILDING SYSTEM (FOR OFFICE AREA)

TCC/SHORE TRANSIT BUS MAINTENANCE FACILITY - PHASE II

SECTION STEEL DECKING

DIVISION 5 - STRUCTURAL STEEL AND IRON WORK

603 Summit Avenue, Suite 102 Greensboro, N.C Voice/FAX (336)

COLQUITT COUNTY BOARD OF COMMISSIONERS 101 East Central Avenue

SSL-175. Specifications

Specifications for FL-100 Soffit Panel

Guide Specifications ADP Series SECTION SHEET METAL ROOFING

SECTION PRE-ENGINEERED EXTRUDED ALUMINUM DECKING WALKWAY COVERS SPECIFICATION

Architectural Wall Products Guide Specifications

Architectural Roof Products Guide Specifications

SECTION METAL ROOF AND SOFFIT PANELS

Architectural Roof Products Guide Specifications

SECTION PRE-ENGINEERED WOOD POST FRAME BUILDING SYSTEM. B. Products Supplied But Not Installed Under This Section:

Architectural Roof and Wall Products Guide Specifications

DL-200. Specifications

ST. JOHNS COUNTY ARCH. PROJ. NO SECTION PREFABRICATED ALUMINUM CANOPIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS

SECTION METAL ROOF PANELS

Butler Manufacturing August 22, Genessee Street Kansas City, MO Product Guide Specification

General Overview SECTION PBR & R PANEL - PREFORMED ROOF AND WALL PANELS

SECTION METAL DECKING. A. Extent of metal decking is indicated on Plans, including basic layout for the following type of deck required:

B. Shop Drawings: For the following metal building system components. Include plans, elevations, sections, details, and attachments to other work.

SECTION METAL BUILDING SYSTEMS

SECTION COMPOSITE METAL DECKING

K. ASTM F436- Standard Specification for Hardened Steel Washers; 2011.

SECTION (05300) - STEEL DECKING

SECTION PRE-ENGINEERED COLD-FORMED METAL ROOF AND FLOOR TRUSSES

A. The extent of extruded aluminum walkway covers is shown on the Drawings and as specified herein.

1. Base plates, setting plates and anchor rods for columns. 8. Lintels if connected to structural steel columns.

1. Temperature Change: 120 deg F (67 deg C), ambient; 180 deg F (100 deg C), material surfaces.

SECTION STANDING SEAM METAL ROOFING

Product Guide Specification DIVISION SPECIALTIES MANUFACTURERS OF PROTECTIVE COVERS

DIVISION 5 METALS SECTION METAL DECKING

SECTION ROOF SPECIALTIES

METAL BUILDING SYSTEM SPECIFICATIONS

DIVISION 5 METALS SECTION STRUCTURAL STEEL

A. Metal Building System Description: Rigid modular, with interior columns with expandable endwall.

TerraClad TM General Specifications

SECTION COLD-FORMED METAL FRAMING

BRYAN COUNTY SCHOOLS DECEMBER 2013 McALLISTER ELEMENTARY SCHOOL - RICHMOND HILL NORTH BRYAN COUNTY 3-5 SCHOOL PEMBROKE 100% GMP DOCUMENTS (1/14/2014)

3' COMMERCIAL RIB PREFORMED METAL SIDING

METAL BUILDING SYSTEM SPECIFICATIONS

STRUCTURAL STEEL FRAMING

Specifiers: Click on the icon in the WORD toolbar to reveal detailed instructions

238T Aluminum Standing Seam Metal Roof System (SSMRS)

Built to Last a Lifetime

Corium Brick Rainscreen System Specifications

SECTION VERTI-LOK - PREFORMED STANDING SEAM ROOF PANELS

2016 CDM Smith All Rights Reserved July 2016 SECTION STEEL ROOF DECK

SECTION COLD-FORMED METAL FRAMING

SECTION COLD-FORMED METAL FRAMING

SECTION ALUMINUM HANDRAIL SYSTEMS

GENERAL SPECIFICATION FOR FIRE RATED APPLICATIONS

SECTION ALUMINUM WALKWAY COVERS. A. The requirements of Division 1 specifications shall apply to work specified in the section.

SECTION PLATE CONNECTED WOOD TRUSSES

CS-100 Guide Specifications

SECTION STRUCTURAL RETROFIT ROOF SUB-FRAMING SYSTEM

Guide Specification SDP 200

SECTION (formerly 05425) PRE-ENGINEERED, PRE-FABRICATED COLD-FORMED STEEL ROOF & FLOOR TRUSSES

PRESTON HEALTH SERVICES ARCHITECT'S NO MITCHELL-HOLLINGSWORTH NURSING & REHAB ADPH #B

SECTION MISCELLANEOUS METALS

Architectural Roof & Wall Products Guide Specifications MANUFACTURER KLOECKNER METALS KALAELOA BLVD, KAPOLEI, HI 96707,

UNIFIED FACILITIES GUIDE SPECIFICATIONS

OSU PROJECT NO PAGE 1 02 NOV 2006 SECTION METAL ROOF PANELS

SECTION HANDRAILS AND RAILINGS. A. Section Cast-In-Place Concrete; coordination with substrate.

C. Delegated-Design Submittal: For metal-plate-connected wood trusses indicated to comply with


SECTION COMPOSITE METAL DECKING

A. The work under this section consists of furnishing and installing gauge steel framing and bracing as indicated on the drawings and as specified.

ABS Pre-Fab Building S ystem

GUIDE SPECIFICATIONS CURA ADJUSTABLE REROOF FRAMING SYSTEMS SECTION REROOFING ADJUSTABLE FRAMING SYSTEM

1. Engineer metal building systems according to procedures in MBMA's "Metal Building Systems Manual." 2. Design Loads: As indicated on Drawings.

2016 CDM Smith All Rights Reserved July 2016 SECTION COMPOSITE STEEL FLOOR DECK

ITEM 442 METALS FOR STRUCTURES

SECTION ORNAMENTAL WELDED STEEL FENCING

COLLEGE CLASSROOM & DORMITORY SPECIFICATION SECTION 08100

SECTION PREFORMED CLADDING. A. Part A and DIVISION 1 of PART B are hereby made a part of this SECTION.

SECTION METAL BUILDING SYSTEMS. A. Section Placement of anchor bolt, leveling plates, and grout.

Guideline Specifications

SECTION COLD-FORMED METAL TRUSSES

SECTION SEM-LOK - PREFORMED STANDING SEAM ROOF PANELS

SECTION METAL EQUIPMENT LOCKERS

SECTION NON-STRUCTURAL METAL FRAMING

General. 2. Design. 3. Anchor Bolts And Foundations. 4. Drawings. 5. Structural Framing. 6. Roof Covering Nucor Classic Roof Panel

SECTION COMPOSITE WALL PANELS PART 1 GENERAL 1.01 SECTION INCLUDES

SECTION PRE-ENGINEERED MEMBRANE STRUCTURE

SECTION STRUCTURAL METAL FRAMING

Transcription:

SECTION 13121 PRE-ENGINEERED METAL BUILDING PART 1 GENERAL 1.01 SCOPE OF WORK A. Furnish all labor, materials, equipment and incidentals required to design, fabricate, deliver to project site, and erect the pre-engineered Building as shown on the Plans and as specified herein. B. Material furnished shall include the structural framing, connections, anchor bolts, metal roofing, gutters, downspouts, flashing, closures, fasteners, sealants, and all other component parts for a complete Pre-Engineered Metal Building. C. All materials shall be new, fabricated in a workmanlike manner, and free of defects. 1.02 RELATED WORK A. Formwork, reinforcement and cast-in-place concrete are included on the drawings. 1.03 SUBMITTALS A. Submit to the ENGINEER as provided complete plans showing superstructure column lines set to coordinate with concrete dimensions shown. Indicate anchor bolt size and locations and foundation reactions in KIPS at all columns. B. Submit product information, specifications, and installation instructions for all components and accessories proposed. C. Submit shop drawings and complete erection drawings for review, including: 1. Anchor bolt and base plate settings. 2. Sidewall, end wall, roof framing, and bracing. 3. Transverse cross-sections and details of covering, and trim. D. Records 1. Furnish the ENGINEER the following records: a. Letter signed and sealed by a professional engineer registered in the State of Florida certifying that the structural framing and covering panels proposed meet the design criteria set forth by the ENGINEER. b. Two sets of design calculations signed and sealed by a Professional Engineer registered in the State of Florida. c. One set of reproducible "as-built" erection plans. PRE-ENGINEERED METAL BUILDING 13121-1

E. Samples 1. Two each of the following samples shall be submitted for approval of materials, finish, color, and texture. F. Color Charts a. Full panel width by 12-inch minimum long roofing in proposed colors and finish. b. Twelve-inch minimum long formed sections of gutter, gutter tailpiece, and flashings in proposed colors and finish. c. Each proposed fastener. d. Sealants and closures. 1. Submit standard MANUFACTURER's color charts for initial color selection. 2. Colors shall be selected by ENGINEER and approved by CITY. G. Signed and sealed plans and design calculations shall be submitted to the ENGINEER for approval prior to erection. H. Submit building manufacturers welder certifications. 1.04 DELIVERY, STORAGE, AND HANDLING A. Deliver, store, and handle prefabricated components, sheets, panels, and other manufactured items so they will not be damaged or deformed. Stack materials on platforms or pallets, covered with tarpaulins or other suitable weather-tight ventilated covering. Store metal sheets or panels so that water accumulations will drain freely. Do not store sheets or panels in contact with other materials which might cause staining. 1.05 WARRANTY A. The metal panel coating system shall be warranted not to blister, peel crack, chip or experience material rust through for a period of 20 years. B. The metal building system shall be warranted not to leak water caused by ordinary wear and tear by the elements for a period of 10 years after final acceptance of the work. PART 2 PRODUCTS 2.01 GENERAL A. The specification is for a pre-engineered metal building by Butler Manufacturing Company, Kansas City, Missouri; Varco-Pruden Buildings, Memphis, Tennessee; or equal. All components listed are those manufactured by Butler Manufacturing Company and are used as a basis for the design. All components provided shall meet or exceed the requirements of the specification. PRE-ENGINEERED METAL BUILDING 13121-2

B. Design of the structural system for the Building is to be a clear span rigid frame with tapered columns, tapered roof beams, and a gabled roof. C. Actual building length and building width to be structural line to structural line, incorporating nominal bays and widths in the MANUFACTURER's standard sizes. D. Roof to be sloped as shown on drawings. E. All components and parts of the structural system to be as indicated on the Plans and in this section of the Specifications. F. All components and parts to be clearly marked. G. Erection Drawings signed and sealed by a Professional Engineer registered in the state to be supplied for identification and assembly of parts. H. Field modification to be in accordance with best standard procedures and to be the responsibility of the building erector. I. All reactions for the foundation design are to be supplied by the pre-engineered building manufacturer prior to building foundation shop drawing submittal. J. The foundation sizing and reinforcement details are to be based on the MANUFACTURER's building details and are to be compatible with the reactions, loadings, stresses and column locations supplied by the pre-engineered building manufacturer. The foundation sizing and locations as shown on the Plans are preliminary and have been based on realistic reactions for the building dimensions and loadings specified herein. The cost for any required amendments to the foundation material quantities as shown on the Plans shall be a subsidiary obligation of the CONTRACTOR and shall not result in any additional cost to the CITY. K. Anchor bolt locations, size and quantity to be designed by the building manufacturer and supplied by the CONTRACTOR. 2.02 DESIGN CRITERIA A. Primary and secondary members and covering shall be designed for all applicable loads and combinations of these loads as set forth in the MBMA "Recommended Design Practices Manual", as required by the governing building code, and as specified herein. Roof system shall have a U.L. wind uplift Class 90 rating. B. Design shall allow for concentrated loads for equipment attached to building structure as shown and for the dead load of the structure itself. C. Column reactions shall be vertical and horizontal only. No bending moments will be allowed at the column bases. D. Deflection of primary structural framing members shall not exceed l/240 of their span. E. The design, fabrication, and erection of the building shall conform to the applicable sections of the latest edition or revision of the following codes and standards. PRE-ENGINEERED METAL BUILDING 13121-3

1. American Institute of Steel Construction a. Specifications for the Design, Fabrication, and Erection of Structural Steel for Buildings 2. American Iron and Steel Institute a. Specifications for the Design of Cold-Formed Steel Structural Members b. Design of Light Gauge Steel Diaphragms 3. American Welding Society a. Structural Welding Code 4. Metal Building Manufacturer's Association a. Recommended Design Practices Manual 5. American Society of Testing and Materials a. Material designation as specified herein by ASTM number 2.03 MATERIAL (FRAMING) A. Primary Framing 1. Rigid Frames: a. Frames shall consist of welded up plate section columns and roof beams complete with necessary splice plates for bolted field assembly. b. Welding shall be done in accordance with the American Welding Society Code for Building Construction. 1) Certification of welder qualifications to be supplied. c. All base plates, cap plates, compression plates, and stiffener plates to be factorywelded into place and have the connection holes shop fabricated. d. All splice plates to be shop fabricated complete with bolt connection holes. e. Columns and roof beams shall be fabricated complete with holes in webs and flanges for the attachment of secondary structural members and bracing. 2. All bolts for field assembly of frame members shall be high strength bolts as indicated on erection Drawings. 3. Endwall Structurals: a. Endwalls shall be rigid frames as shown on the drawings. PRE-ENGINEERED METAL BUILDING 13121-4

B. Secondary Structural Members 1. Purlins: a. Purlins shall be 9-1/2-in deep "Z" sections, precision roll formed. b. Outer flange of all purlins shall contain factory-punched holes for panel connections. 2. Eave Struts: a. Eave struts shall be 12-in deep "C" sections. b. Outer flange of all eave struts shall contain factory-punched holes for panel connections. 3. Bracing: a. Diagonal bracing shall be designed by the building manufacturer and attached to columns and roof beams. b. Flange braces, sag angles, etc., when required, shall be supplied by the building manufacturer. c. All bracing locations shall be coordinated with ductwork, piping, door openings, and ventilation openings. D. Structural Painting: 1. Primary Frames: Clean all steel per SSPC-SP6. Apply one coat of Tnemec Series 90-97 Tneme-zinc at a dry film thickness of 2.5-3.5 mils. 2. Secondary Structurals: Clean all steel per SSPC-SP8. Apply one coat of coil applied polyester primer to a minimum coating thickness of 0.5mil (purlins). 3. Finish Paints System (Primary Frames and Secondary Structurals) a. 1 st Coat: Tnemec Series 66HB Epoxoline (or equal) with a dry film thickness of 3.0 5.0 mils. b. 2 nd Coat: Tnemec Series 1075 Endurashield (or equal) with at dry film thickness of 2.5 4.0 mils. 2.04 MATERIAL (ROOF SYSTEM) A. General 1. The building roof panels shall be precision roll formed MR-24 panels as furnished by Butler Manufacturing Company. 2. Details shall be in accordance with the MANUFACTURER's drawings. PRE-ENGINEERED METAL BUILDING 13121-5

3. Installation shall be in accordance with the MANUFACTURER's drawings. B. Panel Description 1. Panels shall be roll formed to provide width coverage of 24". a. There shall be two major corrugations, 2" high, spaced 24" on center. b. There shall be minor corrugations, spaced 6" on center between and perpendicular to the major corrugations. 2. The panel endlaps shall be 6". a. Panels shall be of maximum length so as to minimize panel endlaps. b. Endlaps shall be engineered to occur over and be fastened to a secondary structural member. c. The upper end of all panels shall be marked for the proper location of endlap sealant. 3. Ridge assembly shall be designed to allow for expansion and contraction. 4. Eave panels shall extend beyond the building structural line. 5. Panels shall be factory pre-punched at panel ends to match pre-punched holes in the eave structural members. Panel end splices shall be factory pre-punched and pre-notched. Panel end splices shall allow for expansion and contraction of the panels. 6. Panel Material and Finish C. Panel Design a. 24 gauge steel, coated both sides with a layer of Galvalume aluminum-zinc alloy (approximately 55% aluminum, 45% zinc) applied by the continuous hot dip method. Minimum 0.55 ounce coated weight per square foot as determined by the triple-spot test per ASTM Specification A792. 1. Panel design shall be in accordance with paragraph 2.02 herein. 2. Panel design shall provide for expansion and/or contraction as caused by an ambient temperature range of 120 degrees F without causing harmful buckling, opening of joints, and other detrimental effects. D. Fasteners 1. Bearing plates, and panel clips shall be fastened to structural members with fasteners as per manufacturer's erection drawings, using factory pre-punched holes in structural members. 2. All connections of MR-24 panels to structural members except at eave shall be made with clips with moveable tabs that are seamed into the standing seam sidelap. PRE-ENGINEERED METAL BUILDING 13121-6

3. Panel clips shall be fastened to structural members with fasteners as per MANUFACTURER's erection drawing, using factory pre-punched holes in structural members. 4. MR-24 panel-to-panel connections shall be made with a positive, field formed standing double-lock seam. E. Accessories 1. Accessories to be standard with Butler Manufacturing Company, unless otherwise noted and furnished as specified. Location of standard accessories on the erection drawings as furnished by the MANUFACTURER. Installation of accessories shall be in accordance with the MANUFACTURER's instructions and as shown on the drawings. F. Panel Application a. Metal curbs and pipe flashings to be Butler standard except that interior faces of curbs must be fully enclosed also. b. Gutters, downspouts, and trim pieces are to be standard Butler Manufacturing products installed in accordance with MANUFACTURER's instructions and as shown on the erection drawings. c. All miscellaneous trim, gutters, downspouts and accessories are to match adjacent panel colors. 1. All panels shall be factory cut-to-length according to the erection drawings as furnished by Butler Manufacturing Company. 2. All panels shall be positioned and aligned to hold the 24" module throughout the building length. 3. Pre-punched panels shall be positioned and aligned by matching the pre-punched holes in the panel with the pre-punched roof structurals. 4. Panel sidelaps shall be field seamed; all sidelap sealant shall be factory applied. 5. All endlaps will be at least 6" and fastened together over and to structural members. 6. All panel sidelaps and endlaps shall be sealed with weather sealing compound to prevent the entry of capillary moisture. 7. Fasteners shall be installed with proper tools, in a workmanlike manner according to the recommendations of the MANUFACTURER. PART 3 EXECUTION 3.01 INSTALLATION A. The pre-engineered building shall be erected on the site as indicated on the Plans. PRE-ENGINEERED METAL BUILDING 13121-7

B. The pre-engineered building shall not be fabricated or erected until: 1. Structural loadings, as required herein to be supplied by the building manufacturer, have been approved by the ENGINEER. 2. The foundation design and details based on the structural loadings, have been approved by the ENGINEER. C. No erection of the pre-engineered building shall take place until the foundation work, the concrete floor slab, plumbing and other incidentals required to be built prior to the building installation have been approved by the ENGINEER. D. No erection of the pre-engineered building shall take place until sufficient components of the building to enable a stable structure to be erected are on site. E. The CONTRACTOR is responsible for ensuring that all safety procedures for the erection of the building are strictly enforced and that any required ties, stays and temporary works are positioned as necessary to keep the structure stable and secure at all times. F. All installation of the building to be to the MANUFACTURER's instructions and requirements. G. The building manufacturer shall provide all necessary framing details to the openings in the roofing and other components where shown on the Plans. The cost of all such framing shall be included in the installed cost of the pre-engineered building. H. The building manufacturer shall provide, at no additional cost to the CITY, all necessary repair and touch-up work required as a result of damage to building components due to required cutouts, penetrations or by mishandling prior to and during erection. END OF SECTION PRE-ENGINEERED METAL BUILDING 13121-8