Fire Resistance Rated Truss Assemblies. Educational Overview

Similar documents
HOOVER TREATED WOOD PRODUCTS, INC. TECHNICAL NOTE FOR ADDITIONAL INFORMATION: TEC-WOOD ( )

Code Compliance for Fire Resistance-Rated Assemblies in Light-Frame Buildings. John Buddy Showalter, PE VP, Technology Transfer American Wood Council

Code Compliance for Fire Resistance-Rated Assemblies in Light-Frame Buildings

Type III Fire-Resistant Design and Detailing: Exterior walls, Intersections and Balconies. For Light-Frame Wood Construction

A Review of Thermal and Ignition Barrier Requirements for Spray Foam Insulation

Code Compliance for Fire Resistance-Rated Assemblies in Light-Frame Buildings

TECO Certified Rim Board in Fire-Rated Assemblies TER No

Preventing a Floor Truss Ban in Ohio. SBCRI/Qualtim TER Produces A Win for All Component Manufacturers (CMs)

BUILDING CODE REQUIREMENTS

LEGACY REPORT Reissued October 1, Legacy report on the BOCA National Building Code/1999

Fire Resistive Construction Based on the 2015 IBC BIANCO Education Day August 15, 2016

SECTION GYPSUM BOARD

Canadian Wood Council G063. Fire Resistance Tools and Information for Wood-Frame Buildings

LISTING INFORMATION OF International Beams - IB Series Joists SPEC ID: 27316

LISTING INFORMATION OF Mitek Design No. MCI/WI SPEC ID: MiTek Canada, Inc. 100 Industrial Road Bradford, ON L3Z 3G7 Canada

ESR-1826 Reissued May 1, 2009 This report is subject to re-examination in one year.

Fire Resistive Construction

Statewide Alternate Method January 2015 No Cross-Laminated Timber Provisions

Appendix D. -Weyerhaeuser Fire Rated Assembly Listings-

PHOTO 1: View from Inside the Structure. Note the Rotation of the WSP, Failure at the Lower Leading Edge and Deformation of the Top Plate

Wood-Framed, Exterior Walls in Type III Construction

2015 IBC Inspection of Fire-Resistance Rated Floors, Ceilings and Roofs

Protecting Penetrations in Fire Rated Construction

Stark Truss Company, Inc. Revised December 14, 2018

ESR-2847 Reissued September 1, 2013 This report is subject to renewal September 1, 2015.

REPORT HOLDER: KINETICS NOISE CONTROL 6300 IRELAN PLACE DUBLIN, OHIO EVALUATION SUBJECT: KINETICS NOISE CONTROL WAVE HANGER

2012 IBC Inspection of Fire-Resistance Rated Floors, Ceilings and Roofs

2018 IBC Chapter 6 Types of Construction

2012 IBC Inspection of Fire-Resistance Rated Floors, Ceilings and Roofs

Updated references to SEI/ASCE 7 to the 2016 edition once it is available.

Mid-Rise Engineering Considerations for Engineered Wood Products

REPORT HOLDER: GYPSUM ASSOCIATION 962 WAYNE AVENUE, SUITE 620 SILVER SPRING, MARYLAND EVALUATION SUBJECT:

research report Fire Resistance Ratings of Load Bearing Steel Stud Walls With Gypsum Wallboard Protection RESEARCH REPORT RP REVISION 2007

LISTING INFORMATION OF ClarkDietrich Steel 'H' Stud and 'U' Track Fire-resistance-rated Area Separation Wall Assemblies SPEC ID: 26662

REPORT HOLDER: GYPSUM ASSOCIATION 6525 BELCREST ROAD #480 HYATTSVILLE, MARYLAND EVALUATION SUBJECT:

FCIA Webinar Gypsum Wall Patching

Gypsum Board Systems Manual

HIGH PERFORMANCE FIRE RETARDANT TREATED WOOD PRODUCTS

Shaft Wall Solutions for Wood-Frame Structures. Ricky McLain, PE, SE WoodWorks Wood Products Council Boston & Waltham Workshops, December 6 & 7, 2017

2009 International Building Code Errata (Portions of text and tables not shown are unaffected by the errata)

ICC-ES Evaluation Report Reissued February 1, 2011 This report is subject to re-examination in one year.

UDC Wall Bracing Provisions Emergency Rule effective date 4/1/2014. A How To guide for use of the new provisions

interior finishes 2 l

Attachment of Residential Deck Ledger to Metal Plate Connected Wood Truss Floor Systems

July 23, 2010 PARTIES INTERESTED IN REFLECTIVE FOIL INSULATION

FIRE RESISTANCE TESTS OF BRICK VENEER / WOOD FRAME WALLS J. GREGG BORCHELT

Shaft Wall Solutions for Wood-Frame Structures. Ricky McLain, PE, SE WoodWorks Wood Products Council Charlotte WSF, November 2, 2017

ReWall EssentialBoard, NakedBoard & Ceiling Panels TER No

Intertek Research Report IRR-1011

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: THE DOW CHEMICAL COMPANY

BASF HP+ Wall XR Series Limit States TER No

R-Matte Plus-3: Insulation for the Building Envelope

FUTURE OF FIRE-RESISTIVE COATINGS IN WOOD CONSTRUCTION

Enthusiastic customers We create success for our customers by Identifying their needs and providing Innovative and value adding solutions.

ICC-ES Evaluation Report Reissued September 1, 2011 This report is subject to renewal in two years.

Floor Truss Ribbon Board Load Path

Code Compliant Fire- Resistance Design for Wood Construction

Multi-Institutional Academic Health Science & Research Center Evansville, IN

Code Compliant Fire- Resistance Design for Wood Construction

FIRE FACTS. For ilevel Engineered Lumber Products iLevel8 ( ) WALL SOLUTIONS. Thorough Fire Testing

Originally Issued: 11/06/2017 Valid Through: 11/30/2018

Versetta Stone Panelized Stone Veneer Applications Over Continuous Insulation. TER No Boral Stone Products LLC

USG Co. Plant # th Street Mediapolis, IA Atlantic Wallboard Ltd. # Jervis Lane St. John, NB E2J 0A9

SECTION STRUCTURAL INSULATED PANELS

Following contains common verbiage found in major model building codes and has been edited for the purpose of inclusion on this CD.

Copyright Materials. Learning Objectives. Design is in the Details: Solutions to Common to Mid Rise Design. Challenges

Code Compliant Fire Resistance Design for Wood Construction. Paul Coats, PE, CBO Southeast Regional Manager American Wood Council

PinkWood Ltd. Revised September 29, 2017

TER No Use of Icynene Classic Plus Spray Polyurethane Foam (SPF) in Unvented Attics & Crawlspaces

Boise Cascade Company Revised June 25, 2018

Exterior Brick Masonry Veneer Supported by Metal Plate Connected Wood Trusses (MPCWT) Design Guide Revised 11/17/2016

Originally Issued: 02/01/2019 Valid Through: 02/28/2020

Originally Issued: 2/12/2016 Revised: 07/28/2017 Valid Through: 2/28/2018

Thermasheath -3. Insulation for the Building Envelope ROOF WALL SPECIALTY

RLGA. Gypsum Board Construction 2012 International Building Code. By Ronald L. Geren, AIA, CSI, CCS, CCCA, SCIP

Fire Retardants and Truss Design. Overview

FIRE & SOUND MANUAL ARCHITECT VERSION 4.18

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: DEMILEC (USA) LLC

Deer Ridge Consulting, Inc.

XHBN.FF-D Joint Systems. Joint Systems. System No. FF-D-3008

June 7, 2012 PARTIES INTERESTED IN HVAC DUCT ENCLOSURE ASSEMBLIES

Building Envelope

BASF HP+ Wall XR Series Ontario TER No

SECTION FIRE RESISTIVE JOINT SYSTEMS

PHYSICAL FACILITIES Consultant s Handbook Specifications Division 07 Thermal and Moisture Protection 8400 Firestopping

2012 NC Building Code Table Required Separation of Occupancies. ( Item B-1)

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: ICYNENE, INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: FIRESTOPPING REPORT HOLDER: PASSIVE FIRE PROTECTION PARTNERS

Joint Evaluation Report ICC-ES (800) (562)

FIRE ENDURANCE RATINGS CLAY BRICK MASONRY

Designing to Meet IRC Fire Protection Provisions for I-Joist Floor Systems

FIRE RATED ASSEMBLIES OF COLD-FORMED STEEL CONSTRUCTION

2012 IBC Inspection of Fire-resistance Rated Walls

Originally Issued: 08/03/2017 Revised: 02/01/2019 Valid Through: 08/31/2019

Image courtesy of KTGY, Inc. ENGINEERED FOR FIRE CODE COMPLIANCE AND DESIGN FLEXIBILITY

Thermasheath -3. Insulation for the Building Envelope ROOF WALL SPECIALTY

Technical Features Fire Construction There Is A Difference In Drywall

ESR-1812 Reissued October 1, 2012 This report is subject to renewal November 1, 2013.

TYPICAL BEARING WALL FRAMING

Transcription:

Fire Resistance Rated Truss Assemblies Educational Overview

Introduction Building codes may require a fire endurance rating for several applications where trusses are used: Floor/ceiling Roof/ceiling Attic separation

Generic fire rated wood truss assembly

Introduction Truss protection in fire resistance rated assemblies is covered in the IBC States that requirements shall be based on the results of full-scale tests or combinations of tests or approved calculations based on such tests that demonstrate fire resistance 704.5 Truss protection.

Key Definitions Approved Source: An independent person, firm or corporation, approved by the building official, who is competent and experienced in the application of engineering principles to materials, methods or systems analyses. Fire Resistance: That property of materials or their assemblies that prevents or retards the passage of excessive heat, hot gases or flames under conditions of use. Fire-Resistance Rating: The period of time a building element, component or assembly maintains the ability to confine a fire, continues to perform a given structural function, or both, as determined by the tests, or the methods based on tests, prescribed in Section 703.

Introduction The IBC allows five methods for determining fire resistance (Section 703.3): 1. Fire-resistance designs documented in sources. 2. Prescriptive designs of fire-resistance-rated building elements, components or assemblies as prescribed in Section 721. 3. Calculations in accordance with Section 722. 4. Engineering analysis based on a comparison of building element, component or assemblies designs having fire-resistance ratings as determined by the test procedures set forth in ASTM E119 or UL 263. 5. Alternative protection methods as allowed by Section 104.11.

Method 1: Documented fire-resistance designs To qualify as a documented design, testing is performed in accordance with one of the following tests: ASTM E119 Standard Methods for Fire Tests of Building Construction and Materials ANSI/UL 263 Fire Resistance Ratings

Method 1: Documented fire-resistance designs Tested assemblies may be specified where a rated assembly is required Assemblies can generally be applied to both floor and roof applications

Method 1: Documented fire-resistance designs Some sources of documented fire-resistance designs include: Gypsum Association Fire Resistance Design Manual (GA-600) Online Manual (read only)

Method 1: Documented fire-resistance designs Underwriters Laboratories: Fire Resistance Directory Searchable Database Many UL tested designs can also be found in the product literature of companies whose products are certified to be listed in the assemblies

Method 1: Documented fire-resistance designs Other sources of documented fire-resistance designs include: Warnock Hersey (Intertek Directory) Factory Mutual PFS Corporation

Method 1: Documented fire-resistance designs General: The fire resistance rating of listed assemblies applies to the entire assembly Components are NOT intended to be interchanged between assemblies. Modifications?

Method 1: Documented fire-resistance designs However, evaluation by comparison of tested assemblies is permitted by IBC Section 703.3 Method 4.

Method 1: Documented fire-resistance designs Depth/Spacing: Depths given are minimums Greater depths are allowed Spacings given are maximums Smaller spacings are allowed Maximum spacing Minimum depth

Method 1: Documented fire-resistance designs Insulation: Some assemblies allow addition of insulation if an additional layer of gypsum is installed at the ceiling. Modifications?

Method 1: Documented fire-resistance designs However, IBC Section 703.3 Method 4 and Method 5 permit modifications to assemblies This would include modifications involving insulation Rational design must be provided to the building official

Method 1: Documented fire-resistance designs Use of floor/ceiling designs for roof/ceiling (or reverse): UL BXUV.GuideInfo Section III.19 states: Class A, B or C roof coverings may be used on floors without reducing the fire-resistance rating A nailer of equal thickness to the length of the mechanical fasteners must be added to the flooring

Method 1: Documented fire-resistance designs Use of floor/ceiling designs for roof/ceiling (or reverse): The reverse case is not typical Floor/ceiling designs that specify a finish floor cannot be used as roof/ceiling assemblies

Method 1: Documented fire-resistance designs However, IBC item 4 or item 5 would allow use of assemblies tested as floor/ceiling or roof/ceiling in the other application, even if not specified as such in the listing Rational design must be provided to the building official.

Method 2: Prescriptive designs IBC Table 721.1(3), item 21-1.1 describes one prescriptive 1-hour rated floor or roof assembly that includes wood trusses: Base layer: 5/8" Type X gyp attached w/1-1/4 Type S or W drywall screws @ 24 o.c. at right angles to truss/joist Face layer: 5/8" Type X gyp or veneer base attached thru base layer w/1-7/8 Type S or W drywall screws 12 o.c. at joints and intermediate truss/joist. Type G drywall screws placed 2 back on either side of face layer end joints @ 12 o.c. 1/2" (min) WSP glued & attached w/8d nails at right angles to truss/joist Max spacing 24

Method 2: Prescriptive designs The National Building Code of Canada (NBC) 2010 provides an extensive listing of prescriptive assemblies that include metal plate connected wood trusses in Table A-9.10.3.1.B. These listings also include sound ratings, so can be very useful to the building designer.

Method 3: Calculated designs IBC Section 722.6 addresses fire resistance calculations for wood assemblies The unexposed side membrane is NOT included in the calculation Fire-exposed side membrane + Framing members + Other (e.g. Insulation) = Fire-resistance rating (minutes)

Method 3: Calculated designs The maximum fireresistance rating allowed using this method is 1-hour. This section includes tables with times assigned to both structural members and membranes.

Method 4: Comparison The IBC allows the determination of fire resistance ratings based on a comparison of building element, component or assembly designs having fire-resistance ratings as determined by the test procedures set forth in ASTM E119 or UL 263.

Method 4: Comparison Combined with the provisions of IBC Section 104.11 listed at item 5, this allows the building official to approve a design that "complies with the intent of the provisions of this code, and that the material, method or work offered is, for the purpose intended, at least the equivalent of that prescribed in this code in quality, strength, effectiveness, fire resistance, durability and safety."

Method 4: Comparison SBCA has calculated a two hour fire rated MPCWT assembly based on this provision See SBCA SRR 1509-02 for full details

Method 4: Comparison One basis for this type of analysis is Harmathy s Ten Rules of Fire Endurance Rating Consult Section 4-13 in the SFPE Handbook of Fire Protection Engineering for further info

Method 5: Alternative materials and methods 104.11 Alternative materials, design and methods of construction and equipment. The provisions of this code are not intended to prevent the installation of any material or to prohibit any design or method of construction not specifically prescribed by this code, provided that any such alternative has been approved. An alternative material, design or method of construction shall be approved where the building official finds that the proposed design is satisfactory and complies with the intent of the provisions of this code, and that the material, method or work offered is, for the purpose intended, at least the equivalent of that prescribed in this code in quality, strength, effectiveness, fire resistance, durability and safety.

Method 5: Alternative materials and methods This allows for other methods of developing a design by an approved source that complies with the intent of the code and, unless it can be demonstrated not to comply with the code, should be approved by the building official.

Conclusion A Building Designer may submit to a code jurisdiction a fire resistance rated design incorporating metal plate connected wood trusses using any of the five methods allowed by Section 703.3. If it is not a listed design, the Building Designer should submit details regarding how the submitted design was determined and show how it complies with the intent of the building code.

References SBCA Research Report 1509-01 National Design Specification for Wood Construction (NDS ) 2012 or 2015, American Wood Council (AWC), Section 16, Fire Design of Wood Members. Analytical methods for determining fire resistance of timber members, Robert White, 2008, included in the SFPE handbook of fire protection engineering. Quincy, Mass.; National Fire Protection Association; Bethesda, Md.: Society of Fire Protection Engineers, c2008: pages 4.346-4.366. Guidelines on Fire Ratings of Archaic Materials and Assemblies. International Code Council (ICC). National Building Code of Canada, 2010.

References International Building Code (IBC), 2012 and 2015, International Code Council (ICC). BXUV.GuideInfo, Underwriters Laboratory. Gypsum Association Handbook, GA-600, 2012 Fire Resistance Provided by Gypsum Board Membrane Protection, GA-610, 2013 ESR-1338, Gypsum Wall and Ceiling Assemblies and Gypsum Board Interior and Exterior Applications Intertek Directory of Certified Products PFS Corporation Factory Mutual