MATERIAL STANDARD FOR ELECTRICAL HEAT TRACING ORIGINAL EDITION JAN. 1996

Similar documents
MATERIAL STANDARD FOR COLD-APPLIED LAMINATED PLASTIC TAPE INNER-LAYER TAPE FOR TAPE COATING SYSTEM OF BURIED STEEL PIPES ORIGINAL EDITION JULY 1994

SECTION METAL-ENCLOSED BUS MEDIUM VOLTAGE

NUCLEAR POWER CORPORATION OF INDIA LTD. (A GOVT. OF INDIA ENTERPRISE) SPECIFICATION NO.PB-E-542/REV. No.0

Heating Cables DATASHEET

SECTION HEAT TRACING FOR PLUMBING PIPING

SPECIFICATIONS FOR Gas-to-Cable termination

SECTION HEAT TRACING FOR PLUMBING PIPING

MATERIAL AND EQUIPMENT STANDARD FOR ROTATING ELECTRICAL MACHINES DIRECT CURRENT MOTORS ORIGINAL EDITION MAY 1993

MATERIAL STANDARD FOR CABLES AND WIRES

TABLE OF CONTENT

SECTION SECONDARY UNIT SUBSTATIONS

PIPEWORK INSULATION. 14/ Page 1 of 10 Pipework Insulation Rev D

DRAFT TANZANIA STANDARD. Part 7: Underground Power Cables for rated voltages 0.6kV/1kV (Um 1.2kV)

Revision:C Pipework Insulation Issued:14/11/2012 PIPEWORK INSULATION CU14. 14/11/2012 Page 1 of 10 Pipework Insulation - RevC

SPECIFICATION FOR FRLS POWER CABLES

MATERIAL AND EQUIPMENT STANDARD FOR BITUMEN PRIMER (COLD APPLIED) FOR USE WITH ORIGINAL EDITION JULY 1994

MATERIAL AND EQUIPMENT STANDARD FOR COAL TAR PRIMER (COLD APPLIED) FOR USE WITH HOT APPLIED COAL TAR ENAMEL (IPS-M-TP-290) ORIGINAL EDITION JULY 1994

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

Insulated sheath power cable systems

TECHNICAL SPECIFICATION FOR L. T. XLPE POWER CABLE

ISO 6722 INTERNATIONAL STANDARD. Road vehicles 60 V and 600 V single-core cables Dimensions, test methods and requirements

SCHEDULE ' A ' TECHNICAL SPECIFICATION FOR L.T.PVC POWER AND CONTROL CABLES FOR DISTRIBUTION NETWORK IN MAHARASHTRA

Type FLX Freezer Floor Frost Heave Protection DESIGN GUIDE

A. All materials shall be tested and listed by an OSHA approved Nationally Recognized Testing Laboratory (NRTL).

NPS/001/024 Technical Specification for Low Voltage Aerial Bundled Conductor Fittings

NPS/002/018 Technical Specification for Pilot, Control and Telephone Cables

SECTION PARK NON-SEGREGATED BUS SPECIFICATION

RESIN FILLING TYPE JOINTING KITS FOR LOW VOLTAGE UNDERGROUND CABLES

NEW GC-16 IN WEST KUWAIT MATERIAL REQUISITION FOR LEVEL GAUGE TABLE OF CONTENTS

Section ARMORED MEDIUM VOLTAGE CABLES SHIELDED 3 CONDUCTOR POWER CABLE - INTERLOCKED ARMOR

A. Section includes busway and fittings including plug-in units.

MATERIAL AND EQUIPMENT STANDARD FOR PIGS ORIGINAL EDITION JULY 1997

NPS/002/018 Technical Specification for Pilot, Control and Telephone Cables

NPS/002/017 Technical Specification for 66 kv and 132 kv Cable Accessories

NPS/002/020 Technical Specification for 11 & 20kV Power Cables

Technical Specification for PVC Insulated Low Voltage Neutral Screened Copper Cable

TABLE OF CONTENT

NPS/002/023 Technical Specification for 132kV Power Cables.

SECTION GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY

SRI LANKA STANDARD SPECIFICATION FOR THREE-PIN PLUGS, SOCKET-OUTLETS AND SOCKET-OUTLET ADAPTORS

NPS/002/013 Technical Specification for Telephone and Pilot Cable Joints

SECTION GROUNDING

--> Buy True-PDF --> Auto-delivered in 0~10 minutes. TB/T Translated English of Chinese Standard: TB/T1484.

MREC March, 2005 Powering the Dairy Industry

SECTION WIRE, CABLE AND BUSWAYS. A. This section specifies providing wire, cable and busways.

11-SDMS-01 REV. 02 SPECIFICATIONS FOR LOW VOLTAGE POWER AND CONTROL CABLES

DESIGN GUIDELINES WIRING AND CONDUITS PAGE 1 of 7

This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update.

Mineral Insulated Platinum Resistance Thermometer PT100 Sensor - Available in 3mm or 6mm diameter x 150mm or 250mm probe lengths

SECTION MEDIUM-VOLTAGE CABLES PART 1 GENERAL

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

The Contractor shall furnish and install all shielded power cable suitable for use on this project.

Installation of CSST Gas Piping Systems

SYRIAN ARAB REPUBLIC MINISTRY OF ELECTRICITY PUBLIC ESTABLISHMENT FOR DISTRIBUTION The ELECTRICITY (PEDE) TENDER DOCUMENTS FOR

ENGLISH. Datasheet. RS single element: Single 4 wire element, allowing connection to any Pt100 2, 3 or 4 wire instrument

ENGINEERING, CONSTRUCTION AND MATERIAL STANDARD FOR FENCING AND GATES ORIGINAL EDITION MAY. 1997

TWO PACK AMINE CURED EPOXY RESIN PAINT PRIMER, INTERMEDIATE AND TOP COAT FOR ATMOSPHERIC ENVIRONMENT ORIGINAL EDITION MAR. 1996

WIRING METHODS CHAPTER 38

NPS/002/001 Technical Specification for Earthing Materials

6. SECONDARY SERVICES (under 600 volts) 6.1 AVAILABILITY For the electrical characteristics of available secondary services see Section 3.4.

ELECTRICAL BULLETIN

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

31-SDMS-03 REV. 01 SPECIFICATIONS FOR

The Canadian Electrical Code (Saskatchewan Amendments) Regulations, 1999

LIFETIME WARRANTY INSTALLATION MANUAL. Ultra thin cable. Easy to install. Fully compliant to latest regulations CE approved INSTALLATION MANUAL

MANUFACTURING TECHNICAL INSTRUCTIONS SAFETY Subject: DESIGN, MAINTENANCE AND INSPECTION OF SECONDARY ELECTRICAL DISTRIBUTION SYSTEMS

*** Supercedes: BECO E and COM , , & ***

THERMOFIT ADHESIVE S Flex Fluid Resistant, High Temperature, One Part-Flexible Epoxy

SECTION BASIC ELECTRICAL REQUIREMENTS

MATERIAL AND EQUIPMENT STANDARD FOR LOW VOLTAGE INDUSTRIAL AND. FLAMEPROOF a.c. MOTOR CONTROL CENTERS (MCC) ORIGINAL EDITON MAY 1993

NEC 2014 Code Changes

SECTION 16496A MTS MANUAL TRANSFER SWITCH (MANUAL CONTROL ONLY) Note to Spec Writer: { } Denotes EATON Feature reference number

SECTION EARTHING AND EARTH FAULT PROTECTION

Replace 210.8(a)(7) with: Sinks. Where receptacles are installed within 6 feet of the outside edge of a sink. Page 1 of 5

SECTION FACILITY LIGHTNING PROTECTION

MATERIAL SPECIFICATION FOR HIGH PRESSURE SODIUM LUMINAIRES FOR UNDERPASS LIGHTING

Kaf-Tech Product Specification

SECTION GENERAL MOTOR REQUIREMENTS FOR HVAC AND STEAM GENERATION EQUIPMENT

BUSWAY LOW VOLTAGE (POW-R-WAY III) SECTION SECTION 16466

NPS/003/015 Technical Specification for 33kV, 66kV and 132kV Post Insulators

Highly flexible, screened control cable with PVC core insulation and abrasion and oil resistant PUR sheath

B. Provide liquid-filled secondary substation transformers as indicated on drawings.

Part 1: On-land pipelines

SECTION 7.3 TECHNICAL SPECIFICATION OF POWER CABLES & CONDUCTOR

ENGLISH Datasheet Platinum Resistance Pt100 4 wire class B Resistance Thermometer with DIN B Head

Technical Specification for Low Voltage Aerial Bundled HDPE Insulated Cables

1 29SEP03 ALL General update with miscellaneous changes in entire document.

ENGLISH. 1metre 7/.02mm Teflon insulated twin twisted lead

TABLE OF CONTENTS. FOREWORD... Error! Bookmark not defined. INTRODUCTION SCOPE NORMATIVE REFERENCES DRAWING...4

Pt100 (100 0 C) to IEC 751, Class B, 4 wire 3.0, 4.0, 4.5 or 6.0mm diameter 316 stainless steel sheath.

SECTION PART 1 GENERAL

Single Core, Aluminum Conductor Extruded Cross - Linked Polyethylene (XLPE) Insulated Power Cable

ENGINEERING, CONSTRUCTION AND MATERIAL STANDARD FOR FENCING AND GATES ORIGINAL EDITION MAY 1997

AMIGA. Installation Instructions

PRODUCT SPECIFICATION

MESP TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 22 kv, SINGLE CORE, 95mm 2 COPPER

Cables for Railway Signalling Applications General Requirements

Petroleum Production and Disposal Facility Static and Lightning Mitigation

CERTIFICATE OF ACCREDITATION

Transcription:

MATERIAL STANDARD FOR ELECTRICAL HEAT TRACING ORIGINAL EDITION JAN. 1996 This Standard is the property of Iranian Ministry of Petroleum. All rights are reserved to the owner. Neither whole nor any part of this document may be disclosed to any third party, reproduced, stored in any retrieval system or transmitted in any form or by any means without the prior written consent of the Iranian Ministry of Petroleum.

CONTENTS : PAGE No. 1. SCOPE... 2 2. REFERENCES...2 3. UNITS... 3 4. ENVIRONMENTAL CONDITIONS... 3 5. TYPE OF HEAT TRACING CABLE... 3 5.1 Self Regulating Heaters... 3 5.2 Zonal Parallel Resistance Heating Tape (Constant Wattage)... 4 5.3 Mineral Insulated Cable for Heat Tracing... 4 6. MINIMUM SAFETY REQUIREMENTS FOR ESH DEVICE AND CONTROL... 5 7. THERMAL INSULATION*... 5 7.1 General Requirements... 5 8.EXPLOSIVEATMOSPHEREAPPLICATIONS(BASIC REQUIREMENTS)... 5 9. FACTORY TESTS OF ESH DEVICES... 6 10. LABELLING AND IDENTIFICATION OF ESH SYSTEMS... 6 10.1 General Requirements... 6 10.2 Specific Requirements for Hazardous Areas... 6 11. DOCUMENTATION... 7 11.1 General Requirements... 7 11.2 Guidance Regarding Certification... 7 APPENDICES: APPENDIX A BASIC ENQUIRY INFORMATION... 8 APPENDIX B ENVIRONMENTAL CONDITIONS... 9 1

1. SCOPE Electric Surface Heating (ESH) system are designed to satisfy two distinct requirements: 1.1 Temperature Maintenance Maintaining temperature requires the provision of heat to a surface equal to the rate of heat loss due to the temperature difference and its surrounding at the required surface temperature. When starting from a lower temperature the time taken to achieve the required temperature will vary according to the ambient temperature and whether the pipe or vessel is empty, partially filled or completely filled under no flow conditions. 1.2 Process Heating This requires the provision of sufficient heat to raise the temperature of surface and contained material within a stated time, change the state of material or to promote or control a chemical reaction. It may also be necessary to maintain material at the required raised temperature. 2. REFERENCES Throughout this Standard the following dated and undated standards/codes are referred to. These referenced documents shall, to the extent specified herein, form a part of this standard. For dated references, the edition cited applies. The applicability of changes in dated references that occur after the cited date shall be mutually agreed upon by the Company and the Vendor. For undated references, the latest edition of the referenced documents (including any supplements and amendments) applies. BSI (BRITISH STANDARDS INSTITUTION) BS 476 (1984) Part 4 BS 1710 (1984) BS 4683(1971) BS 5345 (1976) BS 5501 (1977) BS 5422 (1977) BS 5970 (1981) BS 6207 (1987) BS 6351 (1981) Part 1 BS 6351 (1983) Part 2 BS 6351 (1983) "Fire Test on Building Materials and Structures" "Specification for Identification of Pipelines and Services" "Classification of Maximum Surface Temperature" "Code of Practice for Selection, Installation and Maintenance of Part 1 Electrical Apparatus for Use in Potentially Explosive Atmospheres (other than Mining Applications or Explosive Processing and Manufacture) "Electrical Apparatus for Potentially Explosive Atmospheres" "Specification for the Use of Thermal Insulating Material" "Code of Practice for Thermal Insulation of Pipework and Equipment, in the Temperature Range -100 C to +870 C" "Specification for Mineral Insulated Copper Sheathed Cables with Copper Conductors" "Specification for Electric Surface Heating Devices" "Guide to the Design of Electric Surface Systems "Code of Practice for the Installations, Testing and Maintenance 2

Part 3 of Electric Surface Heating Systems" IEC (INTERNATIONAL ELECTROTECHNICAL COMMISSION) IEC 540 "Test Methods for Insulations and Sheaths of Electric Cables and Cords" (Elastomeric and Thermoplastic Compounds) IEEE (INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS) IEEE 515 "Recommended Practice for the Testing, Design, Installation and Maintenance of Electrical Resistance Heat Tracing for Industrial Application" NEC (NATIONAL ELECTRICAL CODE) NEC Article 427 "Fixed Electrical Heating Equipment for Pipelines and Vessels" ANSI (AMERICAN NATIONAL STANDARD INSTITUTE) NFPA (NATIONAL FIRE PROTECTION ASSOCIATION) (NOW NATIONAL FIRE CODE) ANSI/NFPA 70 "National Electrical Code" 3. UNITS This Standard is based on International System of Units (SI), except where otherwise is specified. 4. ENVIRONMENTAL CONDITIONS See Appendix A. 5. TYPE OF HEAT TRACING CABLE For winterizing and compensation heating the following heater types can be selected accounting to maximum temperature required for the fluid: 1) Self regulating heaters. 2) Zonal constant wattage parallel heaters. 3) Mineral insulated cable (heaters). 5.1 Self Regulating Heaters Self regulating heat tracing strip typically consists of a temperature dependent heating element, conductor, a jacket or electrical insulation. Additional metal braids/and/or jacket may be used as required. 5.1.1 The heating element shall be a conductive polymeric material with a highly temperature dependent resistivity.heat is generated by passing an electric current along the entire length of the parallel circuit heat tracing strip. 5.1.2 The conductors carry electrical current along the entire length of the parallel circuit heat 3

tracing strip. 5.1.3 Jacket or electrical insulation The heating element shall be electrically insulated with one or more dielectric materials having sufficient thickness and uniformity to provide mechanical and electrical integrity. 5.1.4 Metallic braid The heat tracing strip to be surrounded by a metallic braid to: I) Provide additional mechanical protection, and II) Provide an earth path Under normal conditions the braid shall carry no current. 5.1.5 Mechanical and chemical resistant outer jacket The heat tracing strip shall be surrounded by a protective outer covering to provide added mechanical protection and to protect it from chemical environments (corrosives, solvents, water) which might affect its performance. This protective layer is the outer jacket. 5.2 Zonal Parallel Resistance Heating Tape (Constant Wattage) The zonal parallel resistance heating tape can be utilized when the required heat output on the operating temperage is beyond the capabilities of self regulating heaters. 5.2.1 The zone heater consists of two insulated bus wires wrapped with a thin (38-40 American wire gage) Nichrome heating wire and covered with polymer insulation. The heating wire is connected to alternate bus wires at nodes every 30 to 120 cm. The distance between nodes constitutes a heating zone. A metallic braid or outer jacket between nodes constitute a zone, a metallic braid or outer jacket or both are optional. 5.2.2 The main advantage of this tracer is that it can be cut to length in the field. However one must be aware of node location when cutting, because there will be no heating from the cut to be nearest node. 5.2.3 This tracing cable shall not be used where there is demand for service above 215 C. 5.3 Mineral Insulated Cable for Heat Tracing Mineral insulated cable shall consist of an outer seamless sheet (of copper, stainless steel, ixonel or other approved metal. The insulation shall be magnesium oxide and one or more heating conductors inside. Temperature range shall be upto 850 C. Precaution: Mineral insulated cable chief disadvantage is that it can not be cut to length on spliced in the field. This makes design installation and maintenance more difficult with it than with other type of electric tracer. Because it is a series heater an entire circuit is lost if any section fail. For more information on mineral insulated cable see BS 6207. 5.3.1 Mineral insulated cable shall be factory fabricated in the required length and load in section without splices for the entire length. 5.3.2 The cold section shall be enclosed in a flexible stainless steel conduit. Mineral insulation shall be seated from moisture by an epoxy compound. 5.3.3 The cable shall be provided on both ends with proper seals cold connection leads and metal cable glands. 4

5.3.4 Each cable shall be capable of field bending to an inside radius of six times the cable diameter without damage. 5.3.5 The connection box in which heating section and cold sections are connected shall be water proof. 5.3.6 Cable sheaths conductor and termination materials and cable support clamps shall withstand the design temperature of the pipe equipment, or instruments; and when applicable the steam out temperature. Notes: 1) All type of heaters shall have at least 600 volt minimum dielectric withstand rating operating voltages will be 230 single phase, 230/400-3 phase 4 wire, 50 Hz. 2) Temperature limit of selected cables shall not be exceeded by pipe being traced, under any normal, abnormal or maintenance conditions. 3) Heating cables shall be resistant to organic chemical. 6. MINIMUM SAFETY REQUIREMENTS FOR ESH DEVICE AND CONTROL Minimum safety requirements for ESH devices and control equipment shall comply with the requirements of Clause 3 of BS 6351: Part 2. 7. THERMAL INSULATION* 7.1 General Requirements 7.1.1 The thermal insulation system should be generally in accordance with BS 6351: Part 3, Section 6. 7.1.2 Insulation systems and their installation should also comply with BS 5970 and BS 5422. 7.1.3 Thermal insulation for temperature above 230 C should be non-combustible as defined by the test in BS 476: Part 4 and for temperatures below 230 C Grade P of BS 476: Part 5 will apply unless there are special circumstances. 7.1.4 Where external metallic cladding is specified, care should be taken to ensure that bare edges of the metallic cladding cannot come into direct contact with the ESH device. *Note: Calcium silicate insulation is most commonly used in oil industry for thermal insulation in heat tracing. 8. EXPLOSIVE ATMOSPHERE APPLICATIONS (BASIC REQUIREMENTS) Applications in this category must satisfy a number of interrelated safety standards and codes of practice in the design, installation and maintenance of Electric Trace Heating Systems. Primarily, Section 3 of BS 6351: Part 1 1983 in addition to those specified in Section 2 of the same standard i.e., "Electrical Surface Heating", together with related requirements to BS 4683 "Electrical Apparatus for Explosive Atmospheres" and BS 5501 "Electrical Apparatus for Potentially Explosive Atmospheres" (in line with European Standards and eventually to replace BS 4683) covering the design, construction and installation of orthodox electrical apparatus, are the controlling standards. Related codes of practice are contained in BS 6351 and BS 5345, which describe, amongst other things, various categories of hazard. Unlike design practice applied in the specification and design 5

of orthodox electrical apparatus, the design limits for electric surface heating units depend on a number of interdependent factors, including process temperature, the limiting temperature of the material or "T" classification (BS 4683: Part 1), and the method of installation. 9. FACTORY TESTS OF ESH DEVICES Type tests and routine tests of ESH devices in factory shall be carried out according to requirements of Clauses 7 and 8 of Part 1 of BS 6351. Note: For Precommissioning test after installation and inspection see IPS-I-EL-215. 10. LABELLING AND IDENTIFICATION OF ESH SYSTEMS 10.1 General Requirements 10.1.1 Each ESH device should be identified by means of a non-deteriorating engraved label in accordance with Clauses 9 and 15 of BS 6351: Part 1. 10.1.2 In addition all components of an ESH system should be identifiable both individually and as part of a complete circuit or system. Each power supply point, means of isolation, control equipment, junction box and each feeder or branch circuit should be legibly and durably marked to indicate its purpose. BS 6351: Part 3 sub-clause 11.2.2 gives a recommended basis for equipment and service identification. In addition, however, it is recommended that a further indicator be added to indicate the line or vessel being heated. This could be the workpiece (line or vessel) reference used at the particular plant or site of installation. 10.1.3 Warning labels should also be attached at regular intervals to the cladding over each electrically surface heated workpiece to indicate the presence of concealed ESH equipment, in accordance with sub-clause 11.3.2 of BS 6351: Part 3. These should also give the reference to the ESH circuit involved so that during maintenance the requisite isolation point can be identified. 10.1.4 The labels should be of metals suitable for outdoor installation. The engraved marking and fixing should also be satisfactory for outdoor installation. These requirements are particularly important in saliferous atmospheres. The engraved symbols should not be on a black background. 10.2 Specific Requirements for Hazardous Areas Electrical surface heating device for use in hazardous areas shall be marked in accordance with BS 4683 or BS 5501. Approved components shall be marked with the following information in addition to that specified in Sub-clause 10.1 of this Standard. a) Cables tapes and surface heaters: 1) Certificate number 2) Type of protection 3) Apparatus group b) Cable units, tape units and surface heater units: 1) Manufacturer s type reference or identification 2) Certification mark and certificate number 3) Type of protection 6

11. DOCUMENTATION 4) Apparatus group 5) Temperature classification 11.1 General Requirements 11.1.2 The documentation which shall be made available to client shall include: a) A compiled reference of each workpiece requiring heating. b) Isometric diagrams of pipework indicating locations of flanges, valves and supports. c) Details of insulation on each workpiece. d) The required temperature for each workpiece. e) The thermal capacity of each workpiece and its contents, if process heating is required. f) The calculations of power requirements for each ESH circuit or zone. g) The heating devices selected for each circuit or zone, including calculations of maximum temperature to assess suitability for hazardous area group and temperature classification, if applicable. h) Power supply details for each circuit or zone. i) The reference nomenclature of each item of equipment, e.g., supply cable, heating device, junction box, temperature controller, temperature sensor, circuit breaker, fuseswitch, contactor, etc., for each circuit or zone. Note: Any one piping circuit may be included in more than one heating zone. j) Inspection and test certificates at each stage of assembly and installation, precommissioning and commissioning (where applicable). k) As built drawings of the ESH systems. 11.2 Guidance Regarding Certification For certification of ESH devices for use in a flammable (explosive) atmosphere the Certifying Autority will need to assess the devices for compliance with requirements of clauses referred to in Appendix A of BS 6351: Part 1 (1983). 7

APPENDICES APPENDIX A BASIC ENQUIRY INFORMATION 1) Pipework: a) Pipe nominal bore (mm) and lengths (meters)... b) Pipe material... c) Number of flanges and valves... 2) Vessels: a) Vessel dimensions (meters)... b) Vessel material... c) Dry weight of vessel (kg) or wall thickness... d) Normal operating capacity (m 3 )... 3) General: a) Maintain or raise to temperature. ( C)... b) Ambient temperature, (min./max. C)... c) Maximum operating temperature, if different from "3d"... d) Control temperature, tolerance +/-... e) Indoor or outdoor... f) Corrosive environment and hostile agencies... g) Hazardous area: temperature, classification... h) Thermal insulation material and thickness (mm)... i) Type of product... g) Temperature raise, heat up time... h) Product density (kg/m 3 )... 8

APPENDIX B ENVIRONMENTAL CONDITIONS 1) Site elevation: --------------- meters above seal level. 2) Maximum ambient air temperature: ---------------- degree centigrade. (Bare metal directly exposed to the sun can at times reach a surface temperature of ---------------- degree centigrade.) 3) Minimum air temperature: ----------------- degree centigrade. 4) Relative humidity: -------------- percent. 5) Atmosphere: saliferrous, dusty corrosive and subject to dust storms with concentration of 70-1412 mg/cubic meter,h 2 S may be present, unless otherwise specified. 6) Lightning storm isoceraunic level: -------------- storm days/year. 7) Maximum intensity of earthquake ------------- richters. Note: Blanks to be filled by client. 9