Thermal comfort in primary schools: a field study in Chile

Similar documents
SET. An analysis of thermal comfort in primary schools in Vietnam BOLOGNA. Thi Ho Vi LE 1, Mark GILLOTT 2, Lucelia RODRIGUES 3

Do the constants used in adaptive comfort algorithms reflect the observed responses of children in junior school classrooms?

Children thermal comfort in primary schools in Ho Chi Minh City in Vietnam

Available online at ScienceDirect. Procedia Environmental Sciences 38 (2017 )

Adaptive Thermal Comfort in Warm Dry Climate: Economical dwellings in Mexico

Copyright: URL to conference website: Date deposited: This work is licensed under a Creative Commons Attribution-NonCommercial 3.

AUTHORS SUBMISSION VERSION

Air Movement Preference and Thermal Comfort A survey in classrooms during summer season in Brazil

Information paper 17. Prepared by: David Clark. book:

An Assessment of Thermal Comfort in Hot and Dry Season (A Case Study of 4 Theaters at Bayero University Kano)

Perception of Thermal Comfort for Naturally Ventilated High School Classrooms in San Rafael, CA

Neutral humidity in low cost dwellings in arid climate

Development of the adaptive model for thermal comfort in Japanese houses

SUBJECTIVE AND MEASURED THERMAL COMFORT IN ITALIAN UNIVERSITY CLASSROOMS IN HEATED AND FREE RUNNING CONDITIONS

Evaluation methods for indoor environmental quality assessment according to EN15251

Field Investigation of Comfort Temperature and Adaptive Model in Japanese Houses

Thermal Comfort in Architecture

Investigation of comfort temperature and the adaptive model in Japanese houses

THERMAL COMFORT ANALYSES IN NATURALLY VENTILATED BUILDINGS

Adaptive thermal comfort evaluation of typical public primary school classrooms in Imo state, Nigeria

681: Environmentally Responsive Architecture; Passive Design for School in Southern India

Thermal comfort evaluation of natural ventilation mode: case study of a high-rise residential building

Thermal environment and thermal comfort in a passive residential building in the severe cold area of China

Shifting Comfort Zone for Hot-Humid Environments

Nocturnal natural ventilation for low and zero energy office buildings in Central Chile

INTEGRATION OF LIGHTING PERFORMANCE INDICATORS INTO A DASHBOARD FOR DAYLIGHTING ASSESSMENTS. Beatriz Piderit 1, Daniela Besser 2

Energy and indoor temperature consequences of adaptive thermal comfort standards

AN ASSESSMENT OF THERMAL COMFORT IN NATURALLY VENTILATED ARCHITECTURAL STUDIO IN ABIA STATE UNIVERSITY, UTURU

A Field Study of Thermal Comfort in Open-plan Office Buildings during Transition Seasons in Harbin. Yunsong Han 1, 2, Huixuan Sun 1, 2, Cheng Sun 1, 2

A Comparison of Calculated and Subjective Thermal Comfort Sensation in Home and Office Environment

Bio Climatic Analysis of Bhubaneswar-An Investigation to Arrive Human Comfort through Natural Ventilation

Assessing thermal comfort of dwellings in summer using EnergyPlus

Investigation of the comfort temperature and adaptive model in Japanese houses in summer

Using an inappropriate thermal benchmark leads to overheating in UK primary schools

Evaluation of indoor air quality in classrooms equipped with different methods of ventilation

Findings of Field Survey for Thermal Comfort and Ventilation in US Office Buildings

Short-term acclimatization effects in an outdoor comfort study

Chalmers Publication Library

The Nottingham eprints service makes this work by researchers of the University of Nottingham available open access under the following conditions.

Assessment of thermal comfort in shopping centre transitional spaces

Retrofitting Adaptive Comfort Strategies into Conventionally Air Conditioned Commercial Buildings

Comfort Temperatures Inside Low-Cost Housing Case: six warm climate cities in Mexico

Thermal comfort under transient seasonal conditions of a bioclimatic building in Greece

PREDICTION OF THERMAL SENSATION IN NON-AIR- CONDITIONED BUILDINGS IN WARM CLIMATES

A Comparative Study of the Thermal Comfort of Different Building Materials in Sana a

Are heavyweight buildings more comfortable? The potential of thermal mass in increasing thermal comfort

Modelling Analysis of Thermal Performance of Internal Shading Devices for a Commercial Atrium Building in Tropical Climates

Analysis of Night Ventilation Potential for Residential Buildings in Hot-Humid Climate of Malaysia

CLIMATE CONTROL: INTENT/CRITERIA

THERMAL COMFORT OF A COURTYARD IN GUANGZHOU IN SUMMER

Procedia - Social and Behavioral Sciences 216 ( 2016 )

Thermal comfort assessment of Danish occupants exposed to warm environments and preferred local air movement

REAL-TIME CONTROL OF OCCUPANTS THERMAL COMFORT IN BUILDINGS. Galway, Ireland

Assessment of thermal comfort inside primary governmental classrooms in hot-dry climates Part II a case study from Egypt

CLIMATE CONTROL: OPR

AREN 3050 ENVIRONMENTAL SYSTEMS FOR BUILDINGS I FALL 2005

171: An urban office designed for the southern Brazilian climate

Thermal Comfort Assessment Based on Measurement and Questionnaire Surveys in a Large Mechanically Ventilated Space

Thermal comfort conditions in outdoor spaces

PERSONAL COOLING USING THERMAL CONDUCTION ON THE DESK

Adaptive thermal comfort explained by PMV

Influence of Building Orientation on the Indoor Climate of Buildings

Potential for Improved Outdoor Comfort by Design in U.S. Climates

The applicability of the ISO 7730 (Fanger's comfort model) and the adaptive model of thermal comfort in Jakarta, Indonesia.

Available online at ScienceDirect. Procedia Engineering 169 (2016 )

Field Study of Auckland Housing Winter Indoor Health Conditions Associated with Insulation, Heating and Energy

Thermal Environment evaluation in Commercial kitchens: Procedure of data collection

Allowing for Thermal Comfort in Free-running Buildings in the New European Standard EN15251

ACCEPTED FOR PUBLICTION AUTHORS SUBMISSION VERSION. Please cite the RPG version of this paper using the following DOI: /j.buildenv

Investigation on Hourly and Monthly Thermal Comfort in the Humid Tropics of Malaysia

Application of the adaptive model proposed by ASHRAE 55 in the Brazilian climate context: raising some issues

An Approach to Human Adaptability towards its Built Environment: A Review

Thermal comfort and occupant adaptive behaviour in university offices with cooling and free running modes

Thermal Environment evaluation in commercial kitchens

Comparison between thermal comfort predictive models and subjective responses in Italian university classrooms

Investigation and Analysis of Winter Classroom Thermal Environment. In Chongqing

ATBU, Journal of Science, Technology & Education (JOSTE); Vol. 3 (4), December, 2015 ISSN:

Thermal Comfort Zone for Thai People

THE THERMAL PERFORMANCE EVALUATION OF A FUTURE CHINESE LOWENERGY APARTMENT WITHIN CHANGING CLIMATE IN HOT SUMMER AND COLD WINTER ZONE IN CHINA

Prediction of Thermal Comfort. mech14.weebly.com

ADAPTIVE THERMAL COMFORT - AN EXTENDED APPROACH FOR CONDITIONED INDOOR ENVIRONMENT USING COMPUTATIONAL FLUID DYNAMICS

Passive Strategies and Low-Carbon Technologies: Evaluating the Energy Performance and Thermal Comfort of a Passive House Design

Comfort models as applied to buildings

Climatic Adaptation: Impacts On The Thermal Comfort Of Offices Buildings At Curitiba - Brazil.

ANALYSIS OF ENVELOPE THERMAL BEHAVIOUR THROUGH PARAMETRIC STUDIES. Civil Engineer, PhD, Assistant Professor, Civil Engineering Department (3)

Using passive solutions to improve thermal summer comfort in timber framed houses in South-west France

Thermal Comfort Evaluation of HDB flats

Performance Investigation of Building Ventilation System by Calculating Comfort Criteria through HVAC Simulation

Thermal comfort in Lebanese residential unit case studies: a coastal region in Lebanon

Case Study: Bio-Climatic Building Design for Tropical Climates

Optimization of air tightness and night ventilation for Passive houses in Italian climates under Fanger and Adaptive comfort models

Passive cooling effect of building features in traditional Japanese buildings

Outdoor Thermal Comfort in the Hot Arid Climate The effect of socio-economic background and cultural differences

COMFORT IN AUSTRALIAN OFFICES

GREEN CONCEPT OF THERMAL COMFORT DESIGN FOR SUSTAINABLE HOUSING IN THE TROPICS: Learning from Thermal Comfort in School Buildings 1 INTRODUCTION

Work Package 2: Performance of naturally ventilated buildings

REDEFINING APPROPRIATE THERMAL COMFORT STANDARD FOR NATURALLY VENTILATED BUILDINGS IN TROPICS (SINGAPORE AND INDONESIA PERSPECTIVE)

HUMAN-BEHAVIOR ORIENTED CONTROL STRATEGIES FOR NATURAL VENTILATION IN OFFICE BUILDINGS

INVESTIGATING THE EFFECT OF CO 2 CONCENTRATION ON REPORTED THERMAL COMFORT

Transcription:

Proceedings of 8 th Windsor Conference: Counting the Cost of Comfort in a changing world Cumberland Lodge, Windsor, UK, - April. London: Network for Comfort and Energy Use in Buildings, http://nceub.org.uk Thermal comfort in primary schools: a field study in Chile Maureen Trebilcock, Jaime Soto and Rodrigo Figueroa Department of Architectural Design and Theory, Universidad del Bío-Bío, Concepción, Chile, email: mtrebilc@ubiobio.cl Department of Building Science, Universidad del Bío-Bío, Concepción, Chile, email: jsotom@ubiobio.cl CITEC UBB, Universidad del Bío-Bío, Concepción, Chile, email: rfiguero@ubiobio.cl Abstract This paper presents the first results of a field study on thermal comfort in school buildings that is been carried out in Chile, with the aim of determining comfort temperature of students in state-owned primary schools. The paper presents the results of four schools located in Santiago, a city with low temperatures in winter and high temperatures in summer, which are typically free-running, as they have neither a heating nor a cooling system. The methodology included measurements of thermal parameters complemented with questionnaires based on the adaptive model and modified for the understanding of 9- years-old students. The field work was organized in two phases: winter (August) and summer (December), where in each phase the students responded the questionnaire up to three times per day in a period of three to four days. The results show that comfort temperature derived from the field work is significantly lower than comfort temperature calculated from Humphreys formula, while they also show that students form highly vulnerable schools voted lower comfort temperatures than those from less vulnerable realities. Keywords: thermal sensation vote, primary school, children, comfort temperature Introduction The fact that thermal comfort in school classrooms has a significant impact on children s performance and health (Sensharma et al, 998), while children spend more time in schools than in any other building except at home (Bluyssen, ) evidences the importance of achieving a comfortable thermal environment in school buildings. There are very few studies on thermal comfort in schools (Mors et al ; Teli et al, Montazami and Nicol, ; De Giuli et al ) and their results indicate that children have a different thermal perception compared with adults, suggesting that current comfort standards may not apply to school children, which emphasizes the need of more studies in this field. In Chile, school buildings represent the most passive building typology, as the great majority of them has no heating or cooling system, even in climatic zones with relatively cold winters and hot summers. In addition, they usually have a poorly insulated envelope with single glazing and no solar protection, which results in important indoor temperature variations, both seasonally and daily. Currently, there are no regulations to control the quality of the thermal envelope and the only requirement for thermal comfort is an indoor temperature of C, but only in the southern and colder climatic zones (south on latitude 6 ) where a heating system is required. Post occupancy evaluations in school classrooms in the country (Armijo et al, Trebilcock et al ) have found very low indoor temperatures

in winter and high temperatures in summer, stressing the need for more studies in the field, with the aim of improving thermal comfort of school children. Therefore, this work is based on a field study carried out in Santiago, Chile, which looks at thermal comfort in free running schools in both summer and winter conditions. The adaptive model has proven to be suitable for free running buildings (Nicol et al, ) as it suggests that there is a relation between preferred indoor comfort temperature and outdoor temperature. Methodology The paper presents part of the findings of a larger research project that covered a field study along three cities in Chile, showing only the case studies located in the capital city of Santiago, as they represent one of the most interesting results, due to the fact that the four cases are free-running schools, with different socio-economic backgrounds. In this climatic zone, school buildings are not legally required to have a heating or cooling system, and in general there are very limited regulations that apply to thermal environment. Consequently, students only manage their thermal comfort by regulating the number of articles of clothing they wear.. The context of Santiago Santiago is the capital city of the country, with approximately 6 million inhabitants or 7% of the national population, and an extension of more than 6 km, located at latitude 6 South and longitude 7 West. It has a Mediterranean climate, with an extended dry season in summer, with average temperatures in January varying from C to 9.5 C, and a maximum temperature of C. In winter, average temperatures in July vary from.9 C to.9 C, with minimum temperatures that can go below C, although on very few occasions. Precipitation is concentrated in winter, with an annual rate of 5mm, and low relative humidity with an average of 7%. Figure. Climatic data of Santiago. Selection of cases In the Santiago Metropolitan Area, there are a total of,87 educational establishments, which are categorized based on ownership and administration as public, subsidized, and private. The four case studies were selected from the universe of 5 state-owned schools within this group. The criteria for the selection of cases responded to the need of looking at schools from different socio-economic levels calculated by an index that represent the social vulnerability of the students (IVE SINAE index). This index reflects vulnerabilities associated to poverty, family composition, and all other factors that could lead to academic

desertion. Figure shows the location of the four cases in the urban area of Santiago, as well as their IVE index, where the higher value reflects higher vulnerability of the school s students. According to this, Escuela Membrillar and Escuela República de India receive students from higher vulnerability levels than Liceo Juan Pablo Duarte and Liceo República de Siria. Photographs of each school are presented in Figure. Figure. Location of case studies and their Index of Vulnerability The unit of analysis for each school was one th year elementary class, with students varying in age from 9 to years old, which was chosen for giving a good balance between a minimum age for properly understanding the questionnaire and a longer permanence in the classroom than older children. The number of students in each classroom varied from 5 to, but the number of responses was lower due to school attendance factors. Membrillar School República de India School

República de Siria School Juan Pablo Duarte School Figure : images of the four case studies Figure shows images of all four cases, where it is clear that the schools have different architectural characteristics. In terms of materiality, India, Siria and Juan Pablo Duarte schools have a heavyweight structure with high thermal mass, typically brick and concrete; while Membrillar has a lightweight structure of steel and timber. The thermal envelope is poor in all cases, with single glazing and no wall insulation. All four classrooms analysed have the main glazed façade facing eastwards, but JP Duarte school has an additional glazed area facing north, as it is located at the corner of the building. They are all accessed by an external corridor located at the west of each classroom.. Design of the questionnaire The difficulties associated to the development of questionnaires for students have been discussed by some authors (Teli et al,, Mors et al ). Therefore, the questionnaires for this project were developed according to Teli et al. (), using graphic information and colours that could be more easily understood by children. The questions included thermal sensation, thermal preference, thermal acceptability, clothing and activity. The clothing was simplified to include typical layers that students could wear over their uniform (usually a jumper and/or a parka), in the same way that the activity was simplified to include typical students activities (sitting during the class, running during the break, etc). The questions for thermal sensation vote and thermal preference vote did not include numbers in order to avoid confusing the children, but they did include colours and images accompanying the concepts, which ranged over the seven points scale; using terms in Spanish that are familiar to the children (Figure ).

Figure : the first part of the questionnaire (own elaboration based on Teli et al, ) Each questionnaire was designed to fit in a single colourful page, in order to be simple and attractive for the students, while all questionnaires were put together in a booklet with a front page that registered personal data and the location of the student in the classroom. In this way, each student holds his/her own booklet of questionnaires that had to be responded up to three times per day (8: : and 5:hrs) during the period of study. Field work The field work was carried out in two phases: winter (August) and summer (December). In each phase, the students responded to the questionnaire up to times per day during a period of to days, for a total of 6 answered questionnaires in winter and 7 in summer. The amount of responses was higher in winter than in summer, with a total of 89 responses in winter and 77 responses in summer for all the cases, due to higher absenteeism during the summer period, as it was the week previous to summer holidays. The questionnaire was administered by the class teacher, who was trained by the researchers. The measurements of thermal parameters covered a period of six days, as they started on the previous weekend. They included typical thermal data: dry bulb temperature ( C), globe temperature ( C), relative humidity (%) and air velocity (m/s). The instruments were located at the back/centre of the classroom, at.m high, registering thermal data for one week in winter and one week in summer. It was not possible to locate the instrument at the centre of the classroom due to visibility and security problems, as they were fixed in that position for the whole measurement period. Figure 5 shows the location of the instrument in the classroom.

Figure 5. The instruments in two different case studies: Membrillar School (left) and Siria School (right) The responses were firstly analysed in terms of their consistency, eliminating from the study all those responses that were inconsistent, such as giving a thermal sensation vote of - while stating that they prefer the classroom to be cooler. Measurements The measurements are presented in Figure 6 and Figure 7, which covers dry bulb temperature and external temperature for each case study during the winter period and during the summer period. External temperature was obtained from Quinta Normal meteorological station, located close to the city centre and near the schools. 5.. Temperature C 5.. 5. T ext T int Membrillar T int India T int JP Duarte T int Siria. -5. Figure 6. Internal temperature in each classroom winter period The results show that in winter internal temperatures are generally low, varying between C and 7 C during the occupancy period for India, JP Duarte and Siria School, while temperatures in Membrillar School were C lower than the rest of the cases. These low values are the result of free running schools that lack of an appropriate thermal envelope, or other appropriate design strategy that could help to passively heat the building up in winter.

In addition, Membrillar shows the worst building quality, with a very poorly insulated and leaky envelope. 5.. 5. Temperature C. 5.. 5. T ext T int Membrillar T int India T int Duarte T int Siria. :: :: 6:: 9:: :: 5:: 8:: :: :: :: 6:: 9:: :: 5:: 8:: :: :: :: 6:: 9:: :: Figure 7. Internal temperature in each classroom summer period Similarly, indoor temperatures in summer are high, with maximum temperatures reaching C during the occupancy period. Again, Membrillar School registered the poorest performance, due to its inadequate thermal envelope and lightweight structure that allows internal temperature to fluctuate according to the external temperature, while in the other three cases it is possible to observe the effect of thermal mass. 5 Thermal sensation vote The results of the survey are presented in Figure 8, which shows the correlations between the thermal sensation vote and dry bulb temperature. The regression lines are shown in the graphs, giving the comfort temperature for each case for both winter and summer. The graphs are based on (w) and (s) votes for Membrillar; 88(w) and 9(s) votes for India; (w) and 6(s) votes for JP Duarte; and 98(w) and 9(s) votes for Siria.

Thermal sensation vote - Membrillar School Dry bulb temperature ( C) Summer y =.x - 5.8 R² =.85 Winter y =.998x -.57 R² =.7 Thermal sensation vote - Republica de India School 5 5 Dry bulb temperature ( C) Summer y =.96x -.86 R² =.8 Winter y =.x -.68 R² =.6 Thermal sensation Juan Pablo Duarte School - 5 5 Dry Bulb Temperature ( C) winter y =.78x -.565 R² =.6 summer y =.5x -.765 R² =.6 Thermal sensation vote - Republica de Siria School 5 5 Dry bulb temperature ( C) Winter y =.76x -.7 R² =.668 Summer y =.7x -.77 R² =.8 Figure 8: thermal sensation vote for each case study

Table : Neutral temperature from field study Neutral temperature winter ( C) Neutral temperature summer ( C) Membrillar School 5.5. Republica India School 5.5. JP Duarte School 7. - Republica Siria School 7. - All cases 6.7. Table shows the neutral temperature for each case study, where it is possible to note that the two schools with highly vulnerable students (Membrillar and Republica de India) have significantly lower comfort temperature in winter than those with lower vulnerable students (Juan Pablo Duarte and Republica de Siria). In summer, the responses for Juan Pablo Duarte and Republica de Siria School presented a very low correlation, so only the comfort temperatures for the other two schools are presented in the table. The results of the winter survey considering 89 votes are shown in Figure 9, where the regression line gives a comfort temperature of 6.7 C; while the results of the summer survey considering 77 votes are shown in Figure, giving a comfort temperature of. C. Thermal sensation vote / Dry bulb temperature Thermal sensation vote - 5 5 5 Dry bulb temperature Winter y =.78x -. R² =.9 Figure 9: thermal sensation vote winter period

Thermal sensation vote / Dry bulb temperature Thermal sensation vote - 5 5 5 Dry bulb temperature Summer y =.8x -.87 R² =.97 Figure : thermal sensation vote summer period Table shows the results obtained from using the Humphreys formula (Humphreys et al, ) to calculate comfort temperature based on monthly mean outdoor temperature obtained from meteorological data, for the months when the survey took place. The results show that comfort temperature from the field work is considerably lower than the one calculated from Humphreys formula, for both winter and summer. Table : Comfort temperature from Humphreys formula Comfort temperature from Humphreys formula ( C) July 8.8 August 9.5 November. December.5 6 Conclusions The conclusions of the first analysis of data obtained by this field study show that the comfort temperature derived from the thermal sensation vote of primary school students is significantly lower ( C to C) than those obtained from Humphreys adaptive comfort formula for free running buildings in Santiago. These results could be partly explained by the higher metabolic rate of children. In addition, the results suggest that it might be a relation between the socio-economic vulnerability of the students in each school and comfort temperature in winter, as those students coming from highly vulnerable schools voted lower comfort temperatures than those coming from less vulnerable realities. These results might relate to the very low temperatures registered inside the classrooms, as well as fuel poverty at the children s homes, which motivate them to adapt to very low indoor temperatures in winter. Although these results are based on very few cases, they show a tendency that could be explored further with a larger sample.

7 Acknowledgements This paper is part of the research project Fondecyt N 596 Methodology for the dynamic analysis of thermal comfort during the design process of school buildings funded by the Chilean National Commission for Research in Science and Technology. The authors would also like to thank the teachers and children that were involved in the study, the Ministry of Education and Mrs Gaudy Bravo for their significant contribution. References Armijo, G., Whitman C., Casals, R.,, Post-Occupancy Evaluation of State Schools in 5 Climatic Zones of Chile. Gazi University Journal of Science, (), pp 657. Bluyssen, P.,, The healthy indoor environment: how to assess occupants wellbeing in buildings. London, Routledge. De Giuli, V., et al.,, Measured and perceived environmental comfort: Field monitoring in an Italian school, Applied Ergonomics (in press). Humphreys, M., Rijal, H., Nicol F.,, Examining and developing the adaptive relation between climate and thermal comfort indoors. Proceedings of the Conference Adapting to Change: new thinking on comfort, Cumberland Lodge, Windsor, UK, 9- April. London: Network for Comfort and Energy Use in Buildings. Available at: http://nceub.org.uk Montazami, A., Nicol, F.,, Overheating in schools: comparing existing and new guidelines, Building Research and Information, (), pp 79. Mors, S., Hensen, J., Loomans, M., Boerstra, A.,, Adaptive thermal comfort in primary school classrooms: Creating and validating PMV-based comfort charts, Energy and Buildings, Vol 6, pp 56. Nicol, F., Humphreys, M., Roaf, S.,, Adaptive thermal comfort: principles and practice, London, Routledge. Sensharma, N., Woods, J., A.K. Goodwin, A., 998, Relationship between the indoor environment and productivity: a literature review, ASHRAE Transactions, A, p.. Teli, D., Jentsch, M., James, P.,, Naturally ventilated classrooms: An assessment of existing comfort models for predicting the thermal sensation and preference of primary school children, Energy and Buildings, Vol 5, pp 66-8. Teli D., James, P., Jentsch, M.,, Thermal comfort in naturally ventilated primary school classrooms, Building Research & Information, (), pp 6. Trebilcock, M., Bobadilla, A., Piderit, M., Guzmán, F., Figueroa, R., Muñoz, C., Sánchez, R., Aguilera, C., Hernández, J.,, Environmental Performance of Schools in Areas of Cultural Sensitivity, Proceedings of PLEA (Passive Low Energy Architecture) Conference, Lima, Nov.