Innovative Operation Strategies for Improving Energy Saving in a Cooling Tower System

Similar documents
PERFORMANCE CORRELATIONS FOR COUNTERFLOW COOLING TOWER

RETRO-COMMISSIONING OF A HEAT SOURCE SYSTEM IN A DISTRICT HEATING AND COOLING SYSTEM Eikichi Ono 1*, Harunori Yoshida 2, Fulin Wang 3 KEYWORDS

Performance Improvement on Water-cooled Cold-Plate

HVAC INTEGRATED CONTROL FOR ENERGY SAVING AND COMFORT ENHANCEMENT vahid Vakiloroaya

Performance Mapping for Variable Ductless Heat Pump Systems in Heating, Cooling and Defrost Operation

Chapter Six{ TC "Chapter Six" \l 1 } System Simulation

Application of a cooling tower model for optimizing energy use

EFFECTS OF WEATHERS AND INDOOR TEMPERATURES ON PERFORMANCE OF ENERGY RECOVERY VENTILATOR. Yanping Zhou, Jingyi Wu, Ruzhu Wang

Company Introduction HEATERS. Joint Venture: TIME FOR A COOL CHANGE

Are You Getting 100%?

Application of Near-Optimal Tower Control and Free Cooling on the Condenser Water Side for Optimization of Central Cooling Systems

FLOTATION CONTROL & OPTIMISATION

Compound ejectors with improved off-design performance

CONTROL STRTEGIES FOR FLEXIBLE OPERATION OF POWER PLANT INTEGRATED WITH CO2 CAPTURE PLANT

COUPLING MODEL AND SOLVING APPROACH FOR PERFORMANCE EVALUATION OF NATURAL DRAFT COUNTER-FLOW WET COOLING TOWERS

Investigation on conformal cooling system design in injection molding

Research on Optimization of Metallurgical Process Based on Data-Driven

The 3-D Numerical Simulation of a Walking Beam Type Slab Heating Furnace with Regenerative Burners

Process Control and Optimization Theory

Optimization of NCG System Lineups

GLOBAL OPTIMISATION OF CHILLER SEQUENCING AND LOAD BALANCING USING SHUFFLED COMPLEX EVOLUTION

A Modified Heat Pump Air-Conditioning System for Electric Vehicle

12th International Conference on Fluidized Bed Technology

CHAPTER 3 MODELLING AND SIMULATION

VARIABLE STRUCTURE CONTROL

Technical Note OPTIMIZATION OF THE PARAMETERS OF FEEDWATER CONTROL SYSTEM FOR OPR1000 NUCLEAR POWER PLANTS

A Comparison of Methods to Verify Energy-Saving Benefits for Chillers

A Sensitivity Analysis on Mixing Energy Loss in Air-Conditioned Rooms by Using CFD

Production Scheduling System for Oil and Gas Storage and Transportation Based on GIS and SCADA Technology

Process intergration: Cooling water systems design

Technical Feasibility Study of Hybrid Ventilation for a High-rise Office Building in Shanghai

Motor Systems Optimization Case Studies in the Peoples Republic of China

Whole Building Energy Performance Evaluation through. Similar Control Strategies

OPERATING PARAMETERS Reliable Means to Continuously Monitor Facility Performance

Intelligent. Powerful. Proven. usa.siemens.com/demandflow

D DAVID PUBLISHING. Optimizing Thermal Energy Storage Systems in the Hospitality Industry. 1. Introduction

IMPLEMENTATION OF ANALYTICAL MODELS FOR PASSIVE DOWN-DRAFT EVAPORATIVE COOLING (PDEC) TOWER WITH SPRAY SYSTEMS

Performance enhancement of a photovoltaic thermal (PVT) and ground-source heat pump system

A New Approach in Control Valve Design With a New Hybrid Flow Characteristic

Study on Valve Management of DEH for Steam Turbine *

A Research Reactor Simulator for Operators Training and Teaching. Abstract

EXPERTISE BEYOND CONTROLS QUENCH CONTROL. Application. A standard quench control application to significantly improve the simple PID loop approach.

Shunt Active Power Filter Wind Energy Conversion System

additional cooling energy consumption. Because the thermal resistance of windows has always been a weak point, even with vacuum glass or low-e glass,

DYNAMIC SIMULATION OF A PROTON EXCHANGE MEMBRANE FUEL CELL SYSTEM FOR AUTOMOTIVE APPLICATIONS

Special edition paper Research on Utilizing Air Thermal Energy for Railway Facilities

The Benefit of Variable-Speed Turbine Operation for Low Temperature Thermal Energy Power Recovery

ANALYSIS FOR NATURAL CIRCULATION LOOP

UNDERFLOOR AIR DISTRIBUTION INTEGRATED WITH AN INDIRECT AND DIRECT EVAPORATIVE COOLING ASSISTED 100% OUTDOOR AIR SYSTEM

WLTP Validation 2. Evaluation Issues. ACEA Guidance Document. after Bern

International Forum on Energy, Environment Science and Materials (IFEESM 2015)

Introduction to Pinch Technology

Modeling Techniques for Increased Accuracy

ARMSTRONG DESIGN ENVELOPE FAQ

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

Proceedings of BS2013: 13th Conference of International Building Performance Simulation Association, Chambéry, France, August 26-28

Dynamic Heat Process in a Climate Chamber

Everyone can be an Expert. Electrochemical Detector. Autosampler. Complete HPLC-ECD

CASE STUDIES IN USING WHOLE BUILDING INTERVAL DATA TO DETERMINE ANNUALIZED ELECTRICAL SAVINGS

The impact of the work under partial load on the energy efficiency of an air-to-water heat pump

Influence of the control strategy on the heat rejection potential and electricity consumption of air-to-water condensers for solar cooling systems

Batch Annealing Model for Cold Rolled Coils and Its Application

Study of the Electric Vehicle Heat Pump Air-conditioning System

The energetic optimization of water-water heat pump heating systems

ERT 318/4 UNIT OPERATIONS SEMESTER 1 (2013/2014)

A Method for On-Going Commissioning of VRV Package Systems Using a. Simulation Model

DESIGN OF LIQUID COOLING FOR HIGH HEAT DISSIPATION ELECTRONIC BOARDS USING CFD

Evaluation of the Impact of Off-Design Operation on an Air-Cooled Binary Power Plant. G. L. Mines. September 22, 2002 September 25, 2002

Performance Analysis for Natural Draught Cooling Tower & Chimney through Numerical Simulation

PINCH ANALYSIS: For the Efficient Use of Energy, Water & Hydrogen. PULP AND PAPER INDUSTRY Energy Recovery and Effluent Cooling at a TMP Plant

OPTIMAL CONTROL OF CHILLER PLANTS USING BAYESIAN NETWORK

ME 215. Mass and Energy Analysis of Control Volumes CH-6 ÇANKAYA UNIVERSITY. Mechanical Engineering Department. Open Systems-Control Volumes (CV)

Administrative Building Cooling Tower. University of Tennessee Chattanooga

FIELD TEST STUDY ON THE PERFORMANCE OF AIR SOURCE HEAT PUMP IN LOW TEMPERATURE IN BEIJING

Study on the deformation process of titanium alloy bars based on compact hot continuous rolling

40-Ton Articulated Truck Cooling System Modelling Using STAR-CCM+

Persistence Tracking in a Retro-commissioning Program

Simulation and Design of Fuzzy Temperature Control for Heating and Cooling Water System

Chiller plant optimization

In typical commercial buildings, water-cooled chilled water plants use a signifi cant amount of energy.

Modelling and Control of Fuel Cell and Micro Gas Turbine Hybrid Power System for Ship Application

A Case Study in Energy Modeling of an Energy Efficient Building with Gas Driven Absorption Heat Pump System in equest

Transient and Succession-of-Steady-States Pipeline Flow Models

High Efficiency Operation Method for Solid Oxide Fuel Cell System

OPTIMIZATION OF HIGH QUALITY PRODUCTION IN HOT ROLLING MILLS USING ADVANCED PROCESS MODELS*

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

ADVANCED HYBRID MODELLING OF SEPARATORS FOR SAFE DESIGN IN OIL/GAS PRODUCTION PLANTS

PINCH ANALYSIS: For the Efficient Use of Energy, Water & Hydrogen. PULP AND PAPER INDUSTRY Energy Recovery and Effluent Cooling at a TMP Plant

ADVANCED PROCESS CONTROL

VERIFICATION OF OPTIMUM OPERATION METHOD BY SIMULATION FOR THE HVAC SYSTEM WITH A THERMAL STORAGE TANK IN AN ACTUAL BUILDING

DANIELI S GREEN STEEL VISION: FIRST STEP TOWARDS ZERO ENERGY FTP AT ABS STEELMAKING PLANT (ITALY)*

Study on the heat transfer model and the application of the underground pipe system

Improvement of Cooling Process for Strip in Annealing & Coating Line

Simulation on Cooling System of Automotive Waste Heat Thermoelectric Generator

Performance Evaluation of Cooling Tower in Thermal Power Plant - A Case Study of RTPS, Karnataka

Performance Analysis of Cooling Tower

CONSIDERATIONS REGARDING THE OPTIMIZATION OF A RENEWABLE ELECTRICAL ENERGY GENERATION SYSTEM'S FUNCTIONING

Lecture 8. Design of cooling systems for effluent temperature reduction. L08-1 Energy System Design Update

Predictive Intelligence Optimizing Performance & Reliability. Neeraj Agarwal Manish Khetrapal

Optimal Design for a Hybrid Ground-Source Heat Pump

Transcription:

58 China Steel Technical Report, Innovative No. 28, Operation pp.58-62, Strategies (2015) for Improving Energy Saving in a Cooling Tower System Innovative Operation Strategies for Improving Energy Saving in a Cooling Tower System YING TSOU*, CHUN-CHENG CHANG* and SHI-SHANG JANG** *New Material Research & Development Department, China Steel Corporation **Department of Chemical Engineering, National Tsing Hua University In cooling towers, the replacement of traditional single-speed fans with Variable-Frequency Drive (VFD) fans or two-speed fans can achieve significant energy saving. However, concerns regarding frequent on/off switching and the lack of a well-devised controller discourage the widespread implementation. In this study, a temperature zone setting method is proposed to replace the traditional point setting method on fan control strategy. We also developed a multi-fans control strategy. Additionally, the highest allowed temperature of output water in the process is set as the upper limit of a temperature zone in order to further conserve energy. Both strategies are comprehensively analyzed for a virtual cooling tower that uses operational data from an existing VFD-fan-based cooling tower system at CSC. The results of on-site implementation show energy savings of 38% for a 0.75 C zone without increasing the on/off switching frequency. The proposed strategies were further verified by an on-line field experiment. The proposed strategies can be universally and easily applied to any existing cooling tower with significant energy conservation. Keywords: Cooling tower, Variable-frequency drive, Zone setting control 1. INTRODUCTION Cooling towers are a commonly utilized device of industrial plants, especially in energy-intensity sectors such as the iron, steel, or petrochemical industries. A cooling tower dissipates heat to the atmosphere through a combination of heat- and mass-transfer processes. Many studies in cooling towers have focused on design (1-3) and performance parameters (4,5) to improve the performance of cooling towers. Those results told us that any improvement in cooling tower operations would provide significant opportunity for energy conservation. Variable-Frequency Drive (VFD) devices have been available for more than four decades, but were not applied to cooling tower fans until their prices fell sharply over the past decade (6-8). Recently, two-speed fans have been gradually replaced with VFD-fans. Practical concern is how to avoid frequent start/stop fan operation, which can cause sudden increases in stress due to the large inertia moment. This drawback prevented widespread implementation of cooling systems based on VFD-fans. The energy-saving potential of VFD-fans is more compelling and significant in large-scale, multi-cell systems used in energy-intensive industries (9,10). This study proposes two operational strategies to fully exploit the energy-saving potential represented by VFD-fan-based cooling tower systems. Feedback control is not used in traditional cooling towers, due to a lack of operational choices. With improving affordability, VFD fans have gained popularity and gradually replaced two-speed fans in cooling towers. This provides a great opportunity to fully exploit the energy-saving potential of VFD technology by applying feedback control to ensure outlet water temperatures are maintained at set points. Nevertheless, frequent on/off switching of fans and the lack of a well-devised controller prevented industry from widely adopting this technology. As an alternative, rule based coded Programmable Logic Controllers (PLC) were used instead of the feedback controller. The control of the outlet water temperature at the highest allowable temperature is then compromised, as is the energysaving potential associated with the introduction of VFD-fans. The shortfall is more apparent in a largescale cooling tower system comprising multiple cells. Therefore, this study proposes two operational strategies to fully exploit the energy-saving potential of VFD-fan-based multi-cell cooling towers. The content of this article includes five sections. Besides the introduction in Section 1, Section 2 presents the theoretical development and step-by-step implementation of the proposed strategies. The strategies will be modeled using operational data acquired from an existing cooling tower with variable-fan cooling in

Ying Tsou, Chun-Cheng Chang and Shi-Shang Jang 59 Section 3, and the virtual cooling tower is established by this model. The proposed strategy validation, implementation and on-line experiments are documented in Section 4. The final section presents a brief summary of the findings. 2. OPERATIONAL STRATEGIES Section 2.1 describes the effects of a larger approach value on energy savings during fan operation. Section 2.2 details the implementation and theoretical development of zone setting Proportional-Integral (PI) controllers. 2.1 Larger approach strategy Two kinds of temperature differences are indexed for the design and operation of tower systems, namely, the range and approach. The temperature difference between water entering and leaving the cooling tower is called the range. The range is determined using the heat load and water flow rate, rather than by the thermal capability of the cooling tower. The difference between the outlet water temperature and the wet-bulb temperature of inflowing air is termed the approach. At steady state, the heat load and water flow are constant and thus, the range is also constant. Subsequently, the enthalpy driving force increases as the outlet water temperature increases. Taking the selected cooling tower as an example, the operational conditions are assumed as follows: input water temperature of 35.0 C, air temperature of 25.4 C, relative humidity of 75%, and ratio of liquid to air flow rate of 2.02. If the output water temperature is 31.5 C, then the operation line is AB and the driving force is the average distance between line AB and line A B, as shown in Fig.1. If the output water temperature is maintained at 33.0 C, then the operation line shifts to the line CD; the driving force becomes the average distance between line CD and line C D, which is larger than the previous case. Operations with a large driving force consume less energy. For the operation of an existing cooling tower, a large driving force requires a large approach and as indicated in Fig.1, a high outlet water temperature. Equipped with feedback control, a cooling tower with variable-speed fans can be automatically operated at the highest allowable outlet temperature. 2.2 Temperature zone control strategy For a feedback control system, two process variables must be identified: the controlled (CVs) and manipulated (MVs) variables. In a VFD-controlled cooling tower, operators adjust the fan operating frequency (Hz), which in turn determines the fan speed and controls the outlet water temperature. Given the relationship between fan operating frequency (Hz) and power requirement, the power necessary to achieve the desired outlet water temperature can be calculated. Hence, outlet water temperature and fan power are considered as CV and MV respectively. In the following feedback controller, the objective is to reduce the error to zero: e k= y sp,k- y k...(1) where K is the sequence index, e k is the error term on the kth run, y k is the measured value of the CV at the kth run, and y sp is the set point of the CV. The discrete PI control algorithm is considered the most appropriate, given its flexibility, computational simplicity, cost effectiveness, and transparency. The goal of feedback control is to maintain the measured value of the CV at its set point. In this study, the measured value of the CV can be lower than the set point during periods of cold weather. When this occurs, the integral term accumulates until the controller output eventually fails. The velocity form of PI control is chosen in order to avoid this problem for the proposed temperature control. This approach inherently resolves anti-reset windup, because the summation of errors is not explicitly calculated. The velocity form of the formula for discrete PI control is described in Eq.(2). P k+1= P k +K c +[(e k -e k-1 )+ ( t/τ I )e k ]...(2) Fig.1. Driving force diagram for the studied cooling tower. Here, P is the value of the MV, namely the power requirement of fan set; K c is the controller gain; τ I is an adjustable parameter and is referred to as integral time; t is the sampling period, and K c and τ I are determined by a data-driven estimation.

60 Innovative Operation Strategies for Improving Energy Saving in a Cooling Tower System In order to reduce the number of on/off events, the temperature zone control strategy is adopted in this work. When the measured outlet temperature is outside the temperature zone, the target is set as the zone mid-value; the target is set to the present outlet temperature when its value is within the zone i.e..... (3) Fig.2. Modeled sets of the virtual plant. where T UL and T LL are the upper and lower limit values, respectively; and T sp is the set point temperature, i.e. T sp ( T UL + T LL )/2. The three values have the following relationship: The power requirement can be calculated using Eq.(3). If the outlet temperature remains within the target zone, no adjustments are necessary and so the power requirement remains constant. 3. VIRTUAL PLANT ESTABLISHMENT This study uses real operational data of CSC s #300k cooling tower system from an eight-day period in late March, 2014 to model the energy-saving effect of the proposed strategies. During that period, average daily energy consumption was 1334.6 kwh, and statistics for cooling water and air properties are shown in Table 1. The air temperature and humidity data reflect the typical spring season in Taiwan. Table 1 Ambient air and cooling-water data used to model a virtual plant Tw,in Tair H (%) Tw,out Max. 36.6 31.9 94.6 32.9 Min. 32.6 18.8 52.3 30.2 Average 34.7 25.4 74.6 31.6 Standard Deviation 0.7 3.2 7.8 0.5 The model estimates outlet water temperature for the selected cooling tower, which is a function of inlet water temperature, air temperature, relative humidity, water flow rate, and air flow rate. The following Eq.(4) is obtained from linear regression of the first seven days data in Fig.2, and functions as the virtual cooling tower system: T w,out = 0.54 T w,in,1 + 0.21 T w,in,2 + 0.63 T w,in,3 +0.92 H - 0.01 P + 0.02...(4) where T w,in,1, T w,in,2, and T w,in,3 are the temperatures of each inlet water stream; T air is air temperature; H is relative humidity; and P is total power consumption of the cooling tower fans. Figure 2 shows the modeled and prediction results. Besides the data from the first seven days are implemented as the modeled set, the data of the last day are used as the prediction set. The model gives an R 2 value of 0.85 and the Mean Square Error (MSE) of the prediction set is 0.05. The results indicate that the model can accurately represent a cooling tower system to examine the implementation of the proposed operational strategies. To validate the proposed strategies, the virtual plant must be equipped with a PI feedback controller, which replaces the rule-based PLC used in the existing system. The construction of the proposed control loop is described in Section 2. To reduce on/off switching of the fans, this PI feedback controller must adopt hybrid operations that combine rule- and equation-based operations. When ambient air temperature is low, partial startup of the four-fan set can sufficiently cool the water. Once all fans are required i.e., power requirement exceeds 55.36 kw, the Eq.(5) is executed: f = 12.1+0.006p 3-0.12p 2 + 0.4p...(5) where f is the operated frequency and p is the power requirement. In equation, the MV (i.e. power requirement) is calculated automatically in the controller. The proportional and integral parameters, K c andτ I, of the controller in the virtual system are calculated via the data-driven method. K c and τ I are obtained as 42.62 and 0.52 respectively. The heat load of the process is assumed to be constant during the studied period.

Ying Tsou, Chun-Cheng Chang and Shi-Shang Jang 61 4. VALIDATION OF THE PROPOSED STRATEGIES Two short term field experiments were conducted to demonstrate the validity of the proposed strategies. Considering of the maximum allowable temperature of water in outlet (32.5 C) and some tolerant value, we conducted the first experiment by the traditional (precise target) feedback control with a set point of 32 C to verify the large approach strategy control, and was run from 10:35 to 15:50 on a day in late spring. During the experimental period, average air temperature was 27.2 C, relative humidity was 57.9% and wet-bulb temperature was 21.1 C. Figure 3 clearly shows that the traditional feedback control keeps adjusting the fans power, and after one or two cycles, the outlet temperatures gradually converge to the set point. Figure 3 shows corresponding temperature and power profiles for the simulated rule-coded PLC operation that was run at the same time. At 12:35, the outlet temperature dropped below 31.5 C, causing one of the fans to be turned off. During this period, the average power level was 47 kw, while that for the original PLC operation would be 55 kw. The energy saving was about 14.5% by applying the large approach strategy. However, the proposed control method involves 11 on/off operation, compared with 1 for the original PLC operation. Observably, the large approach strategy had the shortcoming of much more on/off switching cycles than original operation. feedback control with a 0.5 C zone as described in Section 2. During the experimental period, average air temperature was 31.0 C, relative humidity was 59.3%, and wet-bulb temperature was 24.5 C. The target temperature zone was set between 32.0 C and 32.5 C. Figure 4 shows that the temperature dropped below the lower bound of the zone interval; at 10:30, the fan frequencies decreased with resulting energy consumption of 55.3 kw. The temperature remained below the lower zone boundary; at 10:34, one fan turned off, and the frequency of the other increased from 35 to 40 Hz, with resulting energy consumption of 50.4 kw. At 11:00, the temperature remained below the lower bound of the zone interval; the frequency of the one operational fan decreased from 40 to 35 Hz, with resulting energy consumption of 44.8 kw. At 11:30, the temperature exceeded the lower bound and the same fan increased frequency from 35 to 40 Hz. In summary, the fan operation was only adjusted when the temperature dropped below the lower limit; otherwise, it remained unchanged. The experimental period involved 14 fan adjustments, with only 1 on/off operation. The outlet water temperatures were controlled around the target region. Fig.4. Experimental zone temperature control strategy. Fig.3. Field experiment using precise feedback control with set point of 32 C. To overcome the shortcoming of large approach strategy with point setting control, the zone setting strategy was employed. The second field experiment was run from 9:45 to 13:15 on the next day, using PI Under the same ambient air conditions as the field experiment, the operations following the rule-coded PLC are documented in Fig.4. At 10:00, outlet water temperature was 32.5 C; according to the PLC rules, all fans turned on, with corresponding energy consumption of 63 kw. Subsequently, the temperature fluctuated slightly but never dropped below 31.5 C, and therefore all the fans remained on. Average energy consumption of zone control throughout this period was 56.3 kw,

62 Innovative Operation Strategies for Improving Energy Saving in a Cooling Tower System compared with 63 kw for the original PLC operation. The zone control case required 1 on/off operation, whereas the PLC scenario required none. The second case showed that combine the proposed large strategy and zone setting control can really save energy without increasing much more on/off switching cycles than the original PLC operation. The results of two months on-site implementation further showed that for the 0.75 C zone, daily energy consumption was 826.2 kwh, which was 62% of the original energy consumption and the 63 times of on/off cycle was much lower than the original mode (103 times). In other words, by employing a PI controller operating a temperature zone strategy, a VFD fan can achieve 38% energy saving in a cooling tower without increasing the frequency of on/off switching. It is worth saying that we can save energy by just applying the proposed strategies to the PLC system without installing any new hardware. 5. CONCLUSION The replacement of traditional two-speed fans with VFD-fans in a cooling tower can significantly reduce energy use. Concerns of frequent on/off switching and the lack of a well-devised controller lead to conservative operations, which allow for further improvements in energy efficiency. In this work, a PI feedback controller with a temperature zone setting was proposed for an existing VFD-controlled cooling tower system to manage the outlet water temperature while reducing fan energy consumption and solving the problem of frequent on/off switching. A successful on-site implementation verified the proposed strategies. The results showed that the original energy consumption can be reduced by 38% with a 0.75 C temperature zone without increasing on/off switching frequency. It is worth noting that the proposed strategies can be implemented without further investment or any additional hardware if the existing system is operated by a Distributed Control System (DCS). The cost of purchasing the additional hardware needed is still much lower than that of maintaining the original operating strategy, given the long-term economic benefits of energy saving, not to mention the reduction in CO 2 emissions. It was concluded that the proposed energy-saving strategies are very promising for further improvements in any VFD-fan-based cooling tower system. REFERENCES 1. N. Milosavljevic and P. Heikkilä: Applied Thermal Engineering, 2001, vol. 21, pp. 899-915. 2. M. H. Panjeshahi et al.: Chemical Engineering Research and Design, 2009, vol. 87, pp. 200-209. 3. Zou Z et al.: Energy Conversion and Management, 2013, vol. 76, pp. 945-955. 4. F. W. Yu and K. T. Chan: Applied Energy, 2006, vol. 83, pp. 628-648. 5. T. H. Pan et al.: Energy Conversion and Management, 2011 vol. 52, pp. 1377-1385. 6. CTI 105-ATC (00) CTI Code Tower Standard Specifications for Acceptance Test Code for Water Cooling Towers: Cooling Technology Institute, 2000, pp. 67-69. 7. G. F. Cortinovis et al.: Energy Conversion and Management, 2009, vol. 50, pp. 2200-2209. 8. J. G. Wang et al.: Energy Conversion and Management, 2013, vol. 73, pp. 226-233. 9. N. Muntean, C. Volosencu and A. Hedes: The 9 th WSEAS International Conference on International Conference on Automation and Information, Bucharest, Romania, 2008, pp. 184-189. 10. F. W. Yu and K. T. Chan: Applied Energy, 2008, vol. 85, pp. 931-950.