TABLE OF CONTENTS. PUD SERVICE TERRITORY & CONTACTS... Page 1. NEW SERVICE QUESTIONNAIRE... Page 2. TRENCHING SECONDARY (120/240 volts)...

Similar documents
Section 4 Underground Service

Electric Service Handbook

Post Office Box 500 Carson, WA Phone (509) Fax (509) Toll Free (800)

Contact Clark Public Utilities Construction Services department at (360) to initiate a request for service.

[Type text] Heber Light & Power. Developers & Excavators. Electrical Service Requirements Manual

Basic Service. This Section provides information regarding a. Introduction

GENERAL NOTES PEDERNALES ELECTRIC COOPERATIVE, INC. RESIDENTIAL AND COMMERCIAL AMP METER LOOP SPECIFICATIONS

UNDERGROUND SERVICES - GENERAL SERVICE AND MULTI-UNIT RESIDENTIAL

NORTHEASTERN REMC ELECTRIC STANDARDS MANUAL

NORTHEASTERN REMC ELECTRIC STANDARDS MANUAL

Effective June, Eaton-Durham Model # UTRS223ACH. Siemens, Model # SUAS877-PG. (or Landis & Gyr # UAS877-PG) Milbank. Model # U1980-O.

PRIMARY LINE EXTENSION

Please check with your local inspection authority for any additional requirements before installation.

Electric Service Handbook

UNDERGROUND SERVICES (RESIDENTIAL) SINGLE FAMILY RESIDENTIAL, DUPLEXES, OR TOWNHOUSES

UNDERGROUND SERVICES SECONDARY

ELECTRICAL SERVICE UPGRADE RESIDENTIAL AND COMMERCIAL QUICK INFORMATION REFERENCE

OVERHEAD SERVICES - SECONDARY

Underground Residential Distribution (Specifications for Installation) PES March 2008 Spec 11

Welcome to Douglas County PUD

(Condensed from National Electric Code)

An altered service that is moved, upgraded (ex., 200 to 400 amp) or changed to meet today's standards for electric service.

Section 2: Underground

Specifications for Residential Underground Electric Service Installation

Huntsville Utilities Underground Residential Service Requirements

RESIDENTIAL QUICK REFERENCE

Specifications for Residential Overhead Electric Service Installation

ELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS

Specifications for Residential Overhead Electric Service Installation

CONSTRUCTION HANDBOOK Guidelines and Information for Members, Builders & Developers

If a new residence s electrical service is not located within 200 feet of existing

Section 7: Specifications

TEMPORARY FACILITIES

OVERHEAD SERVICES - RESIDENTIAL & GENERAL SERVICE. See Chapter 3, Section 3.01 for more information about point of entrance (POE).

Electric Service Standards

OVERHEAD SERVICE. Table of Contents - Section 400

ELECTRIC DEPARTMENT CONSTRUCTION STANDARDS

CONDUITS AND FITTINGS

Electric Engineering Division RESIDENTIAL CONDUIT RULES AND REGULATION. S:\COO_ACM_US_Electric_Telecommunications\COO_ET_Engineering\Conduit Policies

COMMERCIAL CONDUIT RULES AND REGULATIONS

Merrimac Municipal Light Department. Commercial Developments Policy

CHAPTER 11 CONDUITS AND FITTINGS

1. Contractor shall obtain a valid electrical permit from the Town of Perinton.

SPECIAL SPECIFICATION 6623 Multi-Duct Conduit System

a) Line and load compartments must be separated by a stable barrier.

Large Basic Service. This Section applies to members requiring new. Introduction. Service Types

A. Section Includes: Electrical site utilities and coordination of requirements with the utility company and service specifications.

CITY OF UNION, OREGON TECHNICAL SPECIFICATIONS SECTION 9 UNDERGROUND UTILITIES

SECTION UNDERGROUND ELECTRICAL CONSTRUCTION

6. SECONDARY SERVICES (under 600 volts) 6.1 AVAILABILITY For the electrical characteristics of available secondary services see Section 3.4.

6. SECONDARY SERVICES (under 600 volts) 6.1 AVAILABILITY For the electrical characteristics of available secondary services see Section 3.4.

Central Lincoln PUD Single-Family Residential Guidelines & Standards April 21, 2017

SECTION CONDUITS AND BOXES PART 1- GENERAL. A. Work covered by this section includes the furnishing and installation of conduits and boxes.

SALEM CITY POWER ELECTRICAL REQUIREMENTS & STANDARDS MANUAL

SECTION ELECTRICAL SITE UTILITIES

Indianapolis Power & Light Company

ELECTRICAL UTILITY CONSTRUCTION REQUIREMENTS FOR PLATS & LAND DEVELOPMENT

TEMPORARY METER POLE INSTALLATION

Metering Installations for Mobile Homes or Mobile Home Parks:

UNM IT/Telecommunications Guide Specification Communications Underground Ducts, Raceways and Structures /27/06

Electric Service Requirements. Residential Overhead. Engineering Specification T002. February

400 watt, high pressure sodium. Type C watt, high pressure sodium Collector Street Light Units

Residential Electric Policy

Specifications for Electrical Underground Residential Distribution Systems

Gas meter clearances and service installation requirements

Welcome to Douglas County PUD

CONSTRUCTION SPECIFICATION FOR GROUNDING

Underground Service Requirements and Instructions

SECTION ELECTRICAL UTILITY SERVICES

Central Lincoln PUD Commercial Service Guidelines & Standards

Primary Contact: Owner Customer Electrician Builder

City of Santa Monica Building and Safety Division

ANY SPECIFICATION DRAWINGS OR DATED PRIOR TO SEPTEMBER 2015 WILL NOT BE HONORED.

ELECTRICAL SAFETY Information Bulletin

1993 SPECIFICATIONS CSJ SPECIAL SPECIFICATION ITEM 4110 CONCRETE ENCASED DUCT BANK

DIVISION 26 RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS PART 1 - GENERAL RELATED DOCUMENTS

3. Intermediate metal conduit (IMC). 4. Electric metallic tubing (EMT). 5. Flexible metal conduit (FLEX). 6. Polyvinyl chloride conduit (PVC).

OPERATING PROCEDURE NO. 310

METERING INSTALLATION

WIRING METHODS CHAPTER 38

ASTM C857 A -16 AASHTO H -20 (for vaults beneath roadways) ASTM C857 A-8 (for vaults beneath incidental light truck traffic)

A. Product Data: For surface pathways, wireways and fittings, floor boxes, hinged-cover enclosures, and cabinets.

SECTION GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY

SECTION UNDERGROUND ELECTRICAL CONSTRUCTION

CITY OF OCEANSIDE. Electrical Lines, Plumbing and Mechanical Burial & Support Requirements. Informational Bulletin

For more information contact: Engineering Department (800) Ext RURAL RESIDENTIAL SERVICE INSTALLATION GUIDE.

Specifications for Electrical Underground Distribution Systems from Overhead Transformation, Apartments & Condominiums

VOLUME 15 Section 6: Gas Metering Guidelines

Electric Service Requirements & Guidelines

Electric Service Requirement Handbook

SPECIAL SPECIFICATION 6664 Level (3) Communications System

CONSTRUCTION STANDARDS SECTION CS 15 STREET LIGHTING

SPECIAL SPECIFICATION 6658 Time Warner Communications System

SECTION PATHWAYS FOR ELECTRONIC SAFETY AND SECURITY

Permit Requirements Mobilehome Park Utility Upgrade Program

Request for Electric and Gas Service Form

SERVICE ENTRANCE SPECIFICATIONS FOR RESIDENTIAL AND COMMERCIAL

Member Service Electric Wiring Guidelines

Gainesville Technical Center 5399 Wellington Branch Drive Gainesville VA Phone (703)

Transcription:

UNDERGROUND

TABLE OF CONTENTS PUD SERVICE TERRITORY & CONTACTS... Page 1 NEW SERVICE QUESTIONNAIRE... Page 2 GENERAL... Page 3 TRENCHING SECONDARY (120/240 volts)... Page 3 CONDUITS FOR PUD-INSTALLED CONDUCTORS... Page 5 PUD OR CUSTOMER-INSTALLED SECONDARY SERVICE WIRE (120/240 volts)... Page 7 RESIDENTIAL SERVICE EQUIPMENT... Page 8 METER PEDESTAL - 200 AMP SERVICE... Page 14 METER PEDESTAL - 400 AMP SELF-CONTAINED & 400 AMP CT RATED... Page 16 CONVERSIONS, OVERHEAD TO UNDERGROUND...Page 20 PRIMARY SERVICE (7200 Volts) - RESIDENTIAL SYSTEMS ON PRIVATE PROPERTY...Page 22

PUD Service Territory PUD Contacts Everett (Headquarters) 425-783-8272 2320 California ST Everett, WA 98201 Arlington PUD office 425-783-1000 210 E. Division Arlington, WA 98223 Lynnwood PUD office 425-783-1000 21014-63rd AV W Lynnwood, WA 98036 Monroe PUD office 425-783-1000 120 E. Fremont Monroe, WA 98272 Snohomish PUD office 425-783-1000 807 Rainier Snohomish, WA 98290 Stanwood PUD office 425-783-1000 9124-271 ST NW Stanwood, WA 98292 PUD Real Estate Services 425-783-4408 1802-75th ST SW Everett, WA 98203 Monday through Friday, 8:00 AM to 5:00 PM Toll-free in Western Washington and outside the Everett local calling area at 1-877-783-1000 OTHER UTILITIES Telephone: Frontier Gas: Water: Cable: Puget Sound Energy Cascade Natural Gas Contact your local provider Contact your local provider ELECTRICAL INSPECTIONS State of Washington L&I (Everett) 425-290-1309 State of Washington L&I (Mt. Vernon) 360-416-3000 City of Everett 425-257-8810 City of Lynnwood 425-670-5417 City of Marysville 360-363-8223 City of Mountlake Terrace 425-775-9694 Snohomish County PUD Electric Service Handbook Residential Underground Service Rev. April 2018 1

1097R REV. 05/08 RESIDENTIAL NEW SERVICE QUESTIONNAIRE / AGREEMENT SNOHOMISH COUNTY PUD Customer s Name email (LEGAL NAME FOR CONTRACTS) Phone: Work ( ) home ( ) Cell ( ) FAX ( ) Service Address Mailing Address (HOUSE NUMBER AND STREET ADDRESS, CITY, STATE, ZIP CODE) (HOUSE NUMBER AND STREET ADDRESS, CITY, STATE, ZIP CODE) Architect/Surveyor Work Phone ( ) Electrical Contractor email Phone: work ( ) FAX ( ) CelL ( ) General Contractor email Phone: work ( ) FAX ( ) Cell ( ) House Mobile Home Other (PLEASE SPECIFY: RECREATIONAL VEHICLE, PUMP HOUSE, GARAGE, ETC.) PUD Main Line on your property to be: Overhead Underground Service Line (transformer to residence) to be: Overhead *if Underground: PUD installed Underground* Customer installed Electrical service entrance size: 200 amp 400 amp amp In order to proceed with the engineering and determination of charges, the following information may be required: 1. Copy of the survey for the property showing lot lines, property corner stakes, dimensions, easements and right-of-way. Attached? Yes No 2. Legal description of property (copy of deed). Attached? Yes No 3. Plot plan of lot showing approximate locations of buildings, driveways, and proposed electrical facilities and service location. Attached? Yes No 4. Snohomish County or appropriate governmental agency Critical Area Regulation or other requirements have been met and details attached? Yes No (If NO, information must be provided to the PUD before proceeding with engineering) ELECTRICAL INFORMATION Type of heat: Electric Gas Wood Other (specify) Type of electric heat and kilowatt (kw) load: Furnace kw Air Conditioning: Heat Pump: tons Wall kw Amps starting current Amps starting current Baseboard kw Amps running current Amps running current Boiler kw Soft start: Yes No Soft start: Yes No Other kw Hot Water: Miscellaneous Loads: Gas Electric kw Tankless kw Hot Tub kw Pool kw Sauna kw Welder kw Other (specify) kw Approximate date service will be required: Present condition of building site: Grades & Stakes Form signed?: Yes No (This is a form attesting that property corner locations and final grade is ESTABLISHED.) It is understood that if additional work is required of the PUD, due to customer revisions of the electrical load and/or voltage requirements or other information as supplied or requested on this form, the additional costs shall be borne by the customer. The PUD provides for installed load, not future load. Prior to energizing the service, all PUD standards and service requirements must be met and approved by the PUD. Customer Signature date: 2 Snohomish County PUD Electric Service Handbook Residential Underground Service Rev. April 2018

GENERAL 1. Availability and location of PUD facilities for providing underground service shall be determined at the PUD s office before proceeding with the wiring. Site Plans, Legal Description and New Service Application shall be submitted to the PUD as much in advance as possible prior to any construction. Application for Service is on page 2. 2. The PUD will design, install, own and maintain the complete primary underground electric distribution system and all associated residential secondary distribution. 3. Underground service installation requiring a special voltage or road boring will require individual consideration for feasibility and charges required. 4. Required permits and easements will be obtained prior to construction. Please respond to easement request immediately when contacted by the PUD s Real Estate Department. This will help ensure that your project will not be delayed. 5. It is the customer s responsibility to contact appropriate gas, cable, phone companies, and any other utilities needed to arrange for their installation. 6. For questions or clarifications, contact a PUD Area Designer. Electrical Service Requirements (ESR) and ESR Bulletins supercede any information in this handout. TRENCHING - SECONDARY (120/240 volts) 1. In general, all trenching, backfilling and restoration work on private property shall be done by the customer. 2. The minimum cover required for secondary (0-600V) shall be 24 inches. Refer to Figures 4-1 and 4-2. 3. The minimum horizontal and vertical separation between electric and gas shall be 12 inches. The gas line shall be staked or shaded with backfill every 10 feet or as required to maintain separation. The minimum separation between electric and water or sewer shall be 36" horizontal and 12" vertical at crossings. Refer to Figure 4-1. 4. Backfill containing large rock or paving material, cinders, large or sharply angular substance, or corrosive material shall not be placed in an excavation where materials may damage conduits, cables or other substructures or prevent adequate compaction of fill or contribute to corrosion of conduits, cables or other substructures (NEC 300 5). 5. The customer shall prepare a work area at the metering point to allow the service conductors to be safely installed by the PUD. Continuous secondary service conduit shall stop 3 feet from the point of service (pedestal or pole) as provided by the PUD. The formed deep socket coupling (large flared end) of the conduit may be pointed in either direction. A bellend shall not be installed on the end of the conduit; however, a tapered, manufactured poly conduit plug shall be installed on each open end to keep out dirt and foreign objects prior to the PUD installing the conductors. Snohomish County PUD Electric Service Handbook Residential Underground Service Rev. April 2018 3

Refer to Figure 4-2 (Conduit Extensions). The customer shall prepare a work area 5 feet x 5 feet minimum centered around the meter base, backfilled and compacted to within 4 inches of final grade and clear of obstructions. The meter socket and riser shall be secured to the building studs or other structural members to provide a solid base for cable pulling. Refer to Figures 4-4 through 4-7. 6. The maximum continuous service conduit run shall be 250 feet in length, from the meter base to the point of service. Contact a PUD Area Designer prior to installation. Note: The PUD must inspect and approve all conduit installations prior to backfilling. Minimum Clearances from PUD Underground Lines in Conduit Type of Utility Line Electric Primary Vertical Separation (Crossings) Electric Secondary Main Electric Secondary Service (300V Max.) Electric Primary Horizontal Separation Electric Secondary Main Electric Secondary Service (300V Max.) Communication 6" 6" 6" 0" 0" 0" Communication Service 3" 3" 3" 0" 0" 0" High Pressure Gas 12" 12" 12" 36" (60" Preferred) 36" (60" Preferred) 36" (60" Preferred) Low Pressure Gas 6" 6" 6" 12" 12" 12" Gas Service 6" 6" 6" 12" 12" 12" Sewer Main & Lateral 12" 12" 12" 36" (60" Preferred) 36" (60" Preferred) 36" (60" Preferred) Sewer Service 12" 12" 6" 36" 36" 12" Water Main & Lateral 12" 12" 12" 36" (60" Preferred) 36" (60" Preferred) 36" (60" Preferred) Water Service 12" 12" 6" 36" 36" 12" Storm & Roof Drains 12" 12" 6" 36" (60" Preferred) 36" (60" Preferred) 36" (60" Preferred) Lighting & Electric Supply 6" 6" 6" 0" 0" 0" Figure 4-1 4 Snohomish County PUD Electric Service Handbook Residential Underground Service Rev. April 2018

CONDUITS FOR PUD-INSTALLED CONDUCTORS 1. All Non-metallic conduit must meet the following requirements a. The following information shall be imprinted on all PVC conduit: 1. Manufacturers name or trademark 2. Nominal size 3. Material (PVC) 4. Utility duct and Standards (specification) number b. 2", 21/2" and 3" shall be gray and meet or exceed the requirements of any one of the following standards: 1. NEMA TC-2 (Schedule 40 or 80) c. Schedule 40 or 80 PVC is required for service riser according to the NEC 300-5d. and NEMA Standard TC-2 for applications listed below: 1. Type III - Designed for normal-duty applications above ground (Sch 40) 2. Type IV - Designed for heavy-duty applications above ground (Sch 80) (Hazardous areas, e.g., next to driveways). d. All conduit bends shall be long radius type. Conduit Diameter Minimum Radius 2", 21/2", 3" 24" PVC conduit shall not be mechanically heated to form any sweep (bend). e. Each PVC conduit joint must be permanently assembled using a PVC solvent cement appropriate for the application. 2. Secondary Conduit Requirements a. The conduit size for a 200 amp residential service riser shall be a minimum of 21/2 inches for 4/0-2/0 triplex. b. The conduit size for a 201-400 amp residential service riser shall be a minimum of 3 inches for 350 kcm -4/0 triplex. c. Secondary conduit shall be allowed a maximum total aggregate of 270 of bends, including the riser. All bends shall be long radius type (24-inch minimum). d. A tapered, manufactured poly conduit plug shall be installed on all conduit ends to seal exposed ends of conduits to keep out dirt and foreign objects prior to the PUD installing the conductors. (Do not use duct tape.) e. A continuous length of knot-free 1/4-inch polypropylene pull rope or Herculine P125OW 1/2" polyester pull tape shall be installed by the customer with a 2-foot tail at each end for all secondary conduit(s), including future conduits, regardless of length of run. f. The lower end of all service entrance conduits shall be turned so that they face towards the PUD s facilities (the source of the customer s service). Snohomish County PUD Electric Service Handbook Residential Underground Service Rev. April 2018 5

Figure 4-2: Secondary Trench TRENCHING DETAIL CONDUIT EXTENSIONS 6 Snohomish County PUD Electric Service Handbook Residential Underground Service Rev. April 2018

PUD OR CUSTOMER-INSTALLED SECONDARY SERVICE WIRE (120/240 volts) 1. There is a fee for the PUD supplied and installed secondary service cable installation, for up to 100 ft of cable. Over 100 ft is charged on a per-foot basis. (Contact your PUD Area Designer for the current fee for this service.) 2. The customer has the option of supplying and installing the secondary service cable. PUD Area Designer will specify service termination locations for the meter and PUD connection point. PUD Area Designer will specify cable size. Acceptable wire sizes include: 200 amp 1/0-1/0 - #2 or 4/0 4/0 2/0 aluminum URD triplex XLPE USE-2 400 amp 350kCM - 350kCM - 4/0 aluminum URD triplex XLPE USE-2 Verify wire size with the appropriate PUD Designer prior to installation. Customer will supply and install approved cable with a qualified installer, leaving an adequate excess length of service cable (5 ) at the PUD source connection point. The customer will provide trenching and backfilling. Approved conduit will be supplied and installed by the customer. A scheduled PUD inspection and approval is required prior to backfilling conduit. The customer will provide connection at the meter socket. Connections shall be made providing excess conductor as illustrated in Figure 4-3. Connection at the PUD source will be provided by PUD. A PUD inspection/connection fee for this option is required. (Contact your PUD Area Designer for the current fee for this service.) PUD Engineering / Inspection fee includes a maximum of two site visits. PUD connection fee covers the service connection of the customer s conductor to the existing available PUD facilities. Snohomish County PUD Electric Service Handbook Residential Underground Service Rev. April 2018 7

RESIDENTIAL SERVICE EQUIPMENT 1. A meter socket with a minimum capacity of 125 amps is required. Sockets shall be listed for use with aluminum/copper conductors. Typically a 200-amp socket is used, refer to Figure 4-3. A 200-amp socket is designed to accommodate size 4/0 conductor. The customer s wiring entrance into the meter socket shall be offset from the PUD s so as not to physically block the source lugs. An oxide inhibitor is required on stranded aluminum conductors of #8 awg or larger for terminal connectors (State of Washington Electric Code requirements). Note: Meter socket may be surface mount or flush mount. Figure 4-3: 200 Amp Meter Base 10-1/2"min. Meter base must be grounded. 14" min. Source Lugs See Note #1 Service Entrance Riser: 2-1/2" rigid steel or PVC conduit. Load Lugs Alternate neutral lug position 6' max. 4' min. Final Grade Notes: 1. Requires double lock nuts and protective bushing on rigid steel conduit. PVC plastic conduit requires threaded terminal coupling, one lock nut and protective bushing. 2. Underground service sockets must have a minimum enclosure depth of four inches (4"). 2. The standard 200-amp service entrance conduit shall be a minimum of 21/2 inch. Service entrance conduits with a 90 bend shall terminate 24 inches minimum below the final earth grade measured to the top of the conduit (NEC 710-4.b). The lower end of all service entrance conduits shall be turned so that they face towards the PUD s facilities (the source of the customer s service). 8 Snohomish County PUD Electric Service Handbook Residential Underground Service Rev. April 2018

3. Secure riser conduit with galvanized pipe straps and lag bolts, a maximum 5-foot spacing. a. Schedule 40 PVC required for normal-duty applications above ground. b. Schedule 80 PVC required for heavy-duty applications above ground. (Hazardous areas, e.g. next to driveways). 4. Service riser conduit shall not enter at the center of the bottom of the meter-base but shall be offset to one side. 5. Conduit couplings are not allowed on an underground service riser (above final grade). Exception: A formed deep socket coupling may be used on the service riser provided that it is a manufactured integral part of the conduit and it shall be oriented pointed away from the meter socket, towards the source. Refer to Figure 4-2. 6. Install ground per NEC Requirements. Snohomish County PUD Electric Service Handbook Residential Underground Service Rev. April 2018 9

Figure 4-4: 200 Amp Service, Riser 2.5 Minimum, Continuous Riser Style Secure meter base to building studs or other structural members Work Area Meter 6' max. 4' min. Secure conduit with pipe straps, two min., and lag bolts 5' max. spacing Conduit: To be backfilled and compacted to within 4" of final grade after inspection approvals No coupling allowed on conduit riser above grade 24" min. Integrally Formed Deep Socket Coupling (may point in either direction) 90 bend 24" radius Continuous Conduit to Pedestal Location Install a poly duct plug to keep out dirt. Install 1/4" pull rope. 10 Snohomish County PUD Electric Service Handbook Residential Underground Service Rev. April 2018

Figure 4-5: 201-400 Amp Self-contained Meter Socket Service, Riser 3 Minimum Secure meter base to building studs or other structural members Work Area Conduit: To be backfilled and compacted to within 4" of final grade after inspection approvals Meter 6' max. 4' min. 400 Amp Meter Base Secure conduit with pipe straps, two min., and lag bolts 5' max. spacing No coupling allowed on conduit riser above grade 24" min. Integrally Formed Deep Socket Coupling (may point in either direction) Install a poly duct plug to keep out dirt. Install 1/4" pull rope. 90 bend 24" radius Continuous Conduit to Pedestal Location Snohomish County PUD Electric Service Handbook Residential Underground Service Rev. April 2018 11

Figure 4-6: 201-400 Amp (CT Enclosure) Service, Riser 3 Minimum 50' max. Conduit 1" min. 6 terminal meter socket with test switch provision Work Area 8' max. 6' min. Secure conduit with pipe straps, two min., and lag bolts 5' max. spacing Conduit: To be backfilled and compacted to within 4" of final grade after inspection approvals No coupling allowed on conduit riser above grade Meter 6' max. 4' min. 24" min. Integrally Formed Deep Socket Coupling (may point in either direction) Install a poly duct plug to keep out dirt. Install 1/4" pull rope. 90 bend 24" radius Continuous Conduit to Pedestal Location 12 Snohomish County PUD Electric Service Handbook Residential Underground Service Rev. April 2018

Figure 4-7: 201-400 Amp (CT Enclosure) Service - DETAIL For enclosure and bracket information, see notes below. 50' max. Conduit 1" min. Enter on any side Enclosure shall be grounded and mounted on an outside wall. 8' max. 6-terminal meter socket with test switch provision Mounting height 4' min. - 6' max. Service conduit 3" min. Source 6" min. Ground per NEC Final grade Final grade NOTES: PUD will furnish, install and wire the current transformers. The PUD will also make metering connection and nal service connection. For single-phase units, the cabinet shall be 24" x 36" x 11" minimum. Refer to NEC for additional requirements. VIEW A N 8" Min. 1-3/8" 8-1/8" Pre-fabricated brackets required for terminating conductors and mounting current transformers shall be specified in 328A of the EUSERC Manual. Refer to Figure 5-20. Landing pads shall be rated at 50,000 amps. 2' Min. 2-1/2" Max. View A 1-3/8" 3-1/2" Figure 5-20 EUSERC DWG. NO. 328A Snohomish County PUD Electric Service Handbook Residential Underground Service Rev. April 2018 13

METER PEDESTAL - 200 AMP SERVICE 1. A factory assembled pedestal must be listed and approved or PUD approved and accepted. It must be set a minimum of 2 feet in the ground with a concrete pad of 2 feet x 2 feet x 31/2 inches poured in place around the pedestal for support. The customer shall backfill, compact and install the concrete pad after inspection and prior to service installation. Refer to Fig 4-8, Exhibit A. 2. An on-the-job assembled meter pedestal, which is composed of listed or approved meter socket and conduit or raceways, must be supported by one of several methods. The preferred installation is by using two pieces of Unistrut channel embedded in a 12" diameter poured concrete footing 36" deep. Minimum Unistrut channel acceptable shall be hot dip galvanized 12 gauge steel 15/8" x 15/8", or PUD-approved equivalent. Also acceptable is using two pieces of 2" hot dip galvanized steel angle iron or 2" hot dip galvanized rigid steel pipe with a 2" hot dip galvanized steel cap embedded in a 12" diameter poured concrete footing 36" deep. The customer shall install the poured concrete footing, backfill and compact prior to inspection and service installation. The concrete footing should not encase the service riser conduits. Alternately, the PUD will accept a fully pressure treated 6" x 6" x 10' wood post set a minimum of 36" deep; however, it is the least desired method since it may not last as long as the other methods. The wood post shall not be encased in concrete, but shall be backfilled with gravel to facilitate drainage. Refer to Fig 4-8, Exhibit B. 3. The conduit shall be 21/2 inch minimum. Exhibit A Manufactured underground pedestal 4' max. 3' min. Concrete pad 2' x 2' x 3-1/2" min. Final Grade 24" min. Ground per NEC 90 bend 24" radius Figure 4-8, Exhibit A 14 Snohomish County PUD Electric Service Handbook Residential Underground Service Rev. April 2018

Exhibit B Meter socket min. 14"H x 10-1/2"W x 4"D Disconnect switch per NEC 6' max. 3' min. Support posts 2 pcs Unistrut channel Final Grade 24" Ground per NEC 90 bend 24" radius 36" Poured concrete footing 12" in diameter. Crown footing above final grade and slope taper away from Unistrut channel. Concrete footing should not encase service conduit. Figure 4-8, Exhibit B Snohomish County PUD Electric Service Handbook Residential Underground Service Rev. April 2018 15

METER PEDESTAL - 400 AMP SELF-CONTAINED & 400 AMP CT RATED 1. An on-the-job assembled meter pedestal, which is composed of listed or approved meter socket and conduit or raceways, must be supported by one of several methods. The preferred installation is by using two pieces of Unistrut channel embedded in a 12" diameter poured concrete footing 36" deep. Minimum Unistrut channel acceptable shall be hot dip galvanized 12 gauge steel 15/8" x 15/8", or PUD-approved equivalent. Also acceptable is using two pieces of 2" hot dip galvanized steel angle iron or 2" hot dip galvanized rigid steel pipe with a 2" hot dip galvanized steel cap embedded in a 12" diameter poured concrete footing 36" deep. If needed, a minimum of 3/4" exterior grade plywood backing should be attached between the footings to support the equipment. The customer shall install the poured concrete footing, backfill and compact prior to inspection and service installation. The concrete footing should not encase the service riser conduits. Alternately, the PUD will accept a fully pressure treated 6" x 6" x 10' wood post set a minimum of 36" deep; however, it is the least desired method since it may not last as long as the other methods. The wood post shall not be encased in concrete, but shall be backfilled with gravel to facilitate drainage. Refer to Fig. 4-8, Exhibit C; Fig. 4-9 and Fig. 4-10. 2. The conduit shall be 3-inch minimum. 16 Snohomish County PUD Electric Service Handbook Residential Underground Service Rev. April 2018

Exhibit C 400 Amp Meter Base with link by-pass 6' max. 3' min. Support posts 2 pcs Unistrut channel Final Grade 24" Ground per NEC 90 bend 24" radius 36" Poured concrete footing 12" in diameter. Crown footing above final grade and slope taper away from Unistrut channel. Concrete footing should not encase service conduit. Figure 4-8, Exhibit C Snohomish County PUD Electric Service Handbook Residential Underground Service Rev. April 2018 17

Figure 4-9: Typical Meter Pedestal for 201-400 Amp Self-Contained Meter Socket for Use With a Class 320 Meter, Riser 3" Minimum Preferred Construction: Bolt service entrance equipment to *Unistrut channels with two pieces of *Unistrut crossmembers, two 2" x 6" fully pressure treated crossbeams or 3/4" min. exterior grade plywood. Extend each *Unistrut leg 36" min. below grade and embed each leg in a 12" diameter poured concrete footing. The concrete should not encase the service entrance conduit. *Minimum Unistrut channel acceptable shall be hot dip galvanized 12 gauge steel 1-5/8" x 1-5/8" or District-approved equipment. Alternate Construction: 2" hot dip galvanized steel angle iron or 2" hot dip galvanized rigid steel pipe with a hot dip galvanized pipe cap embedded in a 12" diameter poured concrete footing, or two fully pressure treated 6" x 6" x10' wood post set 36" min. below grade and backfilled with gravel to facilitate drainage. 400 Amp Meter Base with link by-pass. Attach meter base to back support. Disconnects as per NEC. Ground rod, wire & clamp per NEC Final Grade 6" min. 6' max. 4' min. Min. 3" PVC conduit 2' min. 2' min. Integrally Formed Deep Socket Coupling (may point in either direction) 90 bend 24" radius 36" Continuous conduit to pedestal location. Install a 1/4" pull rope. Install a poly duct plug to keep out dirt. Poured concrete footing 12" in diameter. Crown footing above final grade and slope taper away from Unistrut channel. Concrete footing should not encase service conduit. 18 Snohomish County PUD Electric Service Handbook Residential Underground Service Rev. April 2018

Figure 4-10: Typical Meter Pedestal for a 201-400 Amp Current Transformer Enclosure Installation, Riser 3" Minimum Preferred Construction: Bolt service entrance equipment to *Unistrut channels with two pieces of *Unistrut crossmembers, two 2" x 6" fully pressure treated crossbeams or 3/4" min. exterior grade plywood. Extend each *Unistrut leg 36" min. below grade and embed each leg in a 12" diameter poured concrete footing. The concrete should not encase the service entrance conduit. *Minimum Unistrut channel acceptable shall be hot dip galvanized 12 gauge steel 1-5/8" x 1-5/8" or PUD-approved equipment. Alternate Construction: 2" hot dip galvanized steel angle iron or 2" hot dip galvanized rigid steel pipe with a hot dip galvanized pipe cap embedded in a 12" diameter poured concrete footing, or two fully pressure treated 6" x 6" x10' wood post set 36" min. below grade and backfilled with gravel to facilitate drainage. Disconnects as per NEC. 6-terminal meter socket with test switch provision. Attach meter base to back support. Minimum 1" conduit nipple. Seal all connections. For enclosure and bracket information, contact PUD Area Designer. Ground rods, wire, and clamps per NEC. Final Grade Min. 3" PVC conduit 6" min. 6' max. 4' min. 2' min. 2' min. Integrally Formed Deep Socket Coupling (may point in either direction) 90 bend 24" radius 36" Continuous conduit to pedestal location Install a 1/4" pull rope and poly duct plug to keep out dirt. Poured concrete footing 12" in diameter. Crown footing above final grade and slope taper away from Unistrut channel. Concrete footing should not encase service conduit. Snohomish County PUD Electric Service Handbook Residential Underground Service Rev. April 2018 19

CONVERSIONS, OVERHEAD TO UNDERGROUND 1. In general, overhead to underground service conversion requires individual attention on specific requirements. Contact your PUD Area Designer for specific requirements and fees. Note: The NEC requires that, where necessary, existing breakers, switches, panels, etc. must be upgraded to present requirements. Contact the Department of Labor and Industries - Electrical Division or your local electrical inspecting authority for specifics. 2. The underground service equipment installation shall comply with PUD requirements for a new service. a. An underground riser conduit may be extended up to match the height of the existing overhead mast. This new riser must be within 18 inches of the existing mast. Refer to Figure 4-11. DETAIL See detail #4 cu. min. bond on steel conduits 18" max. Riser must be the same height. See detail 17' max. 18" min. leads Conduit 2-1/2" min. Proposed conduit or riser Connections by PUD. Approved conduit grounding clamp as required. Existing conduit or riser Figure 4-11 20 Snohomish County PUD Electric Service Handbook Residential Underground Service Rev. April 2018

b. Existing 200 amp surface-mounted meter bases, may be converted by installing an underground service riser conduit into the bottom of the meter base for installation of new underground service conductors. Refer to Figure 4-12. Exceptions: The following conditions must apply: 1) Conduit must enter to one side of the bottom, not the center. 2) Meter base must be a minimum size of 101/2" wide, 14" tall and 4" deep. Coordinate with the PUD. Discontinue OH service. Remove conductor. Cap off if conduit is removed Meter socket must meet U.G. requirements Secure conduit with pipe straps and lag bolts 5' max. spacing Continuous conduit 2-1/2" min. Min. 24" radius 90 bend 24" min. 90 bend 24" radius Figure 4-12 Snohomish County PUD Electric Service Handbook Residential Underground Service Rev. April 2018 21

PRIMARY SERVICE (7200 volts) - RESIDENTIAL SYSTEMS ON PRIVATE PROPERTY 1. The customer shall prepare the vault site, provide easements, trenching and conduits 2. The PUD will install, own and maintain the vault, grounds, secondary handhole and secondary service conductors. 3. All trenching, backfilling and restoration work on private property shall be done by the customer. 4. The minimum cover required for primary is 36". The maximum cover for primary conductor shall be 47". 5. The minimum separation between electric and gas shall be 12 inches. The gas line shall be staked or shaded with backfill every 10 feet or as required to maintain separation. The minimum separation between electric and water/sewer shall be 36". Refer to Figure 4-1A. 6. Backfill containing large rock or paving material, cinders, large or sharply angular substance, or corrosive material shall not be placed in an excavation where materials may damage conduits, cables or other substructures or prevent adequate compaction of fill or contribute to corrosion of conduits, cables or other substructures (NEC 300 5). 7. The customer shall backfill within 24 hours after PUD inspection and before conductors are installed. 8. Conduits terminating in a handhole or vault shall have protective bushings on steel conduits. PVC conduit shall extend 5 inches into the vault and be temporarily sealed with a tapered, manufactured poly conduit plug. The PUD will install all bell ends on PVC conduit entering vaults, for primary conductors. a. The customer shall prepare the vault site in accordance with Figure 4-13. b. The PUD will provide and install the vault, ground rods, ground wire and secondary service pedestal. c. The vault hole shall be plumb, level and square. d. The customer shall install both the primary and the secondary conduits, pull ropes, seal all ends with a tapered, manufactured poly conduit plug to keep out dirt. e. After inspection and approval, the customer shall backfill the trenches prior to the installation of the electrical system. 22 Snohomish County PUD Electric Service Handbook Residential Underground Service Rev. April 2018

9. Primary Conduits in Trenches a. Conduit is required for all primary conductors on private property. All bends shall be long radius fiberglass or rigid steel electrical conduit. A maximum of 180 of bends shall be allowed. Exception: Naturally formed long sweeps of PVC conduit of 1 to 90 will be allowed. 1.) PVC Conduit shall not be mechanically heated to form any sweep (bend). 2.) Conduit shall not be placed in the trench to form a long sweep prior to the setup of cement in all joints involved. Cement setup time shall be per the manufacturer recommendations. b. Primary conduit sizes shall be 2 inches for single phase. c. The customer shall install a continuous length of knot-free 1/4-inch polypropylene pull rope or Herculine P1250W 1/2-inch polyster pull tape with a 2-foot tail at each end and a tapered, manufactured poly conduit plug (do not use duct tape) at each end for all primary conduit(s), including future conduit(s), regardless of length of run. Primary Distribution Trench With Joint Utilities Final Grade Primary Conductor 36'' min. 47'' max. Water / Sewer 36'' Compacted Backfill Select Backfill Electrical TV Cable Telephone 12'' min. Natural Gas: staked or shaded with backfill every 10' or as required to maintain separation. Figure 4-1A Snohomish County PUD Electric Service Handbook Residential Underground Service Rev. April 2018 23

The following information shall be imprinted on all PVC conduits: 1. Manufacturers name or trademark 2. Nominal size 3. Material (PVC) 4. Utility duct and Standards (specification) number 5. DB (direct buried) 2", shall be gray and meet or exceed the requirements of any one of the following standards: 1. NEMA TC-2 (Schedule 40 or 80) All conduit bends shall be 24" long radius type. Note: Primary conduit bends shall be fiberglass or rigid steel electrical conduit. Typical service trench by customer Conduit to rise 8" in last 5' and terminate 14" and off-center of vault hole. (See note below.) Temporarily seal ends of conduit prior to installation of conductor. 60" Pedestal by PUD 24" min. 28" 60" After inspection approval, backfill to within five feet of hole. 1/4" pull rope 36" Bellend provided by PUD Continuous 2" duct as directed by PUD engineer. Primary trench, conduit and pull rope NOTE: Primary trench and conduit to enter front of vault site and off-center to allow alignment of conduit with mouse holes in vault. Figure 4-13 24 Snohomish County PUD Electric Service Handbook Residential Underground Service Rev. April 2018

Call two (2) full working days before you dig! It s a required by law, and you could be held liable for any damages you incur to utility services Call 811 or 1-800-424-5555 At no charge to you, Utilities Underground Location Center (DIAL DIG) will mark where power, gas lines, and other utilities are located on your property, using the following color codes: RED... Electric YELLOW... Gas Oil ORANGE... Telephone CATV BLUE... Water GREEN... Sewer PURPLE... Reclaimed Water PINK... Survey WHITE... Proposed excavation

PO Box 1107 Everett WA 98206-1107 425-783-8272 snopud.com FORM 2240 Rev. 04/18