An Experimental Study on Effect of Steel Corrosion on the Bond Slip Performance of Reinforced Concrete

Similar documents
Experimental study of bond-slip performance of corroded reinforced concrete under cyclic loading

Bond between Reinforcement and Concrete Influence of Steel Corrosion

6.4.1 Concrete mix design. The four concrete mixes were designed using the absolute volume method as shown below:

Probability Model of Corrosion-Induced Cracking Time in Chloride-Contaminated Reinforced Concrete

Experimental investigation on the dynamic properties of RC structures affected by reinforcement corrosion

Stress-Strain Response of Corroded Reinforcing Bars under Monotonic and Cyclic Loading

Shear Behavior of RC Slender Beams with Corrosion-Damaged Stirrups

Bond of high strength concrete under monotonic pull out loading.

Bond Slip of High Relative Rib Area Bars under Cyclic Loading

Relationship between corrosion and element severity score for reinforced concrete beams

EXPERIMENTAL STUDY ON CHLORIDE PENETRATION DEPTH IN CRACKED REINFORCED CONCRETE

Effect of corrosion on the bond between steel and concrete: an overview K. Lundgren

In-plane testing of precast concrete wall panels with grouted sleeve

Effects of Corrosion on Reinforced Concrete Beams with Silica Fume and Polypropylene Fibre

ISSN MATERIALS SCIENCE (MEDŽIAGOTYRA). Vol. 24, No

INFLUENCE OF SHEAR REINFORCEMENT ON RESIDUAL LOAD CAPACITY OF RC BEAMS WITH CORROSION

Seismic Behavior of Low Strength RC Columns with Corroded Plain Reinforcing Bars

Effect of corrosion products on bond strength and flexural behaviour of reinforced concrete slabs

Influence of chloride-induced corrosion cracks on the strength of reinforced concrete

Prediction of Corrosion-Induced Crack Width of Corroded Reinforced Concrete Structures

SHEAR STRENGTH OF ASR-DETERIORATED RC MEMBERS AND SHEAR REINFORCING EFFECT OF REPAIR BY ADDING REBAR

INFLUENCE OF REINFORCING STEEL CORROSION ON FLEXURAL BEHAVIOR OF RC MEMBER CONFINED WITH CFRP SHEET

Malaysian Journal of Civil Engineering 26(3): (2014) Department of Civil Engineering, Tripoli University, Tripoli, Libya 2

18. Durability studies carried out in the present investigation in. ordinary grade and standard concrete, through acid attack test

1. INTRODUCTION. (a) Sand/ Fabric-coated (b) Sand-coated deformed. (c) Helical wrapped/ribbed Fig.1 FRP anchors with different outer surfaces

The effect of corrosion on bond in reinforced concrete

Analytical Model for Concrete Jacketed RC Columns with Precorrosion and Postcorrosion Damages Under Uniaxial Loading

Seismic response of corroded r.c. structures

Experimental Study and Design Method of High-Performance Recycled Aggregate Concrete

FLEXURAL FAILURE BEHAVIOR OF RC BEAMS WITH REBAR COR- ROSION AND DAMAGE EVALUATION BY ACOUSTIC EMMISSION

Bond between ribbed bars and concrete. Part 1: Modified model K. Lundgren

PULLOUT CAPACITY BEHAVIOUR OF FRP-HEADED REBARS

Experimental Investigation on the Effect of Bond-Slip Behaviour of Steel Rebars in Concrete

Reinforced Concrete Corrosion and Protection

Experimental investigation of the use of CFRP grid for shear strengthening of RC beams

EXPERIMENTAL STUDY ON SEISMIC BEHAVIOR OF INTERIOR JOINTS OF PRECAST PRESTRESSED CONCRETE FRAMES

EFFECT OF ENVIRONMENTAL CONDITIONING ON BOND BETWEEN COMMERICAL FRP RODS AND CONCRETE

STUDY ON SEISMIC BEHAVIOR OF RECYCLED CONCRETE FRAME JOINTS UNDER LOW CYCLIC LOAD

65 mm 2 mm 65 mm D6 SD295A D6 SUS34 D13 SD39 SD39 15mm mm Series 1: Stirrup Series 2 : Main rebar 45 a = 45 mm SUS34 D25 SD39 2 mm mm 2

STEEL CORROSION IN CONCRETE: A COMPREHENSIVE EXPERIMENTAL PROGRAM AND PRELIMINARY RESULTS Steel corrosion in concrete

Strength Assessment of RCC Beams Subjected to Corrosion

EXPERIMENTAL INVESTIGATION OF PRECAST CONCRETE BEAM TO COLUMN CONNECTIONS SUBJECTED TO REVERSED CYCLIC LOADS

PSEUDO-DYNAMIC TEST AND NON-LINEAR ANALYSIS OF A 1:10 SCALE PRE-STRESSED CONCRETE CONTAIN VESSEL MODEL FOR CNP1000 NUCLEAR POWER PLANT

Effect of Waste Steel Shavings on Bond Strength between Concrete and Steel Reinforcement

INVESTIGATION OF CURING PERIOD OF CEMENTITIOUS ADHESIVE AND PERFORMANCE OF RUST PREVENTION

Chalmers Publication Library

Experimental Study on Seismic Behavior of Double Steel Plates Shear Wall with Concrete-filled Steel Tubular Frames and Seams

SHEAR STRENGTHENING OF REINFORCED CONCRETE DEEP BEAMS USING EMBEDDED THROUGH SECTION (ETS) TECHNIQUE

Strengthening of Beams Using Glass Fiber Reinforced Polymer (GFRP) Laminate

Study on shear performance and residual shear strength of concrete members after fire

CORROSION MONITORING IN REINFORCED CONCRETE BY ACOUSTIC EMISSION

Experimental Investigation on Flexural Behaviour of Corroded R.C Beam Retrofitted with Basalt Fiber Sheet

TO STUDY EFFECT OF BOND STRENGTH WITH PROVIDED EFFECTIVE DEVELOPMENT LENGTH IN CONCRETE STRUCTURE

Critical Study of Corrosion Damaged Concrete Structures

Experimental Research on Corrosion-Induced Cracking Monitoring Based on Optical Fiber Sensor

Investigation of Chloride Ingress in Cracked Concrete Treated with Water Repellent Agents

1. CORROSION OF REINFORCEMENT

Effect of Distribution in Cross Sectional Area of Corroded Tensile Reinforcing Bars on Load Carrying Behaviour of RC Beam

MODELING THE BOND-SLIP BEHAVIOR OF CONFINED LARGE- DIAMETER REINFORCING BARS

Durability of Seawater Mixed Concrete with Different Replacement Ratio of BFS (Blast Furnace Slag) and FA (Fly Ash)

Development of Simulation Model of Chloride Ion Transportation in Cracked Concrete

Available online at ScienceDirect

Concrete-filled Double-skin Tubular Columns with External Steel Rings

COMPARATIVE STUDY OF BEAMS BY USING DIFFERENT TYPES OF RETROFITING TECHNIQUES

Evaluation of Current Condition State of Reinforced Concrete Structures Exposed to Severe Environmental Condition

Assoc.Prof.BOONCHAI STITMANNAITHUM. Department of Civil Engineering, Faculty of Engineering Chulalongkorn University, Thailand

An Experimental Study on Corrosion Protection Performance of HPFRCCs with Fine Cracks

Corrosion Detection of Embedded Steel in Concrete

Effect of stirrup corrosion on the shear strength of reinforced concrete short beams

Tests of R/C Beam-Column Joint with Variant Boundary Conditions and Irregular Details on Anchorage of Beam Bars

AN APPLICATION OF HPFRCC AND FIBER NET FOR RECOVERING STRENGTH OF RC MEMBERS DETERIORATED BY CHLORIDE INDUCED CORROSION

Residual Strengths of Reinforced Concrete Beams With Heavy Deterioration

EXTERNAL CONFINEMENT OF PLAIN AND REINFORCED CONCRETE COLUMNS USING PVC PIPES

CONFINEMENT CAPACITY OF SQUARE AND CIRCULAR CONCRETE COLUMNS REINFORCED WITH PREFABRICATED CAGE REINFORCEMENT SYSTEM

Using CFRP for Enhancing of Circular Cutout in High Strength RC Deep Beam

COMPRESSION BEHAVIOR OF CIRCULAR AND RECTANGULAR RC COLUMNS RETROFITTED BY GFRP LAMINATES: AN EXPERIMENTAL STUDY

Effect of corrosion damage on the performance level of a 25-year-old reinforced concrete building

Experimental study on properties of concrete reinforced with basalt bars

CHAPTER 2 SPECIMEN DETAILS, TEST SETUP AND TESTING PROCEDURE

RESILIENT INFRASTRUCTURE June 1 4, 2016

The Joining Method for Permanent Formwork

Southeast University, Nanjing, Jiangsu , China. *Corresponding author

CORROSION EFFECTS ON THE FLEXURAL STRENGTH BEHAVIOUR OF CONCRETE CONTAINING MANUFACTURED SAND

DIFFUSION OF Cl - IONS IN PARTIALLY DRY AND SATURATED CRACKED REINFORCED CONCRETE MEMBERS

Fatigue flexural behaviour of corroded RC beams strengthened with CFRP sheets

EVALUATING MITIGATION METHODS FOR CHLORIDE INDUCED CORROSION OF REINFORCED CONCRETE STRUCTURES

EXPERIMENTAL STUDY ON SEISMIC BEHAVIOR OF REINFORCED CONCRETE CORE WALL

Effect of Near Surface Mounted (NSM) Steel Bars on Shear Strength of RC Beams

NUMERICAL SIMULATION ON LOCAL BOND-SLIP BETWEEN STEEL AND CONCRETE WITH EXPERIMENTAL VERIFICATION

ISSN: Volume - 4, Issue - 4, July - August , Page No

ABC-UTC. Research Progress Report (Feasibility Study) Title: Alternative ABC Connections Utilizing UHPC. March, 2017

Experimental Study on behavior of Interior RC Beam Column Joints Subjected to Cyclic Loading P.Rajaram 1 A.Murugesan 2 and G.S.

INFLUENCE OF WATER IMMERSION ON THE BOND BEHAVIOR BETWEEN CFRP AND CONCRETE SUBSTRATE

INHERENT DUCTILITY OF REINFORCED CONCRETE SHEAR WALLS WITH NON-SEISMIC DETAILING

Experimental Study on Bonding Strength of High Strength Concrete Subjected to Elevated Temperatures

INTERNATIONAL JOURNAL OF CIVIL AND STRUCTURAL ENGINEERING Volume 3, No 1, 2012

Multi-Scale Pull-Out Resistance of Steel Reinforcing Bar Embedded in Hybrid Fiber Reinforced Concrete (HYFRC)

The Experimental Study on BFRP Rebar and Coral Concrete Bond. Performance. Jiayi Li1, a

AN INVESTIGATION OF SEISMIC RETROFIT OF COLUMNS IN BUILDINGS USING CONCRETE JACKET

Strengthening of Reinforced Concrete Column via Ferrocement Jacketing

Transcription:

5th International Conference on Durability of Concrete Structures Jun 30 Jul 1, 2016 Shenzhen University, Shenzhen, Guangdong Province, P.R.China An Experimental Study on Effect of Steel Corrosion on the Bond Slip Performance of Reinforced Concrete Xiaolin Zhang, Xuebing Liang, Zeqiang Wang, Hancheng Huang, and Haijun Zhou Department of civil Engineering, Shenzhen University ABSTRACT This paper studied the effects of reinforcement corrosion on bond performance between rebar and concrete. Tests were carried out to evaluate the degradation of bond between reinforcing steel and concrete for different corrosion levels of reinforcing steel. A series of 20 specimens of different concrete strength with various reinforcing steel corrosion levels were designed and manufactured. Each specimen was casted as a 200-mm concrete cube, and a steel rebar was centrally embedded with two stirrups around it. The steel rebar were corroded using an electrochemical accelerated corrosion technique. The corrosion crack opening width and length were recorded after the corrosion process. Then, monolithic pull-out loading tests were carried out on the specimens. The effects of reinforcement corrosion on crack opening, maximum bond stress, and energy dissipation were discussed in detail. It was found that reinforcement corrosion has non-negligible effects on bond performance of reinforcing bar in concrete. Keywords: reinforced concrete, corrosion, bond slip, pullout, rebar 1. INTRODUCTION While it is known that corrosion of steel reinforcement is a major problem influencing the long-term performance of reinforced concrete infrastructures (Duan, Dai, & Jin, 2015). It normally occurs due to attack by aggressive agents, such as chloride ions, from the marine environment. Therefore, expansive stresses are induced around corroded steel bars, causing possible cracking, spalling of the concrete cover, and loss of bonding between the steel and concrete (Cairns, Du, & Law, 2008). Bonding facilitates load transfer across the steel concrete interface, which is essential for the composite action of reinforced concrete structures. Bonding behaviors primarily dependent on three factors: the compressive strength of concrete, confinement, and the surface of the rebar (deformed or round) (Wu & Zhao, 2013). Previous studies have been undertaken to evaluate the effects of corrosion on the bond strength (Almusallam, Al-Gahtani, Aziz, & Rasheeduzzafar 1996; Bhargava, Ghosh, Mori, & Ramanjam, 2008; Eligehausen, Popov, & Bertero, 1983; Fang, Gylltoft, Lundgren, & Plos, 2006; Fang, Lundgren, Chen, & Zhu, 2004; Kivell, 2012; Mangat & Elgarf, 1999; Yalciner, Eren, & Sensoy, 2012). However, little information is available on the effects of concrete strength on bond performance of reinforcing steel in concrete. This is to further study the effects of concrete strength and reinforcement corrosion on bond behavior of reinforcing steel in concrete by both monolithic pull-out loading tests. 2. TEST SETUP AND PROCEDURE 2.1 Test specimen The configuration of test specimen followed the previous studies (Zhou, Lu, Xv, Dong, & Xing, 2015). Specimens consisted of deformed steel rebar set in a concrete prism with two stirrups to provide confinement (Figure 1). Figure 1. Specimen geometry (Unit: millimeter). Two PVC pipes were used to limit the bonded length to 80 mm. The bonded length was much less than the development length of the rebar, so the bond stress along the rebar was relatively uniform. The two closely spaced stirrups provided confinement along the bonded length and helped to limit any end effects (Figure 2). Twenty specimens were casted in total in this test: 10 specimens of concrete strength have designed 20 MPa, and other 10 specimens of concrete strength have designed 40 MPa, as shown in Table 1. 290

An Experimental STUDY ON EFFECT OF STEEL CORROSION ON THE BOND SLIP PERFORMANCE OF REINFORCED CONCRETE 291 this concrete of two kinds was found to have a 28-day average compressive strength of 20.7 and 44.4 MPa. Figure 2. Mould for specimen. Table 1. Reinforcement corrosion level, maximum crack width, and total length of tested specimens. Specimen number Designed corrosion Measured corrosion Total crack length (cm) Maximum crack width (mm) 1 0 0.27 No crack No crack 2 0 0.33 No crack No crack 3 5 3.95 No crack No crack 4 5 3.76 19 0.3 5 10 7.17 33.4 0.42 6 10 7.45 25.1 0.43 7 15 10.78 39 0.3 8 15 10.45 35.3 0.43 9 20 13.18 53.4 0.45 10 20 13.56 53.3 0.4 11 0 0.30 No crack No crack 12 0 0.18 No crack No crack 13 5 3.78 49.80 0.40 14 5 4.13 37.30 0.30 15 10 7.74 41.10 0.80 16 10 7.32 77.70 0.43 17 15 11.52 88.00 0.87 18 15 11.87 100.20 0.50 19 20 14.81 56.70 1.30 20 20 14.66 52.00 1.02 2.2 Concrete mix design The first concrete was designed to have a compressive strength of about 20 MPa with a w/c ratio of 0.6. The concrete mix per cubic meter was 336.02 kg ordinary Portland cement, 201.61 kg water, 725.81 kg sand, and 1236.56 kg stone. The second concrete was designed to have a compressive strength of about 40 MPa with a w/c ratio of 0.48. The concrete mix per cubic meter was 418.06 kg ordinary Portland cement, 200.67 kg water, 677.26 kg sand, and 1204.01 kg stone. Concrete cubes with the dimensions of 100 mm 100 mm 100 mm were also cast for compressive strength testing. And 2.3 Accelerated corrosion program The specimens were corroded using an electrochemical accelerated corrosion technique that involves impressing a direct current through the specimens to accelerate the oxidation process in a 5% NaCl solution (Fang et al., 2006). Table 1 lists the tested specimens, the expected mass loss ranged from 0 to 20%. The level of corrosion was roughly estimated according to the mass loss of the rebar to establish different corrosion levels for the reinforcement. To ensure that only the bonded zone would be corroded, one end of the steel bar was insulated during the corrosion. The lower part of the steel bar was coated with paraffin, and wrapped with insulated plastic membrane (Figure 3). Figure 3. Insulated end of steel bar during corrosion. The theoretically calculated amount of corrosion products, in terms of the electrolytic time, can be expressed by Faraday s Law: m 2 F t T = (1) I 55.847 where T is the corrosion duration time, m t is the mass loss, I is the average electrical current, and F is the Faraday constant. In this study, the current density was set as 300 ma/ cm 2 ; the corresponding current in the rebar was 13.57 ma per specimen. The above current density was smaller than 500 ma/cm 2 as the maximum current density for electrochemical accelerated corrosion in concrete (Zhou et al., 2015). The specimens were soaked for 5 days prior to application of the current. The accelerated corrosion of the reinforcement was actually carried out for three specimens in series (Figure 4). The experimental research program consisted of testing a total of 20 reinforced concrete specimens with different corrosion levels. The maximum required artificial corrosion process took approximately 92 days.

292 5TH INTERNATIONAL CONFERENCE ON DURABILITY OF CONCRETE STRUCTURES 3. TEST RESULTS Figure 4. Schematic representation of the electrochemical system. 2.4 Pull-out loading In this experiment, the loading of all the specimens is monolithically increased slip loading with the loading speed of 0.4 mm/min. The corroded specimens were tested in a loading machine with a specially designed and fabricated loading frame. Figure 5(a) shows the schematic drawing of the loading system. And Figure 5(b) shows the details of the extensometer installation. Load force was measured through the load cell and the free-end slip was measured using an extensometer with precision of ±0.001 mm. Table 1 lists the measured crack lengths and the corresponding maximum crack width. The crack length was measured by ruler, and the width was measured by width gauge (3 5 cm reading once, then calculate the maximum width). The critical mass loss of reinforcement for crack opening to occur was identified as about 4%, but not for any specimens with lower mass loss. It clearly shows an increase in both maximum crack width and total crack length as the reinforcement corrosion level increases. Compared with 20.7 MPa concrete strength specimen, the crack of the 44.4-MPa concrete strength specimen is longer and wider in the case of same corrosion level. 3.1 Crack opening after artificial corrosion As recent studies have shown the potential effects of crack opening on bond performance (Coronelli, Hanjari, & Lundgren, 2013; Law, Tang, Molyneaux, & Gravina, 2011), the crack information was recorded in detail in this test. Figure 6 shows corrosion-induced cracks for typical specimen of different rebar corrosion and concrete strength of concrete prism after corrosion process. As the corrosion rate increases, the surface of specimens appeared more and more corrosion products, and there are also increase of the crack number, crack width, and length. Figure 5. Loading and measuring system. Figure 6. Corrosion-induced cracks. (a) Typical specimens crack in the one of side and the concrete strength is 20.7 MPa, the reinforcement corrosion is 0.33, 3.95, 7.17, 10.45, and 13.18% from left to right. (b) Photo of Typical specimens from (a). (c) Typical specimen s crack in the one of side and the concrete strength is 44.4 MPa; the reinforcement corrosion is 0.3, 4.13, 7.74, 11.87, and 14.66% from left to right. (d) Photo of Typical specimens from (c).

An Experimental STUDY ON EFFECT OF STEEL CORROSION ON THE BOND SLIP PERFORMANCE OF REINFORCED CONCRETE 293 3.2 Measured mass loss of reinforcement The reinforcement was cleaned using a 12% hydrochloric acid solution to remove scale and rust products and weighed before casting the specimens. After the corrosion process and loading test, the corroded reinforcements were retrieved by opening the specimens (Figure 7). Then, they were cleaned and weighed again. Then, the mass loss of each stirrup was derived by the following equation: m m S0 ξ = S m S0 S 100% (2) where m s is the mass of steel bar after removal of the corrosion products, and m s0 is the mass of steel bar before corrosion. The mass loss can be regarded as the steel bar area reduction (corrosion rate) considering that artificial corrosion is more uniform than natural pitting corrosion. Table 1 also shows that the expected mass loss agrees well with the actual measured mass loss. From Table 1, it can be seen that the measured corrosion levels were generally lower than the designed ones. The difference in results indicates that the permeability of concrete plays a role in the magnitude of actual corrosion; the permeability of the concrete was not included in the equations for the theoretical calculation of corrosion amounts. Although the specimens were immersed in the NaCl solution, it would have taken a period of time for the solution to reach the reinforcement through the concrete cover. Another factor that affects the corrosion may be the heterogeneity of the coarse aggregate within the specimen. 3.3 Pull-out loading Figure 8(a) shows pull-out bond stress slip curves of the tested specimens of 20.7 MPa. The five specimens had different reinforcement corrosion rates (from 0.33 to 13.6%). Figure 8(b) shows pull-out bond stress slip curves of the tested specimens of 44.4 MPa. The five specimens had different reinforcement corrosion rates (from 0.3 to 14.81%). The bond stress was derived from the measured load force by the following formulation: τ = P πdl (3) where l is the bond length, d is the diameter of rebar, and P is the measured load force. =0.33% =3.95% =7.45% =10.78% =13.6% =0.3% =3.78% =7.74% =11.52% =14.81% Figure 7. Corroded reinforcement. (a) (20.7 MPa concrete strength x S = 10.45%, specimen No. 8), (b) (44.4 MPa concrete strength x S = 11.87%, specimen No. 18). Figure 8. Bond stress slip curves under monotonic slip loading. (a) 20.7 MPa and (b) 44.4 MPa.

294 5TH INTERNATIONAL CONFERENCE ON DURABILITY OF CONCRETE STRUCTURES 3.4 Maximum bond stress Figure 9 shows the maximum bond stress vs. reinforcement corrosion ratio. It clearly shows the effects of corrosion. As the corrosion rates increase, the maximum bond stress has increased first and then decreased, and the maximum bond stress is highest for a reinforcement corrosion ratio of about 4% both two kinds of specimens. With 20.7 MPa specimens, when the degree of corrosion was 13.56%, the maximum bond stress decreased 32%. For 44.4 MPa specimens, however, when the degree of corrosion was 14.66%, the maximum bond stress decreased 9.5%. maximum bond stress(mpa) 27 24 21 18 15 12 9 6 3 0 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 ξ S 20.7MPa 44.4MPa Figure 9. Maximum bond stress vs. reinforcement corrosion ratio. 3.5 Energy dissipation The energy dissipation in pull-out loading was derived by calculating the area of the hysteresis loop in the force slip curve (0 10 mm slip). Figure 10 shows the energy dissipation vs. reinforcement corrosion ratio. High strength specimens are more energy consuming than low strength specimens. When the corrosion rates increase, the energy dissipation has increased Energy dissipation(n*m) 900 800 700 600 500 400 300 200 100 0 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 ξ S 20.7MPa 44.4MPa Figure 10. Energy dissipation vs. reinforcement corrosion ratio. first and then decreased. And the energy dissipation is highest for a reinforcement corrosion ratio of about 4% both two kinds of specimens. It should be noted that, for 20.7 MPa specimens, energy dissipation for a corrosion level of 13. 56% is about 6.77% lower than that of a corrosion level 0.33%. While for 44.4 MPa specimens, when the degree of corrosion was 14.66%, the energy dissipation decrease 21%. 4. CONCLUSION This paper reported a preliminary study of reinforcement corrosion effects on bond performance of reinforcing steel in concrete. Compare the parameters of bond slip relation for specimens with concrete strength and corrosion rates. It was found that: (1) The test results of monotonic slip loading showed that bond strength was very sensitive to corrosion levels and generally decreased with the corrosion level. Bond strength decreased rapidly as the corrosion level increased both in the different strength specimens. The exception is that when the corrosion level was very low, when bond strength increased as the corrosion level increased; (2) When the lower the concrete strength of the specimens, the degradation of the bond stress is more obvious as the corrosion level increase. With 20.7 MPa specimens, when the degree of corrosion was 13.56%, the maximum bond stress decreased 32%. For 44.4 MPa specimens, however, when the degree of corrosion was 14.66%, the maximum bond stress decreased 9.5%. (3) When the corrosion rates increase, the energy dissipation has increased first and then decreased, and it is highest for a reinforcement corrosion ratio of about 4%. The degradation of the energy dissipation of lower strength of the specimens is more obvious compared with higher strength of the specimens. For 20.7 MPa specimens, energy dissipation for a corrosion level of 13. 56% is about 6.77% lower than that of a corrosion level 0.33%. While for 44.4 MPa specimens, when the degree of corrosion was 14.66%, the energy dissipation decrease 21%. ACKNOWLEDGMENTS The w ork described in this paper was financially supported by the Ministry of Science and Technology for the 973-project (No. 2011CB013604), the National Natural Science Foundation of China (Grant No. 51378313), and the Department of Education of Guangdong Province (Grant No. 2013KJCX0157), to which the writers are grateful.

An Experimental STUDY ON EFFECT OF STEEL CORROSION ON THE BOND SLIP PERFORMANCE OF REINFORCED CONCRETE 295 REFERENCES Almusallam, A. A., Al-Gahtani, A. S., Aziz, A. R., & Rasheeduzzafar. (1996). Effect of reinforcement corrosion on bond strength. Construction and Building Materials, 10(2), 123 129. Bhargava, K., Ghosh, A., Mori, Y., & Ramanjam, S. (2008). Suggested empirical models for corrosioninduced bond degradation in reinforced concrete. ASCE Journal of Structural Engineering, 134, 221 230. Cairns, J., Du, Y., & Law, D. W. (2008). Structural performance of corrosion-damaged concrete beams. Magazine of Concrete Research, 60(5), 359 370. Coronelli, D., Hanjari, K., & Lundgren, K. (2013). Severely corroded RC with cover cracking. ASCE Journal of Structural Engineering, 139, 221 232. Duan, A., Dai, J. G., & Jin, W. L. (2015). Probabilistic approach for durability design of concrete structures in marine environments. ASCE Journal of Materials in Civil Engineering, 27(2), 1 8. Eligehausen, R., Popov, E. P., & Bertero, V. V. (1983). Local bond stress-slip relationships of deformed bars under generalized excitations (EERC Report No. UCB/EERC-83/23). Berkeley, CA: University of California at Berkeley. Fang, C. Q., Gylltoft, K., Lundgren, K., & Plos, M. (2006). Effect of corrosion on bond in reinforced concrete under cyclic loading. Cement and Concrete Research, 36(3), 548 555. Fang, C. Q., Lundgren, K., Chen, L., & Zhu, C. (2004). Corrosion influence on bond in reinforced concrete. Cement and Concrete Research, 34(11), 2159 2167. Kivell, A. (2012). Effects of bond deterioration due to corrosion on seismic performance of reinforced concrete structures (Master thesis). University of Canterbury, New Zealand. Law, D. W., Tang, D. L., Molyneaux, T. K. C., & Gravina, R. (2011). Impact of crack width on bond: Confined and unconfined rebar. Materials and Structures, 44(7), 1287 1296. Mangat, P. S., & Elgarf, M. S. (1999). Bond characteristics of corroding reinforcement in concrete beams. Materials and Structures, 32, 89 97. Wu, Y. F., & Zhao, X. M. (2013). Unified bond stress slip model for reinforced concrete. ASCE Journal of Structural Engineering, 139(11), 1951 1962. Yalciner, H., Eren, O., & Sensoy, S. (2012). An experimental study on the bond strength between reinforcement bars and concrete as a function of concrete cover, strength and corrosion level. Cement and Concrete Research, 42(5), 643 655. Zhou, H., Lu, J., Xv, X., Dong, B., & Xing, F. (2015). Effects of stirrup corrosion on bond slip performance of reinforcing steelin concrete: An experimental study. Construction and Building Materials, 93, 257 266.