Technical Specification for PVC Insulated Low Voltage Neutral Screened Copper Cable

Similar documents
Technical Specification for Insulated Low Voltage Single Core Copper Cable

Technical Specification for Low Voltage Aerial Bundled HDPE Insulated Cables

Technical Specification for Substation 11kV and 22kV Single Core Underground Cable

Technical Specification for Single Core 19/33kV Copper / TR-XLPE Underground Cable

Technical Specification for Single Core 38/66kV TR-XLPE Insulated Underground Cable

Technical Specification for Aluminium Castings, Pole Caps and Pressed Symbols

Technical Specification for Helical Fittings for Overhead Power Lines

660 Volts 630 & 800AMP

Technical Specification for Live Line Tap Connectors

Technical Specification for Galvanised Fabricated Steelwork

Technical Specification for LV ABC Fuse Switch Disconnectors

Technical Specification for Steel Forged Fittings

L1-CHE-SPE-171 TECHNICAL SPECIFICATION FOR ELECTRIC CABLE

P.V.C. INSULATED UNARMOURED COPPER CABLES

NPS/002/020 Technical Specification for 11 & 20kV Power Cables

MESP TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 400mm 2 ALUMINIUM CONDUCTOR 1.9kV XLPE INSULATED WITH METALLIC SCREEN

NPS/002/023 Technical Specification for 132kV Power Cables.

MESP TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 70mm 2 FLEXIBLE TINNED COPPER CONDUCTOR 3.3kV EPR INSULATED WITHOUT METALLIC SCREEN

MESP TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 22 kv, SINGLE CORE, 95mm 2 COPPER

MATERIAL STANDARD FOR CABLES AND WIRES

11-SDMS-01 REV. 03 ( )

Cables for Railway Signalling Applications General Requirements

11-SDMS-01 REV. 02 SPECIFICATIONS FOR LOW VOLTAGE POWER AND CONTROL CABLES

Conduits. Technical Specification for Conduits and Associated Materials. JTS Version 1

TECHNICAL SPECIFICATION FOR L. T. XLPE POWER CABLE

DRAFT TANZANIA STANDARD. Part 7: Underground Power Cables for rated voltages 0.6kV/1kV (Um 1.2kV)

137-1: 2015 CEB SPECIFICATION. XLPE INSULATED SINGLE CORE UNDERGROUND CABLES OF 11 kv RATED VOLTAGE

NPS/002/018 Technical Specification for Pilot, Control and Telephone Cables

TECHNICAL SPECIFICATION FOR 1.1KV XLPE POWER CABLE SECTION-1

Four Core, Copper Conductor Extruded Cross - Linked Polyethylene (XLPE) Insulated Power Cable

P.V.C. INSULATED ALUMINIUM SERVICE MAIN WIRE-FINISHED PRODUCT

Technical Specification for Low Voltage Regulator

SCHEDULE ' A ' TECHNICAL SPECIFICATION FOR L.T.PVC POWER AND CONTROL CABLES FOR DISTRIBUTION NETWORK IN MAHARASHTRA

Specification FOR. 12.7/22KV AL-CV/WS 12.7/22KV Aluminum Conductor XLPE Insulated Copper Wire Screened PVC Sheathed Power Cable.

Single Core, Copper Conductor Extruded Cross - Linked Polyethylene (XLPE) Insulated Power Cable

NPS/002/018 Technical Specification for Pilot, Control and Telephone Cables

Single Core, Aluminum Conductor Extruded Cross - Linked Polyethylene (XLPE) Insulated Power Cable

Four Core, Aluminum Conductor Extruded Cross - Linked Polyethylene (XLPE) Insulated Power Cable

RESIN FILLING TYPE JOINTING KITS FOR LOW VOLTAGE UNDERGROUND CABLES

10-SDMS-02 SPECIFICATIONS FOR BARE COPPER CONDUCTORS

Technical Specification for Aluminium Conductor Underground Power Cables for Nominal System Voltages of 11 and 33 kv

SPECIFICATION FOR FRLS POWER CABLES

Test Report No.: Page 2 of 35

Technical Specification for 12kV, 24kV and 36kV Disconnector (Isolators)

SECTION 7.3 TECHNICAL SPECIFICATION OF POWER CABLES & CONDUCTOR

MGVCL/MM/ 3Cx240 mm 2 XLPE Cables/2077 TECHNICAL SPECIFICATION FOR 11 KV XLPE POWER CABLE (CROSS LINKED POLYTHELENE DRY GAS CURED) SECTION I

138-1: 2015 CEB SPECIFICATION. AERIAL BUNDLE CONDUCTORS - 33 kv (95mm 2 and 150mm 2 )

SPECIFICATION FOR STAY INSULATORS (PORCELAIN)

Technical Specification for Outdoor Porcelain Station Post Insulators

NUCLEAR POWER CORPORATION OF INDIA LTD. (A GOVT. OF INDIA ENTERPRISE) SPECIFICATION NO.PB-E-542/REV. No.0

SPECIFICATION FOR ALL ALUMINIUM ALLOY STRANDED CONDUCTOR

MEDIUM VOLTAGE XLPE INSULATED POWER CABLES [6.35/11kV Copper XLPE Three-Core HDPE Sheathed]

Specification for UDC Electrical Testing

093 : 2000 CEB STANDARD MEDIUM VOLTAGE PIN POST INSULATORS AND HARDWARE CEYLON ELECTRICITY BOARD SRI LANKA

Maharashtra State Electricity Distribution Co. Ltd.

Section ARMORED MEDIUM VOLTAGE CABLES SHIELDED 3 CONDUCTOR POWER CABLE - INTERLOCKED ARMOR

Type 1 Machine Cable. Oxygen free tinned annealed copper wire interwoven with high tensile poly-yarn

NPS/002/013 Technical Specification for Telephone and Pilot Cable Joints

31-SDMS-03 REV. 01 SPECIFICATIONS FOR

Title Cables for Railway Signalling Applications - Traction Return Bonding and Track Connection Cables

SPECIFICATION FOR THHN/THWN-2/THW/THWN/TW ARROW ROUTE, FONTANA CA

CONSULTATIONS TECHNICAL GUIDELINE. HVDC extruded cable

Test Report No.: Page 2 of 34

The Contractor shall furnish and install all shielded power cable suitable for use on this project.

DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW)

DATA SHEET Single Core 2HR Fire Rated Cable

NPS/002/017 Technical Specification for 66 kv and 132 kv Cable Accessories

CONSTRUCTION SPECIFICATION FOR INSTALLATION OF CABLE

MATERIAL STANDARD FOR ELECTRICAL HEAT TRACING ORIGINAL EDITION JAN. 1996

SPECIFICATION FOR DISC INSULATORS (Standard Type)

094: 2000 CEB STANDARD. MEDIUM VOLTAGE PIN INSULATORS & HARDWARE (12kV & 36 kv) CEYLON ELECTRICITY BOARD SRI LANKA

Highly flexible, screened control cable with PVC core insulation and abrasion and oil resistant PUR sheath

TECHNICAL SPECIFICATION OF UNARMOURED FLAT 1100 VOLTS L.T. PVC INSULATED TWIN CORE 4.0mm² CABLE WITH ROUND ALUMINIUM CONDUCTOR BLACK SHEATHED.

CONSTRUCTION SPECIFICATION FOR CABLE INSTALLATION

0.6/1 kv LOW VOLTAGE CONTROL CABLES. Conductors. Insulation. Assembly. Standard Colour Code. Armour (Optional) Screening (Optional) Outer Sheath

SYRIAN ARAB REPUBLIC MINISTRY OF ELECTRICITY PUBLIC ESTABLISHMENT FOR DISTRIBUTION The ELECTRICITY (PEDE) TENDER DOCUMENTS FOR

Highly flexible, screened control cable with PVC insulation and PVC inner and outer sheath - certified

ACCELARATED POWER DEVELOPMENT AND REFORM PROGRAMME. Technical Specification (T.S)

SPECIFICATION OF LT AERIAL BUNCHED (AB) CABLES (Size: 3C x 35mm² +1C x mm²) FOR LT LINES (APPLICABLE FOR LT AB CABLE WITH XLPE INSULATION ONLY)

WESTERN UNDERGROUND COMMITTEE GUIDE 2.14 (2.14/01/0990)

NATIONAL ELECTRIC POWER COMPANY (NEPCO) TENDER NO.8/2013 FOR THE SUPPLY OF CONDUCTORS FOR DOUBLE AND QUADRUPLE CIRCUITS 132 kv OHTL's

project 36 MW 1.0 INTRODUCTION AND PROJECT INFORMATION

HDPE Conduit Specification 2011

Highly flexible, screened control cable with PVC insulation and PVC inner and outer sheath - certified

Engineering Data for Copper and Aluminum Conductor Electrical Cables

U.V resistance UL Sunlight Resistance. Flame retardant IEC

Specification Technical Requirements for Overhead Conductors up to and including 33 kv

Standard. Extra High Voltage (EHV) Post Insulators Standard R Version 1.0, June Tasmanian Networks Pty Ltd (ABN )

CONSTRUCTION SPECIFICATION FOR INSTALLATION OF CABLE

SPECIFICATION FOR 11 & 33kV COMPOSITE INSULATORS Part 1: Pin Type

SOUTH CAROLINA ELECTRIC COOPERATIVES' PRIMARY UNDERGROUND POWER CABLE SPECIFICATION

3 MODIFICATIONS TO EXISTING STANDARDS

TABLE OF CONTENTS. Page FOREWORD INTRODUCTION SCOPE NORMATIVE REFERENCES

Specification No. CSC-70/DH/UH/P&D/

YKY, YKY-żo 0,6/1kV PN-93/E-90401, PN-HD-603 S1, IEC

CONSTRUCTION SPECIFICATION FOR GROUNDING

EHV XLPE CABLES CDCC LINE

CE ELECTRIC UK Document reference NPS / 002 / 013 Version:- 2 Date of Issue:- Jan 2011 Page 1 of 11

Purchase Now ANSI/ICEA S STANDARD FOR 600 VOLT SINGLE LAYER THERMOSET INSULATED UTILITY UNDERGROUND DISTRIBUTION CABLES

SECTION 07. TECHNICAL SPECIFICATIONS OF 11 KV XLPE CU CABLE (1x500 mm 2 )

Transcription:

Ergon Energy Corporation Limited Technical Specification for PVC Insulated Low Voltage Neutral Screened Copper Cable ETS03-01-05 Specification ETS03-01-05 Ver 4

Contents 1. Purpose and Scope... 1 2. References... 1 2.1 Applicable Standards... 1 3. Drawings... 2 3.1 Drawings by the Purchaser... 2 3.2 Drawings by the Tenderer... 2 4. Service Conditions... 2 5. Design and Construction... 3 5.1 General... 3 5.2 Core Conductors... 3 5.3 Insulation... 3 5.4 Neutral Screen... 3 5.5 Sheath... 3 5.6 Insect Protection Jacket... 3 5.7 Oversheath... 3 5.8 Marking of Cables... 3 6. Performance and Testing... 4 6.1 Testing... 4 6.2 Type Tests... 4 6.3 Sample and Routine Tests... 4 6.4 Carbon Black Test... 4 7. Risk Assessment... 4 8. Quality Assurance... 5 8.1 Purchasers Policy... 5 8.2 Documentary Evidence... 5 9. Samples... 5 9.1 Production Samples... 5 10. Packaging and Marking... 5 10.1 Cable Length... 5 i Specification ETS03-01-05 Ver 4

10.2 Drum Sizes... 5 10.3 Drum Durability... 5 10.4 Lagging... 5 10.5 Marking of Drums... 6 10.6 Quarantine Requirements... 6 11. Service Performance... 6 12. Reliability... 6 12.1 Service Life... 6 12.2 Evidence in Support of Reliability... 6 13. Training... 6 14. Environmental Considerations... 7 15. Information To Be Provided... 7 15.1 Specific Technical Requirements... 7 15.2 Checklist of Supporting Documentation... 7 16. Attachment 1 Technical Details... 8 17. Attachment 2 Technical Documentation Checklist... 10 ii Specification ETS03-01-05 Ver 4

1. Purpose and Scope This specification sets out the requirements for PVC insulated low voltage neutral screened copper cable for use on underground distribution systems in Queensland. The items covered by this technical specification are listed below: ITEM No. DESCRIPTION Stock Code 1 CABLE ELECTRICAL UNDER GROUND 0.6/1kV, 2 Conductor, 4mm2 (7/0.85) Cu Neutral screened PVC Insulated, PVC Sheathed Nylon Jacket 2400260 2 CABLE ELECTRICAL UNDER GROUND, 0.6/1kV, 2 Conductor, 16mm2 (7/1.70) Cu, Neutral Screened, PVC Insulated/PVC Sheathed/Nylon Jacket 2406943 2. References 2.1 Applicable Standards The cable shall be designed, manufactured and tested in accordance with the following Australian Standards and all amendments issued prior to the date of closing of tenders except where varied by this specification: STANDARD AS 1125 AS 1574 AS 1660 AS 2857-1986 AS/NZS 4961:2003 AS/NZS 5000.1:2005 AS/NZS 3808 AS/NZS 9001 ASTM D1603 TITLE Conductors in Insulated Electric Cables and Flexible Cords Copper and Copper Alloys - Wire for Electrical Purposes Methods of Test for Electric Cables, Cords and Conductors Timber Drums for Insulated Electric Cables and Bare Conductors Electric cables Polymeric insulated For distribution and service applications Electric Cables - Polymeric Insulated for Working Voltages up to and Including 0.6/1kV Insulating and sheathing materials for electric cables Quality Management Systems Requirements Standard Test Method for Carbon Black Content in Olefin Plastics Should inconsistencies be identified between standards and/or this specification, the Tenderer shall immediately refer such inconsistencies to the Purchaser for resolution. Page 1 of 10 Specification ETS03-01-05 Ver 4

3. Drawings 3.1 Drawings by the Purchaser There are no drawings attached to this specification. 3.2 Drawings by the Tenderer The Tenderer shall supply with the tender, detailed drawings or pamphlets of the items tendered. 4. Service Conditions The conditions under which the cables will be required to operate are: DESCRIPTION Installation Ambient Air Temperatures Ambient Ground Temperatures Altitude Humidity CONDITION Installed, directly buried in fine grain bedding material, or, in PVC conduits at a nominal depth of up to 1000 mm, with cable ends rising up concrete or timber poles and exposed to direct sunlight. Not exceeding 50 o C as determined by a shaded thermometer Not exceeding 35 o C Not exceeding 500 metres above sea level 90% high humidity combined with a high temperature (40 o C) followed by a sudden drop in temperature of up to 10 o C Exposed sections of the cable will be subject to the following additional service conditions: DESCRIPTION Solar Radiation Level Precipitation Atmospheric classifications CONDITION 1100 watts per square metre with high ultraviolet content Tropical summer storms with gust wind speeds above 160km/h and an annual rainfall in excess of 1500mm Areas of coastal salt spray and / or industrial pollution with equivalent salt deposit densities in the range of 2.0 3.0 g/m 2 Page 2 of 10 Specification ETS03-01-05 Ver 4

5. Design and Construction 5.1 General The cables shall be designed and manufactured in accordance with AS/NZS 4961:2003 5.2 Core Conductors The conductors shall be circular plain annealed stranded copper in accordance with Section 2 - Copper Conductors of AS 1125. 5.3 Insulation The insulation material on shall be PVC - V90 complying with AS/NZS 3808. The thickness of the cable insulation shall be in accordance with Table 1 of AS/NZS 5000.1. The cable insulation shall be red in colour. 5.4 Neutral Screen The neutral screen shall be of a cross sectional area equal to the phase conductor and be stranded annealed copper conductors to AS 1125. The wires shall be applied helically and evenly over the protected core offering a maximum coverage of the core. 5.5 Sheath Sheath shall be PVC-V90 extruded over, and coaxial with, the neutral screen and shall be capable of removal without screen damage. The sheath shall be compatible with other materials with which it is in contact. The thickness of the sheath shall be in accordance of Clause 13.4 of AS/NZS 5000.1. Sheath colour shall be black. 5.6 Insect Protection Jacket A continuous UV stabilised nylon jacket (nylon 12) not less than 0.4 mm radial thickness producing a smooth glossy surface free from defects or scratches shall be extruded to an even thickness over the entire length of the cable. The jacket must be capable of removal without damage to the sheath. Jacket colour shall be black. 5.7 Oversheath The nylon jacket shall be protected by an oversheath of UV stabilised sheathing grade PVC. The oversheath thickness shall be in accordance with Clause 13.4 of AS/NZS 5000.1 to provide adequate protection to the nylon jacket during cable installation in conduit. The colour of the over sheath shall be black. 5.8 Marking of Cables The cables shall be clearly marked with the following information in accordance with clause 16 of AS/NZS 5000.1. (a) Registered name/trade mark of the manufacturer. (b) Year of manufacture. Page 3 of 10 Specification ETS03-01-05 Ver 4

(c) The words, "Electric Cable, U/G Neutral Screened V-90 followed by 0.6/1kV. (d) Cross sectional area of the conductor in sq. mm. (e) Metre markings at 1 metre intervals for the purpose of indicating the length of the cable remaining on partially used drums. It is not essential but the sequence of numbering commences at zero. However, start and finish numbers shall be included in the information to be provided on the drum flange. The lower number of the metre markings sequence shall correspond to the end attached to the drum flange. The height of the letters and numerals shall comply with clause 6.4.4(b) of AS / NZS 5000.1. 6. Performance and Testing 6.1 Testing The cable shall be tested in accordance with Clause 17 of AS / NZS 5000.1. The following Routine test shall be carried out, on each completed drum of cable, in addition to those required by Clause 17 of AS/NZS 5000.1 Insulation resistance tests between one core and the other cores joined with readings in MΩ. The test will be carried out at a voltage level of 1.0kV DC and the results recorded after 1 minute or when the reading settles whichever the sooner. Test configurations shall be from active to neutral / earth i.e. A N+E. Acceptance level for new cable is 100MΩ. 6.2 Type Tests Certificates for Type Tests conducted in accordance with clause 17 of AS / ANZ 5000.1 shall be submitted with the tender. 6.3 Sample and Routine Tests Sample and Routine Test Certificates are not required to be despatched with each delivery of cable but shall be made available to the purchaser when requested, within 1 working day. A certificate of compliance shall be provided with each delivery. 6.4 Carbon Black Test Carbon black content of the outer sheath shall be tested in accordance with ASTM D1603. Test Certificates are not required to be despatched with each delivery of cable but shall be made available to the purchaser when requested, within 1 working day. 7. Risk Assessment There is no requirement for the Tenderer to provide a safety risk assessment for the items covered by this specification. Page 4 of 10 Specification ETS03-01-05 Ver 4

8. Quality Assurance 8.1 Purchasers Policy It is the Purchaser s policy to procure goods, equipment and services from sources that demonstrate the ability to support quality products. 8.2 Documentary Evidence Documentary evidence shall be provided concerning the level of Quality System Certification associated with the Tenderer and/or manufacturer. This documentation shall include the Capability Statement associated with the Quality System Certification. It is expected that the Tenderer and manufacturer will have a quality system certified to ISO 9001 in operation. 9. Samples 9.1 Production Samples When requested, Tenderers shall submit a production sample of each item offered as part of the tender package. 10. Packaging and Marking 10.1 Cable Length The cable shall be supplied in 250 metre lengths unless specified otherwise by the Purchaser. The cable shall be in one length on each drum. 10.2 Drum Sizes Cable shall be supplied on timber drums manufactured in accordance with AS 2857-1986. Operational difficulties are anticipated with the use of timber drums manufactured in accordance with AS 2857-1996. Hence this specification is based on cables supplied on timber drums manufactured in accordance with the requirements of superseded standard AS 2857-1986. 10.3 Drum Durability The cable drums shall be sufficiently robust to ensure that the cable is delivered undamaged, giving due consideration to the method of transportation and the distances involved. All cable drums shall withstand a minimum of 24 months exposure to all types of weather conditions during outdoor storage, without deterioration. 10.4 Lagging The outer layer of cable shall be protected by a sheet form wrapping (with an overlap) located between the inner faces of the flanges. Page 5 of 10 Specification ETS03-01-05 Ver 4

10.5 Marking of Drums The marking of information on the cable drum shall be in accordance with Clause 16.3 of AS / NZS 5000.1. In addition, the following information shall be provided indelibly and legibly marked directly on the flanges: a) The name Ergon Energy and the relevant stores stock code. b) Contract number. c) Order release authority or purchasing order number. d) Manufacturer's traceability number derived from Manufacturer s first letter, hyphen, batch number, hyphen, drum number for this batch. 10.6 Quarantine Requirements Should cable be supplied from overseas manufacturers, then it is mandatory that all conditions and inspections required by the Australian Quarantine Act are met and that all these costs are included in the tendered price. In particular, timber drums must be fumigated with methyl bromide with a concentration of 48 grams per cubic metre for 24 hours at 210C. The Tenderer shall ensure that the procedure does not produce any deleterious effects to the cable supplied on the drum. 11. Service Performance The Tenderers shall state: a) The period of manufacture of PVC insulated cables for use within Australian service conditions. b) Electricity supply authorities within Australia that have a service history of the items offered; AND c) Contact names and telephone numbers of relevant employees of those supply authorities who can verify the service performance claimed. 12. Reliability 12.1 Service Life Tenderers are required to comment on the reliability of the cable and the performance of the materials offered for a service life of 40 years under the specified service conditions. 12.2 Evidence in Support of Reliability Such comments shall include evidence in support of the reliability and performance claimed including information on Failure Mode and Effect Analysis. 13. Training Training material in the form of drawings, instructions, technical papers and/or audio visuals shall be provided for the items accepted under this offer within one (1) month on request. This material shall include, but is not limited to, the following topics: Handling (especially during installation). Page 6 of 10 Specification ETS03-01-05 Ver 4

Storage. Application (particularly in areas of heavy coastal pollution. Installation. Maintenance. Electrical performance. Disposal. 14. Environmental Considerations Tenderers are required to comment on the environmental soundness of the design and the materials used in the manufacture of the items offered. In particular, comments should address such issues as recycling and disposal at the end of service life. 15. Information To Be Provided 15.1 Specific Technical Requirements The Tenderers shall complete Attachment 1 of the specification and guarantee all the details provided. 15.2 Checklist of Supporting Documentation Attachment 2 details a checklist of supporting technical documentation, which shall be submitted with the tender. Page 7 of 10 Specification ETS03-01-05 Ver 4

16. Attachment 1 Technical Details Particulars Nominal area of core conductors Number of conductor strands Cross-sectional area of conductor strand Average radial thickness of insulation Minimum radial thickness of insulation Insulation material and grade Neutral screen Material Nominal area of screen conductors Number of screen strands Cross-sectional area of screen strand Cover (as a percentage of area of insulation) Average radial thickness of sheath Material type and grade Thickness of the nylon jacket Grade of nylon Oversheath material and grade Oversheath thickness - Average Outer sheath colour Cable overall diameter ID of recommended minimum duct size Cable mass (kg/m) Recommended maximum pulling tension Recommended minimum bending radius (a) during installation (times cable diameter) (b) setting (times cable diameter) (mm²) (mm²) (mm²) (mm²) (kn) 0.6/1 kv NEUTRAL SCREENED SERVICE CABLE 4mm2 2 Cond. 16mm2 2 Cond. N/S N/S S/C 2400260 S/C 2406943 Page 8 of 10 Specification ETS03-01-05 Ver 4

Particulars Maximum continuous current rating (Soil Temp. 30 o C,Resistivity 1.2K.m/W) (a) Buried direct (b) In ducts (A) (A) Design maximum conductor operating temperature (a) Normal ( C) (b) Emergency (2 hour) ( C) (c) Short Circuit ( C) Maximum D.C. resistance @ 20oC (Ω/km) Maximum AC resistance of conductor of completed cable at 50Hz and 90 C (Ω/km) Positive and negative sequence impedance at 50Hz of completed cable (resistive and reactive components) (a) At 20 C (Ω/km) (b) At max. operating temperature (Ω/km) Zero sequence impedance at 50 Hz of completed cable at 20 C (resistive and reactive components) (Ω/km) Capacitance per phase in microfarads per 1000 metres at 20 C (mf/km) Power frequency withstand voltage five minutes (kv RMS) Insulation Megger readings 100 metre section tested with 2.5 kv Megger - Phase/Neutral screen (a) Expected value (GΩ) (b) Minimum acceptable value (GΩ) Type Test copies attached Type Test Certificate Number Length of cable per drum Drum mass complete with cable and lagging Australian Standard drum size ( FxBxW) Spindle Hole Diameter Manufacturer's Name and Address (yes/no) (m) (kg) 0.6/1 kv NEUTRAL SCREENED SERVICE CABLE 4mm2 2 Cond. 16mm2 2 Cond. N/S N/S S/C 2400260 S/C 2406943 SIGNATURE OF TENDERER: Page 9 of 10 Specification ETS03-01-05 Ver 4

17. Attachment 2 Technical Documentation Checklist Have full and comprehensive details been submitted WITH the tender documents associated with each of the following items: Clause Particulars Units 3.2 Detailed drawings of cable offered Yes / No 6.2 Type Test Certificates Yes / No 8.2 Documentary evidence of the Quality System Certification of BOTH the TENDERER and the MANUFACTURER (including Capability Statement) Yes / No 10.4 Method of lagging protection Yes / No 11 Service Performance Yes / No 12 Reliability Yes / No 13 Training materials Yes / No 14 Environmental considerations Yes / No 15 Completed Attachment 1 and Attachment 2 Yes / No NAME OF TENDERER: ADDRESS OF TENDERER: SIGNATURE: FOR AND ON BEHALF OF TENDERER DATE: Page 10 of 10 Specification ETS03-01-05 Ver 4