Electrical PIP ELILS000 Lighting and Receptacle Installation Details for Class I, Division 2, Class II, Division 2, and Unclassified Areas

Similar documents
PIP STF05520 Details for Pipe Railing for Walking and Working Surfaces

PIP STF05521 Details for Angle Railings for Walking and Working Surfaces

COMPLETE REVISION January Process Industry Practices Electrical. PIP ELIGD000 Grounding Installation Details

REAFFIRMATION WITH EDITORIAL REVISION September Process Industry Practices Insulation. PIP INIH1000 Hot Insulation Installation Details

REAFFIRMATION WITH EDITORIAL REVISION October Process Industry Practices Insulation. PIP INIC1000 Cold Insulation Installation Details

PIP STF05511 Fixed Industrial Stairs

COMPLETE REVISION September Process Industry Practices Piping. PIP PNSM0120 Purchasing Requirements for Bolting

EDITORIAL REVISION January Process Industry Practices Vessels. PIP VEFV1100M Vessel/S&T Heat Exchanger Standard Details (Metric Units)

PIP STF05501 Fixed Ladders Fabrication Details

PIP VEFV1100 Vessel/S&T Heat Exchanger Standard Details (U.S. Customary Units)

COMPLETE REVISION November Process Industry Practices Structural. PIP STF05530 Grating Fabrication Details

PIP VEFV1100 Vessel/S&T Heat Exchanger Standard Details (U.S. Customary Units)

March Process Industry Practices Structural. PIP STE05535 Vessel Circular Platform Detail Guidelines

PIP RFTB1000 Brick Refractory Installation Qualification, Inspection, and Testing

PIP PCEPA003 Process Analyzer System Field Installation Guidelines

PIP RFTF1000 Ceramic Fiber Refractory Installation Qualification, Inspection, and Testing

PIP VESSP002 Supplemental Design and Fabrication Specification for Shell and Plate Heat Exchangers ASME Code Section VIII, Divisions 1 and 2

PIP PNC00001 Pipe Support Criteria for ASME B31.3 Metallic Piping

PIP PNSM0115 Purchasing Requirements for Pipe

PIP PNEM0001 Piping Service Index

PIP STE05501 Fixed Ladders and Cages Design Guide

Pipeline Systems PIP PLSC0013 Non-Destructive Examination of ASME B31.4 and B31.8 Metallic Pipelines

EDITORIAL REVISION August Process Industry Practices Insulation. PIP INEG2000 Guidelines for Use of Insulation Practices

PIP RFTA1000 Refractory Anchor and Accessory Installation Qualification, Inspection, and Testing

COMPLETE REVISION October Process Industry Practices Piping. PIP PNSC0036 High Density Polyethylene (HDPE) Piping Installation Specification

COMPLETE REVISION April Process Industry Practices Piping. PIP PNC00004 Piping Stress Analysis Criteria for ASME B31.

March Process Industry Practices Refractory. PIP RFIA1000 Refractory Anchor and Accessory Installation Details

PIP INSA1000 Acoustic Insulation Systems Specification

PIP ARS08111 Standard Steel Doors and Frames Supplier Specification

COMPLETE REVISION November Process Industry Practices Architectural. PIP ARS08111 Standard Steel Doors and Frames Supplier Specification

Pipeline Systems PLSC0017 Requirements for Welder Qualifications in Accordance with ASME Section IX

PIP RFTM1000 Monolithic Refractory Installation Qualification, Inspection, and Testing

PIP REEE002 Reliability Indicators for Rotating Machinery

COMPLETE REVISION October Process Industry Practices Civil. PIP CVC01017 Plant Site Data Sheet

EDITORIAL REVISION March Process Industry Practices Refractory. PIP RFSM1000 Monolithic Refractory Material Specification

PIP ARS08710 Standard Steel Door Hardware Supplier Specification

PIP STE05501 Fixed Ladders Design Guide

The Canadian Electrical Code (Saskatchewan Amendments) Regulations, 1999

SECTION 200 CLEARANCES

COMPLETE REVISION February Process Industry Practices Structural. PIP STS05130 Structural and Miscellaneous Steel Erection Specification

PIP INSR1000 Installation of Flexible, Removable/Reusable Insulation Covers for Hot Insulation Service

COMPLETE REVISION May Process Industry Practices Piping. PIP PNSM0110 Purchasing Requirements for Valves

COMPLETE REVISION June Process Industry Practices Architectural. PIP ARS08390 Blast Resistant Doors, Frames, and Related Hardware Specification

SPECIAL SPECIFICATION 1924 Neighborhood Friendly High Mast Illumination System

PIP PNSC0011 Installation of ASME B31.3 Metallic Piping

SECTION GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY

SECTION EXTERIOR ATHLETIC LIGHTING

PIP CTSC1000 Application of Coatings to Concrete

SECTION GROUNDING AND BONDING

SECTION LUMINAIRES AND ACCESSORIES

MATERIAL SPECIFICATION FOR LUMINAIRE RAISING AND LOWERING EQUIPMENT

PIP VESST002 Supplemental Design and Fabrication Specification for Shell and Tube Heat Exchangers ASME Code Section VIII, Divisions 1 and 2

SCAFFOLDS Revision No: 3

PIP VESST002 Supplemental Design and Fabrication Specification for Shell and Tube Heat Exchangers ASME Code Section VIII, Divisions 1 and 2

CONSTRUCTION SPECIFICATION FOR INSTALLATION OF UNDERPASS LUMINAIRES

SECTION BASIC ELECTRICAL REQUIREMENTS

CAMINO REAL REGIONAL MOBILITY AUTHORITY BOARD RESOLUTION

AASF#2 Brooksville Lighting Upgrade PN Scope of Work Specification summary

SECTION EARTHING AND EARTH FAULT PROTECTION

SECTION HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS

JONES NICHOLSON PTY LTD CONSULTING ENGINEERS

I am hopeful that you will find the attached document satisfactory and acceptable for use on federal-aid projects.

Please check with your local inspection authority for any additional requirements before installation.

SPECIAL SPECIFICATION 7191 Illumination

G2-0 List of Active Ministry of Transportation of Ontario Drawings (MTOD s)

SECTION GROUNDING

CONTENTS. B. System Design and Performance Requirements

ITEM 686 TRAFFIC SIGNAL POLE ASSEMBLIES (STEEL)

ADDENDUM NO. 1. Addendum 1. Page 1. Barrier Free Accessibility Upgrades. F.J. McElligott Secondary School. Mattawa, Ontario

General Symbols, Ducts and Cables

A. Section includes busway and fittings including plug-in units.

(Condensed from National Electric Code)

Drawing Modification Summary Effective:

A. All materials shall be tested and listed by an OSHA approved Nationally Recognized Testing Laboratory (NRTL).

TELECOMMUNICATIONS ROOMS. Table of Contents PART 1 GENERAL 2 A. LOCATION: 2 B. SIZE 2 C. STRUCTURAL 3 D. ENVIRONMENTAL 3 E. ELECTRICAL AND LIGHTING 3

ADDENDUM TO THE CONTRACT. for the. Eaglecrest Learning Center Contract No. E ADDENDUM NO.: ONE CURRENT DEADLINE FOR BIDS: December 17, 2013

SECTION GROUNDING AND BONDING

ADA RESTROOM 79 LF EXISTING ANDERSON MAINTENANCE BUILDING (E) SNOW STORAGE AREA: 160 SF EXISTING STORAGE BUILDING (E) ELECTRICAL PAD

G2-0 List of Active Ministry of Transportation of Ontario Drawings (MTOD s)

General Symbols, Ducts and Cables

PARTICULAR SPECIFICATION E11: GENERAL ELECTRICAL EARTHING AND LIGHTNING PROTECTION

NOVADYNE 365 Lansdowne St. E., Unit 1, Peterborough, ON K9L 2A3

A 2" MICHIGAN DEPARTMENT OF TRANSPORTATION. 1" (Min.) \ Bracket to \ bottom chord. 24-3" (Max.) 45 (Typ.) * W40 x 149. or l5 x 5 x 1/2 (see

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

ATTACHMENT 4. New Eastside Regional Park Phase 1. BIM (Building Information Modeling) 3D Design & Modeling Program Requirements

B. Verify that electrical installation may be made in complete accordance with all pertinent codes and regulations and the original design.

PART 1- General LULA Elevator Section 14200

SECTION NON-PENETRATING PORTABLE ROOFTOP SUPPORTS AND WALKWAYS. For best results, display hidden notes to specifier.

210 Series UL Listed Modular Vault Panel Installation Procedures January 15, 2009

This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update.

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

Design Standard Basic Electrical Requirements

AS/NZS 3000: 2018 Changes to Wiring Rules Standard

Questions & Answers. Amendments to Ontario Electrical Safety Code 23 rd Edition/2002

ITEM L-119 AIRPORT OBSTRUCTION LIGHTS DESCRIPTION

5-1 Street Lights Required Street Lights on Private Roadways Developer s Responsibility...5-1

This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update.

APPENDIX 1 PROJECT REQUIREMENTS

Project Procedure 1.0 PURPOSE 2.0 SCOPE 3.0 REFERENCES. No.: P /19/2011 PAGE 1 OF 4 FACILITY LIGHTING SYSTEMS INSTALLATION

Transcription:

August 2017 Electrical PIP ELILS000 Lighting and Receptacle Installation Details for Class I, Division 2, Class II, Division 2, and Unclassified Areas

PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort to minimize the cost of process industry facilities, this Practice has been prepared from the technical requirements in the existing standards of major industrial users, contractors, or standards organizations. By harmonizing these technical requirements into a single set of Practices, administrative, application, and engineering costs to both the purchaser and the manufacturer should be reduced. While this Practice is expected to incorporate the majority of requirements of most users, individual applications may involve requirements that will be appended to and take precedence over this Practice. Determinations concerning fitness for purpose and particular matters or application of the Practice to particular project or engineering situations should not be made solely on information contained in these materials. The use of trade names from time to time should not be viewed as an expression of preference but rather recognized as normal usage in the trade. Other brands having the same specifications are equally correct and may be substituted for those named. All Practices or guidelines are intended to be consistent with applicable laws and regulations including OSHA requirements. To the extent these Practices or guidelines should conflict with OSHA or other applicable laws or regulations, such laws or regulations must be followed. Consult an appropriate professional before applying or acting on any material contained in or suggested by the Practice. This Practice is subject to revision at any time. Process Industry Practices (PIP), Construction Industry Institute, The University of Texas at Austin, 3925 West Braker Lane (R4500), Austin, Texas 78759. PIP Member Companies and Subscribers may copy this Practice for their internal use. Changes or modifications of any kind are not permitted within any PIP Practice without the express written authorization of PIP. Authorized Users may attach addenda or overlays to clearly indicate modifications or exceptions to specific sections of PIP Practices. Authorized Users may provide their clients, suppliers and contractors with copies of the Practice solely for Authorized Users purposes. These purposes include but are not limited to the procurement process (e.g., as attachments to requests for quotation/ purchase orders or requests for proposals/contracts) and preparation and issue of design engineering deliverables for use on a specific project by Authorized User s client. PIP s copyright notices must be clearly indicated and unequivocally incorporated in documents where an Authorized User desires to provide any third party with copies of the Practice. PUBLISHING HISTORY August 2017 Issued Not printed with State funds

August 2017 Electrical PIP ELILS000 Lighting and Receptacle Installation Details for Class I, Division 2, Class II, Division 2, and Unclassified Areas Table of Contents 1. Scope... 2 2. References... 2 2.1 Process Industry Practices... 2 3. Installation Practices... 2 3.1 Lighting Layout... 2 3.2 Lighting Installation... 2 3.3 Receptacle Layout and Installation... 3 4. Use of Details... 3 Details ELILS001 Stanchion Mount on Handrail ELILS002 Column Mount Fixture ELILS003 Column Mount Floodlight ELILS004 Platform Mount Floodlight ELILS005 Column Mount Receptacle ELILS006 Handrail Mount Receptacle ELILS007 Pendant Mount Fixture ELILS008 Ceiling Mount Fixture ELILS009 Column Mount Receptacle ELILS010 Handrail Mount Receptacle ELILS011 Column Mount Emergency Lighting Battery Unit ELILS012 Roadway Lighting Detail ELILS013 Chain Hung Fluorescent Fixture ELILS014 High Bay Lighting Fixture with Hook Assembly Hanger Beam Mounted ELILS015 Typical AC Lighting Contactor Without CPT ELILS016 Pole Mounted Floodlight 1 Fixture ELILS017 Pole Mounted Floodlight 4 Fixtures ELILS018 Wall Mounted Fixture ELILS019 Hand Rail Mounted Aircraft Obstruction Lighting Process Industry Practices Page 1 of 3

ELILS000 August 2017 Lighting and Receptacle Installation Details for Class I, Division 2, Class II, Division 2, and Unclassified Areas 1. Scope This Practice provides installation details for luminaires and receptacles located in Class I, Division 2 areas, Class II, Division 2 areas, and unclassified areas. This Practice describes the basic assumptions used in developing these details and provides guidelines for their use. Installation details for Class I, Division 1 and Class II Division 1 areas are excluded from the scope of this Practice. 2. References Applicable parts of the following Practices and industry codes and standards shall be considered an integral part of this Practice. The edition in effect on the date of contract award shall be used, except as otherwise noted. Short titles are used herein where appropriate. 2.1 Process Industry Practices (PIP) PIP ELCGL01 Electrical Design Criteria PIP ELSGL01 Electrical Construction Specification 3. Installation Practices 3.1 Lighting Layout 3.1.1 Minimum illumination levels for all process and working areas shall be in accordance with PIP ELCGL01. 3.1.2 The luminaire layout shall be made with a view towards minimizing the impact and visibility in the community outside of the process site. 3.1.3 Luminaires shall be located to avoid conflict with ductwork, piping, steel structures, cable tray, equipment, or other items which could cause shadow areas. 3.2 Lighting Installation 3.2.1 Installation shall be in accordance with PIP ELSGL01. 3.2.2 All luminaires shall be accessible for maintenance. 3.3.3 Floodlight poles shall be accessible to bucket trucks or have a lowering mechanism for servicing the luminaire. 3.2.4 Luminaires mounted above grade, such as on process towers 3.2.4.1 Shall be accessible from permanent platforms. 3.2.4.2 Shall not be mounted to ladders or ladder ways. 3.2.4.3 The use of a lowering type pole (such as Swivel Pole, V-Spring, or similar) shall be considered so maintenance on these luminaires can be done without the use of portable ladders. 3.2.4.4 When installed inside buildings, the luminaires shall be located to allow for routine maintenance without extraordinary measures. An example of Process Industry Practices Page 2 of 3

ELILS000 August 2017 Lighting and Receptacle Installation Details for Class I, Division 2, Class II, Division 2, and Unclassified Areas extraordinary measures may include such measures as draining a pool to maintain luminaires. 3.2.5 An appropriately-sized grounding conductor shall be routed to each luminaire. The conduit system shall not be used as the grounding conductor for luminaires in process areas. 3.2.6 Each luminaire circuit shall have an individual neutral conductor. Common neutrals shall not be used. 3.3 Receptacle Layout and Installation 4. Use of Details 3.3.1 Layout shall be in accordance with PIP ELCGL01. 3.3.2 Installation shall be in accordance with PIP ELSGL01. 3.3.3 An appropriately-sized grounding conductor shall be routed to each receptacle. The conduit system shall not be used as the grounding conductor for receptacles in process areas. 3.3.4 Each receptacle circuit shall have an individual neutral conductor. Common neutrals shall not be used. 4.1 Details apply to multiple luminaires or receptacles and are intended to convey general concepts of desired installation. 4.2 If specific fields are lined out on a detail bill of material, the item is not applicable to the detail. 4.3 Specific sizes are included in the detail bill of material only if the size of the part is common to all applicable luminaires or receptacles. 4.4 Details shall be customized as appropriate for a specific installation by copying as required and entering size and corresponding part number as appropriate. Process Industry Practices Page 3 of 3

H O A

13 1/4" BC 4-11/16" HOLES @ 90 NOTE 1 (TYPICAL) NOTE 5 (TYPICAL) A A SECTION "A-A" NOTE 4 (TYPICAL) NOTE 1 HANDRAIL REDUCER AS REQUIRED WELD OR BOLT TO HANDRAIL POST 6" TO 12" (TYPICAL) HANDRAIL (TYPICAL) HANDRAIL POST (TYPICAL) WELD OR BOLT TO HANDRAIL POST (TYPICAL) MIDRAIL HANDRAIL POST MIDRAIL PLATFORM GRATING PLATFORM GRATING WELD WELD MOUNTED OPTION 'A' AT MID LEVEL MOUNTED OPTION 'B' AT TOP LEVEL