4C Foods Data Integrator Notes

Similar documents
Rochester Airport Data Integrator Notes

Hazel Towers Data Integrator Notes

CLARKSON UNIVERSITY, DG/CHP SYSTEM NOTES

Burrstone Energy Center, LLC, St. Lukes Hospital, Home, and Utica College Data Integrator Notes

Vassar College - Data Integrator Notes

Allied Frozen Storage Site - Data Integrator Notes

Schenectady Water Pollution Control Plant

East Rochester School District East Rochester, NY

Noblehurst Dairy Linwood, NY

Pepsi Co. College Point, NY

NYSERDA s s DG/CHP Integrated Data System. chp.nyserda.org

NYSERDA CHP Assessment Report A S S E S S I N G T H E C H P P L A N T A T C L A R K S O N U N I V E R S I T Y

NYSERDA CHP Assessment Report A S S E S S I N G T H E C H P P L A N T A T T O R E N C O N D O M I N I U M S

FOR. Burrstone Energy Center LLC. August Submitted to:

NYSERDA CHP Assessment Report A S S E S S I N G T H E C H P P L A N T A T C O - O P C I T Y - R I V E R B A Y

M&V Plan for DG/CHP System

NYSERDA CHP Assessment Report A S S E S S I N G T H E C H P P L A N T A T V A S S A R C O L L E G E

Addendum Gateway CHP Verification and Commissioning

SAMPLE MEASUREMENT AND VERIFICATION (M&V) PLAN

Avalon Fort Greene. Site Contact. Summary. Avalon Fort Greene Site Information. 343 Gold St Brooklyn, NY 11201

FOR THE PURECELL 200 FUEL CELL. Draft. July 5, Submitted to: United Technologies Power 195 Governor s Hwy South Windsor, CT

Ultraflex MV2 Final Data Summary

MEASUREMENT AND VERIFICATION (M&V) PLAN

300 Central Park West. Site Contact. Overview. Monitoring Notes. M&V Instrumentation Installation. 300 Central Park West Site Information

MONITORING AND DATA COLLECTION FOR DISTRIBUTED GENERATION/ COMBINED HEAT AND POWER (DG/CHP) SYSTEMS AT ALLIED FROZEN FOODS BROCKPORT, NEW YORK.

4-C Foods CHP Plant NYSERDA Demonstration Project June 24, William Cristofaro P.E. Energy Concepts Engineering PC Rochester, NY

MEASUREMENT AND VERIFICATION PLAN

Gregory W. Stevens and Ronald K. Ishii, Alternative Energy Systems Consulting, Inc.

Times Square Apartments. Site Contact. Overview. M&V Instrumentation Installation. Times Square Apartments Site Information

Digester Gas Utilization at SWRP Where Should the Biogas Go?

Heat Recovery. Integrated CHP Systems Corp.

MEASUREMENT AND VERIFICATION (M&V) PLAN

MEASUREMENT AND VERIFICATION PLAN

MONITORING AND DATA COLLECTION STANDARD FOR DISTRIBUTED ENERGY RESOURCE (DER) SYSTEMS. Submitted to:

Arrow Linen: CHP Washes Away Energy Costs of Commercial Laundry

ADVANCED ABSORPTION CHILLER CONVERTS TURBINE EXHAUST TO AIR CONDITIONING

National Grid USA Service Company. Impact Evaluation Of 2006 Design2000plus Custom Comprehensive Projects. Final Report

CHILLED WATER THERMAL ENERGY STORAGE NEW MEXICO

Applying Cogeneration to Facilities with Industrial Refrigeration

ACEEE Hot Water Forum February 23, 2016

Energy Ideas for Galvanizing

6 Cost Analysis. Table 6.1 Initial System Costs

MEASUREMENT AND VERIFICATION (M&V) PLAN

MONITORING PLAN FOR THE PURECELL 400 FUEL CELL

A guide to cogeneration unit sizing. Product series September 2018

How to Import Timesheet Data into Payroll Mate Using T-Sheets

ENERGY INITIATIVE ENERGY EFFICIENCY PROGRAM Impact Evaluation of Prescriptive and Custom Lighting Installations. National Grid. Prepared by DNV GL

BUILDING FOR THE FUTURE

Electric Standard Offer Program

Microturbine Combined Heat and Power Systems. September 14, 2017: AEE Northern Ohio Chapter. Presenter: Glenn Powers Operations Manager, GEM Energy

OPTION 1: PERFORMANCE RATING METHOD

Draft Results Capital Cost and Performance of New Entrant Peaking Unit

Integration of the hidden refrigeration capacity as a heat pump in smart energy systems

MEASUREMENT AND VERIFICATION (M&V) PLAN FOR ROACH DAIRY FARM ANAEROBIC DIGESTER GAS (ADG) SYSTEM

Optimization of a Cogeneration System in the Automotive Industry

Cogeneration. Thermal Chillers. and. .. ASHRAE National Capital Chapter. Arlington, VA 10/10/2012

Testing of the micro-cogenerator TOTEM 20 manufactured by TOTEM Energy

Implications of Measured Commercial Building Loads on Geothermal System Sizing

Demand-Response Performance of Electric Resistance and CO 2 Refrigerant Heat Pump Water Heater

Testing of the micro-cogenerator TOTEM 10 manufactured by TOTEM Energy

Combined Heat & Power An Overview

The Influence of Distributed Energy Resources on the Hourly Clearing Price of Electricity in a Restructured Market

Sample Reports. for. HAP v4.80 Example Problem

THERMAL ENERGY STORAGE OVERVIEW

CHP Case Studies. Midwest CHP Application Center (MAC) .org (312) University of Illinois at Chicago Energy Resources Center UIC

Tim A. Hansen, P.E. Southern Research Institute NDIA E2S2 May 2012

MONITORING PLAN FOR THE PURECELL 400

Thesis Final Presentation

Introduction to Pinch Technology

Cabrini Terrace Combined Heat and Power

Chilled Water Plant Redesign

Observations on variations in grid carbon intensity

7 Measurement and Verification for Generic Variable Loads

Investigation of the Performance of Trigeneration and CO 2 Refrigeration Systems in Supermarket Applications

Doc. CEN/TC 228 N541 CEN/TC 228

University of Minnesota Duluth Civil Engineering Building

2017 Seasonal Savings Evaluation

ImprovIng energy efficiency with chp: how to evaluate potential cost savings

MATHEMATICAL MODELLING AND OPTIMIZATION OF CHP SYSTEMS FOR HOSPITALS IN TURKEY

An Application of Mixed Mode Cooling using Termodeck with CHP

Uncertainty and Sustainable Energy Investments

Experiences from Geothermal Heat Pump Systems with Variable Flow Pumping

RETRO-COMMISSIONING OF A HEAT SOURCE SYSTEM IN A DISTRICT HEATING AND COOLING SYSTEM Eikichi Ono 1*, Harunori Yoshida 2, Fulin Wang 3 KEYWORDS

Dharam V. Punwani Avalon Consulting, Inc. Tom L. Pierson Turbine Air Systems, Ltd.

Sample Reports. for. HAP v4.90 Example Problem

ALDRON. CHP SOLUTIONS Environmental, Economic & Resiliency Implications NFMT 2015

3.17. PROCESS INTEGRATION AND PINCH TECHNOLOGY

Gas vs. Diesel Generator Sets Performance Cost & Application Differences

Combined Heat and Power Basics Advanced Inverter Based CHP Systems ASHRAE CONNECTICUT CHAPTER JANUARY 11, 2018

Senior Thesis Report Spring Appendix - A. HAP Calculations without Enthalpy Wheel Excel Graphs

Measurement & Verification Report for Alltemp Refrigerant: Preliminary Results Macy s Department Store Manhattan Beach, CA

Penn Power Load Profile Application

Green Data Center CRYOGEL Ice Ball Thermal Storage

QUALITY ASSURANCE/QUALITY CONTROL (QA/QC) PLAN

DATA LOGGER Model DL-SA11

University of Illinois at Chicago

YANMAR s 35 kw Combined Heat and Power System.

SIMULATION AND OPTIMIZATION ON POWER PLANT OPERATION USING SEGA'S EOP PROGRAM

Adjustments To Aegis CHP Thermal Data at The Schwab House

2. Chilled Water Storage: A 4.4-million gallon chilled water storage tank improves Cornell s ability to meet peak cooling needs.

Transcription:

4C Foods Data Integrator Notes This site is a food processing plant located in Brooklyn, NY. Three 150 kw Coast Intelligen engine generators use natural gas to generate the electric baseload for the facility. Heat is recovered from the engines for use in various processes including blending, soup packaging, iced tea processing, bread packaging and cheese drying. Heat is also recovered for cooling through 2 20-ton absorption chillers. Data for this site is collected by Connected Energy and provided to CDH Energy. Data Point Details The data at this site is provided by Connected Energy in the form of comma-separated value (CSV) files. There is one file for each day containing 15-minute timestep data for 59 data points. One data file is uploaded on a nightly basis containing the previous days data. From these 15- minute values, the hourly database is formed. It is unclear whether the 15-minute data is sampled or averaged across the interval. The details for each individual data point are outlined below. The timestamp in the raw data files is in Eastern Local Time. This means it obeys the Standard to Daylight savings times rules for the Eastern timezone. For display purposes, we convert the timestamp from Local Time to Eastern Standard Time for all graphical figures on the website. This means that during the Daylight Savings Time period from the first Sunday in April until the last Sunday in October the monitored data plots, CSV output and standardized PDF reports are in Eastern Standard Time and do not obey Daylight Savings time rules. Presenting data in Standard Time throughout the year is common practice for graphical time series plotting because it eliminates skipping an hour in April and duplicating an hour in October. DG/CHP Generator Output (total kwh) The data for Generator Output comes from a 15-minute average for the power produced by the engine. The column of origin for this data point is labeled Total Cogen Power in the data files received from Connected Energy. The data is converted from a rate to energy per interval and then summed into hourly data. DG/CHP Generator Output Demand (peak kw) The data for Generator Output comes from a 15-minute average for the generator demand. The column of origin for this data point is labeled Total Cogen Power in the data files received from Connected Energy. The maximum for a given hour is assigned to the hourly database. DG/CHP Generator Gas Input (cubic feet) The data for Generator Gas Input comes from a 15-minute accumulator for biogas flow. The column of origin for this data point is labeled Daily Cumul Cogen Gas Use in the data files received from Connected Energy. The difference between consecutive records is assigned as the gas consumed by the engine for that interval. This 15-minute gas data is then summed into hourly data. CDH Energy Corp. 1 February 2007

Total Facility Purchased Energy (total kwh) The data for Facility Purchased Energy comes from an average for the demand imported from the utility grid. The column of origin for this data point is labeled Total Utility Import Power in the data files received from Connected Energy. The rate data is converted to energy per interval and is then summed into hourly data. Total Facility Purchased Demand (peak kw) The data for Facility Purchased Demand comes from the 15-minute average for total utility import. The column of origin for this data point is labeled Total Utility Import Power in the data files received from Connected Energy. The maximum for a given hour is assigned as the Total Facility Purchased Demand in the hourly data. Other Facility Gas Use (cubic feet) There is no information for this data channel available from the Connected Energy data. Total Facility Energy (total kwh) and Total Facility Demand (peak kw) These two data points are the sum of the DG/CHP Generator Output and Total Facility Purchased data points. Unused Heat Recovery (total MBtu/h) The Unused Heat Recovery comes from the 15-minute average for dump cooler heat rate. The column of origin for this data point is labeled Dump Cooler Heat Rate in the data files received from Connected Energy. The rate data is converted to energy, in MBtus, for the interval and then summed into hourly data. Useful Heat Recovery (total MBtu/h) The Unused Heat Recovery comes from a 15-minute average for the utilized heat recovery rate. The column of origin for this data point is labeled Cogen Heat Recovery Rate in the data files received from Connected Energy. The rate data is converted to energy, in MBtus, for the interval and then summed into hourly data. Status/Runtime of DG/CHP Generator (hrs) The engine is defined as being fully on for a 15-minute interval if the engine power output is greater than 1 kw for the period (the fully-loaded capacity is approximately 150 kw). The status is given a value of 0.25 if the generator output is above 1 kw and the status is assigned 0.0 if it is below for each of the three generators. These status values are then summed for each 15-minute interval and then summed into hourly data for the online database. Ambient Temperature (avg F) The Ambient Temperature comes from a 15-minute average for outdoor temperature. The column of origin for this data point is labeled Outside Air Temp in the data files received from Connected Energy. The 15-minute average temperature is averaged into hourly data for the online database. CDH Energy Corp. 2 February 2007

Total CHP Efficiency (%) The Total CHP Efficiency is calculated from the online hourly database as the sum of the Useful Heat Recovery and the DG/CHP Generator Output, converted from kwh to MBtus, divided by the DG/CHP Generator Gas Input. The gas input is converted to MBtus using the Lower Heating Value (LHV) of the fuel which is 0.930 MBtu/cubic foot (Natural Gas). Electrical Efficiency (%) The Electrical Efficiency is calculated from the online hourly database as the DG/CHP Generator Output, converted from kwh to MBtus, divided by the DG/CHP Generator Gas Input. The gas input is converted to MBtus using the Lower Heating Value (LHV) of the fuel which is 0.930 MBtu/cubic foot (Natural Gas). Data Quality Checks The Data Quality Checks consist of three levels of verification: does the data exist, does the data pass reasonable range checking and does the data pass relational checks. The methodology for applying the data quality begins by creating a contiguous database. This is necessary to maintain compatibility between the many sites on the server. Next, the data received for this site is fit into the database, in this case we are using 15-minute data. For any period where there is data, the data quality level is set to 3 for Passes Relational Checks. We then work backwards to identify data that does not meet Relational and/or Range Checking. The next step is to apply the relational checks. Relational checks attempt to identify data which is uncorroborated by the rest of the data set. For instance, data received indicating a DG/CHP Generator output when the gas use is zero is suspect. For data failing a relational check, the data quality level is set to 2 for Data Passes Range Checks or 1 for Data Exists. The last step is evaluating the range checks. The range checks consist of reasonable high and low values based on facility and DG/CHP Generator information. Data that falls outside the defined range for the database value has its data quality level set to 1 for Data Exists. It is necessary to work backwards when applying data quality checks to insure that data gets set to the lowest applicable data quality level. It is possible for data to pass the relational check and fail the range check and such data will be set to a data quality level of 1 for Data Exists. CDH Energy Corp. 3 February 2007

Table 1. Data Quality Definitions Data Description Quality Levels 3 Passes Relational Checking 2 Passes Range Definition This data passes Range Checks and Relational Checks. This is the highest quality data in the data set. This data passes the Range Checks but is uncorroborated by Relational Checks with other values. Checks 1 Data Exists This data does not pass Range Checks. This data is found to be suspect based on the facility and/or CHP equipment sizing. 0 Data Does Not Exist This data is a placeholder for maintaining a contiguous database only. Details on the Range and Relational Checks are found below. Relational Checks These checks are applied to the 15-minute data before it is converted to hourly data. If any of the 15-minute data points fails the relational check, the data for the entire hour is marked as failed. Table 2. Relational Checks for 4C Foods Evaluated Point Criteria Result FG WG > 0 and FG <= 0 DQ Level for FG set to 2 WG, WG_KW, SG WG = 0 and WG_KW > 0 DQ Level for WG_KW, WG and SG set to 2 QHR CHP Efficiency (LHV) > 100 % DQ Level for QHR set to 2 Notes: FG DG/CHP Generator Gas Use WG DG/CHP Generator Output WG_KW DG/CHP Generator Output Demand QHR Total Useful Heat Recovery SG Status/Runtime of DG/CHP Generator Range Checks These checks are applied to the 15-minute data before it is converted to hourly data. If any of the 15-minute data points fails the range check, the data for the entire hour is marked as failed. CDH Energy Corp. 4 February 2007

Table 3. Range Checks for 4C Foods Data Point Hourly Data Method Upper Range Check Lower Range Check DG/CHP Generator Output Sum 112.5 kwh 0 kwh DG/CHP Generator Output Demand Maximum 450 kw 0 kw DG/CHP Generator Gas Use Sum 2,000 cubic feet 0 cubic feet Total Facility Purchased Energy Sum 75 kwh 0 kwh Total Facility Purchased Demand Maximum 300 kw 0 kw Other Facility Gas Use Sum N/A N/A Unused Heat Recovery Sum 250 MBtu 0 MBtu Useful Heat Recovery Sum 250 MBtu 0 MBtu Status/Runtime of DG/CHP Generator Sum 0.75 hrs 0 hrs Ambient Temperature Average 130 F -30 F Notes: Data failing the Range Check has the data quality level set to 1 for Data Exists ASERTTI Protocol Adherence This site adheres fully to the ASERTTI Long-Term Monitoring Protocol. Data is provided in 15- minute intervals satisfying the protocol. In addition, this site also has most of the optional performance parameters. Monitoring Notes December 20, 2006 CDH begins receiving daily file uploads from Connected Energy for this site. January 12, 2007 CDH finishes reviewing data. At 4C Foods, we see the Cogen and Dump Cooler heat rates drop off substantially after mid-october. The Utilized Heat Recovery Rate looks normal during this same period. It is unclear why the Cogen and Dump Cooler drop off and the Utilized HR continues to show a steady trend. CDH Energy Corp. 5 February 2007

5000 4C Foods, Bronx, NY - QHRR - Cogen Heat Recovery Rate 4000 HIGH LIMIT 3000 Mbtuh 2000 1000 0 June July August September October November December 2006 2007 4000 Min: 0.00 Max: 4282.92 High Limit: 4000.00 Low Limit: 0.00 # Out Of Range: 6 4C Foods, Bronx, NY - QHDCR - Dump Cooler Heat Rate Mbtuh 2000 0 June July August September October November December 2006 2007 Min: 0.00 Max: 3587.47 High Limit: 4000.00 Low Limit: 0.00 # Out Of Range: 0 CDH Energy Corp. 6 February 2007

3000 4C Foods, Bronx, NY - QHUR - Utilized Heat Recovery Rate 2500 2000 Mbtuh 1500 1000 500 0 June July August September October November December 2006 2007 Min: 0.00 Max: 2760.00 High Limit: 4000.00 Low Limit: 0.00 # Out Of Range: 0 CDH Energy Corp. 7 February 2007