RESEARCH ON THE ADVANCED USE OF MULTI-SPLIT TYPE AIR-CONDITIONING SYSTEM

Similar documents
A Method for On-Going Commissioning of VRV Package Systems Using a. Simulation Model

A Sensitivity Analysis on Mixing Energy Loss in Air-Conditioned Rooms by Using CFD

DISPLACEMENT VENTILATION

Practical research on effective use of simulation for HVAC systems in the retro-commissioning process H. Tanaka 1, S. Ito 2, Y. Morikawa 3, Y. Akashi

An Assessment of Thermal Comfort in Hot and Dry Season (A Case Study of 4 Theaters at Bayero University Kano)

BUILDING DESIGN FOR HOT AND HUMID CLIMATES IMPLICATIONS ON THERMAL COMFORT AND ENERGY EFFICIENCY. Dr Mirek Piechowski 1, Adrian Rowe 1

IMPACT OF THE AIRFLOW INTERACTION ON OCCUPANTS THERMAL COMFORT IN ROOMS WITH ACTIVE CHILLED BEAMS

EVALUATION OF ANNUAL ENERGY CONSUMPTION OF MULTI-SPLIT TYPE EHP AIR-CONDITIONER FOR BUILDINGS

THERMAL ENVIRONMENT OF OUTDOOR UNITS OF VRV SYSTEM IN HIGH- RISE BUILDING. Gang Wang, Yafeng Hu, and Songtao Hu

C D VALUE OF COOLING SEASONAL PERFORMANCE FACTOR

Thermal Comfort and Energy Consumption according to the Indoor Control Logic

The New Variable Refrigerant Flow System Models in EnergyPlus: Development, Implementation and Validation

THERMAL CHARACTERISTICS AND ENERGY CONSERVATION MEASURES IN AN INDOOR SPEED-SKATING ARENA

Findings of Field Survey for Thermal Comfort and Ventilation in US Office Buildings

DEVELOPMENT OF NEW SELF-COMPARISON TEST SUITES FOR ENERGYPLUS

FIELD TEST STUDY ON THE PERFORMANCE OF AIR SOURCE HEAT PUMP IN LOW TEMPERATURE IN BEIJING

You Can t Afford Discomfort. Dan Int-Hout Chief Engineer, Krueger Richardson, Texas

COMPUTER MODELING OF UNDERFLOOR AIR SUPPLY SYSTEM

EFFECTS OF WEATHERS AND INDOOR TEMPERATURES ON PERFORMANCE OF ENERGY RECOVERY VENTILATOR. Yanping Zhou, Jingyi Wu, Ruzhu Wang

HVAC INTEGRATED CONTROL FOR ENERGY SAVING AND COMFORT ENHANCEMENT vahid Vakiloroaya

Thermal comfort study of a hawker center in Singapore

2-Pipe fan coil terminal units were selected as the parallel system to handle the remaining sensible cooling load.

Effect of Evaporative Cooling Techniques by Spraying Mist Waster on Energy Saving in Apartment House

HVAC SYSTEM CONFIGURATIONS, AN ENERGY ASPECT

Commissioning of a Coupled Earth Tube and Natural Ventilation System at the Post-Acceptance Step

EXPERIMENT FOR VERIFICATION OF GROUND SOURCE HEAT PUMP USING THE DIRECT EXPANSION METHOD

Energy Analysis of Using Thermal Mass in a Hot Humid climate

THE ANALYSIS OF A THERMAL STORAGE SYSTEM UTILIZING BUILDING MASS IN A COLD REGION. Katsuhiro Miura 1

Katsuyuki Edahiro d, Toshihiro Oka d

Performance evaluation of an actual building airconditioning

A DEVELOPMENT OF A HVAC EXPERIMENTAL CHAMBER AND ITS NUMERICAL MODELâ ÒNUMERICAL HVAC EXPERIMENTAL CHAMBER,Ó ON A COMPUTER

Thermal Environment evaluation in Commercial kitchens: Procedure of data collection

DEVELOPMENT OF A HYBRID AIR-CONDITIONING SYSTEM DRIVEN BY LOW TEMPERATURE WASTE HEAT

AMENDMENT NO. 4 AUGUST 2010 TO IS 1391 (PART 1) : 1992 ROOM AIR CONDITIONERS SPECIFICATION

Performance Mapping for Variable Ductless Heat Pump Systems in Heating, Cooling and Defrost Operation

Special edition paper Research on Utilizing Air Thermal Energy for Railway Facilities

Center for Environmental Energy Engineering Department of Mechanical Engineering University of Maryland College Park, MD

Fault detection method for heat source system using comparison between simulation and measured data Y.Tai 1, D.Sumiyoshi 2, Y.Akashi 3, Y.Kuwahara 4,

Energy Efficiency in Building Active Design Part II

Air Movement Preference and Thermal Comfort A survey in classrooms during summer season in Brazil

Evaluating Variable Air Volume (VAV) Packaged Rooftop Systems for Use in High Performance Environments

Indoor Airflow Modeling and Data Assimilation. Hengye Yang Ph.D. Student, LISC Dec. 21, 2018

REAL-TIME CONTROL OF OCCUPANTS THERMAL COMFORT IN BUILDINGS. Galway, Ireland

Ceiling Radiant Cooling Panels

Ceiling Radiant Cooling Panels

UNDERFLOOR AIR DISTRIBUTION INTEGRATED WITH AN INDIRECT AND DIRECT EVAPORATIVE COOLING ASSISTED 100% OUTDOOR AIR SYSTEM

PSYCHROMETRICS. A bit of new; a bit of review. Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 1. What is Psychrometrics?

Conversion Factors for Comparing the Performance of Variable Refrigerant Flow Systems

IMPLEMENTATION OF ANALYTICAL MODELS FOR PASSIVE DOWN-DRAFT EVAPORATIVE COOLING (PDEC) TOWER WITH SPRAY SYSTEMS

Combined heat, moisture and CFD modelling to assess the impact of climate control on local climates near cultural objects in a museum exhibition room

Mechanical Systems Redesign Proposal. Thesis Proposal. Morton Hospital Expansion

Detailed Experimental data of Indoor Air and Thermal Environment in the Working Spaces using Under-floor Air Distribution (UFAD) System

Thermal environment in detached houses with atrium

Occupancy-Based Control of Indoor Air Ventilation: A Theoretical and Experimental Study

Performance Characteristics and Mapping for a Variable-Speed Ductless Heat Pump

Optimizing Indoor Environments for Occupant Satisfaction. Presented by: Kelli Goldstone April 2016

Meeting the Variable Needs of Energy- Efficient Mechanical Ventilation When and Where You Need It

Thermal comfort evaluation of natural ventilation mode: case study of a high-rise residential building

Energy Saving Performance of Buoyancy-Driven Natural and Hybrid Ventilation

of corresponding author:

Heat Pump Hot Water Supply Systems

OUTDOOR AIR, HEAT WHEELS AND JCPENNEY: A NEW APPROACH TO RETAIL VENTILATION

Introduction and utilizing of natural energy in Net ZEB practice

Set Free Modular FSXN. Engineering for tomorrow. And the tomorrow after that.

Field investigation on indoor thermal environment of a high-rise condominium in hot-humid climate of Bangkok, Thailand

Relevant parameters on the energy efficiency of closed refrigerated multideck display cases

CAE 331/513 Building Science Fall 2017

Analysis of Uniformity and Energy Consumption in. Supermarket installed DurkeeSox Air Dispersion System. with PE Air Dispersion Model

Coupling night ventilative and active cooling to reduce energy use in supermarkets with high refrigeration loads

Fresh air pre-cooling and energy recovery by using indirect evaporative cooling in hot and humid region a case study in Hong Kong

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress volume 9 Heiselberg, Per Kvols. Publication date: 2016

Effect of Evaporative Cooling Techniques (Sprayed Water Mist) on Reducing Urban Heat Flux and Saving Energy in an Apartment House

ENGINEERING UPDATE JULY VOLUME 11 THIS PACKAGE INCLUDES A COLLECTION OF ARTICLES FROM VOLUME 11 OF THE JULY 2013 ENGINEERING UPDATE.

Thermo Active Building Systems Using Building Mass To Heat and Cool

Modelling Analysis of Thermal Performance of Internal Shading Devices for a Commercial Atrium Building in Tropical Climates

OUTSIDE AIR REDUCTIONS

Relationship between Thermal Environmental Acceptability and Individual Characteristics in an Office

Numerical Analysis of Ventilation Effectiveness in Occupied Zones for Various Industrial Ventilation Systems

COMPARISON OF ENERGY USE INDICATORS OF A NON-RESIDENTIAL PASSIVE HOUSE WITH ASHRAE 90.1 BUDGET BUILDING

COMPARATIVE SUMMER THERMAL AND COOLING LOAD PERFORMANCE OF NATURAL VENTILATION OF CAVITY ROOF UNDER THREE DIFFERENT CLIMATE ZONES

UC Berkeley Indoor Environmental Quality (IEQ)

Performance Testing of Cold Climate Air Source Heat Pumps

Development of New Self-Comparison Test Suites for EnergyPlus

Technical Feasibility Study of Hybrid Ventilation for a High-rise Office Building in Shanghai

Laboratory Assessment of a Demand Response Controller for Rooftop Units

DAIKIN MXS SERIES MULTI-ZONE HEATING & COOLING SYSTEMS NEW! NOW CONNECT UP TO5 INDOOR UNITS!

A Performance Based Method to Determine Refrigerant Charge Level For Commissioning Unitary AC and HP Systems

MODELLING BUOYANCY INDUCED FLOWS OF PASSIVE COOLING SYSTEMS Pedro Correia da Silva 1, Vítor Leal 1 and J. Correia da Silva 2

Perception of Thermal Comfort for Naturally Ventilated High School Classrooms in San Rafael, CA

enables to easily calculate the energy consumption of air conditioning in various conditions (MLIT). In this study, the university building is the obj

Renovation of Earth Port for Net-Zero Energy Building

EnergyPro Building Energy Analysis. Single-story School Building

Proposed Addendum L to Standard , Ventilation for Acceptable Indoor Air Quality

The Influence of Operation Modes, Room Temperature Set Point and Curtain Styles on Energy Consumption of Room Air Conditioner

FEDERATION TOWER MOSCOW DIFFERENT ROOM CLIMATES UNDER ONE ROOF

ENERGY ANALYSIS AND ENERGY CONSERVATION OPTION FOR THE WAREHOUSE FACILITY AT THE HUMAN SERVICES CENTER COMPLEX DRAFT REPORT.

Thermal Environment evaluation in commercial kitchens

Chilled Beams Selection BY DAN INT-HOUT, FELLOW ASHRAE; AND LILLI WILBAR

SKYLIGHT DESIGN PERFORMANCE EVALUATION METHOD DEVELOPMENT WITH THERMAL AND DAYLIGHT SIMULATION

in UFAD Systems The control of room-air stratification is Design Guidelines for Stratification

Transcription:

- 1 - RESEARCH ON THE ADVANCED USE OF MULTI-SPLIT TYPE AIR-CONDITIONING SYSTEM Yoshinori Suzuki, Master course Student, Masaya Hiraoka, Kajima Corporation, Shin-ichi Tanabe, Professor, Waseda University, 3-4-1 Okubo, Shinjuku-ku, Tokyo 169-8555, JAPAN; Abstract: An energy performance of a multi-split type air-conditioning system was evaluated based on BEMS data and an investigation under actual operation. A simulation model developed in other research was verified. In accuracy evaluation of model based on BEMS data, it was confirmed that output values of the model are highly similar to BEMS data. In addition, it was confirmed that outdoor DB temperature is connected to a compression work because a heat exchange increases due to decrease in outdoor DB temperature. The indoor thermal environment in summertime of Building A under the multi-split type air-conditioning system that uses developed models was investigated. By a continuous measurement and punctual measurement, it was confirmed that the air temperature in task zone didn t fluctuate rapidly, and an air draft didn t influence comfort in task zone. Key Words: multi-split type air conditioning system, BEMS, ADPI 1 INTRODUCTION Recently, a multi-split type air-conditioning system has treated as the energy saving airconditioning system with high flexibility which can correspond to the wide range of building use. It is important to consider the energy performance of a multi-split type air-conditioning system as well as the handiness and the cost of building. Rated COP in the specific condition is set as the standard about an index of energy saving, but the operating characteristic undergoes influence by the outside temperature and the heating or cooling load. A gap forms between the rated performance and the real performance in operation. Therefore rated COP is not an enough index to evaluate energy saving in actual operation. In this paper, a multi-split type air-conditioning system was evaluated in both side of energy performance and indoor comfort. The energy calculation model developed by other research (Togashi et al. 2008) was verified, and the energy performance of the system was evaluated by analyzing the response of the system based on BEMS data according to the building use situations. The indoor comfort was considered to evaluate general performance of the system quantitatively based on actual investigation. 2 THE FACILITY UNDER STUDY Table 1 shows the information of the facility under study. Building A is constructed in Tokyo as office and residence. This 8 th floor is the floor under study, and the floor area is about 2,000m 2. To save energy, keeping indoor air quality and thermal comfort, this building uses an airconditioning system logs indoor air temperature. Air-conditioner in task zone treat sensible heat load, and air-conditioner in ambient zone treat latent heat load. Figure 1 shows the airconditioning system in Building A. Air-conditioner in task zone is controlled by the remote

- 2 - sensor logs temperature of the zone, and it operates only a presence part by occupant sensors on the ceiling. Types of supply air outlet which can be chosen are directional and diffusion, and they can effect on thermal comfort in task zone. Table 1; The information of the facility under study Building Building A Location Minato-ku, Tokyo, Japan Site area 14,587m 2 Building area 2,721m 2 Total floor area 33,512m 2 Structure SRC/RC Height Number of stories 58m above the ground ; 15 stories underground ; 2 stories Uses office, residence appearance Figure 1; The air-conditioning system in Building A 3 ACCURACY EVALUATION OF MODEL BASED ON BEMS DATA Predicting values simulated based on BEMS data were compared with the data of heat source system during summertime, and the developed model was evaluated.

- 3-3.1 DATA SELECTION FOR ANALYSIS The BEMS data that was collected from Building A was used. This data was collected in summertime (from 8:00 to 16:00, in August and September). However, the data collected on Saturday and Sunday was excepted, and the data in the period when the system often stopped was excepted too. Table 2 shows the data for analysis. To grasp the actual condition of the heat source system, indoor heat load was estimated by using the inlet air state of indoor unit. Based on inlet/outlet DB temperature and relative humidity, the inlet air state was estimated. It was supposed that the sensible heat was removed to 95% RH, and the outlet air state was specified. Differences between inlet and outlet enthalpy was specified by inlet/outlet air state of indoor unit, and removed heat load of every indoor unit was calculated. Table 2; The data for analysis August September 181 points 110 points From 8/8 to 8/30 (except Saturday, Sunday, 13th, 17th, 24th) From 9/3 to 9/28 ( except Saturday, Sunday, 5th, 12th, 14th, 24th) 3.2 OPERATION ANALYSIS Characteristics of the heat source system under the real operation were estimated by using BEMS data and calculated indoor heat loads in 3.1. Figure 2 shows load factor duration curves of indoor unit and outdoor air processing unit. In all indoor units, the time under the operation whose load factor was lower than 50% was more than 50% of the operating time. That time of indoor units (2, 3, and 6) was longer than that of other units. A load of an outdoor unit is a total of loads of all indoor units. The load under most operations was less than half of 40kW that was the rated performance. Figure 3 shows the relationship between an indoor heat load, a condensing temperature, and a evaporating temperature. As the indoor heat load increases, the condensing temperature increases, and the evaporating temperature decrease. In addition, the condensing temperature in relation to the indoor heat load in August is higher than that in September. The reason for this difference is that the outdoor temperature in August is higher than that in September. Table 3 shows average of outdoor air state, indoor heat load, and electric consumption in August and September. The average of outdoor DB temperature in September is more than 3 C lower than that in August. Figure 4 shows the relationship between outdoor temperature and condensing temperature, and between condensing temperature and compression work. Outdoor DB temperature in September is lower than that in August, and the electric consumption in September is lower than that in August. The reason for this difference is that a heat exchange increases due to decrease in outdoor DB temperature.

- 4-100% 40% 100% Incidence time rate [%] 80% 60% 40% 20% 0% 0-20- 40-60- 80-100- Load factor [%] Indoor unit 1 Indoor unit 2 Indoor unit 3 Indoor unit 4 Indoor unit 5 Indoor unit 6 Incidence time rate [%] 30% 20% 10% 0% 0.0-8.0-16.0-24.0-32.0-40.0- Heat load of outdoor unit [kw] 75% 50% 25% 0% Figure 2; Load factor duration curves of indoor unit and outdoor air processing unit Condensing temperature (August) Condensing temperature (September) 50 Evaporating temperature (August) 50 Evaporating temperature (September) 45 45 40 40 35 35 Temperature [ C] 30 25 20 15 10 y = 0.8x + 28.699 R 2 = 0.611 Temperature [ C] 30 25 20 15 10 y = 0.6893x + 25.366 R 2 = 0.5705 5 5 0 0-5 -5 0 5 10 15 20 25 Heat load [kw] 0 5 10 15 20 25 Heat load [kw] Figure 3; The relationship between a indoor heat load, a condensing temperature, and a evaporating temperature Table 3; Average of outdoor air state, indoor heat load, and electric consumption Outdoor DB temperature [ C] Outdoor absolute humidity [ C] Indoor heat load [kw] Electric consumption [kw] August 32.62 0.021 8.80 3.08 September 29.26 0.020 9.26 2.79

- 5-50 Condensing temperature (August) Condensing temperature (September) 7 Compression work (August) Compression work (September) 45 6 Temperature [ C] 40 35 30 25 Electric consumption [kw] 5 4 3 2 1 20 24 26 28 30 32 34 36 38 40 0 20 25 30 35 40 45 50 Outdoor temperature [ C] Condensing temperature [ C] Figure 4; The relationship between outdoor temperature and condensing temperature, and between condensing temperature and compression work 3.3 COMPARISON BEMS DATA WITH OUTPUT OF MODEL Figure 5 shows the relation between indoor heat load and compression work. For analysis, the data in August was used. Output values of model are approximately lower than BEMS data, and especially the margin of error is large in the range of low load operation. When the indoor heat load is lower than 5kW, output values of model don t change. The reason for this error is that compressor revolution speed of model can t be less than 10rps that is a setting value. The value is produced by manufacturer data. However, in the other range, output values of model are highly similar to BEMS data. 8 7 BEMS data Output of model Electric consumption [kw] 6 5 4 3 2 1 0 0 5 10 15 20 25 Heat load [kw] Figure 5; The relation between indoor heat load and compression work

N - 6-4 INVESTIGATION OF INDOOR THERMAL ENVIRONMENT The indoor thermal environment in summertime of Building A under the multi-split type airconditioning system that uses developed models was investigated. This building that uses task ambient air-conditioning system, aims to accomplish the efficient energy performance through segmented processing of building loads. Every floor is divided into six zones and for each zone exist an outdoor air processing unit for task zone and an outdoor air processing unit for ambient zone. For each outdoor unit for ambient zone, one indoor unit is connected. 4.1 OUTLINE OF INVESTIGATION Measurement of horizontal distribution of temperature, vertical distribution of temperature, and airflow rate was carried out at the typical floor. Figure 6 shows the plan at the typical floor and each measurement point. Table 4 shows measurement items. During the investigation, there are two conditions for preset temperature, and for each of those conditions, there are two types of air outlet. Table 5 shows preset conditions during the investigation. Horizontal distribution of temperature Vertical distribution of temperature Cart measurement Figure 6; The plan at the typical floor and each measurement point Table 4; Measurement items Measurement items Measuring instrument Measurement interval Continuous measurement Air temperature/rh Vertical distribution of temperature Thermo Recorder RS-12 5min Punctual measurement Air temperature Airflow rate KANOMAX1560 10:00/13:30 16:00/18:00

- 7 - Table 5; Preset conditions during the investigation Ambient airconditioning Task airconditioning Task air outlet 8/22(Wed) 8/23(Thu) 8/24(Fri) 8/25(Sat) Outlet temperature 18 C Indoor temperature 26 C Outlet temperature 18 C Indoor temperature 26 C Outlet temperature 18 C Indoor temperature 28 C Outlet temperature 18 C Indoor temperature 28 C 100%diffusion 100%directional 100%directional 100%diffusion 4.1.1 CONTINUOUS MEASUREMENT Measurement of Horizontal distribution of temperature consists of forty-two points that are set on the partitions (FL+1.1m). Each measuring instrument is equally spaced from every air outlet. Measurement of vertical distribution of temperature consists of three points in perimeter and interior zone. 4.1.2 PUNCTUAL MEASUREMENT To grasp the environment of the task zone, punctual measurement was carried out using a cart pushed by an investigator. In order to investigate the impacts caused by the airflow from task air diffusion, air temperature and airflow rate were measured in three points for every six aisle between desks (18 points in total). At each point, measurement of vertical directions in four points (FL+0.1, 0.6, 1.1, 1.7m) took place simultaneously. Measurement took more than three minutes for every point. Through this measurement, EDT (Effective Draft Temperature) was worked out and using these values, ADPI (Air Diffusion Performance Index) was calculated. 4.2 MEASUREMENT RESULT 4.2.1 HORIZONTAL DISTRIBUTION OF TEMPERATURE Horizontal distribution of temperature at 13:00 on 23th August represents all data during the investigation. Figure 7 shows horizontal distribution of temperature (13:00, 23th August). A margin of error between most average air temperatures and preset air temperature was lower than 1 C, and during investigation, the maximum error between average air temperature and preset air temperature was lower than 2 C. Temperature in perimeter was higher than that in interior. This trend stood out when preset air temperature was 28 C.

- 8-24 25 26 27 28 29 30 Figure 7; Horizontal distribution of temperature (13:00, 23th August) 4.2.2 VERTICAL DISTRIBUTION OF TEMPERATURE During the investigation, temperature difference between 0.1m and 1.7m was lower than 3 C, and satisfied ASHRAE standard 55-2004. 4.2.3 DISTRIBUTION OF AIRFLOW RATE During the investigation, most average airflow rates was moderate (within 0.2m/s), and vertical difference in airflow rate was moderate too. There was not so much influence by the type of air outlet at the respective measuring spots. Even if the type was changed to directional from diffusion, the airflow rate didn t rise effectively. Figure 8 shows distribution of airflow rate at respective measuring spots at 13:00 and 15:00 on 23th August. Preset air temperature on 23th August was low, and the type of air outlet was directional, so there was a possibility that it's felt discomfort by the airflow. But in that case, the maximum airflow rate was lower than 0.25m/s, and design condition was satisfied. 0.35 0.30 13:00 0.1m 13:00 0.6m 13:00 1.1m 13:00 1.7m 0.35 0.30 15:00 0.1m 15:00 0.6m 15:00 1.1m 15:00 1.7m Airflow rate [m/s] 0.25 0.20 0.15 0.10 0.25 0.20 0.15 0.10 0.05 0.05 0.00 0.00 1 3 5 7 9 11 13 15 17 1 3 5 7 9 11 13 15 17 Measuring Measuring Figure 8; Distribution of airflow rate at respective measuring spots(13:00,15:00, 23th August)

- 9-4.2.4 ADPI (Air Diffusion Performance Index) EDT was worked out based on air temperature and airflow rate measured by cart, and using these values, ADPI was calculated. Modified air temperature and temperature correction for ADPI referred to ANSI/ASHRAE standard 113-2005 (ASHRAE. 2005). Table 6 shows ADPI during the investigation. ADPI at most measuring spots was higher than 90%, and design condition was totally satisfied. Distribution of measuring spots where the EDT didn t satisfied standard values was sparse, and it was not characteristic. Table 6; ADPI during the investigation 8/22(Wed) 8/23(Thu) 8/24(Fri) 8/25(Sat) 10:00 94.4% 100.0% 97.2% 98.6% 13:00 97.2% 98.6% 98.6% 94.4% 15:00 100.0% 100.0% 97.2% 100.0% 17:00 95.8% 98.6% 86.1% 100.0% Average 96.9% 99.3% 94.8% 98.3% 4.2.5 ANALYSIS BASED ON BEMS DATA Operation conditions of Indoor units were made sure based on BEMS data during the investigation, and was compared with the measurement result. About arbitrary indoor units for task and ambient, figure 9 shows temporal changes of supply/return air temperature based on BEMS data and air temperature in task zone which was near each air outlet. The data on 23th August represents all data because the heat load on 23th August was the largest in all day. While air-conditioning systems were operated (from 7:00 to 18:00), supply air temperatures of task and ambient indoor units fluctuated due to their operation conditions. The supply air temperature of the ambient indoor unit hovered around 17 C, but that of the task indoor unit often fell below 10 C. Table 7 shows average of supply air temperature of each indoor unit during operation. In average of supply air temperature, supply air temperature of ambient indoor unit was lower than that of task indoor unit because of amount of thermo ON operation (processing heat load) time. But in minimum temperature, supply air temperature of task indoor unit was lower than that of ambient indoor unit, so the cool draft may be uncomfortable. Meanwhile, air temperature in task zone didn t undergo influence by supply air temperature, and didn t fluctuate rapidly. When outdoor air processing unit stopped, indoor unit was under thermo OFF operation (not processing heat load, but blowing). In this case, supply air temperature was sometimes higher than return air temperature by heat quantity of fans. Indoor heat load that is input for developed simulation model is calculated on the basis of supply/return air temperature. So to modify the error between supply and return air temperature can made heat load accurate, and might made predicting performance of simulation model accurate too.

- 10-35 30 [ C] 25 Temperature 20 15 10 Ambient supply air temperature Ambient return air temperature 5 Task supply air temperature Task return air temperature Air temperature in task zone 0 0:00 3:00 6:00 9:00 12:00 15:00 18:00 21:00 0:00 Time Figure 9; Temporal changes of supply/return air temperature and air temperature in task zone Table 7; Average of supply air temperature of each indoor unit 8/22(Wed) 8/23(Thu) 8/24(Fri) 8/25(Sat) Preset temperature [ C] 26.00 26.00 28.00 28.00 Average supply air temperature [ C] Minimum temperature [ C] Task 1 18.82 21.81 27.17 29.76 Task 2 23.37 23.20 27.10 28.45 Task 3 26.55 26.27 27.01 28.30 Task 4 17.94 20.01 26.68 29.01 Task 5 19.96 21.57 26.57 28.25 Task 6 23.78 24.93 25.37 27.96 Ambient 16.93 17.01 17.19 28.79 Task 1 9.80 8.00 12.80 19.70 Task 2 7.80 7.70 15.70 20.10 Task 3 14.70 14.10 16.80 20.40 Task 4 10.70 11.20 13.40 27.60 Task 5 13.60 14.30 17.00 17.70 Task 6 14.10 16.90 17.60 22.90 Ambient 16.20 16.30 16.40 28.00

- 11-5 CONCLUSION The energy calculation model developed by other research was verified, and the energy performance of the system was evaluated by analyzing the response of the system based on BEMS data according to the building use situations. The indoor comfort was considered to evaluate general performance of the system quantitatively based on actual investigation. Predicting values simulated based on BEMS data were compared with the data of heat source system during summertime, and the developed model was evaluated. In operation analysis, as the indoor heat load increases, the condensing temperature increases, and the evaporating temperature decrease. The evaporating temperature changes based on outdoor air state, and influences the compression work. In calculation of compression work, output values of model are approximately lower than BEMS data, and especially the margin of error is large in the range of low load operation. When the indoor heat load is lower than 5kW, output values of model don t change. The reason for this error is that compressor revolution speed of model can t be less than 10rps. However, in the other range, output values of model are highly similar to BEMS data. The indoor thermal environment in summertime of Building A under the multi-split type airconditioning system that uses developed models was investigated. A margin of error between most average air temperatures and preset air temperature was lower than 1 C, and during investigation, the maximum error between average air temperature and preset air temperature was lower than 2 C. During the investigation, most average airflow rates were moderate (within 0.2m/s), and the maximum airflow rate was lower than 0.25m/s, and design condition was satisfied. There was not so much influence by types of air outlet at the respective measuring spots. ADPI was calculated based on EDT. ADPI at most measuring spots was higher than 90%, and design condition was totally satisfied. The supply air temperature of the task indoor unit often fell below 10 C, but the air didn t influence the air temperature in task zone so much. And the air temperature in task zone didn t fluctuate rapidly. 6 REFERENCES Please list all references according to the following examples. Eisuke Togashi and Shin-ichi Tanabe, 2008. Development of energy calculation model of Multi-split type air-conditioning system, Heat Pump Conference 2008(plan) ANSI/ASHRAE Standard 113-2005. Method of Testing for Room Air Diffusion, American Society of Heating, Refrigerating, and Air-Conditioning Engineers, Inc., Atlanta.