Optimization of Irreversibilities in Water-Lithium Bromide Absorption Refrigeration System

Similar documents
Minimization of Irreversibilities in Vapour Absorption system by placing Organic Rankine Cycle at Condenser

and Exergy Analysis of a Typical LiBr/H 2 O VAR

THERMAL ENERGY ANALYSIS OF SOLAR POWERED VAPOUR ABSORPTION COOLING SYSTEM

Parametric Study of a Double Effect Absorption Refrigeration System

II. SYSTEM DESCRIPTION AND MATHEMATICAL MODELING

Exergy Analysis of a Single-Effect Water-Lithium Bromide Absorption Chiller Powered by Waste Energy Source for Different Cooling Capacities

Waste Heat Recovery of IC Engine Using VAR System

Conceptual Design of Nuclear CCHP Using Absorption Cycle

Energy and Exergy Analysis of Combined Ejector-Absorption Refrigeration System

R13. II B. Tech I Semester Regular/Supplementary Examinations, Oct/Nov THERMODYNAMICS (Com. to ME, AE, AME) Time: 3 hours Max.


Problems in chapter 9 CB Thermodynamics

Investigation of Separator Parameters in Kalina Cycle Systems

EXERGETIC ANALYSIS OF A SOLAR ABSORPTION HEAT TRANSFORMER

Refrigeration Cycle. Definitions , , 11-46, 11-49,

DESIGN OF VAPOUR ABSORPTION REFRIGERATION SYSTEM OF 1.5TR CAPACITY BY WASTE HEAT RECOVERY PROCESS

COMPARATIVE ANALYSES OF TWO IMPROVED CO 2 COMBINED COOLING, HEATING, AND POWER SYSTEMS DRIVEN BY SOLAR ENERGY

Thermodynamic Analysis of Gas Turbine Trigeneration System

Performance Assessment of Large Vapor Absorption System

Evaluating the Potential of a Process Site for Waste Heat Recovery

Thermodynamic Analysis of Combined Power and Cooling Cycle Using Process Heat from a Passout Turbine as a Heating Source

Theoretical analysis of an integrated thermoelectric-absorption cooling system

Performance Study and Energy Saving Mechanism Analysis of an Absorption/mechanical Hybrid Heat Pump Cycle

Thermodynamic Analysis of Organic Rankine Cycle using Different Working Fluids

CHAPTER 1 BASIC CONCEPTS

K.S. Rawat 1, H. Khulve 2, A.K. Pratihar 3 1,3 Department of Mechanical Engineering, GBPUAT, Pantnagar , India

- 2 - SME Q1. (a) Briefly explain how the following methods used in a gas-turbine power plant increase the thermal efficiency:

Low-Grade Waste Heat Recovery for Power Production using an Absorption-Rankine Cycle

Solar Absorption Aqua-Ammonia Absorption system simulation base on Climate of Malaysia

Energy and Exergy Analysis of M.P.C Absorption Chiller

Fundamental Investigation Of Whole-Life Power Plant Performance For Enhanced Geothermal Systems

Solar Powered Vapour Absorption Refrigeration (SPVAR) System as a rural microenterprise

Department of Mechanical and Materials Engineering. Solar Energy Research Institute Faculty of Engineering and Built environment.

IOP Conference Series: Earth and Environmental Science PAPER OPEN ACCESS

Chapter 1 STEAM CYCLES

EXPERIMENTAL ANALYSIS OF TRIPLE FLUID VAPOUR ABSORPTION REFRIGERATION SYSTEM DRIVEN BY ELECTRICAL ENERGY AND ENGINE WASTE HEAT. Kancheepuram, India

Combined Heat and Power

MODELING THERMODYNAMIC ANALYSIS AND SIMULATION OF ORGANIC RANKINE CYCLE USING GEOTHERMAL ENERGY AS HEAT SOURCE

OPTIMIZING THE GENERATOR AND ABSORBER THERMAL LOAD OF COMBINED ABSORPTION-EJECTOR REFRIGERATION SYSTEM

UNIVERSITY OF TORONTO FACULTY OF APPLIED SCIENCE AND ENGINEERING FINAL EXAMINATION, DECEMBER 2008 MIE 411H1 F - THERMAL ENERGY CONVERSION

ENERGY AND EXERGY ANALYSIS OF HEAT PUMP USING R744/R32 REFRIGERANT MIXTURE

Eng Thermodynamics I: Sample Final Exam Questions 1

Second Law Analysis of a Carbon Dioxide Transcritical Power System in Low-grade Heat Source Recovery

Experimental investigation of solar-driven double ejector refrigeration system

Eng Thermodynamics I - Examples 1

Design Features of Combined Cycle Systems

General performance characteristics of an irreversible vapour absorption refrigeration system using finite time thermodynamic approach

Eng Thermodynamics I - Examples 1

ABSORPTION/RESORPTION REFRIGERATION SYSTEMS WORKING WITH AMMONIA/WATER MIXTURES: MODELLING AND PERFORMANCE

Investigations of N 2 O Transcritical Refrigeration Cycle Using Dedicated Mechanical Subcooling. Sanjeev Kumar 1 and Dr. D.K.

Exergy analysis of transcritical carbon dioxide refrigeration cycle with an expander

a. The power required to drive the compressor; b. The inlet and output pipe cross-sectional area. [Ans: kw, m 2 ] [3.34, R. K.


THERMODYNAMIC ANALYSIS OF R134A DMAC VAPOR ABSORPTION REFRIGERATION (VAR) SYSTEM

Exergy Analysis of Absorption Power Cycle Depending on Source Temperatures

JJMIE Jordan Journal of Mechanical and Industrial Engineering

The Performance of Compression-absorption Heat Pump System Using Low-temperature Geothermal Tail Water

Analysis of Solar Thermal Cooling System Using TRANSOL

Improvement of distillation column efficiency by integration with organic Rankine power generation cycle. Introduction

Conceptual Design of Nuclear CCHP Using Absorption Cycle

ME ENGINEERING THERMODYNAMICS UNIT III QUESTION BANK SVCET

Energy Conversion and Management

ANALYSIS OF ABSORPTION REFRIGERATION SYSTEM WITH AMMONIA-WATER

Effect of Suction Nozzle Pressure Drop on the Performance of an Ejector-Expansion Transcritical CO 2 Refrigeration Cycle

Thermodynamic Modelling of a Vapor Absorption Cogeneration Cycle

Energy Saving Report. Frigi-Tech Oil Additive. Application. In HKU Central Plant. Chiller No. 3

LECTURE-14. Air Refrigeration Cycles. Coefficient of Performance of a Refrigerator:

SOLAR COOLING WITH SMALL SIZE CHILLER: STATE OF THE ART

Enhancement of CO2 Refrigeration Cycle Using an Ejector: 1D Analysis

FEE, CTU in Prague Power Engineering 2 (BE5B15EN2) Exercise 3

LIFE CYCLE COST ANALYSIS OF WASTE HEAT OPERATED ABSORPTION COOLING SYSTEMS FOR BUILDING HVAC APPLICATIONS

heat from a space to be cooled to a high temperature sink (place to be heated). Low

Lecture No.1. Vapour Power Cycles

Chapter 10 POWER CYCLES. Department of Mechanical Engineering

Studies on Reduced Inlet Temperature of Compressor and Water

Comparative Exergetic Analysis of Vapor Compression Refrigeration Systems in the Superheated and Subcooled Regions

Second Law of Thermodynamics

Development of an Innovative 2.5 kw Water- Silica Gel Adsorption Chiller

S.Y. Diploma : Sem. III [PG/PT/ME] Thermal Engineering

Thermodynamic performance of Kalina cycle system 11 (KCS11): feasibility of using alternative zeotropic mixtures

THERMODYNAMIC ANALYSIS OF A SMALL-CAPACITY AMMONIA / WATER ABSORPTION HEAT PUMP FOR HEATING AND COOLING

wb Thermodynamics 2 Lecture 11 Energy Conversion Systems

Pool Boiling Heat Transfer to Water/Lithium Bromide Mixture

A STUDY OF ABSORPTION CHILLER/HEATER APPLICATION IN MARINE ENGINEERING

Chapter 10 VAPOR AND COMBINED POWER CYCLES

ENHANCEMENT OF REFRIGERATION EFFECT USING FLUE GASES FROM CHIMNEY

Chapter 9: Vapor Power Systems

THE SECOND LAW OF THERMODYNAMICS

SIMULATION OF A THERMODYNAMIC CYCLE WITH ORGANIC ABSORBENTS AND CO 2 AS WORKING FLUID

OUTCOME 2 TUTORIAL 2 STEADY FLOW PLANT

Parametric Study of a Vapor Compression Refrigeration Cycle Using a Two-Phase Constant Area Ejector

Application of Exergy Analysis. Value and Limitations

Comparison of the performances of working fluids for absorption refrigeration systems

Single-stage and advanced absorption heat transformers operating with lithium bromide mixtures used to increase solar pond's temperature

Design considerations for integration of two 5 MW vapour compression heat pumps in the Greater Copenhagen district heating system

2 nd Law of Thermodynamics

Chapter 6 THE SECOND LAW OF THERMODYNAMICS

Exergy in Processes. Flows and Destruction of Exergy

Transcription:

August 016 IJIRT Volume 3 Issue 3 ISSN: 349-600 Optimization of Irreversibilities in Water-Lithium Bromide Absorption Refrigeration System P.Tharun Sai, Dr.K.Appa Rao Lakkireddy Balireddy College of Engineering Abstract The main objective of Vapour Absorption Refrigeration system(var) is to Produce refrigeration effect by consuming low grade energy(heat). The basic components of VAR system are Evaporator, Absorber, Generator, Solution heat exchanger, Expansion valve, Condenser. Since VAR system is heat operated cycle. The temperatures of generator, condenser, evaporator and absorber plays crucial role on performance of the VAR system. To analyze variation of temperatures on each component of VAR system a TR water lithium bromide system is designed based on first law analysis and Second law analysis is going to be carried out on each component of VAR to identify irreversibilities. After identification of the irreversibilities attempts to increase COP and decrease irreversibilities of VAR system is going to be done by optimization of temperatures on generator, condenser, absorber by keeping refrigerating load and evaporator temperature constant and writing entire procedure of thermodynamic analysis in MAT LAB script. The MAT LAB script runs on user provided inputs of generator, evaporator, absorber and condenser temperatures. After various iteration of temperatures on VAR system. The optimum temperatures are going to be found out on each component by keeping other component temperatures constant andvarying the specified component temperature in VAR cycle. The temperature which produces minimum irreversibilities in the cycle (i.e. irreversibilities should be greater than zero if irreversibilities are less than zero process is impossible) is taken as optimum temperature. After finding out all optimum temperatures the program runs over optimized temperatures (or nearer to optimum temperatures care should be taken to avoidsystem entering into crystallization zone). The performance parameters (COP, irreversibilities, second law efficiency) are obtained. The performanceparameters before optimization of VAR system are compared with obtained results. Index Terms MAT LAB, second law, irreversibilities, crystallization zone I.INTRODUCTION The continuous increase in the cost and demand for energy has led to move research and development to utilize available energy resources efficiently by minimizing waste energy. A better understanding of second law revealed that entropy generation minimization is important technique in achieving optimal system configurations and/or better operating conditions. The vapour Absorption refrigeration system becoming more important because it can produce higher cooling capacity than vapour compression systems. And it can be powered by low grade heat sources like flue gases from boiler, geothermal, biomass other than electricity. The absorption cycle uses a heat driven concentration difference to move refrigerant vapour from evaporator to condenser. So with use of second law analysis optimum temperatures going to be found out. It is crucial to promote absorption based cooling system to meet the cooling demand in place of VCRS. A number of researchers have investigated the performance a VAR with aqua-ammonia and lithium bromide (LiBr) water as absorbent refrigerant pair, with cooling capacity ranges from 5 to 50 kw. Small scale cooling system gives very low COP with slow cooling rate, which require a focus for improvement of its COP with compact designing. Additionally the small scale system must be operating on low temperature driving source. Most of the researchers inclined their work towards aquaammonia pair because of the low boiling temperature of ammonia (-33 C), which allows to go for cooling effect below 0 C. Ammonia is corrosive to copper tubings, toxic and flammable in nature. In addition to these limitations, water as absorbent is reasonably volatile which leads to presence of appreciable amount of water vapour in ammonia vapour leaving the generator. This may result in clogging of evaporator tubing due to which an analyzer and a IJIRT 14386 INTERNATIONAL JOURNAL OF INNOVATIVE RESEARCH IN TECHNOLOGY 8

August 016 IJIRT Volume 3 Issue 3 ISSN: 349-600 rectifier is used in aqua-ammonia system, which increases the system complexity.based on these restrictions of aqua ammonia system, LiBr-water absorption system is more suitable to study.most of research and development studies regarding solar absorption refrigeration systems (VARs) deals with the single stage system type. It is important to note that system performance can be enhanced by reducing the irreversible losses in the system by using the principles of the second law of thermodynamics. A better understanding of the second law of thermodynamics [1] has revealed that entropy generation minimization is an important technique in achieving optimal system configurations and/or better operating conditions. Some researchers [,3,4] have used the principles of entropy generation minimization to analyze different systems and to improve the systems performance. Theoretical and experimental studies on the performance and thermodynamic analysis of VARs are available in the literature. Chen and Schouten [5] conducted an optimal performance study of an irreversible VAR. They considered irreversibility viaan irreversibility factor and optimized the expression for COP with respect to a number of system parameters. Chua et al. [6] modeled an irreversible ammonia water absorption chiller by considering the internal entropy production and thermal conductance of the heat exchangers. The model was applied to a single-stage chiller, and the results showed that the highest heat dissipation occurred in the rectifier. Kececiler et al. [] performed an experimental study on the thermodynamic analysis of a reversible lithium bromide water VAR. However, recent analyses of VARs have included the second law thermodynamics to provide better understanding of the thermal performance characteristics of each system components. This facilitated the detection of a component with high energy dissipation or irreversible losses. Attention can then be focused on such a component to minimize its irreversible losses. Lee and Sherif [8] applied both the first and the second law of thermodynamics to analyze multi-stage lithium bromide water VARs. The second law efficiency of the chillers was calculated from the thermal properties, as well as the entropy generation and exergy of the working fluids. Furthermore, Lee and Sherif [8] used the second law efficiency to quantify the irreversible losses compared to the total entropy.generation, which represents the energy dissipation of the system. Adewusi and Zubair [4] used the second law of thermodynamics to study the performance of single-stage and two-stage ammoniawater VARs. The entropy generation of each component and the total entropy generation of all the system components as well as the coefficient of performance (COP) of the VARs were calculated. The results show that the two stage system has a higher total entropy generation and COP, while the single-stage system has a lower total entropy generation and COP. Apart from other studies this paper deals with optimization of system performance by doing second law analysis on the system and finding out optimum temperatures and running simulation of VAR system nearer to optimum temperatures in mat lab script. The properties for calculations various state points for solutions at different concentration are taken from R. Gonzales3 and S. A. Nebra[9]. II.SYSTEM DESCRIPTION AND WORKING Fig.1 shows main components of Vapour Absorption Refrigeration system Qg is the heat input rate from source rejecting by fluid entering at point 15 and leaving at 16.The Weak solution from the solution heat Exchanger enters into generator by gaining heat water vapour at state1 enters into condenser and rejects heat to external circuit. Which flows at cooler temperature (T1) by gaining heat it gets heated taking Qc from the water vapour at Point 1 and converting it into high pressure liquid at Point.After the Expansion valve the pressure of refrigerant is decreased to point 3(saturated liquid).after getting Qe heat load from Evaporator circuit refrigerant gains latent heat and becomes saturated vapour at point4, Circulating Water is cooled from Point 11(T11) to Point(1) (T1).In the absorber strong solution absorbs water vapour from the evaporator and becomes weak solution at point 5.pump pressurizes weak solution up to generator pressure at point 6.After entering into solution heat exchanger Weak solution at point 6 is heated to point by taking heat from strong solution coming from generator at point 8(which is equals to generator temperature). The strong solution is cooled to point 9 after heat IJIRT 14386 INTERNATIONAL JOURNAL OF INNOVATIVE RESEARCH IN TECHNOLOGY 9

August 016 IJIRT Volume 3 Issue 3 ISSN: 349-600 exchanger and expanded to point 10 after strong solution expansion valve. Figure.1:-Vapour Absorption Refrigeration system Mass conservation:- (Σm)in = (Σm)out ʓ = m libr /(m libr +m w ) Energy conservation:- (Σm*e)in = ((Σm*e)out Irreversibility generation rate:- I = T0*[m R *(S system out -S system in )+m surroundings *(S surr out S surr in )] Coefficient Of Performance:- Q e /(Q g + W p ) III..ASSUMPTIONS:- III. THERMODYNAMIC ANALYSIS OF TR WATER-LITHIUM BROMIDE REFRIGERATION SYSTEM Generator Temperature = 90ºc Absorber Temperature = 35 ºc Condenser Temperature = 35 ºc Evaporator Temperature = 10 ºc Generator source Temperature = 150 ºc (Isothermal heat addition) Absorber cooling water entering Temperature = 0 ºc Absorber cooling water leaving Temperature = 5 ºc Condenser cooling water entering Temperature = 30 ºc Condenser cooling water leaving Temperature = 35 ºc Refrigerating load = 6.18 kw III.1.FIRST LAW &SECOND LAW STEADY STATE ANALYSIS ON VAPOUR ABSORPTION REFRIGERATION SYSTEM 1. The system is operated under steady state conditions.. Pressure drops and heat transfer losses in the pipelines are neglected. 3. Expansion of the LiBr- water mixture through throttle valves is isenthalpic in nature. 4. The solution pump is isentropic in nature. 5. The refrigerant states at outlet of condenser and evaporator are saturated liquid and saturated vapour respectively. III.3.EVAPORATOR:- ṁ 3 = ṁ 4 m 11 = m 1 Qe = ṁ 3 (h 4 h 3 ) İevaporator = T 0 [ṁ 3 (S 4 S 3 )+ ṁ 11 (S 1 -S 11 )] III.4.ABSORBER:- ṁ 3 + ṁ 10 = ṁ 5 Refrigerant mass balance:- ṁ 3 + ṁ 10 (ʓ ss ) = ṁ 5 (ʓ ws ) ṁ 13 = ṁ 14 Qa = ṁ 3 h 3 +ṁ 10 h 10 -m 5 h 5 İabsorber = T 0 [(ṁ 5 S 5 -(m 3 S 4 + ṁ 10 S 10 ))+ ṁ 13 (S 14 -S 13 )] IJIRT 14386 INTERNATIONAL JOURNAL OF INNOVATIVE RESEARCH IN TECHNOLOGY 10

August 016 IJIRT Volume 3 Issue 3 ISSN: 349-600 III.5.PUMP:- Wp = ṁ 5 (h 6 -h 5 ) III.6.HEAT EXCHANGER:- İshx = T 0 [ṁ 10 (S 9 -S 8 )+ ṁ 5 (S -S 6 )] III..GENERATOR:- ṁ = ṁ 8 + ṁ 1 ṁ 15 = ṁ 16 Qg = ṁ 1 h 1 +m 8 h 8 -m h İgenerator = T 0 [(ṁ 1 S 1 + ṁ 8 S 8 )-( ṁ S )+( ṁ 15 (S 16 -S 15 )] III.8.CONDENSER:- Qc = ṁ 1 (h -h 1 ) ṁ 1 = ṁ 18 İcondenser = T 0 [ṁ 1 (S -S 1 )+ ṁ 18 (S 18 -S 1 )] İtotal = İgenerator+ İshx+ İabsorber+ İcondenser+İevaporator Stat e poin ts Table.1.Thermodynamic Properties at various points of system P (kp a) T (ºC) ʓ h (kj/kg ) S (kj/kg -k) ṁ (kg/sec ) 1 5.6 90-660. 1.480 0.016 5.6 35-146.6 0.505 0.016 3 1.3 10-4 0.151 0.016 4 1.3 10-50 8.90 0.016 5 1.3 35 5. 5 5.85 0.6 0.016 6 5.6 35 5. 5.85 0.6 0.03 5 5.6 6 5. 151.6 0.445 0.03 5 91 65 8 5.6 90 65 35.3 0.48 0.03 5 6 9 5.6 5 65 156.5 5 0.8 60 0.0610 4 10 1.3 5 65 156.5 0.8 0.0610 5 60 4 11-30 - - 0.43 0.35 1-10 - - 0.151 0.35 13-0 - - 0.43 0.9961 64 14-5 - - 0.36 0.9961 64 15-150( v) - 06.19 0.0163 4 16-150( l) - 36.9 1.193 0.0163 4 1-30 - - 0.43 1.511 18-35 - - 0.505 1.511 Table..Heat transfer rates into and out system and irreversibility generation rate in VAR along with COP and second law efficiency obtained from MAT LAB script S.No Out puts(kw) Qe 6.18 Qa.0433 Qg.54 Qc 6.69 İtotal.369 (COP)designed system 0.85185 Second law efficiency 0.45631 IV. RESULTS AND DISCUSSIONS Optimization of Temperatures by Second law analysis:-since the analysis mainly focuses on minimization of irreversibilities. The system must be operated at various temperatures to decrease irreversibilities. Temperature differences among the system must beminimized so that system runs nearer to thermal equilibrium. While varyingtemperatures the irreversibilities produced at expansion valve are constant. So while plotting graphs irreversibilities associated with expansion valve are omitted. During variation of temperatures on a particular component remaining temperatures are held fixed. IV.1. Variation of Generator Temperature:- From Fig.&Fig.3.it is observed that Actual cop decreases with increase in generator temperature. This is may due to increase in finite temperature difference between heat exchanger. which is also effects Irreversibility s associated with the system. Although IJIRT 14386 INTERNATIONAL JOURNAL OF INNOVATIVE RESEARCH IN TECHNOLOGY 11

August 016 IJIRT Volume 3 Issue 3 ISSN: 349-600 the higher temperature difference produce more vapour at the same time this will result in increase in absorber load will effect absorption process and Cop of system decreases beyond 85ºC.But Irreversibilities associated with system in other hand increases continuously due to increase in temperature difference among the components. IV..Variation of Evaporator temperature:-from Fig.4&Fig.5 by increasing evaporator temperature increases the vapour pressure in absorber leads in significant increase in absorption process of the strong solution at constant cooling load with increase in evaporator temperature causes generator load, absorber load decreases. Irreversibilities among the cycle decreases due to decrease in temperature difference among the components. So heat addition at low temperature difference causes lower entropy generation and low irreversibilities. IV.3. Variation of condenser Temperature:-From Fig.6&Fig. it is observed that if cooling load is kept constant then with increase in condenser temperature increases corresponding increase in condenser pressure. This leads to increase in load in generator as a result cop decreases with increase in condenser temperature. But increase in condenser temperature causes drop in temperature difference across circuit so irreversibilities decreases with increase in temperature. IV.4. Variation in absorber Temperature:- From Fig.8&Fig.9 the absorption efficiency decreases with increase in absorber temperature this results in increase in generator load and absorber load with increase in mixing losses at absorber. As the temperature difference between strong solution and weak solution increases with increase in absorber temperature negatively impacting with absorption process.the process is similar for external reservoir temperatures (i.e. source, sink temperatures) to find out optimal temperatures to produce minimum irreversibilities. Temperatures obtained from the mat lab simulation which produces least irreversibilities and higher cop are noted. And the system again runs nearer to these optimum temperatures. By considering both internal and external irreversibilities. Since condenser operating temperature change can cause opposite effects for Cop and irreversibilities. Organic rankine cycle is placed near the condenser to decrease Irreversibilities at Condenser. IV.5. Optimized values taken from MAT LAB are:- Evaporator operating temperature = 10ºC Condenser operating temperature = 35 ºC Generator operating temperature = 85 ºC Absorber operating temperature = 30 ºC Chilled water entering temperature = 30 ºC Chilled water cooling temperature = 10 ºC Absorber Cooling water entering temperature = 5 ºC Absorber Cooling water leaving temperature = 30 ºC Generator hot water temperature at entering = 130 ºC (vapour) Generator hot water leaving temperature = 130 ºC (liquid)from the above optimized values given to the mat lab script the values obtained are as follows Table.3.Thermodynamic properties required for MAT LAB Script State point s T (ºC) Concentrat ion s(kj/kg-k) 5 30 49.449 0.13913 6 30 49.449 0.13913 60. 49.449 0.4348 8 85 6.90 0.46391 9 46.5 6.90 0.434 COP = 0.86 İtotal = 1.9410 kw second law efficiency of system = 0.50435 VI.FiGURES IJIRT 14386 INTERNATIONAL JOURNAL OF INNOVATIVE RESEARCH IN TECHNOLOGY 1

COP Total Irreversibilities in Kw Irreversibilities assosciated with Evaporator in Kw COP COP August 016 IJIRT Volume 3 Issue 3 ISSN: 349-600 0.8536 generator temperature vs cop 0.9 Evaporator Temperature Vs COP 0.8534 0.89 0.853 0.88 0.853 0.858 0.856 0.8 0.86 0.854 0.85 0.85 0.84 0.85 0.8518 80 8 84 86 88 90 generator temperature in ºc Fig..Variation of COP with Tg 0.83 5 6 8 9 10 11 1 13 14 15 Evaporator Temperature in ºC Fig.4.Variation of COP with Te.11 Evaporator Temperature Vs Irreversibilities.11 Generator Temperature Vs Total Irreversibilities.108.106.1.09.08.104.10.1 5 6 8 9 10 11 1 13 14 15 Evaporator operating Temperature in ºC Fig.5.Variation of irreversibilities with Te.0 0.865 Condenser operating Temperature Vs Cop.06 80 81 8 83 84 85 86 8 88 89 90 Generator Temperature in Degree celsius Fig.3.Variation of irreversibilities with Tg 0.86 0.855 0.85 0.845 0.84 0.835 35 36 3 38 39 40 41 4 43 44 45 Condenser Operating Temperature in ºc Fig.6.Variation of COP with Tc IJIRT 14386 INTERNATIONAL JOURNAL OF INNOVATIVE RESEARCH IN TECHNOLOGY 13

Total Irreversibilities in Kw COP Total Irreversibilities in Kw August 016 IJIRT Volume 3 Issue 3 ISSN: 349-600.16.14.1.1.08.06.04 35 36 3 38 39 40 41 4 43 44 45 Condenser operating Temperature in Degree Celsius Fig.. Variation of Irreversibilities with Tc 0.91 0.9 0.89 0.88 0.8 0.86 0.85 0.84 Condenser Temperature Vs Total Irreversibilities 0.83 5 30 35 40 Absorber temperature in celsius degree Fig.8.Variation of Irreversibilities with Ta. Absorber Temperature Vs COP Absorber Temperature Vs Total Irreversibilities V.CONCLUSION Second law analysis provides minimum temperatures to operate cycle to avoid exergy destruction. COP of system is optimized without affecting the feasibility of process. COP of system after optimization is increased by 1.9% Irreversibilities after optimization of temperatures is decreased by 1% Heat added in generator, Heat rejected in absorber is decreased slightly compared to original system. Circulation ratio of the system is decreased by 1.4%.As circulation ratio decreased COP increases. Irreversibilities at condenser are negligibly decreased so in order to decrease destruction of availability any heat recovery system is used to decrease destruction of exergy. Since in practical systems irreveribilities at generator are so high but by making system design by thermodynamic analysis generator irreversibilities can be decreased considerably. Second law efficiency of the system is improved by 10%. MAT LAB gives reasonable accurate results and avoids number of iterations and find outs optimum temperatures with minimum data input. NOMENCLATURE.15.1.05 Te,Tg,Tc,Ta= Evaporator,generator,condenser,absorber temperatures(ºc) ṁ= mass flow rate(kg/sec) in = entering into system 5 30 35 40 Absorber Temperature in celsius Degree Fig.9.Variation of irreversibilites with Ta ʓ = concentration of lithium bromide in solution m w = mass of water in solution S system in = specific entropy of working fluid entering into system in (kj/kg-k) IJIRT 14386 INTERNATIONAL JOURNAL OF INNOVATIVE RESEARCH IN TECHNOLOGY 14

August 016 IJIRT Volume 3 Issue 3 ISSN: 349-600 S system out = specific entropy of system leaving from system(kj/kg-k) m surroundings = mass flow rate entering from external sources and sinks(kg/sec) S surr in = specific entropy of surroundings at entry of system(kj/kg-k) S surr out = specific entropy of surroundings at exit of system(kj/kg-k) Energy Conversion and Management 000;41:3 48. [8] Lee SF, Sherif SA. Second-law analysis of multi-effect lithium bromide/water absorption chillers. ASHRAE Trans 1999;105(1):156 66. [9] Exergy calculation of lithium bromide water solution and its application in the exergetic evaluation of absorption refrigeration systems LiBr-HO Reynaldo Palacios-Bereche1,, R. Gonzales3 and S. A. Nebra. Qe = evaporator load in kw Qg = heat supply at generator in kw Qc = condenser heat rejection rate in kw Qa = absorber heat rejection rate in kw Wp = Work supplied to pump in kw h = specific enthalpy (kj/kg) REFERENCES [1] Lieb EH, Yngvason J. A fresh look at entropy and the second law of thermodynamics. Phys Today000;53(4):3 6. [] Ogulata RT, Doba F. Experiments and entropy generation minimization of a cross-flow heat exchanger. Int.J.Mass.Transfer 1998;41():33-81. [3] Vargas J, Bejan A, Siems D. Integrative thermodynamic optimization of cross-flow heat exchanger for an aircraft environmental control system. J Heat transfer 001;18:60-9. [4] Adewusi S.A., Syed M. Zubair. Second law based thermodynamic analysis of ammonia water absorption systems. Energy Conversion andmanagement 004 ;45:355 369. [5] Chen J, Schouten JA. Optimum performance characteristics of an irreversible absorption refrigeration system.. Energy Conversion and Management 1998;39:999 100. [6] Chua HT, Toh HK, Ng KC. Thermodynamic modeling of an ammonia/water absorption chiller. Int J Refrig 00;5:896 906. [] Kececiler A, Acar HI, Dogan A. Thermodynamic analysis of absorption refrigeration system with geothermal energy: an experimental study. IJIRT 14386 INTERNATIONAL JOURNAL OF INNOVATIVE RESEARCH IN TECHNOLOGY 15