Tech Tip: Cold Weather Roof Coating Recommendations

Similar documents
BAYBLOCK HT/BAYBLOCK HT BASE

Primers: Why, When and How to Use Them In spray polyurethane and/or elastomeric coating systems

STAYCELL APPLICATION GUIDE

Refer to Substrates & Surface Preparation.

Nutech Roof Coatings Nutech Paint Application Instructions & Guidelines Nutech Roof Coating Range of Products

GULF COAST PAINT MFG., INC

Refer to Substrates & Surface Preparation.

Concrete Masonry Unit Block Fill Installation and Estimating Guide

the SureCoat Roof System.

THE BRITE THING TO DO

Measured in accordance with ASTM D 2697.

OPERATION, SAFETY & PROCEDURE GUIDELINE MANUAL FOR

Technical Bulletin. Open-Cell Spray Polyurethane Foam Equipment Set Up and Processing: (Please Review Technical Data Sheet)

DURA 500 LIQUID RUBBER THERMOPLASTIC ROOF COATING SYSTEM BY SUPERIOR POLYMERS INC.

Measured in accordance with ASTM D 2697.

INSTALLATION GUIDE SPECIFICATION

Application Guidelines for Field-Applied Touch-up Paint Systems on Metal Panels

A Guideline for Securing Roofing Components with SPF Adhesives

838 Coatings System Specification Single-Ply Restoration (838 SPR)

DURA 500 THERMOPLASTIC FLAT ROOF COATING SYSTEM BY SUPERIOR POLYMERS INC.

Aliphatic Acrylic-Polyester Polyurethane

Recommended Application Procedures

CAS Number. Pipe exteriors

JAXSAN AG-102 HIGH GLOSS PAINT/SEALANT

Fire Protection Products

Data Sheet Eco-Smart Membrane WS M1

Master-Seal Surface-Applied Waterproofing System

POLYURETHANE FOAM SAMPLE DESIGN GUIDELINE ACRYLIC

MEMBRANE 510/510R Low VOC Flexibilized, Urethane Membrane mils

Rust-Oleum Industrial Brands Specification

RENEW ELASTOMERIC ACRYLIC COATING (PAINT GRADE) MANUFACTURERS SPECIFICATION / SECTION

ACRYLIC. AGED (PVC, CPE, CPA) SINGLE-PLY (Thermoplastic) Membrane Restoration Sample Design Guideline

Compliance Standards of Coated SPF System: inclusive of Permax 108 or Permax 115 Acrylic Elastomeric Coating ± 100

A/D Firefilm III PRODUCT DATA SHEET

Simalfa 335-Of {Overspray Free}

Carboxane 950 Metallic

Simalfa 900-PU. Product Description. Key Properties. Certifications. Physical Properties

Fire Protection Products

Carboguard 890 PRODUCT DATA SHEET SELECTION & SPECIFICATION DATA. Generic Type. Cycloaliphatic Amine Epoxy

ASTEC Re-Ply Roof System for ASPHALT & MODIFIED BITUMEN ROOFS

Recommended Application Procedures

ASTEC Re-Ply Roof System for ASPHALT & MODIFIED BITUMEN ROOFS

Solventless, two-component, cross-linked epoxy. Epoxies lose gloss, discolour and eventually chalk in sunlight exposure.

FLUID APPLIED ROOFING - HYPALON ROOF RESTORATION

3,Rothwell Street, Timaru, South Canterbury. ; : Phone or

URETHANE. Asphalt Restoration Aged BUR and Modified Bitumen Sample Design Guideline

A. Submit product data sheets and literature verifying fire ratings and physical properties of materials.

A. Supplier Qualifications: The ACRYSHIELD SPF Roofing System, as supplied by National Coatings Corporation, is approved for use on the project.

SOLAR COATING SYSTEMS ACRYLIC RENOVATION ROOF 4.5. Specification for Built-Up Roofing SUMMARY

APPLICATION GUIDELINES EXTERIOR DECK SYSTEM

NSP SPECIALTY PRODUCTS Technical Data Sheet. NSP 120 High Performance Epoxy Coating

APPLICATION GUIDELINE Recoating Spray Foam Acrylic System

Refer to Substrates & Surface Preparation.

Elastomeric Protected Membrane Roofing Fluid-Applied Protected Membrane Roofing. Restoration Coating System (RCS) over Cap Sheet

ASTEC Re-Ply Roof System for AGED SINGLE PLY MEMBRANE (PVC, EPDM, THERMOPLASTIC) ROOFS

3M Fast Tack Water Based Adhesive 1000NF

Product Data Sheet Waterproofing Membrane for Ponds and Water Features Description Uses Suitable Surfaces Additional Uses Specification

ERSYSTEMS ONESTEP PLUS

EPDM ROOF RESTORATION

Hydrophilic Polyurethane Grout

TOPCOAT System Specifications Corrugated Transite Panels

Scotch-Weld Metal Bonder Acrylic Adhesive DP8407NS Gray

TL-280 Sprayable Flake Glass Vinyl Ester Lining System

NAVSEA REVIEWED ASTM F-718. If this product is to be applied as part of a coating system, all components of the system must be as listed on the QPL.

Understanding new Acceptance Criteria of Alternative Assemblies Thermal and Ignition Barriers over SPF

Rust-Oleum Industrial Brands Specification

Application Specification:

SOLAR COATING SYSTEMS SYSTEM EMULSION /ACRYLIC. Specification for Built-Up Roofing MULSION/A 1.01 SUMMARY

Guideline Specification ACRYMAX ARS-1-C Reinforced Composite Elastomeric Membrane System for Concrete Roofs Fluid-Applied Roofing

Enduris * silicone roof coating

SPECIALTY PRODUCTS AQUACHECKTM ASPHALT PRODUCTS - SPECIALTY PRODUCTS

DAP WELDWOOD Nonflammable Contact Cement

Retrofit Installation Guide

DAP WELDWOOD Nonflammable Contact Cement

Substrate/Ambient Temperature Standard 50 F to 120 F Polar 30 F to 80 F

ARDEX GUIDE SPECIFICATION ARDEX CD Concrete Dressing and ARDEX CD FINE Concrete Dressing Polymer-Modified, Portland Cement-Based, Resurfacing Compound

Hydrophilic Polyurethane Grout Cartridge Application

NAVSEA REVIEWED ASTM F-718. Interline 783 Finish, Ultra High Solids Two-Pack Fast Cure Solvent-Free Coating

POLYURETHANE FOAM SAMPLE DESIGN GUIDELINES URETHANE

PERFORMANCE, 100% SOLIDS,

Rust-Oleum Industrial Brands Specification

Rust-Oleum Industrial Brands Specification

Nanoman Anti-Rust & Corrosion TDS

Recommended Application Procedures

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COATED FOAM ROOFING REPORT HOLDER: COVESTRO, LLC

FireShield Restoration Specifications - EPDM

A. Submit product data sheets and literature verifying physical properties of materials.

RG-170 Elastomeric 15yr System/ Metal Roofs

TECHNICAL INFORMATION. 331 and PENNCOAT 340 LINING INSTALLATION. CES /01 Supersedes 04/00 PAGE 1 of 7 1. SURFACE PREPARATION. 1.

DOWSIL Neutral Plus Silicone Sealant

Red Insulating Varnish 4228 Technical Data Sheet 4228-Liquid

Copolymer BEFORE. Copolymer DURING. Copolymer AFTER. (800) TRI-CHEM 3

EPDM SINGLE-PLY SYSTEM SUMMARY

DESIGN GUIDELINE FLUID-APPLIED WATERPROOFING

Adhesion Promoter/Primer 3M Adhesion Promoter AP596

RTV5249. Technical Data Sheet

DESIGN GUIDELINE FLUID-APPLIED WATERPROOFING

TOPCOAT Restoration Specifications Structural Concrete

COOL BARRIER ROOF. High Solar Reflective Elastomeric Liquid Applied Roof Coating Water-Based for Big and Low Slope Roofs

Scotch-Weld Acrylic Adhesives

Transcription:

Tech Tip: Cold Weather Roof Coating Recommendations Copyright: 2010

Page 2 MISSION STATEMENT The mission of the Technical Oversight Committee is to provide a wide range of technical service to the Spray Polyurethane Foam industry such as, but not limited to: 1. Review existing documents and serve as a clearing house to ensure the Continuity of Value of technical information published by SPFA and others concerning the products and services to our industry; 2. Review, research, develop and issue documents concerning new products, systems and services AND 3. To identify, explore, develop, and communicate an understanding of technical issues facing our industry. The information provided herein, based on current customs and practices of the trade, is offered in good faith and believed to be true, but is made WITHOUT WARRANTY, EITHER EXPRESS OR IMPLIED, AS TO FITNESS, MERCHANTABILITY, OR ANY OTHER MATTER. SPFA DISCLAIMS ALL LIABILITY FOR ANY LOSS OR DAMAGE ARISING OUT OF ITS USE. Individual manufacturers and contractors should be consulted for specific information. Nominal values which may be provided herein are believed to be representative, but are not to be used as specifications nor assumed to be identical to finished products. SPFA does not endorse the proprietary products or processes of any individual manufacturer, or the services of any individual contractor.

Page 3 General Cold Weather Roof Coating Recommendations 1. The application of elastomeric protective coatings applied by roller application or by high pressure airless spray requires basic personal protection equipment for the installer and hose tender. This equipment should include; disposable coveralls, fabric gloves fully coated with butyl, PVC, or neoprene, NIOSH-approved air purifying respirator with combination organic vapor/particulate cartridges, and chemical safety goggles. It is important that the installers be trained in the safe use of airless high pressure spray equipment and first aid procedures associated with this equipment. Pumps, delivery hose, and gun/tips require start-up, shut-down, and storage procedures similar to foam application equipment to prevent damage to these components and operators. 2. The definition of cold weather with regard to applying elastomeric coatings is 55 F and dropping. This condition is not dreadfully cold but when applying elastomeric coatings it can be a starting point where it becomes difficult to apply and optimum results can be sacrificed. 3. This discussion will group the three most popular coatings, acrylic, silicone, and polyurethane, as all coatings have similarities when being applied in cold weather conditions. 4. When applying coatings, the goal is to provide a continuous, uniform, fully cured dry film or membrane which is free of voids, pinholes, surface blisters and membrane cellularity with good adhesion to the substrate. 5. The above can only be achieved when the coating material is applied to a clean and dry surface. Furthermore, the temperatures of the substrate, air and coating material must be high enough to provide the heat necessary to evaporate volatiles (solvent or water) and/or effect the appropriate curing action (coalescence, moisture activation or reaction) before the coating membrane is affected by dew, rain or other detrimental conditions. Viscosity and Temperature 1. A viscosity range of 98 Ku to 110 Ku (Krebs units) (1500 to 2250 centipoise) is a good sprayable range. As the temperature drops the coating viscosity increases disproportionately. 2. Increasing pump pressure, output capacity and hose diameter are generally required to compensate for higher viscosity. For every 18 F decrease in material temperature, the viscosity of coatings may double. Material Storage and Handling 1. Job site storage of coating materials can become critical during cold weather. Ensure that coatings are ordered, delivered and stored on the jobsite in insulated or heated trailers. Frozen coatings may not be useable even when heated. Some coatings can experience phase separation, develop crystals or freeze at cooler temperatures. Consult the manufacturer should these conditions develop. Pumping and Spraying 1. Viscosity and Atomization: Regardless of the type coating being used it must be pumped with sufficient pressure to be atomized and sprayed. When working under cold conditions, the viscosity of the coating materials will increase and the create losses in pressure and spray pattern. The spray equipment must be sized to accommodate these conditions.

Page 4 Pumping and Spraying (cont d) 2. Supply: As temperature drops and viscosity increases it is very important that a constant supply of material be fed to the coating pump. A siphon hose and pipe which generally works in warmer weather conditions will not adequately feed high output coating pumps in cooler weather. It is recommended that a 5:1feeder pump with minimum ¾-inch hose be used to supply the coating pump. 3. Coating Pumps: In general terms, high output coating pumps are defined by maximum pressure (psi) and gallons pumped per minute (gpm). The higher the output and pressure of the equipment the easier it will be to pump coatings in cooler weather. 30:1 ratio, maximum pressure with 100 psi pressure is 3000 psi 45:1 ratio, maximum pressure with 100 psi pressure is 4500 psi 56:1 ratio, maximum pressure with 100 psi pressure is 5600 psi The above noted air driven pumps are also supplied in hydraulic driven motors with the same ratios, pressure, and material delivery systems. 4. High Pressure Hose: Coating hose diameter and length affect the pressure at the spray gun: long, narrow hoses may not provide sufficient pressure (especially when material temperature is cold and viscosity is high) to properly atomize the coating. When purchasing coating hose ensure that the hose is rated for the maximum capacity of the coating pump. Higher solids coating materials like silicone and some moisture cure polyurethane coatings, even during warm periods, require minimum ½-inch hose and, with smaller ratio pumps (30:1), may be limited to 200-foot hose length. It is not uncommon to run ¾-inch hose for 100 feet or more when hose requirements exceed 300 feet. A 3/8-inch whip hose 3 to 4 feet in length may still be used just before the gun. As a rule using 3/8-inch coating hose during cold weather will not work. Hoses should be handled and stored to prevent kinking.. It is recommended that when coating work is complete that 50% - 70% of the static pressure be bled-off. The residual pressure left in the hose reduces the chance of kinking the hose when rolling it up. Damaged or kinked hose sections should be replaced immediately. When using flammable solvent based coatings it is imperative that the coating equipment be grounded to prevent any static electricity ignition sources. 2. Spray Gun and Tips: High pressure spray guns designed for high output are basic requirements during warm or cold weather. Make sure the coating gun is designed for the maximum pressure capacity of the coating pump. Tip size can be changed to adapt to more viscous materials along with the coating pump s pressure settings. When the coating becomes more viscous a smaller tip size may be required to atomize and break the coating up into sprayable particles. Application Techniques 1. Coatings installed in cold temperatures may result in uncured or poorly cured coating, blisters, cellular film (cottage cheese), and pinholes. During cold weather and shorter daylight times, apply coatings in thinner coats which have faster cure times. Additionally, use darker colors for the base coat applications as this will help them cure more quickly in cooler temperatures as well as providing a warmer surface which aids in curing subsequent coats. A white top coat may be especially slow to cure in cold temperatures; stop production early in the day to allow 3 to 4 hours of sunlight on the white-coated surface to skin or dry. 2. In the most severe cold conditions, acrylic coatings, if not allowed sufficient time to allow water to evaporate and the surface to skin may freeze at night leaving a glazed cracked surface and sometimes ruining the entire Tech Tip : Cold Weather Roof Coating Recommendations

Page 5 film. Other detrimental effects can be partial or total wash-offs caused by heavy dew or rain if the coating has not skinned. In colder climates the threat of wash-offs may persist for several days. Several manufacturers make fast setting coatings and these should be considered when using acrylic coatings in cold climates. These coatings, depending upon temperature and humidity may dry several hours faster than regular coating formulations but will still have trouble setting up under 50 F. Contact your coating manufacturer for specific drying times of their coatings. 3. Coating heaters are available but check with the coating and equipment manufacturer before using on specific coating products.