Power IT Compact Secondary Substations, CSS. Technical catalogue for sheet steel substations

Similar documents
Power IT Compact Secondary Substations, CSS. Technical Brochure

TECHNICAL CABINS +CONCEPT ALFRED PRIESS

Power Zone Center. Your solution for power distribution and control systems

Prefabrication & Distribution A Global Solution GRC. Prefabricated Substation PARS TABLEAU

MOBILE SUBSTATIONS TRAILER AND SKID. tgood.com. Energy, Fast!

Stainless steel. 1.6 Stainless steel IP 69 K. Premium Panel, protection category IP 69K

56-SDMS-01 REV. 01 SPECIFICATIONS FOR

A SUBSTATION CONCEPT FOR CHANGEABLE LOAD CONDITIONS

Protective devices according to EN ISO 12100

ARGENTA PLUS (FSC) IP55-IP65 steel floorstanding. cabinets. SEMI-COMPACT (FSC) Technical Specifications

TABLE OF CONTENTS. FOREWORD... Error! Bookmark not defined. INTRODUCTION SCOPE NORMATIVE REFERENCES DRAWING...4

Technical Description For MK-CTX Office Cabins

PFS Underground Buildings for Transformer Substations Up to 36 kv

The complete guide to transformers and packaged substations

Sectional Overhead Doors SECTIONAL OVERHEAD DOORS

Important Considerations for Specifying MV Mining Switchgear Western Mining Electrical Association Edmonton, Canada June 13, 2008

Modular Floor Standing Enclosures Steel Powder-Coated MF1S SINGLE DOOR IP55

Siemens Controls. The power distribution board that sets new standards. SIVACON S4 safe, cost-efficient and flexible SIVACON

Series PV. Compact Switchgear Cabinets. Construction subject to change without notice Dimensions in mm

MANUFACTURING TECHNICAL INSTRUCTIONS SAFETY Subject: DESIGN, MAINTENANCE AND INSPECTION OF SECONDARY ELECTRICAL DISTRIBUTION SYSTEMS

Specification for Prefabricated Glass Reinforced Plastic Enclosures

Delta Part Liber Superthermic Insulated Bi-Folding Door. Product Data Sheet 7 / 4

31-SDMS-03 REV. 01 SPECIFICATIONS FOR

30-SDMS-01 SPECIFICATIONS FOR LOAD BREAK SWITCH

INC Pre-Assembled Structures

JUNCTION BOX AND BAYMARSHALLING KIOSK

CONTENTS. B. System Design and Performance Requirements

UNIFIED FACILITIES GUIDE SPECIFICATIONS

SECTION OVERHEAD DOORS. Summary of Structural Steelwork Drawings SECT IONAL OVERH EAD D OORS

Technical Specification for LV ABC Fuse Switch Disconnectors

Arc Resistant Switchgear & Integrated Factory Assembled Buildings

DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT

Fire Protection Valves

660 Volts 630 & 800AMP

Stack Parking Surface Mounted Stackers

DICTATOR Lift Shaft System

Sound insulating doors

Enclosures for fibre optical networks. Elogic Systems offers insight, experience and a wide range of solutions

Standard program overview fire doors

Outdoor + Switchgear, Walk-in Equipment Buildings Low & Medium Voltage NEMA 3R

SERIES 800 / 810 SPECIFICATION 15KV & 25KV PADMOUNTED LIQUID-INSULATED VACUUM LOAD INTERRUPTER ASSEMBLIES

SECTION SECONDARY UNIT SUBSTATIONS

REQUIREMENTS FOR INDOOR INSTALLATION OF PADMOUNTED TRANSFORMERS

50 N E T b o x Wall Mounting C A B I N E T s

WEATHER BREAKER MODEL 175 QUALITY DOOR SOLUTIONS SINCE 1947

IP-5(Dust-Solid Particles) 5(Liquid-Water Oil)

NETbox Wall Mounting CABINETs

Instruction guide Medium Voltage equipment on sites exposed to high humidity and/or heavy pollution. Recommendations for installation and use

PSF Wales QUALITY SERVICE FLEXIBILITY STEEL HOUSINGS, ENCLOSURES BUILDINGS & STRUCTURAL STEELWORK

SECTION ENCLOSED BUS ASSEMBLIES

Gas-insulated medium-voltage switchgear. for wind parks. Answers for energy.

NETbox Wall Mounting CABINETs

Sliding Door Systems

The Versatile & Practical Choice. Gartec Goods Lifts. Modular & Customised

IP-5(Dust-Solid Particles) 5(Liquid-Water Oil)

ENERGY-DISTRIBUTION. TwinLine N 44 The new system of floor-standing cabinets in IP44

Tender specification KLAUS Multiparking TrendVario 4300

19 DYNAmic Basic Cabinets / W:600mm

Delta Level 1000 Hinged Lip Pit Mounted & Suspended Frame Dock Leveller

Substation is equipped with different nominal voltage devices

Marine motors. 10/2 Orientation 10/2 Overview 10/3 Benefits 10/3 Application 10/3 Technical specifications 10/5 More information

Dynamic Bonding Systems B.V. A division of Dutch Bonding Group B.V.

Product brochure Multi Functional Switchgear PASS M kv Flexible and compact switchgear solutions for windfarms

37-SDMS-01 REV. 03 SPECIFICATIONS FOR

Series ESK / ESB. Cabinets in Modular Design. Manufacturing Program: ESK-20 ESK-40 ESK-80 ESB Sandwich construction 20 mm, 40 mm and 80 mm

HEAVY STEEL CONSTRUCTION

MILT-Pro. Built-in units and control centres for halls

Expand your horizons... High quality Aluminium Door & Window Systems Folding Doors Slide & Turn Doors Sliding Doors Windows

ISO 20FT MOBILE FIELD WORKSHOP SHELTER

Moduline. Acoustic Enclosure System. Rugged Noise Control Structures Using Acoustically Rated & Field Proven Demountable Components

Tender specification KLAUS Multiparking MultiBase 2072 outdoor installation EB MultiBase 2072 outdoor installation DB

B. Provide liquid-filled secondary substation transformers as indicated on drawings.

PROTEC. High temperature. low voltage electrical material

ECOTOP VF-HF. high efficiency glazed flat-plate solar collectors > MAXIMUM MODULARITY > SIMPLIFIED INSTALLATION

SECTION ENCLOSED BUS ASSEMBLIES

Tender specification KLAUS Multiparking MultiBase U1 EB / MultiBase U1 DB

OptiLine 70. Service Poles. Technical and Material data

LIGHT-WEIGHT ROOFING TILES QUALITY, VARIABILITY AND DESIGN MODERN ROOFING TECHNOLOGY WARRANTY AND SERVICE.

Air-Insulated Medium-Voltage Switchgear NXAIR Totally Integrated Power NXAIR siemens.com/nxair

Power evolution INNOVATION

42-SDMS-02 SPECIFICATIONS FOR FIBERGLASS REINFORCED LOW VOLTAGE SERVICE CABINET FOR 800A BULK CUSTOMERS

SECTION MOTOR CONTROL CENTER

Ecotop VHT Flat plate solar collector (for forced systems)

LOADING DOCK SYSTEMS HIGH SPEED DOORS LIFT TABLES DOCK SHELTERS SECTIONAL DOORS COMPL. FOOD INDUSTRY L O A D I N G D O C K S Y S T E M S

FALSE CEILING SYSTEM CLADDING SYSTEM FLEXIBITY PANEL ASSEMBLY CEILING ASSEMBLY QUALITY VERTICAL JOINT FLOOR SKIRTING TIME AND COST CONTROL 2 /8

equine For the complete range of Ranbuild products visit

QUADROPARKER SERIES QUADROPARKER N4904 THE IDEAL SOLUTION FOR THE EXTERIORS; ON 4 LEVELS CAR STACKERS

SECTION ELECTRIC FOUR FOLD DOORS MODEL 46 FLAT SHEETED

A. Provide a complete Distribution Panelboard system as indicated on the drawings, and as specified herein.

Totally Integrated Power NXAIR. Flexible in Application, Consistent in Safety. Air-Insulated Medium-Voltage Switchgear NXAIR.

Pre-Qualification Certificate

M I N I C O L D R O O M TECHNICAL SPECIFICATIONS

OS-ALD ACOUSTIC LOUVERS

Mail delivery solutions for the 21st century

The Safety Solution for Free Standing Roof Edge Protection

Steelwork and Security Kiosks

19 EURObox Cabinets / W:600mm

equine Australia wide toll free number For the complete range of Ranbuild products visit

Gas-insulated medium-voltage switchgear. for marine and offshore applications. Answers for energy.

The factory assembled air handler shall conform to the requirements outlined ASHRAE 90.1.

Transcription:

Power IT Compact Secondary Substations, CSS Technical catalogue for sheet steel substations

The New Standard for Individual Solutions The new CSS substations represent a unique concept, which is introducing new standards with its broader, modular product range, a new product configurator, type-tested solutions and shorter delivery times. All products are based on the latest technology and form part of ABB s Industrial IT Platform. The result is a safe energy supply and a reduction in operating costs for the grid. Substations comprise the distribution transformer, medium-voltage switchgear, low-voltage switchboard, connections and associated equipment in an enclosed unit. 2

Substations from ABB Definitions In accordance with the EN 61330 standard, Prefabricated Secondary Substations are defined as substations with type-tested equipment comprising distribution transformer, medium-voltage switchgear, low-voltage switchboard, connections and associated equipment in an enclosed unit. Substations are located in places to which the general public has access, and hence must provide a high level of personal safety. Solutions In substations for outdoor use all components are housed in a building, which protects the equipment against climate effects and unauthorised access. The building will typically be divided into three rooms for the mediumvoltage switchgear, low-voltage switchboard and distribution transformer. A substation may be operated from the inside (Walk-in) or from the outside (Non Walkin). The electrical equipment is cooled by natural ventilation through openings in the substation. Content Application.................... 4 Product overview............... 4 Type designations Modular structure.............. 5 Standard building sizes Additional options available..... 5 Design........................ 6 The building Foundation or base frame Oil collection pit Ventilation Protection against internal condensation Partitioned roof Doors Solutions available............. 8 Model CSS-SW Walk-in Model CSS-SN Non Walk-in and CSS-SC Compact Separate room for other purposes Exterior styling................ 9 Walls Roof Electrical equipment in the substation............... 10 Medium-voltage switchgear Low-voltage switchboard Distribution transformer Cables and cable accessories Type test...................... 11 Quality........................ 11 Personal safety Degree of protection Protection against climate effect Environment The text and illustrations are intended as guidelines. Reservation for changes. 3

Application Product overview Substations are used in a large number of different areas. CSS-SW Walk-in station. Operated from the inside and surfacemounted. Secondary Substation Distribution Operation Supply Customer supply Feeding Satellite Pylon feeder station Application Transformation and public distribution Operation at medium-voltage level Supply to satellite stations Supply to major electricity customers Connection of decentralised power plant to the public network Substations for the end of radial connections Smaller stations connected to overhead lines CSS-SN Non Walk-in station. Operated from the outside and surface-mounted. Type designations Product type CSS = Compact Secondary Substation Materials S = Steel C = Concrete Layout W = Walk-in N = Non Walk-in C = Compact CSS-SC Compact station. Operated from the outside and installed partly below ground level. Width 5 = Number of modules wide Length 5 = Number of modules long CSS-SC.5.5 The CSS range comprises three main models, which we supply with a number of different layouts, designs and materials. 4

Modular structure Additional options available The buildings in the CSS range consist of 300-mm wide modules (M) plus corner sections measuring 115 x 115 mm. We supply the walls in four different heights and the roof with two angles of pitch, 6 and 18. The doors are 2, 3 or 4 M wide, and can be fitted as either single or double doors. The ventilation doors are 2 or 3 M wide. Standard building sizes Other sizes may be supplied on request. The standard buildings can be fitted with a broad range of additional options, so that the individual substation can meet individual, functional and aesthetic requirements. These options include various modifications and accessories, which make the operation, installation and use of the substation easier. There are also several options to vary the substation s appearance. Option Type CSS-SW CSS-SN CSS-SC R H W W = Widths, mm 4 M 5 M 6 M 7 M External width, 1430 1730 2030 2330 steel External width, 1490 1790 2090 2390 wooden cladding L = Lengths, mm 5 M 6 M 7 M 8 M External length, 1730 2030 2330 2630 steel External length, 1790 2090 2390 2690 wooden cladding L = Lengths, mm 9 M 10 M 11 M 12 M External length, 2930 3230 3530 3830 steel External length, 2990 3290 3590 3890 wooden cladding H = Wall heights, mm 1266 1664 1914 2114 R = Roof heights, mm L Width of building 4 M 5 M 6 M 7 M 6 roof pitch 203 219 235 251 18 roof pitch 365 414 463 512 Functionality Snow panel below doors Condensation cover over low-voltage room Separate room e.g. for communication Internal emergency handle Separate oil collection pit Concrete slab as base Lift incl. transformer (depending on the solutions available) IP54 in doors Temperature class K 10 Earthing system to 20 ka Partitioned roof (longer than 3 m) Cylinder lock in doors Aluminium foundation plates Styling Wooden panels on wall Alternative colours and surface structure Increased roof pitch 18 degrees Alternative roof cladding 5

Design Foundation or base frame We supply a model CSS-SC for installation partly below ground level, with a foundation at three different heights: 528, 778 or 978 mm, depending on the size of the transformer. Stations designed for installation at ground level have a 130 mm high base frame. Foundation with an integrated oil collection pit. The building The building will typically be divided into three rooms for the medium-voltage switchgear, low-voltage switchboard and distribution transformer. All standard modules of walls, doors and ceilings are produced using roller formed sections. The roof has a choice of pitches, 6 or 18, and is secured to the corner sections by bolts. The whole roof is detachable, and is supported by a beam with ventilation openings. The doors are fitted as standard with handles for padlocks. The doors are closed by means of a two-point device, which secures the door to the top frame and the base frame. The doors are fitted as standard with stainless steel hinges and are equipped with door stoppers. The wall and roof modules are assembled by means of a self-locking design. Clinching technology is used to assemble walls, roof, doors and foundation. Lifting fittings, corner sections, bearing sections, base plates and cable covers are assembled using bolts. The low-voltage switchboard and the mediumvoltage switchgear are bolted to the building. Walls, roof and doors are made from 1.5 mm AlZn-coated sheet steel with ALC protection. As well as providing protection, ALC also forms an ideal base for the painting process. Once all AlZn parts have been degreased, the whole building is painted with a coat of two-component polyurethane wet paint. Corrosion tests show that the surface treatment of painted materials corresponds to corrosion category C4 H according to ISO 12944. Corrosion protection in the form of hot galvanised foundations and base frames guarantees a long mechanical service life. Height measurements, mm Wall height Door Internal free height D A opening Type height C CSS-SW CSS-SN CSS-SC 1266 1140 1790 2040 2240 1664 1538 1790 2188 2438 1914 1788 2040 2040 2438 2114 1988 2240 2240 Base height Type B CSS-SW 130 CSS-SN 130 528 CSS-SC 778 978 A C B D The foundation and base frame are produced using 2 mm hot-rolled steel, and are hot dipped galvanised prior to assembly. An aluminium foundation is also available for Compact stations. All foundations and base frames have detachable panels in front of the medium-voltage and low-voltage rooms to allow the easy insertion of cables. A CSS for installation at ground level can be supplied with a concrete slab, which reduces installation work on site. The foundation slab matches the size of the substation, and has recesses for cables to the medium-voltage and low-voltage rooms. 6

Oil collection pit CSS solutions that are installed partly below ground are fitted as standard with an integrated oil collection pit made from 1.5 mm galvanised steel. We can supply a separate oil collection pit for stations installed at ground level. The distribution transformer is fitted in the oil collection pit, which has a volume of at least 20% of the transformer s oil volume. The oil collection pit provides protection against oil pollution in case of a leak in the transformer. Protection against internal condensation To avoid any condensation dripping on to the low-voltage switchboard, an additional cover can be installed over the low-voltage room. Partitioned roof The standard roof of up to 3.8 m in length can be detached in one piece. A partitioned roof can be supplied for stations over 3 m. Doors The standard doors are designed for padlocks. The doors can also be fitted with a cylinder lock. The oil collection pit protects the environment. Snow panel below door Snow panels make it easier to open the doors after heavy snowfall. The snow panel replaces the lower third of the door, and is secured to the wall. The snow panel can be removed once the door is open. Ventilation Natural ventilation is provided by means of ventilation openings for air intake in the lower part of the doors. The air is extracted at the top of the roof. Natural air circulation ensures sufficient cooling of the distribution transformer. The ventilation openings to the transformer room are of the labyrinth type. As standard CSS is classified and type-tested in accordance with temperature class K20. Temperature class K10 can be achieved for all groundlevel substations by means of extra ventilation. Extra ventilation is achieved by increasing the ventilation area for the transformer room. Internal emergency handle Substations operated from the inside can be supplied with an internal emergency handle, so that the door can be opened even if it has been locked from the outside. The ventilation openings in the doors are of the labyrinth type. IP54 degree of protection To provide protection against dust being drawn into the medium-voltage and low-voltage rooms, the doors can be fitted with gaskets that increase the degree of protection to IP54. 7

Solutions available The modular structure makes it possible to select a design for a substation that guarantees both ideal content and the best access facilities. The solutions shown here are examples of the many options that we can supply. Model CSS-SW Walk-in Distribution transformers can be supplied in the technology suited for the task. Type CSS-SN Non Walk-in and CSS-SC Compact Medium-voltage switchgears can be supplied pre-configured or fully configurable. Separate room for other purposes In addition to the three normal rooms, the substation can also include a separate room for other purposes, such as street-lighting equipment, telecommunications or cable TV. The room is totally separated from the other rooms by means of walls, and access is through a separate door with its own lock. Low-voltage switchboards are supplied in accordance with local norms and regulations, and are adapted to the customer s requirements. 8 CSS can be fitted with a separate room for other purposes.

Exterior styling Walls Standard wall colours CSS can be painted in the following standard colours: RAL 7015 RAL 7013 RAL 1019 Roof Standard roof colour The standard roof colour is the same as the wall colour. Alternative exterior styling The roof is available with a textured finish in the same colours as the walls. We can also supply the roof with a black textured finish. Alternative roof cladding The roof can be clad using "tiles" made of sheet steel or using shingles made of roofing felt. The roof can also be fitted with wooden panels. The alternative roof cladding requires a roof pitch of 18. Tile Shingles Alternative exterior styling In addition to the standard finish, the substation can be painted with a special textured paint containing fine sand. This provides extra texture to the painted surface. Black Black slate Falun red Moss green Alternative wall cladding CSS can be clad using wooden panels that consist of impregnated boards mounted in metal rails, which are secured to the walls. The rails are fitted with locking pins, which prevent the boards from vibrating. The wooden panels cover all walls and doors. The wooden panels can be painted in various colours. Embossed green Red The painted, profiled surface provides an attractive finish. Dark brown White 9

Electrical equipment in the substation Medium-voltage switchgear The CSS range has been designed and type-tested with ABB s medium-voltage switchgears. We can install the following models: " SafeRing 12-24 kv " SafeRing 12-24 kv " SafeLink 12 kv " UniSwitch 24 kv " NAL unit 12-24 kv " Fuse-switch disconnectors The range of medium-voltage switchgears includes both pre-configured and fully configurable solutions. A high level of personal safety should be guaranteed by the use of type-tested equipment. ABB offers gas-insulated and air-insulated mediumvoltage solutions. The options for gas-insulated solutions comprise the SafeRing, SafePlus and SafeLink models. The options for air-insulated solutions comprise the UniSwitch model (which uses SF 6 gas as a breaking medium), units with purely air-insulated devices with and without fuses, and a fuse-switch disconnector. Low-voltage switchboard CSS is designed to house various low voltage solutions in accordance with national norms and regulations, as well as individual requirements. The product range includes various types of fuse-switch disconnectors, including DIN solutions and moulted case circuit breakers. Equipment for street-lighting, measuring and metering can be supplied as required by the customer. Distribution transformer The CSS stations are designed to house distribution transformers with various technologies up to 1600 kva/24 kv: " Oil-insulated model, hermetically sealed " Oil-insulated with oil conservator " Dry-insulated, vacuumcast windings " Dry-insulated RESIBLOC In many cases we can supply CSS with a readily installed transformer. The possibility of lifting the substation with transformer depends on the type of station, the solution in question and the transformer size. Cables and cable accessories CSS is supplied with cables and cable terminations: " Medium-voltage cables from medium-voltage switchgears to distribution transformers " Low-voltage cables from low-voltage switchboards to distribution transformers. SF 6 gas-insulated medium-voltage switchgears are connected using elbow connections. The cable termination to the transformer is provided by means of regular cable adapters or, if required, elbow connections. The low-voltage cable between the distribution transformer and the lowvoltage switchboard is fitted with the necessary cable lugs. For further information about electrical equipment, order the relevant brochures or visit us at www.abb.com. 10

Type test Quality The CSS range is designed and type-tested in accordance with EN 61330, which covers the following test programs: " Control of insulation level " Control of temperature rise in the main components in the substation " Control of earthing system " Control of internal protection class " Control of the building s resistance to mechanical effects " Function tests on mechanical parts Additional type tests in accordance with EN 61330 " Rated short-time current test " Noise test " EMC test The main components are type-tested in accordance with their individual standards Medium-voltage switchgear " EN 60265: High-voltage switches " EN 60298: Metal-enclosed high-voltage switchgear " EN 60694: High-voltage switchgear Low-voltage switchboard " EN 60439: Low-voltage switchgear and control gear Distribution transformer " EN 60076: Power transformers The CSS range is produced in accordance with ABB s stringent quality and environmental procedures. ISO 9001 and ISO 14001 certification guarantees quality and environmental considerations. Personal safety All live parts in the CSS range are protected against unintentional contact by means of lockable doors. The ventilation openings to the transformer room are of the labyrinth type. Cable connections and fuses in the medium-voltage room are also protected against unintentional contact. Anti-contact protection is tested in accordance with EN 61330. Clinched or screwed connections form electrical connections with all of the station s metal parts. The galvanised steel foundation is bolted to the building. The result is a fully earthed enclosure, providing a high level of personal safety. Degree of protection The standard degree of protection for CSS is IP23D in accordance with EN 60529. If required, CSS can be delivered with doors that comply with IP54, by including gaskets and omitting the ventilation openings in the doors. Protection against climate effect The climate in substations can be extreme, due to moisture, condensation and dirt. In coastal locations sea salt on the surface of open, insulated surfaces can cause leaking current, which can result in flashover. It is strongly recommended that equipment used can withstand harsh climate service conditions. Environment ABB works to develop and supply products and solutions that do not have any unnecessary impact on the environment, are safe to use and can be recycled, reused or disposed of safely. In our research and development we aim to produce sustainable technologies, systems and products. 11

ABB Limited operates a process of continuous product development. We therefore reserve the right to change designs, dimensions and data without prior notice.