HUMAN-BEHAVIOR ORIENTED CONTROL STRATEGIES FOR NATURAL VENTILATION IN OFFICE BUILDINGS

Similar documents
Energy and indoor temperature consequences of adaptive thermal comfort standards

Available online at ScienceDirect. Energy Procedia 78 (2015 )

HVAC INTEGRATED CONTROL FOR ENERGY SAVING AND COMFORT ENHANCEMENT vahid Vakiloroaya

Thermal comfort evaluation of natural ventilation mode: case study of a high-rise residential building

681: Environmentally Responsive Architecture; Passive Design for School in Southern India

Air Movement Preference and Thermal Comfort A survey in classrooms during summer season in Brazil

ScienceDirect. Simulation based mixed mode building design

Thermal Comfort Evaluation of HDB flats

Passive Houses in South West Europe

Thermal comfort under transient seasonal conditions of a bioclimatic building in Greece

Using passive solutions to improve thermal summer comfort in timber framed houses in South-west France

Assessing thermal comfort of dwellings in summer using EnergyPlus

Optimal design for a dual-airflow window for different climate regions in China

UNDERFLOOR AIR DISTRIBUTION INTEGRATED WITH AN INDIRECT AND DIRECT EVAPORATIVE COOLING ASSISTED 100% OUTDOOR AIR SYSTEM

CAE 331/513 Building Science Fall 2017

Demonstration of Load Shifting and Peak Load Reduction with Control of Building Thermal Mass

Work Package 2: Performance of naturally ventilated buildings

ENERGY EFFICIENT TECHNIQUES AND SIMULATION OF ENERGY CONSUMPTION FOR THE SHANGHAI ECOLOGICAL BUILDING

Numerical Investigation on Ventilation Strategy for Laboratories: A Novel Approach to Control Thermal Comfort Using Cooling Panels

Energy simulation of traditional vs. adaptive thermal comfort for two

SMART CONTROL FOR NATURAL VENTILATION HOUSE

Optimizing Indoor Environments for Occupant Satisfaction. Presented by: Kelli Goldstone April 2016

Thermal environment and thermal comfort in a passive residential building in the severe cold area of China

Chapter 6. Space heating load

Modelling Analysis of Thermal Performance of Internal Shading Devices for a Commercial Atrium Building in Tropical Climates

Steven J. Emmerich and W. Stuart Dols National Institute of Standards and Technology Gaithersburg, MD, USA

THERMAL MASS IMPACT ON ENERGY PERFORMANCE OF A LOW, MEDIUM, AND HEAVY MASS BUILDING IN BELGRADE

Chapter 7. Passive Solar Contents

THERMAL MASS IMPACT ON ENERGY PERFORMANCE OF A LOW, MEDIUM AND HEAVY MASS BUILDING IN BELGRADE

BUILDING INTEGRATED VENTILATION SYSTEMS MODELLING AND DESIGN CHALLENGES

BUILDING DESIGN FOR HOT AND HUMID CLIMATES IMPLICATIONS ON THERMAL COMFORT AND ENERGY EFFICIENCY. Dr Mirek Piechowski 1, Adrian Rowe 1

Evaluation of natural ventilation systems in a landscaped office.

Energy simulation of traditional vs. adaptive thermal comfort for two moderate climate regions Hensen, J.L.M.; Hensen Centnerová, L.

Ventilation Approaches for Shopping Malls An Examination of Natural and Hybrid Strategies

REAL-TIME CONTROL OF OCCUPANTS THERMAL COMFORT IN BUILDINGS. Galway, Ireland

CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION

SIMULATION OF THE PERFORMANCE OF A HYBRID VENTILATION SYSTEM IN DIFFERENT CLIMATES. Technicka 2896/2, Brno, Czech Republic

Numerical Study on the Effect of Insulation Materials on the Single Zone building Performance

Utilizing Heat Dump Capacity of a Small Pond Attached to Infloor Slab of a Net-Zero Energy House

Slab cooling system design using computer simulation

Performance of Natural Ventilation in Deep-plan Educational Buildings: Case Study

Maarten G. Sourbron 1, Lieve M. Helsen 1. Corresponding SUMMARY

Thermal comfort assessment of Danish occupants exposed to warm environments and preferred local air movement

Energy Analysis of Using Thermal Mass in a Hot Humid climate

Transient Performance Analysis of a Model Building Integrated with a Trombe-Wall

COMPARATIVE SUMMER THERMAL AND COOLING LOAD PERFORMANCE OF NATURAL VENTILATION OF CAVITY ROOF UNDER THREE DIFFERENT CLIMATE ZONES

A Field Study of Thermal Comfort in Open-plan Office Buildings during Transition Seasons in Harbin. Yunsong Han 1, 2, Huixuan Sun 1, 2, Cheng Sun 1, 2

Higher Education Energy Efficiency Partnership Program BEST PRACTICES AWARDS

Evaluating Energy Savings Retrofits for Residential Buildings in China

PRINCIPLES AND POTENTIALS OF VENTILATIVE COOLING

Optimization of air tightness and night ventilation for Passive houses in Italian climates under Fanger and Adaptive comfort models

Allowing for Thermal Comfort in Free-running Buildings in the New European Standard EN15251

REDEFINING APPROPRIATE THERMAL COMFORT STANDARD FOR NATURALLY VENTILATED BUILDINGS IN TROPICS (SINGAPORE AND INDONESIA PERSPECTIVE)

Mechanical ventilation & cooling energy versus thermal comfort: A study of mixed mode office building performance in Abu Dhabi

carbon-neutral architectural design Pablo La Roche CRC Press Taylor & Francis Croup Boca Raton London NewYork CRC Press is an imprint of the

The Elithis Tower is an experimental and demonstration. Elithis Tower in Dijon, France. nzeb case studies

Work Package 2: Performance of naturally ventilated buildings

SUMMER THERMAL COMFORT IN TYPICAL FRENCH RESIDENTIAL BUILDINGS: IMPACT ASSESSMENT OF BUILDING ENVELOPE INSULATION ENHANCEMENT

Effect of Building Orientation and Window Glazing on the Energy Consumption of HVAC System of an Office Building for Different Climate Zones

Tage Møller Architect office building

Available online at ScienceDirect. Procedia Engineering 145 (2016 ) 18 25

Available online at ScienceDirect. Procedia Engineering 169 (2016 )

Thermal Performance of Solar Heating System with Water Floor

Energy impact of ASHRAE s museum climate classes: a simulation study on four museums with different quality of envelopes

Thermal Comfort Measurements in a Hybrid Ventilated Office Room

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

Opportunities and Limitations of Building Precooling

Perception of Thermal Comfort for Naturally Ventilated High School Classrooms in San Rafael, CA

Cost-Benefit Analysis of Dwelling Retrofit Options

NATURAL VENTILATION STRATEGIES FOR COMMERCIAL BUILDINGS

ANALYSIS OF ENVELOPE THERMAL BEHAVIOUR THROUGH PARAMETRIC STUDIES. Civil Engineer, PhD, Assistant Professor, Civil Engineering Department (3)

Artificial Neural Network Models Using Thermal Sensations and Occupants Behavior for Predicting Thermal Comfort

OPERATION AND CONTROL OF THERMALLY ACTIVATED SLAB HEATING AND COOLING SYSTEMS

Analysis of Night Ventilation Potential for Residential Buildings in Hot-Humid Climate of Malaysia

OPENING DESIGN TO IMPROVE THE NATURAL VENTILATION PERFORMANCE OF HIGH-RISE RESIDENTIAL BUILDINGS

Cold Plane Innovative Method for Humidity Condition Control

Comsol Multiphysics for building energy simulation (BES) using BESTEST criteria Jacobs, P.M.; van Schijndel, A.W.M.

Retrofitting Adaptive Comfort Strategies into Conventionally Air Conditioned Commercial Buildings

COMPARISON OF ENERGY USE INDICATORS OF A NON-RESIDENTIAL PASSIVE HOUSE WITH ASHRAE 90.1 BUDGET BUILDING

A Comparison of Methods for Evaluating Ventilation Cooling Potential Building Program Based Climate Analysis for Early Design Decisions

Practitioner Modeling Competition

An Assessment of Thermal Comfort in Hot and Dry Season (A Case Study of 4 Theaters at Bayero University Kano)

Infiltration simulation in a detached house empirical model validation

Thermal comfort conditions in outdoor spaces

The optimization of the mechanical night cooling system in the office building

Design and retrofitting of a hybrid building in Athens

S. LONGO. The paper shows analysis of the impact on thermal comfort of natural ventilation in a nonresidential Mediterranean case-study.

Potential of passive design strategies using the free-running temperature

A Comparative Study of the Thermal Comfort of Different Building Materials in Sana a

Findings of Field Survey for Thermal Comfort and Ventilation in US Office Buildings

Potential of natural ventilation in shopping centres

Parkview Green, Beijing Microclimatic envelope

MODELLING BUOYANCY INDUCED FLOWS OF PASSIVE COOLING SYSTEMS Pedro Correia da Silva 1, Vítor Leal 1 and J. Correia da Silva 2

Practitioner Modeling Competition

Potential of Natural Ventilation in Shopping Centres Diederichsen, Alice; Friis, Kristina; Brohus, Henrik; Tranholm, Gitte T.

Experimental investigation of zero energy office under natural and forced ventilation

buildings ISSN

Assessing the energy performance of modern glass facade systems

Evaluation methods for indoor environmental quality assessment according to EN15251

Transcription:

HUMAN-BEHAVIOR ORIENTED CONTROL STRATEGIES FOR NATURAL VENTILATION IN OFFICE BUILDINGS Haojie Wang 1, Qingyan Chen 1,2* 1 School of Mechanical Engineering, Purdue University, West Lafayette, IN 47907 2 School of Environmental Science and Engineering, Tianjin University, Tianjin 300072, China *Phone: (765) 496-7562, FAX: (765) 496-0539, Email: yanchen@purdue.edu ABSTRACT Natural ventilation is a cost-effective way to reduce cooling energy for buildings. However, the performance of natural ventilation largely depends on outdoor climate. A good and feasible control strategy is the key to ensure high performance of natural ventilation. Typically, windows are operated by occupants. Therefore, a control strategy that based on human behavior can enhance the performance of natural ventilation. This paper studied four different control strategies that simulate human behavior based on temperature and humidity in a climate with high outdoor humidity. The results showed that human behavior based control strategy can largely reduce the high humidity hours during occupied hours while only slightly increases air temperature. INTRODUCTION Building energy consumes 2/3 of the electricity in the United States and the significant of the electricity consumption is for summer cooling. Natural ventilation has a large potential to reduce cooling energy for many regions in the United States. However, the performance of natural ventilation is largely depended on outdoor climate. Active control on natural ventilation is needed to ensure best cooling performance in summer. Previous studies on control strategies for optimizing natural ventilation performance involved complicated control based on various parameters or even future temperature (Spindler and Norford, 2009; Menassa et al., 2013; Van Paassen et al., 1998). The control strategies are only suitable for automation system and will increase the initial cost. Furthermore, simulation based on such control strategy will often results in large discrepancy with onsite scenario (Roetzela et al. 2010), which is believed to be the discrepancy of control strategies in actual case and in simulations. Since most existing buildings do not have automated windows, only the occupants can operate the windows. This type of buildings posed two restrictions on the control: 1) window cannot be operated when the space is unoccupied, such as during night-time; 2) the window operation should be based on the sensation of human. Recently, some researchers have purposed models that are based on human behaviors for natural ventilation control (un et al., 2008a; un et al., 2008b). Those models were derived from field studies that considered indoor temperature, time of the day and the previous state of the window (e.g. window was already opened or closed). The results showed a large scattering from different field observations because each person s sensation to the environment and the criteria to open the window were different. Moreover, other parameters such as indoor air quality (IAQ) and humidity are also important for the occupants to decide whether to open a window or not. This study investigated four control strategies that are oriented by humidity, ventilation hours and temperature. The strategies represent different typical human behaviors and are suitable for different climates and building types. We conducted numerical simulations of natural ventilation performance with the control strategies for a small office building in Philadelphia by using typical meteorological year (TM3) weather data. Thermal comfort was calculated with the adaptive model from ASHRAE Standard 55-2010, relative humidity and ventilation hours. SIMULATION This paper used the single-sided wind-driven model from Wang and Chen (2012) and modified it to include the buoyancy effect for calculating the ventilation rate. The pressure difference between indoor and outdoor at height z along the opening is calculated based on the wind pressure difference across the opening and the stack pressure due to different indoor and outdoor temperature, as shown in Eq. (1) 2 1 U 2/7 2/7 Ti To Pz ( ) Cp 2/7 z z0 igz ( z0) (1) 2 z T ref The neutral level is an additional unknown which can be calculated based on the mass balance between incoming and outgoing ventilation rate through the opening as: Q Q Q (2) in out o - 1731 -

h2 z0 2 Pz ( ) 2 Pz ( ) d d z0 out h1 out (3) QC l dz C l dz The above equation system can yield mean ventilation rate. Due to the pulsating flow and eddy penetration in single-sided ventilation, fluctuating ventilation rate is very important. The contribution from pulsating flow is calculated as 2 h 2 1 2/7 2/7 2 q Cl p d C 1/7 p z z0 dz u z ref z0 (4) where u is assumed to be 10% of the mean wind velocity. The eddy penetration can only occur when the eddy scale is smaller than the opening scale. By applying the spectrum analysis on the wind velocity, the energy of the penetrated eddy can be calculated as 2 2 2 q e U/ l C A S( n) dn (5) where C Cd Cp /2. The total root mean square (RMS) of the ventilation rate is (6) 2 2 q qe qp Note that the influence of temperature fluctuation is much smaller than the wind velocity fluctuation, thus the temperature fluctuation effect was not considered in this model. The model used Matlab TM to generate the real ventilation rate based on the mean and RMS of the ventilation rate that is calculated as above equations. for the whole simulation period was 1377 hours. The simulations used the first order implicit method to solve energy equations for the indoor air and the building envelop with a time step of six minutes. Figure 2 Building geometry Figure 3 shows the three different control strategies. The first one (hereinafter Control_1 ) as shown in Figure 3(a) controls both temperature and humidity. The first step is to decide whether indoor temperature is comfortable or not based on the adaptive model with 80% satisfaction rate. If the room temperature is not comfortable, natural ventilation will be used if outdoor temperature satisfies the condition. If the room temperature is comfortable, indoor humidity becomes a determining factor for ventilation. If indoor is humid and outdoor absolute humidity is lower than indoor one, natural ventilation will be used even though outdoor temperature is higher than indoor. Note that even though such occasion will increase the indoor air temperature, the prior condition to the humidity determination requires the indoor temperature to be comfortable. Therefore, the temperature increase will not cause the indoor temperature higher than the upper limit of the comfort zone for this time step. Figure 1 Pressure difference at the opening The model was applied to simulate a one-zone small office building. The detail information of this simulation is listed in Table 1. The baseline building construction was based on ASHRAE Standard 90.1-2007 and there was no concrete in the exterior wall. Building2 was with 100 mm thickness of concrete in the exterior wall as thermal storage to improve night cooling performance. The hygroscopic process is neglected in the simulation since no active hygroscopic was used in the building construction. The total number of occupied hours (working hours) is warmer is cooler Too cold Too warm N (a) Is indoor comfortable? Is indoor too humid? humidity is low - 1732 -

is warmer Too cold Is indoor comfortable? Too warm is cooler Control_3 can represent the case when the occupants want more fresh air for better IAQ. Figure 3(d) shows the control strategy (hereinafter Control_4) that tries to use natural ventilation whenever outdoor temperature is within thermal comfort zone, regardless of the humidity. Note that all the control strategies are only used for the daytime when the office is occupied. The windows will remain open from 18:00 of the day to 07:00 of the next day to utilize night cooling. (b) Is outdoor comfortable? Indoor too humid? humidity is low Is outdoor comfortable? Vent (c) Vent (d) Figure 3 (a) Control both temperature and humidity (Control_1); (b) Control only temperature (Control_2); (c) Maximize ventilation hours with control on humidity (Control_3); (d) Maximize ventilation hours (Control_4) The second control strategy (hereinafter Control_2 ) as shown in Figure 3(b) is only based on indoor and outdoor temperature. The third control strategy (hereinafter Control_3 ) as shown in Figure 3(c) tries to maximize the ventilation time while still maintain relatively good thermal comfort and low humidity level. The major difference between Control_3 and Control_1 is that Control_3 will use natural ventilation whenever the outdoor air temperature is within the comfortable range, even though outdoor air might be warmer than indoor. This will enable more ventilation time in exchange for sometimes an increase of indoor temperature. N N N No vent No Vent RESULTS AND DISCUSSION This study used adaptive thermal comfort model to evaluate natural ventilation performance. This model requires no mechanical system used during the whole period and people can freely control the window openings (Brager and Dear, 2001). Only based on these two prerequisites can we assume people will accept larger temperature swing than the PMV model. To satisfy those two requirements, this study did not use any mechanical system, which will results in some discomfortable hours and used control strategies that simulate human behaviors. Table 2 summarizes the results for the four control strategies for the baseline building and building with more thermal mass. The 80% and 90% represents the number of occupied hours with 80% and 90% satisfaction rate, respectively. The RH>80% represents the number of occupied hours when the indoor relative humidity is higher than 80%. VentTime represents the number of occupied hours when natural ventilation was used. The results showed that passive cooling alone could satisfy cooling need for more than 80% of the time in Philadelphia based on temperature. However, the results show that a lot of time the indoor air was too humid without humidity control such as Control_2 and Control_4. Figure 4(a) shows the percentage of number of occupied time when the indoor temperature meets the 80% satisfaction rate. Control_2 showed the best performance in terms of temperature control because it will utilize the most cooling potential from outdoor air. Control_1 has the least 80% satisfaction hours because when the indoor humidity is high, Control_1 will use the outdoor air to decrease the indoor relative humidity when outdoor absolute humidity is lower, even if the outdoor air is warmer. However, the indoor air cannot be heated up by outdoor air without bound. As shown in Figure 3(a), the first condition prior to humidity control is to ensure indoor temperature is within the comfort zone, and then the humidity control will determine whether to use outdoor air to reduce indoor relative humidity. Therefore, the decrease of the 80% satisfaction hours is less than the decrease of the high humidity hours for Control_1 compared with Control_2, as shown in Figure 4(b). Control_3 and Control_4 are the - 1733 -

strategies that would maximize the ventilation time. Control_3 also controls the humidity while Control_4 only considers temperature. Their ventilation time is much longer than that with Control_1 and Control_2 as shown in Table 2. Their humidity level is between Control_1 and Control_2. Figure 5 compares the performance of all control strategies for the baseline building. This study suggests that in addition to indoor temperature, humidity should also be a criterion for thermal comfort analysis in Philadelphia region. Based on both temperature and humidity, Figure 5 shows that Control_1 can provide the best overall thermal comfort for Philadelphia region. As shown in Table 2 and Figure 4, adding more thermal mass will improve the sensible cooling process yet will result in higher relative humidity since passive cooling cannot remove latent heat. Table 1 shows that the increase of high humidity hours is similar to the increase of 80% satisfaction hours between baseline building and buliding2. Generally, the natural ventilation time, indoor humidity and indoor temperature affect each other. Each control strategy has its own advantages and disadvantages and can represent different building owner s behavior. For instance, a person who cares more about IAQ and wants more outdoor air will use Control_3; a person who prefers relatively dry and cool indoor environment might use Control_1. CONCLUSION This paper investigated four human-behavior oriented control strategies for natural ventilation. The study used a small office building in Philadelphia region to evaluate the ventilation performance by simulating the thermal comfort in the building: 1) The control strategy that controls both the temperature and humidity provides the best overall thermal comfort for Philadelphia region; 2) The control strategies that maximizes the ventilation hours provide more ventilation time thus better IAQ among the four control strategies and have moderate performance in terms of thermal comfort; 3) Adding thermal mass into the building envelope will increase comfortable hours in terms of temperature but will also increase high humidity hours. More on-site experiments will be performed in the near future to validate the control strategies and simulation results. NOMENCLATURE A = opening area C d = discharge coefficient C p = pressure coefficient g = gravitational acceleration h 1 h 2 l n Q in Q out S T i T o U z 0 z ref ΔP q = elevation of the lower edge of the window = elevation of the upper edge of the window = width of the window = frequency = incoming ventilation rate = outgoing ventilation rate = velocity temporal spectrum = indoor air temperature = outdoor air temperature = window velocity at 10 m above ground = neutral level elevation = 10 m (reference level) = pressure difference = total RMS of ventilation rate q e =RMS of ventilation due to eddy penetration q p =RMS of ventilation due to pulsating flow i = indoor air density = outdoor air density out REFERENCES ASHRAE Inc., 2007. ASHRAE Standard 90.1. ASHRAE Inc., 2010. ASHRAE Standard 55. Brager, G. S., De Dear, R., 2001. Climate, Comfort, & Natural Ventilation: A New Adaptive Comfort Standard for ASHRAE Standard 55, Moving Thermal Comfort Standards into the 21st Century, Windsor, UK. Hensen J. 2003. Paper Preparation Guide and Submission Instruction for Building Simulation 2003 Conference, Eindhoven, The Netherlands. Menassa, C. C., Taylor, N., Nelson, J., 2013. A Framework for Automated Control and Commissioning of Hybrid Ventilation Systems in Complex Buildings, Automation in Construction, 30, 94-103. Mitchell, J.W., Beckman, W.A. 1995. Instructions for IBPSA Manuscripts, SEL, University of Wisconsin, Madison USA. Roetzela, A., Tsangrassoulisb A., Dietricha, U., Busching, S., 2010. A review of Occupant Control on Natural Ventilation, Renewable and Sustainable Energy Reviews 14(3), 1001-1013. Spindler, H.C., Norford, L.K. 2009. Naturally Ventilated and Mixed-mode Buildings. Part II: Optimal Control, Building and Environment 44(4), 750-761. Van Paassen, A.H.C., Liem, S.H., Groeninger, B.P., 1998. Control of Night Cooling with Natural Ventilation: Sensitivity Analysis of Control Strategies and Vent Openings, AIVC 19th - 1734 -

Conference, proceedings of "Ventilation Technologies in Urban Areas", Oslo, Norway. Wang, H. and Chen, Q. "A new empirical model for predicting single-sided, wind-driven natural ventilation in buildings," Energy and Buildings, 54, 386-394. un, G.., Steemers, K., Baker, N., 2008a. Natural Ventilation in Practice: Linking Façade Design, Thermal Performance, Occupant Perception and Control, Building Research & Information, 36 (6) 608 624. un, G.., Steemers, K., Baker, N., 2008b. Time- Dependent Occupant Behaviour Models of Window Control in Summer, Building and Environment, 43, 1471 1482. - 1735 -

Table 1 Detailed information of simulation (Construction material based on ASHRAE Standard 90.1 (2007)) RunPeriod WeatherData BuildingGeometry ExteriorWall (Fromoutsidetoinside) InteriorWall Roof (Fromoutsidetoinside) Floor Glazing InternalGain Baseline building 25mm Stucco/ R- 0.74 Insulation/ 12.7mm Gypsum May 1 st Sept 30 th TM3 Philadelphia Airport 3.89m 14.26m 3.05m 19mm gypsum board/ R- 0.15 Airspace resistance/ 19mm gypsum board 0.9mm Roof membrane/ R- 4.3 Insulation/ Metal decking Additional thermal mass 25mm Stucco/ R- 0.74 Insulation/ 100mm Concrete/ 12.7mm Gypsum 100mm MAT- CC05 Concrete 4 windows: Each with area of 0.8 m x0.7 m U=3.2; Solar Heat Gain Coefficient = 0.49 Working hours: 8:00-17:00 4 people: Sensible heat 75 W, latent heat 55 W per person Electricity Equipment: 10.7 W/m 2 Lighting: 10 W/m 2 Table 2 Summary of Thermal Comfort for Different Control Schemes UNIT:Hour TotalHours 80% 90% RH>80% VentTime BaselineBUILDING Control_1 1076 783.4 288.1 517.7 Control_2 1189.5 908.5 699.1 360.5 1377 Control_3 1183.7 893.5 492.9 680.6 Control_4 1125.8 890.1 539.9 776 Withmorethermalmass Control_1 1134 865.1 247 1042.4 Control_2 1232.3 1011.1 673.2 1531.3 1377 Control_3 1232.2 1008.5 484.8 1319.7 Control_4 1171.2 995.5 536.7 1389.8-1736 -

100% Baseline With more thermal mass Percentage of time with 80% satisfaction rate 80% 60% 40% 20% 0% Control_1 Control_2 Control_3 Control_4 (a) Percentage of time when RH>80% 60% 40% 20% Baseline With more thermal mass 0% Control_1 Control_2 Control_3 Control_4 (b) Figure 4 Percentage of total working time for different control strategies (a) with 80% satisfaction rate (b) when relative humidity is above 80% - 1737 -

Percentage of total occupied time 100% 80% 60% 40% 20% 0% Control_1 Control_2 Control_3 Control_4 80% 90% RH>0.8 VentTime Figure 5 Performance of different control strategies - 1738 -