IMPACT OF NIGHTTIME SJXJT DOWN ON THE PREDICTION ACCURACY OF MONTHLY REGRESSION MODELS FOR ENERGY CONSUMPTION IN COMMERCIAL BUILDINGS

Similar documents
AHU Models Using Whole Building Cooling and Heating Energy Consumption Data

Estimating Industrial Building Energy Savings using Inverse Simulation

ANALYSIS OF THE POTENTIAL ENERGY SAVINGS FOR 14 OFFICE BUILDINGS WITH VAV SYSTEMS

Potential Operation and Maintenance (O&M) Savings in the Clinical Science Building at UTMB

Methodologies for Determining Persistence of Commissioning Benefits

CASE STUDIES IN USING WHOLE BUILDING INTERVAL DATA TO DETERMINE ANNUALIZED ELECTRICAL SAVINGS

CASE STUDY OF APPLYING DIFFERENT ENERGY USE MODELING METHODS TO AN EXISTING BUILDING

Analysis of the Energy Savings Potential in K-5 Schools in Hot and Humid Climates. Jeff S. Haberl, Ph.D., P.E.

Understanding Industrial Energy Use through Sliding Regression Analysis

Potential Energy Savings from Optimized Schedule & Economizer Cycles in the Moody Library Building at UTMB

LITERATURE REVIEW OF UNCERTAINTY OF ANALYSIS METHODS. (Inverse Model Toolkit) Report to the Texas Commission on Environmental Quality

Uncalibrated Building Energy Simulation Modeling Results

ManagingEnergy.com. Overview of ASHRAE Guideline (American Society of Heating, Refrigerating and Air-Conditioning Engineers)

Joint-Frequency Bins versus Conventional Bin Weather Data in Analysis of HVAC System Operation

Retrospective Testing of an Automated Building Commissioning Analysis Tool (ABCAT)

A Case Study in Energy Modeling of an Energy Efficient Building with Gas Driven Absorption Heat Pump System in equest

Leveraging Smart Meter Data & Expanding Services BY ELLEN FRANCONI, PH.D., BEMP, MEMBER ASHRAE; DAVID JUMP, PH.D., P.E.

ENERGY ANALYSIS AND ENERGY CONSERVATION OPTION FOR THE WAREHOUSE FACILITY AT THE HUMAN SERVICES CENTER COMPLEX DRAFT REPORT.

DEVELOPMENT OF A HIGH-PERFORMANCE OFFICE BUILDING SIMULATION MODEL FOR A HOT AND HUMID CLIMATE

UNDERSTANDING MANUFACTURING ENERGY USE THROUGH STATISTICAL ANALYSIS

A Case Study of Energy Demand in Housing Units

Statistical Modeling of Daily Energy Consumption in Commercial Buildings Using Multiple Regression and Principal Component Analysis

Whole Building Energy Performance Evaluation through. Similar Control Strategies

Figure 26.5 Potential fan energy savings using fan speed limiting 16.

ESTIMATED SAVINGS FROM TURNING OFF UNNECESSARY ELECTRICAL LOADS DURING UNOCCUPIED PERIODS AT THE LANGFORD ARCHITECTURE CENTER

EVALUATION OF BUILDING ENERGY CONSUMPTION BASED ON FUZZY LOGIC AND NEURAL NETWORKS APPLICATIONS

Development of Baseline Monthly Utility Models for Fort Hood, Texas'

Modeling Hourly Electric Utility Loads in the Phoenix Area

Targeting Energy Efficiency in Commercial Buildings Using Advanced Billing Analysis

MEASURING INDUSTRIAL ENERGY SAVINGS

A NEW ALGORITHM FOR SENSORS VERIFICATION AND CORRECTION IN AIR HANDLING UNITS

Energy Analysis of Using Thermal Mass in a Hot Humid climate

AN INVERSE MODEL TO PREDICT AND EVALUATE THE ENERGY PERFORMANCE OF LARGE COMMERCIAL AND INSTITUTIONAL BUILDINGS

Thermal Comfort Zone for Thai People

Sample. Annual Energy Consumption Report. and. Monthly Energy Consumption Report. for. Zachry Engineering Center

COMPARISON OF SIMULATION METHODS FOR EVALUATING IMPROVED FENESTRATION USING THE DOE-2.1E BUILDING ENERGY SIMULATION PROGRAM

Program Overview The Texas LoanSTAR Program; , A 10-Year Experience

MEASUREMENT AND VERIFICATION GUIDELINES FOR RETROFIT AND NEW CONSTRUCTION PROJECTS

Guidelines for Measuring Air Infiltration Heat Exchange Effectiveness (IHEE)

Continuous Commissioning Leading Energy Project Process - An Industry Approach

Submitted to. Texas A&M University - Kingsville The Texas A&M University System. Submitted by. Yeqiao Zhu John Bryant Dan Turner David Claridge

A STUDY OF PREDICTED ENERGY SAVINGS AND SENSITIVITY ANALYSIS. A Thesis YING YANG

Energy Consumption Analysis and Energy Conservation Evaluation of a. Commercial Building in Shanghai

EXTENDING AND FORMALIZING THE ENERGY SIGNATURE METHOD FOR CALIBRATING SIMULATIONS AND ILLUSTRATING WITH APPLICATION FOR THREE CALIFORNIA CLIMATES

Geothermal Heat Pumps at Ft. Polk: Early Results

Demonstration of Load Shifting and Peak Load Reduction with Control of Building Thermal Mass

Monitoring & Analysis Program of Prison Sites for the Texas Department of Criminal Justice

DEVELOPMENT OF THE POTENTIAL ENERGY SAVINGS ESTIMATION (PESE) TOOLKIT

Energy Consumption Simulation and Analysis of Heat Pump Air Conditioning. System in Wuhan by the BIN Method

Truing-Up to Billing Data

Multivariate Methods for Evaluating Building Energy Efficiency

Analysis of the Window Side Thermal Environment Formed by Air Barrier. Technique in Winter Conditions and Its Economy

CONTINUOUS COMMISSIONING OF THE MATHESON COURTHOUSE IN SALT LAKE CITY, UTAH. William D. Turner, P.E., Ph.D. Song Deng, P.E.

HVAC INTEGRATED CONTROL FOR ENERGY SAVING AND COMFORT ENHANCEMENT vahid Vakiloroaya

Hydraulic Modeling of Large District Cooling Systems for Master Planning Purposes

DEVELOPMENT OF A WEB-BASED, EMISSIONS REDUCTION CALCULATOR FOR STORM WATER/INFILTRATION SANITARY SEWAGE SEPARATION

Influence of Building Envelope on the Sensitivity of HVAC System Energy Consumption

Put the Horse Before the Cart Baseline Characterization in Support of Utility Program Design

PREDICTED VS. ACTUAL ENERGY SAVINGS OF RETROFITTED HOUSE

Assessment of Climate Change Robustness of a Deep Energy Retrofit Design of an Existing Day Care Centre

ENERGY SIMULATION AND ANALYSIS OF AN INTERMITTENT VENTILATION SYSTEM UNDER TWO CLIMATES

BASELINE MODELS OF WHOLE BUILDING ENERGY

Evidence based calibration of a building energy simulation model: Application to an office building in Belgium

Evaluating Impact of Retrofit Programs on Commercial Buildings: Results from the Energize Phoenix Project

Bottom-up simulation calibration of zone and system level models using building automation system (BAS) trend data

SECTION 900: BUILDING AND SITES

Energy Modeling Applications for Existing Buildings

Impact of Window Replacement on Yanke Building Energy Consumption

The baseline building system for compliance with Senate Bill 668 is defined by Appendix G,

ENERGY EFFICIENT RETROFIT OF A HIGH-RISE MULTIFAMILY BUILDING

Dynamic simulation of buildings: Problems and solutions Università degli Studi di Trento

SURNA Grow Facility: Systems Comparison - IEA

The energy benefits of View Dynamic Glass

LIST OF TABLES LIST OF FIGURES ACKNOWLEDGEMENTS ABSTRACT INTRODUCTION LITERATURE REVIEW STEEPLE

THE NEW YORK TIMES BUILDING

COMPARING BUILDING PERFORMANCE TRENDS IN THREE ENERGY SIMULATION PROGRAMS

SMART CONTROL FOR NATURAL VENTILATION HOUSE

Lean Energy Analysis: Identifying, Discovering and Tracking Energy Savings Potential

COMPARISON OF ENERGY USE INDICATORS OF A NON-RESIDENTIAL PASSIVE HOUSE WITH ASHRAE 90.1 BUDGET BUILDING

MEASUREMENT AND VERIFICATION TOOLS Spiros Metallinos Regulatory Authority for Energy, Greece

Coupling night ventilative and active cooling to reduce energy use in supermarkets with high refrigeration loads

Improving Energy Retrofit Decisions by Including Uncertainty in the Energy Modelling Process

ESRU. Technical Report. CIBSE TM33 Tests for Software Accreditation and Verification: ESP-r Test Results

MECHANICAL PROJECT PROPOSAL (Revised)

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress Heiselberg, Per Kvols. Publication date: 2016

Building Control Strategies That Work to Improve Your Energy Bottom Line

Impacts of Increased Outdoor Air Flow Rates on Annual HVAC Energy Costs

Building Energy Modeling Using Artificial Neural Networks

ANSI/BPI-2400-S-2015 STANDARD PRACTICE FOR STANDARDIZED QUALIFICATION OF WHOLE - HOUSE ENERGY SAVINGS PREDICTIONS BY CALIBRATION TO ENERGY USE HISTORY

LAHU Heat Recovery System Optimal Operation and Control Schedules

Evaluating Energy Performance and Improvement Potential of China Office Buildings in the Hot Humid Climate against US Reference Buildings

Characteristics of Energy Consumption by building type of a U.S. Navy Installation in Hot and Humid Climate

Coppin State University Physical Education Complex - Technical Report 2

Assessment of the energy demand in energy-saving office buildings from the viewpoint of variations of internal heat gains

Energy and IAQ Implications of Different Outdoor Air Ventilation Strategies for Terminal Reheat Variable Air Volume Systems

USE OF WHOLE BUILDING SIMULATION IN ON-LINE PERFORMANCE ASSESSMENT: MODELING AND IMPLEMENTATION ISSUES

AMI Billing Regression Study Final Report. February 23, 2016

VALIDATION OF THE INTERNATIONAL CODE COMPLIANT CALCULATOR (IC3) v USING THE RESNET VERIFICATION PROCEDURES (NO )

Building Energy Consumption Analysis, Energy Saving Measurements and Verification by Applying HAP Software

Space Heating Load Estimation Procedure for CHP Systems sizing

Transcription:

IMPACT OF NIGHTTIME SJXJT DOWN ON THE PREDICTION ACCURACY OF MONTHLY REGRESSION MODELS FOR ENERGY CONSUMPTION IN COMMERCIAL BUILDINGS Jinrong Wang and David E. Claridge Energy Systems Laboratory Mechanical Engineering Department Texas A&M University College Station, TX ABSTRACT Regression models of measured energy use in buildings are widely used as baseline models to determine retrofit savings fiom measured energy consumption. It is less expensive to determine savings fiom monthly utility bills when they are available than to install hourly metering equipment. However, little is known about the impact of nighttime shut off on the accuracy of savings determined from monthly data. This paper reports a preliminary investigation of this question by comparing the heating and cooling energy use predicted by regression models based on monthly data against the predictions of calibrated hourly simulation models when applied to a medium-sized university building in Texas with (i) DDCAV system operating 24 hours per day, (ii) DDCAV system with nighttime shut down, (iii) DDVAV system operating 24 hours per day, and (iv) DDVAV system with nighttime shut down. The results of the four cases studied indicate : 1) when the AHUs are operated 24 hourstday, the annual prediction error of the cooling regression models is less than 0.5% of the annual cooling energy consumption; however, 2) when the AHUs are operated with nighthme shut down, the annual prediction error of the cooling models becomes as high as 6% of annual energy consumption. It should be noted that the cases considered here include only single end-uses of energy and have not investigated energy-use data which includes multiple enduses. Modified regression models are therefore recommended when AHUs are not operated 24 hours per day and the temperature pattern is significantly different between pre and post retrofit years. INTRODUCTION The North American Energy Measurement and Verification Protocol (DOE, 1996) presents three methods, Options A, B, and C, for measuring energy savings fiom retrofits in commercial buildings. Option C: Whole-Facility Or Main Meter Measurement determines savings as the difference between the energy consumption predicted for the post-retrofit period using a baseline model and measured energy consumption during the post-retrofit period. Single variable daily regression models, which regress daily energy use against daily mean ambient temperature, have been used for the baseline model in the majority of buildings in the LoanSTAR Program (Claridge 1994). However, when monthly utility bills are available, it will generally be less expensive to use monthly utility data for retrofit savings measurement than to record hourly or daily data. However, little is known about the prediction accuracy of the monthly regression models and the impact of nighttime shut down on the accuracy of savings determined fiom monthly data. Therefore this paper reports a preliminary investigation of this question by comparing the heating and cooling energy use predicted by regression models based on monthly data against the predictions of calibrated hourly

simulation models when applied to a medium-sized university building in Texas. When monthly utility bills are used for retrofit savings measurement, software which may be used to determine baseline models and savings includes PRISM (Fels et al. 1986) and EModel (K~ssock et al. 1994). This study uses the EModel software for developing baseline monthly regression models since it includes a set of models applicable to a wider range of commercial buildings than the PRISM. The functional form of the model most appropriate for the monthly data being analyzed in this study is (Ruch and Claridge 1992): +P& -Tp)+(1) where E is the daily average energy consumption for each month or billing period, Tdb is the mean temperature for each month, T, is a change point temperature, Po is the energy consumption at the change point temperature T,, p2 is the slope above T, E= Po +P,(Tp -L)+ and p, is the slope below T,. The notation ( )+ indicates that the quantities within the parentheses should be set to zero when they are negative. Accuracy and reliability of regression models used for analysis of building energy data are generally assessed by comparing statistical indices such as the coefficient of determination (R~), the root mean square error (RMSE), the coefficient of variation of the root mean square error CV (RMSE), and the mean bias error (MBE) (Katipamula et al. 1995). Since the temperature range and temperature distribution for pre- and postretrofit years may be different, these statistical indices may not correctly represent the prediction accuracy and reliability of the regression models. To investigate the prediction capability of the regression models, this study uses two years of weather and energy use data. The first year of data is used for developing models and the second year of data is used to evaluate the prediction accuracy of the regression models. METHODOLOGY The difference between the predicted and measured energy consumption of a building is due to a combination of the prediction error and "noise" due to operational changes and occupancy changes. Therefore, in this study, synthetic data fiom simulations is used to eliminate the "noise" found in measured data. The following procedure is used to identify prediction error in this study: 1. Develop HVAC system simulation models based on a case-study building. 2. Simulate cooling and heating energy use for a mild weather year, aggregate to monthly values and develop monthly regression models based on the simulated data. 3. Predict energy use with the regression models and simulate energy use with the simulation models for an extreme weather year. 4. Determine prediction error as the difference between regression model predicted and simulated energy consumption. avac SYSTEM SIMULATION MODELS The simulation model used in this study is AModel (Liu and Claridge 1995) which is based on the ASHRAE TC4.7 simplified energy analysis procedure (Knebel 1983). This program has been used successfully to identify potential energy savings fiom commissioning in several types of commercial buildings (Liu and Claridge 1995). This hourly simulation emphasizes the air-side systems and requires much less envelope information than many hourly programs. It has successfully predicted the

savings from numerous system and control changes. measured cooling energy consumption and Ec,s - simulated cooling energy consumption) To ensure that the simulation results are reasonable, a simulation of the dual-duct variable air volume (DDVAV) case was calibrated to the measured cooling and heating energy consumption of the Nursing Hall at the University of Texas at Austin. This building has a steel frame and reinforced concrete floors, exterior walls of pre-cast panel with single pane tinted fixed windows and a concrete roof. The total conditioned floor area is 96,000 fi2. It houses nursing classrooms and lecture halls, work shops, lounges and professors' offices. The HVAC system for this building, which operates 24 hourslday, consists of two DDVAV air handling units (2xlOOhp) without pre-treat units or economizers. The measured 1994 hourly cooling and heating energy use data for this building were used for calibrating the simulation models. Figures 1 and 2 compare the calibrated simulated and measured cooling energy consumption for 1994. The figures show daily values of the simulated and measured consumption as well as the residuals, or difference between daily simulated and measured values. The annual fitting error or MBE is 0.87% and the CV-RMSE is 7.24% (on a monthly basis). Figure 2. Calibrated Simulated and Measured Cooling Energy Consumption and Residuals versus Outdoor Temperature Figures 3 and 4 compare the calibrated simulated values and measured heating energy consumption for 1994 in the same manner. The annual fitting error or MBE is 3.15% and the CV-RMSE is 10.12%. The MBE and CV-RMSE values for the heating simulation are higher than the values for the cooling simulation due to a change in domestic hot water usage during the summer and the lower average value of the heating consumption. Since the objective of this calibration is to develop reasonable characteristics for a building, typical operating practices were simulated to assure that the simulation results are reasonable; short-term operating changes were not simulated. PI, Figure 1. Time Series Plots of Calibrated Simulated and Measured Cooling Energy Consumption and Residuals (Ec,m -

Table 1. Summary of the Cases Studied DDVAV 1 Case 3 1 Case 4 I Figure 3. Time Series Plots of Calibrated Simulated and Measured Heating Energy Consumption and Residuals (Eh,m - measured heating energy consumption and Eh,s - simulated heating energy consumption) Figure 4. Calibrated Simulated and Measured Heating Energy Consumption and Residuals versus Outdoor Temperature To investigate the impact of system types (DDCAV and DDVAV systems), and operating schedules (24 houdday & nighttime shut down operation), the calibrated simulation models were modified to represent these cases, as shown in Table 1. Case 1 represents the DDCAV system with 24 houdday operation and Case 2 represents the DDCAV system with nighttime shut down. Case 3 represents the DDVAV system with 24 hourlday operation and Case 4 represents the DDVAV system with nighttime shut down. SIMULATED ENERGY CONSUMPTION DATA AND MONTHLY REGRESSION MODELS The hourly cooling and heating energy consumption were simulated using the simulation models for each of the four cases using 1994 weather data. 1994 had fewer days of extreme weather than any other year in the last decade (Wang, 1995). The simulated hourly data were totaled for each month to get monthly cooling and heating energy consumption. These simulated monthly values were then fit with fourparameter regression models which are summarized in Tables 2 and 3 below. The regression models give MMBtuJday consumption as a function of dry bulb temperature. R~ and CV were determined by EModel (Kissock, 1993; Kissock et. al. 1994). Table 2. Summary of Monthly Cooling Models operation I if Tdb268.3 (F) I Case 2: 1 4.9262+0.1413(Tdb-66.332) 1 0.99 1 5.6 24 hour 9.8596+1.1402(Tdb-68.300) operation if Tdb268.300 (F) Case 4: 4.3675+0.1329(Tdb-66.988) 0.99 5.5 DDVAV, if ~d~66.988 (F) night shut 4.3675+0.5198(Tdb-66.988 off ) if Tdb266.988 (F) I

I ESL-98-06-33 Table 3. Summary of Monthly Heating Models Model DDCAV, 24 hour if TdbC66.988 (F) I.9235-0.1076(Tdb-66.988) operation 1 if Tdb266.988 (F) 1 1 Case 2: 1 0.6294-0.2291[Tdb-66.988) 1 0.97 1 20.8 DDCAV, night shut off Case 3: DDVAV, 24 hour if TdbC66.988 (F) 0.6294-0.0365(Tdb-66.988) if Tdb266.988 (F) 2.21 11-0.6626(Tdb-66.332) if TdbC66.332 (F) 2.21 1 1-0.1065(Tdb-66.332) operation I if Tdb266.332 (F) I I Case 4: 1 0.6063-0.20771Tdb-67.644) 1 0.97 I 19.8 DDVAV, night shut PREDICTION ERROR OF THE MONTHLY REGRESSION MODELS The regression models were evaluated by comparing the energy consumption predicted by the regression models with the values predicted by the calibrated simulation models with weather data from 1985. The 1985 weather year contained the largest number of extreme weather days in the last decade (Wang, 1995). The prediction accuracy of the regression models was judged by the annual differences between the predictions of the regression models and the simulation models as well as the coefficient of variation of these differences. The annual percent difference (error) of a regression model is defmed as: where RMSE is the root mean square error which is: RMSE = 1, Ej is the energy use in month j from the simulation model, and n=12 represents the total number of months in the high energy A consumption year, Ej is the energy use in month j, predicted by the regression model, and p is the number of parameters in the model. - j=1 E= -, is the mean monthly energy n consumption for the year, based on the simulation model. A Ej = Dj * q, where Dj is the number of days in month j, andq is the monthly average daily energy use in month j, predicted by the monthly regression model. Cooling Consumption Prediction Accuracy Table 4 summarizes the annual cooling consumption predicted by monthly regression models and simulation models for 1985 and presents the annual prediction errors for each case. where E,, is the annual consumption predicted by the regression model and E,, is the annual consumption predicted by the corresponding simulation model. The coefficient of variation, CV(?h), on a monthly time scale was calculated for the monthly regression models as:

Case Case 1: DDCAV, 24 hrdday Case 2: DDCAV, nighttime shut down Case 3: DDVAV, 24 hrdday Case 4: DDVAV, nighttime shut dnwn Tab1 1 4. Annual Prediction Error of the Monthly Cooling Regression Models Annual Cooling Consumption MMBtu) 1 Annual Prediction 1 CV-RMSE Predicted by I Error or MSE I (%) I Predicted by Regression ~odels I 6016 Simulation ~odels 602 1 regression models and simulation models and Heating Consumption Prediction Accuracy presents the annual prediction error of the Table 5 summarizes the annual heating regression models. consumption predicted by the monthly Table 5. Annual Prediction Error of the Monthly Heating Regression Models 1 Case 1 Annual Heating Consumption (MMBtu) I Annual ( CVRMSE 1 Case 1 : DDCAV, 24 hrdday Case 2: DDCAV, 520 550 5.7 17.5 nighttime shut diwn I I Case 3: DDVAV, 24 I 1723 1652-4.1-12.3 I hrdday Case 4: DDVAV, nighttime shut down Predicted by Regression Models 1788 510 As we can see, the monthly regression models have consistently higher prediction error when the system is shut down during the nighttime, even when the monthly model has high R ~, low CV and low MSE. In the next section, the modified regression models are developed for the shut down cases. MODIFIED MONTaLY REGRESSION MODELS AND THEIR PREDICTION ACCURACY The regular monthly regression models were developed using the daily average temperature for each utility period. Using the average temperature gives equal weighting to Predicted by Simulation Models 1721 0.1 Prediction Error or MSE -3.7.. 4.9 (%) 11.7 537 5.2 15.9 the influence of all hourly temperatures on the energy consumption. When the HVAC system is shut down at night, the dayhme weather has the major influence on the daily energy consumption. Therefore, for these cases, it is more reasonable to regress the energy consumption against the average temperature during the operating hours for the conesponding period. Modified monthly regression models were developed, based on the average temperatures during the operating hours, for cases 2 and 4. The modified models are summarized in Table 6. The annual prediction errors determined for these modified models are presented in Figure 5.

Case Table 6. Modified Monthly Regression Models for Nighttime Shut Down Cases Models RL CV Annual Prediction % (%I I., Ec=6.6569+0.1 875(67.044-Tdb)'+0.6756(Tdb-67.044)7 1.00 3.4 0.3 Eh=0.909 1 -.3662(67.04-Tdb)'-.0462(Tdb-67.044)' 1.00 14.6-3.9 Case 2 DDCAV, Night Shut Off Case 4 DDVAV, Ec=5.8505+. 1736(67.7082-Tdb)*+.6794(Tdb-67.708)' ~h=0.97 18-0.341 (67.044-~db)'-0.0458(~db-67.044)+ 1.OO 0.99 3.7 13.8 0.6-4.1 case2- case4- case2- case4 coding coding heating heating Cases Figure 5. Prediction Error of Regular and Modified Heating and Cooling Models for Night Shut-Down Cases. Figure 5 compares the annual prediction errors of the modified models and the regular models. The modified cooling regression models reduce the annual prediction error to 0.6% from -6.1 %. The modified heating regression models reduces the annual prediction error to 4.1% from 5.7%. CONCLUSIONS The results of the four cases studied indicate that when the AHUs operate 24 hours per day, the annual prediction error of the regular cooling regression models are less than 0.5% of the annual cooling energy consumption. However, when the AHUs operate with nighttime shut down, the annual prediction error of the regular cooling models is as high as 6.1% of annual energy consumption. Modified regression models based on average temperature values during the operating periods are recommended when AHUs operated less than 24 houdday and the temperature pattern of pre- and postretrofit years are different. The modified cooling regression models reduced the annual prediction error to 0.6% from -6.1%. The modified heating regression model reduced the annual prediction error by about 113. ACKNOWLEDGMENTS This work was funded by the Texas State Energy Conservation Office of the Intergovernmental Division of the General Services Commission (State Agencies Program) as part of the LoanSTAR Monitoring and Analysis Program. REFERENCES Claridge, D.E., Haberl, J., Katipamula, S., O'Neal, D., Chen, L., Heneghan, T., Hinchey, S., Kissock, K., and Wang, J. 1990. "Analysis of the Texas LoanSTAR Data", Proceedings of the Seventh Annual Symposium on Improving Building Systems in Hot and Humid Climates, Texas A&M University, College Station, TX, Oct. 9-10, pp. 53-60. Claridge, D.E. 1994. "Annual Energy Consumption Report", Energy Systems Laboratoly, Texas A&M University, College Station, Texas, May. Department of Energy, 1996. North American Energy Measurement and

Verijication Protocol, DOEEE-008 1, U. S. Department of Energy, Washington, D.C. Fels, M.F. 1986. "Special Issue Devoted To Measuring Energy Savings: The Scorekeeping Approach", Energy and Buildings, Vol. 9, Nos. 1 and 2. Wang, J., 1995. "Comparison of the Prediction Accuracy of Daily and Monthly Regression Models for Energy Consumption in Commercial Buildings," M.S. Thesis, Department of Mechanical Engineering, Texas A&M University, December. Kissock, K., Claridge, D., Haberl, J., and Reddy, T.A. 1992. "Measuring Retrofit Savings for the Texas LoanSTAR Program: Preliminary Methodology and Results", Proceedings of the ASME/JSES/KSES International Solar Energy Conference, Hawaii, March, pp. 299-308. Katipamula, S., Reddy, T.A., and Claridge, D.E. 1995. "Effect of Time Resolution on Statistical Modeling of Cooling Energy Use Ln Large Commercial Buildings", ASHRAE Transactions, Vol. 101, pt. 2. Knebel, D. E. 1983. Simplijled Energy Analysis Using the Modijied Bin Method, American Society of Heating, Refrigerating and Air-conditioning Engineers, Lnc., Atlanta, GA. Liu, M., Claridge, D.E. 1994. "Reducing Building Energy Costs Using Optimized Operation Strategies for Constant Volume Air Handling System ", Proceedings of the Ninth Symposium on Improving Building Systems in Hot and Humid Climates, Arlington, TX, May 19-20, pp. 192-204. Liu, M. and Claridge, D.E. 1995. "An Advanced Economizer Controller for Dual Duct Air Handling Systems-with a Case Application", Proceedings of the 2nd International symposium on Heating, Ventilation and Air Conditioning, Beijing, China, September 25-27, Vol. 2. Ruch, D. and Claridge, D. 1992. "A Four Parameter Change-point Model for Predicting Energy Consumption in Commercial Buildings", Journal of Solar Energy Engineering, Vol. 114, pp. 77-83.