State of the Art of Air-source Heat Pump for Cold Regions

Similar documents
FIELD TEST STUDY ON THE PERFORMANCE OF AIR SOURCE HEAT PUMP IN LOW TEMPERATURE IN BEIJING

Vapor injected heat pump using non-azeotropic mixture R32/R1234ze(E) for low temperature ambient

Performance Comparison of Air-source Heat Pumps Using Economizer Vapor Injection and Internal Heat Exchanger in Cold Regions

A Investigation of the Performance of Two-Stage Compression Refrigeration/Heat pump System with Dual-cylinder Rolling Piston Compressor

DEVELOPMENT OF A HYBRID AIR-CONDITIONING SYSTEM DRIVEN BY LOW TEMPERATURE WASTE HEAT

Experimental Investigation on Heat Pump for Electric Vehicles with different refrigerant injection compressors

NUMERICAL APPROACH TO A LOW PRESSURE GAS-INJECTION SCROLL COMPRESSOR

Application Of Oil Flooded Compression With Regeneration To A Packaged Heat Pump System

Experimental Research and Performance Analysis of a Solar-Powered. Air-conditioning System in a Green Building

Energy demand for hot water supply for indoor environments: Problems and perspectives

Simulation Study on Geothermal Direct Supply Combined with Water Source Heat Pump Qing HAO 1, a, Meng SI 2, b

Recent U. S. R&D results from IEA HPP Annex 41

Low temperature cogeneration using waste heat from research reactor as a source for heat pump

*Corresponding authors. Tel.: x415, address: (N. Zhu)

SOLAR COOLING: STATE OF THE ART, TECHNICAL ANALYSIS AND FIRSTS APPLICATIONS

Customized Absorption Heat Pumps for Utilization of Low-Grade Heat Sources

HPC 2017 Performance simulation and exergy analysis on multi-stage compression high temperature heat pumps with R1234ze(Z) refrigerant

Research on a Novel Heat Recovery Method for Flue Gas Qing HAO 1, a, Yue YANG 2, b

Combined Heat and Power

Comparative Heating Performances of Ground Source and Air Source Heat. Pump Systems for Residential Buildings in Shanghai

Compound ejectors with improved off-design performance

ENERGY AND EXERGY ANALYSIS OF HEAT PUMP USING R744/R32 REFRIGERANT MIXTURE

Cold Climate Heat Pump using Tandem Vapor-Injection Compressors

Heat Pump Water Heaters: Eco-cute Living Lab Tests

High efficient heat reclaim with CO2

a.k.a. David N. Shaw, P. E.

Technical Papers. 32nd Annual Meeting. International Institute of Ammonia Refrigeration. March 14 17, 2010

A new generation, energy-efficient, sanitary hot water solution for commercial applications

CO2 in Vending Machine

THEORETICAL COMPARISONS BETWEEN ABSORPTION HEAT PUMP AND ELECTRICAL HEAT PUMP FOR LOW TEMPERATURE HEATING

A Study on Engineering Application of Solar Heating System Assisted by Heat Pump

DISTRICT HEATING AND COOLING WITH LARGE CENTRIFUGAL CHILLER-HEAT PUMPS

International Forum on Energy, Environment Science and Materials (IFEESM 2015)

Risto Lahdelma Professor, Energy technology for communities Tel:

Draft proposals for Test methods for close-coupled solar water heating systems - Reliability and safety

Heat pumps. WP5 Education and Economic Promotion

CO 2 Transcritical Cycle for Ground Source Heat Pump

Modeling and simulation of a reclaimed water source heat pump system based on TRANSYS 1

Experimental Results on a New Prototype Packaged Heat Pump System Retrofitted with Oil Flooded Compression and Regeneration Technology

Available online at ScienceDirect. Energy Procedia 78 (2015 )

Variable Speed Solutions Outstanding Performance For Heat Pump Applications

Performance Evaluation under the Actual Operation Condition of a Ground Source Multiheat Pump System

AREN 2110: Thermodynamics Spring 2010 Homework 7: Due Friday, March 12, 6 PM

The Opportunity and Requirement of Commerce and Technology Cooperation He Yongheng China Refrigeration and Air Conditioning Industry Association

Water Heating Technologies To Meet Energy & Environmental Challenges

Variable Speed Solutions. Outstanding performance for residential applications

Zuba-Dan Inverter New Mr.SLIM Inverter for colder climate regions

Investigation on effects of piping on heating performance of multi-split variable refrigerant flow system

A NOVEL APPLICATION OF A SCREW ROTOR ENGINE AS AN EXPANSION DEVICE IN AN ORGANIC RANKINE CYCLE

A Scroll Expander with Heating Structure and Their Systems

A Novel LNG and Oxygen Stoichiometric Combustion Cycle without CO 2 Emission

ECONOMIC ANALYSIS OF HEAT PUMP USED AS

PERFORMANCE EVALUATION OF HEAT PUMP SYSTEM USING R744/R161 MIXTURE REFRIGERANT

DESIGN AND PERFORMANCE ASSESSMENT OF THERMAL COMPREHENSIVE UTILIZATION SYSTEM: CASE STUDY

Design and development of a residential gas-fired heat pump

Design and Experiments of a Solar Low-temperature Hot Water Floor Radiant. Heating System 1

The Present and Future of Refrigeration, Power Generation and Energy Storage. R.Z. Wang Shanghai Jiao Tong University

Advanced heat driven cooling cycles for low-temperature waste heat recovery

AE R1 November, 2003

The Separation and Liquefaction of Oxygenated CBM Yang Kejian and Zhang Wu

Kalex Kalina Cycle Power Systems For Use as a Bottoming Cycle for Combined Cycle Applications

Second Law of Thermodynamics

Study on Ejector - Vapor Compression Hybrid Air Conditioning System Using Solar Energy

Heat Pump Hot Water Supply Systems

Faculty of Engineering 2 nd year 2016 Mechanical Engineering Dep. Final-exam (code: M 1222)

Experimental Research of an Active Solar Heating System

EFFICIENT HEAT PUMPS AND TERMINALS FOR DIFFERENT CLIMATE ZONES. Ruzhu WANG

Steady State Modeling of Advanced Vapor Compression Systems with Multiple Air and Refrigerant Loops

DEVELOPMENT OF TWIN PISTON EXPANDER WITH SOLENOID VALVE FOR ORGANIC RANKINE CYCLE

DISTRICT HEAT DRIVEN ABSORPTION COOLING OF DISTRICT COOLING PLANTS IN TRONDHEIM, NORWAY

Improvement of the Performance for an Absorption Refrigerating System with. Lithium bromide-water as Refrigerant by Increasing Absorption Pressure 1

Development of a small capacity directly air-cooled water/libr absorption chiller

HEAT PUMPS FOR THE EXPLOITATION OF GEOTHERMAL SOURCES IN MILANO. University of Brescia. Studio Associato di Ingegneria - Milano

Experimental Investigation of Gas Engine Driven Heat Pump Used in Water Cooling

Special edition paper Research on Utilizing Air Thermal Energy for Railway Facilities

BCM00 Introduction to Building Controls and HVAC (available on request) One day course BCIA Members VAT Non-members VAT

THEORETICAL STUDY OF HEAT PUMP SYSTEM USING CO 2 /DIMETHYLETHER AS REFRIGERANT

A Modified Heat Pump Air-Conditioning System for Electric Vehicle

The Performance of Compression-absorption Heat Pump System Using Low-temperature Geothermal Tail Water

Gregory W. Stevens and Ronald K. Ishii, Alternative Energy Systems Consulting, Inc.

TransPacific Energy Advantage: Case Studies

The Potential and Challenges of Solar Boosted Heat Pumps for Domestic Hot Water Heating

CCHP System with Interconnecting Cooling and Heating Network

Eng Thermodynamics I: Sample Final Exam Questions 1

Critical exergy analysis of counterflow reversibly used cooling towers

- 2 - SME Q1. (a) Briefly explain how the following methods used in a gas-turbine power plant increase the thermal efficiency:

Development of high efficiency VRF systems under partial heat load for commercial buildings

Thermodynamic Performance Assessment of R32 and R1234yf Mixtures as Alternatives of R410A

CO2 solutions February 2018

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

EXPERIMENTAL RESEARCH ON HEAT TRANSFER IN A COUPLED HEAT EXCHANGER

COMPARATIVE ANALYSES OF TWO IMPROVED CO 2 COMBINED COOLING, HEATING, AND POWER SYSTEMS DRIVEN BY SOLAR ENERGY

YEARLY SIMULATION OF CO 2 REFRIGERATION SYSTEMS FOR SUPERMARKET APPLICATIONS

Mechanical Redesign. Existing System: The following schematic was devised below.

Enhancement of LNG Propane Cycle through Waste Heat Powered Absorption Cooling

Research Article Investment and Economy Analysis of Water-Source Heat Pump System in Chongqing, China

Recovery of Waste Heat in Diesel Engine Coolant for Air Conditioning

The Design of Water Intake System and Analysis of Water Quality Conditions of the Regional Energy System of Complex River Water Source Heat Pump

BINARY BLEND OF CARBON DIOXIDE AND FLUORO ETHANE AS WORKING FLUID IN TRANSCRITICAL HEAT PUMP SYSTEMS

ENERGY MODELLING OF A GAS-FIRED ABSORPTION HEAT PUMP IN A RESIDENTIAL HOME FOR COLD CLIMATE USING TRNSYS

Transcription:

State of the Art of Air-source Heat Pump for Cold Regions Changqing Tian Nan Liang Ph D, Associate Prof. Ph D candidate Technical Institute of Physics and Chemistry, Chinese Academy of Sciences Beijing, P. R. China chqtian99@mails.tsinghua.edu.cn Abstract: In this paper, research on air source heat pump systems for cold regions in recent years is first summarized and compared. These systems can be divided into three kinds: a single-stage compression heat pump, liquid/vapor injection heat pump, and a two-stage heat pump. Finally, our research with a two-stage compression variable frequency air source heat pump is presented. A two-control-model with the priority target as COP or heating capacity is advanced. The experimental results show that the COP of this heat pump system is over 2, the compressor discharge temperature under 120, and the heating capacity can meet the heating load needed when the condensing temperature is 50 and outdoor air temperature is over -18. Key words: air source heat pump; cold region; review; two-stage compression; variable frequency 1. INTRODUCTION More and more heat pump systems have been used as the cold source and heat source of air conditioning systems due to their higher efficiency, pollution-free and multi-use. Specially, air source heat pump (ASHP) is the most widely-applied equipment among all kinds of heat pump units for its low initial investment, convenient maintenance and little influence to ambient. Since 1990 s, ASHP had been successfully used in the unconventional heating region of China including the middle and lower reaches of the Yangtze River, south and southwest China since it can meet the building s needs of cooling and heating in these regions with less energy consumption. Nowadays, the coal-fired boilers are still the main heating source in north China where are very cold in winter, however the pollution and slow development of centralized heat-supply network make people search some green and high efficiency heating system to supplement or replace the conventional one. Much research has been made to try to use the ASHP system in cold regions. In this paper, the air source heat pump systems for cold regions are introduced and compared firstly, and then our research with a two-stage compression variable frequency air source heat pump system is presented. 2. THE PROBLEM OF COMMON ASHP FOR COLD REGIONS There are four main problems when the common ASHP systems are used in the winter of cold region: 1) Along with the decrease of ambient temperature, heat capacity goes down obviously whereas the building heat load increases, which cannot be solved completely in common ASHP system. 2) COP decreases and energy consumption increases along with the decrease of ambient temperature. 3) The discharge temperature of compressor goes up so high that the ASHP system cannot operate normally when the ambient temperature is much lower. 4)When the ambient temperature drops to 5 or even lower, the frost will form on the surface of outdoor heat exchanger. The frost layer causes the increase of heat resistance and decrease the rate of air flow, which leads to the decline of the COP. In some conditions, the system even cannot work

with serious blockage. The frost formation is a general problem for all ASHP system, and what is more, less frost will form when the ambient temperature is lower than -10. So the frost formation would not be involved in the paper. 3. TECHNICAL REVIEW OF ASHP FOR COLD REGIONS In the paper, the ASHP systems for cold regions are divided into three groups: single-stage compression heat pump, liquid/vapor injection heat pump, and two-stage heat pump. 3.1 Single-stage Compression Heat Pump For single-stage compression heat pump, there are methods including increasing the fan speed of outdoor heat exchanger, heating evaporator inlet air, and changing the concentration of refrigerant mixture to improve the applicability of ASHP in cold regions. 3.1.1 Variable Speed Fan Wang suggested the variable speed fan is used for the outdoor heat exchanger of ASHP system [1]. When ambient temperature is very low, the fan works with high rotary speed to increase the air flow rate through the heat exchanger, and to improve evaporating temperature and the refrigerant mass flow rate to compressor. But the method is appropriate for the ambient of not very low temperature and its improvement is not obvious. 3.1.2 Air Source Improvement Yamagami used an oil heater to increase the air temperature at the outdoor heat exchanger inlet in order to improve the heating capacity of ASHP [2]. The evaporating temperature becomes higher in cold regions with a kerosene-fired burner. Furthermore, the burner also can be used as an auxiliary heat source. The method is not suitable for small system because the system is more complicated and the initial investment is much higher. 3.1.3 Varying Concentration of Refrigerant Mixture Sami and Tulej improved the heating capacity of ASHP with a ternary refrigerant mixture for cold climates [3]. Chen analyzed the theoretical cycle performances of R32/R134a and R22 [4]. The experimental investigation on a novel ASHP with altering concentration of refrigerant mixture was carried out, and the results showed that R32/R134a has better heating capacity adjustment performance. 3.2 Liquid/vapor Injection Heat Pump Zheng set a vapor injection inlet on one-stage screw compressor and developed a quasi two-stage heat pump system with the mode of one-stage compression and two-stage throttle device [5]. Horiuchi proposed an ASHP system with an inverter scroll compressor and liquid injection [6] (Fig.1). High pressure refrigerant liquid flows into compressor through liquid injection port to reduce the compressor discharge temperature and enhance the heating capacity under low outdoor air temperature. Also, the heating capacity can be improved by means of increasing the power frequency of compressor, but meanwhile the evaporating temperature and COP go down along with the increase of power frequency. 1 5 Fig. 1 Liquid injection heat pump 1. Evaporator 2.Compressor 3. Condenser 4. Expansion valve 5. Injection pipe Ma proposed a quasi two-stage compression ASHP system with an economizer and a scroll compressor basing on the liquid injection heat pump system [7] (Fig. 2). The economizer can make the liquid refrigerant out of condenser a large subcooling degree, and enhance the heat 4 2 3

absorbed from outdoor air for per mass refrigerant and COP. Also, the economizer can reduce the discharge temperature of compressor. The COP of system is 1.69, and discharge temperature is 121.4 when the condensation temperature is 45 and evaporating temperature is -25. 4 condenser 3 el ect r oni c expansi on val ve A compressor suppl ement ar y pi pe 4' subcool er 2' 6 evaporat or val ve 5 2 1 el ect r oni c expansi on val ve B Fig. 2 Quasi two-stage compression heat pump 3.3 Two-stage Heat Pump Ma developed a two-stage coupling heat pump system which obtains heat from cold air through low temperature heat pump loop and produces water of 10-20 [8]. The water is used as the low grade heat source of high temperature heat pump loop to produce the hot water or hot air for building heating (Fig.3). The COP of the system can reach 2.48 in Beijing and the discharge temperature is no more than 60. Hulten and Berntsson combined the absorption heat pump (as low temperature loop) and vapor compression heat pump (as high temperature loop), and developed an absorption/vapor-compression coupling heat as the high grade heat source, absorbs heat from pump [9]. The system, with the industrial waste heat air and produces the medium temperature (higher than ambient temperature) air, with which as low grade heat source, the compression heat pump produces the hot water. The absorption/vapor-compression coupling heat pump is effective system to improve the heating efficiency in cold regions, but it has 5' complicated structure and needs waste heat source with a proper temperature. Low temperature heat pump loop High temperature heat pump loop 空气 / 水热泵 Fig. 3 Two-stage coupling heat pump 3.4 Comparison of Different ASHP for Cold Regions The heating capacity, COP, discharge temperature, system complexity and applicability of the ASHPs for cold regions are compared in Tab.1. It can be seen that all methods extend the applicability of ASHP in cold regions to a certain extent. 4. TV-ASHP SYSTEM Finally, this paper introduces our scheme for cold regions, i.e. two-stage compression variable frequency air source heat pump (TV-ASHP) system [10]. 4.1 Description of TV-ASHP The schematic diagram of TV-ASHP system is shown in Figure 4. The uncompleted intercooling two-stage compression cycle is adapted, and the system mainly includes a low pressure stage compressor, a high pressure stage compressor, an outdoor heat exchanger, an indoor heat exchanger, an intercooler, two throttling devices, a four-way valve, and a solenoid valve. Three work conditions including the single-stage compression cooling, single-stage compression heating and two-stage compression heating can be carried out by controlling four-way valve and /

Tab.1 Comparison of ASHPs for cold regions Method Heating capacity COP Discharge temp. Complexity Applicability Variable speed fan Lower Low Very high Low Poor Air source improvement Varying concentration High Low Little lower High Good Little higher Normal Little lower Little lower Preferable Liquid injection Little higher Little lower Normal Little higher Preferable Quasi two-stage Little higher Little higher Normal Little higher Good Two-stage High High Little lower High Good Fig. 4 Schematic of TV-ASHP system 1- low pressure stage compressor 2- high pressure stage compressor 3-four-way valve 4- intercooler 5- receiver 6-throttling device I 7- throttling device II 8- one-way valve 9-indoor heat exchanger 10-outdoor heat exchanger 11-solenoid valve solenoid valve and changing the refrigerant flow circuit. Two-control-mode with the priority target as COP or heating capacity is advanced to assure the system higher COP when the heating capacity can meet the heating load. That is, when the heating capacity meets the heating load, the system works in the mode of COP priority and is kept the optimal intermediate pressure by changing the power frequency of low pressure stage compressor. But if the heating capacity is insufficient for demand, the control mode of heating capacity priority has to be chosen and the power frequency should be adjusted to meet the heating demand. With the TV-ASHP system, the heating capacity is enhanced with two-stage compression and increase of power frequency of low pressure stage compressor together, COP is improved with two-stage compression and optimal intermediate pressure by power frequency adjustment of low pressure stage compressor together, and the discharge temperature of high pressure stage compressor is decreased with the two-stage compression cycle, which are used to solve the insufficient heating capacity, lower COP, and high compressor discharge temperature in the common ASHP systems. 4.2 Experimental Results The test bench with a standard cooling capacity of 16 kw is built up, the COP and discharge temperatures of single-stage compression and two-stage compression, and heating capacity of two-stage compression are measured. 4.2.1 Comparison of COP in Two-stage and Single-stage Compression COP 3 Single-stage compression Two-stage compression 2 1 T c =50 0-30 -25-20 -15-10 -5 0 T e / Fig. 5 Comparison of COP Fig.5 shows the comparison of COP in

two-stage and single-stage compression heating condition when the condensing temperature (T c ) is 50ºC. The COP of both two-stage and single-stage compression system goes down along with the decrease of the evaporating temperature(t e ), but the decreasing rate is more less for two-stage compression system, especially when the evaporating temperature is lower. As shown in Fig.5, the COP of two-stage compression system is still more than 2 when the evaporating temperature is -25ºC. The COP of two-stage compression system exceeds the one of single-stage compression system when the evaporating temperature is below -7ºC. The results above show that the COP of TV-ASHP system is noticeably higher than the common single-stage compression heat pump in cold regions. The lower outdoor temperature, the more the energy saving. 4.2.2 Comparison of Discharge Temperature in Two-stage and Single-stage Compression The variations of the discharge temperature of compressor, T d, along with the evaporating temperature in two-stage and single-stage compression system are shown in Fig.6 when the condensing temperature is 50ºC. The discharge temperature in single-stage compression system increases dramatically when the evaporating temperature goes down. When the evaporating temperature is -15ºC, the discharge temperature rises to 130ºC, which is harmful to the compressor. In the case of two-stage compression system, the increasing rate of discharge temperature is less. When the evaporating temperature is down to -25ºC, the measured discharge temperature of high pressure stage compressor is below 120ºC, with which the compressor can still run reliably and safely. Fig. 7 shows the variations of the heating capacity, Q c, along with the evaporating temperature when TV-ASHP system is operating at the optimal intermediate pressure. The heating capacity goes down along with the decrease of the evaporating temperature, and is only 9kW when the evaporating temperature is -25ºC (outdoor temperature is about -18ºC) though it has been greatly improved. Td / 150 Single-stage compression Two-stage compression 130 110 90 70 T c=50 50-30 -25-20 -15-10 -5 0 T e / Fig. 6 Comparison of discharge temperature 4.2.3 Heating Capacity of TV-ASHP For the heat pump unit with the standard cooling capacity of 16kW, the minimal heating capacity must be higher than 12kW in order to meet the heating demand. That means only the two-stage compression in optimal condition alone cannot satisfy the heating requirement when the outdoor temperature is very low. So the system should adjust the power frequency of low pressure stage compressor by the control mode of heating capacity priority. stage compressor, f 1, when the condensing temperature is about 50ºC and the evaporating stage compressor, f 1, when the condensing temperature is about 50ºC and the evaporating temperature is -25. The heating capacity rises along with the increase of the power frequency of low pressure stage compressor and the heating capacity reaches 12.6 kw when f 1 =80Hz. Basing on the improvement of two-stage compression in optimal condition, increase of power frequency can enhance the heating capacity further, which can meet the heating demand without auxiliary heat source in cold regions. Fig. 8 shows the variations of the heating capacity with the power frequency of low pressure

Qc / kw 20 T c=50 15 10 5-30 -25-20 -15-10 -5 0 T e/ Fig. 7 Heating capacity vs. evaporating temperature room air conditioners. Technical Review Mitsubishi Heavy Industries, 1998, 35 (2) (in Japanese). [3] SAMI S M, TULEJ P J. A new design for an air source heat pump using a ternary mixture for cold climates. Heat Recovery Systems & Chp, 2001, 15(6):521-529. [4] CHEN G, ZHANG L, CHEN B. Study of air heat pump with altering concentration of mixture refrigerant. Fluid Machinery, 2005, 33(supplement): 168-171 (in Chinese). 14 12 T c=50 T e=-25 [5] ZHENG Z, JIN L, QIAN R. The research on air source heat pump system. Chemical Engineering & Machinery, 1994, 21(5): 292-294 Qc / kw 10 8 (in Chinese). [6] HORIUCHI N. Development of package air conditioner for cold regions. Refrigeration, 6 20 40 60 80 100 f l / Hz Fig. 8 Heating capacity vs. power frequency 5. CONCLUSIONS In this paper, the researches on air source heat pump systems for cold regions in recent years are summarized and compared firstly. These systems can be divided into three kinds: single-stage compression heat pump, liquid/vapor injection heat pump, and two-stage heat pump. And then, our scheme for cold regions, i.e. two-stage compression variable frequency air source heat pump is introduced. The COP of this system is over 2, the compressor discharge temperature under 120, and the heating capacity can meet the heating load needed when the condensing temperature is 50, which can be used in the cold regions where outdoor temperature is over -18. REFERENCES [1] WANG H. Discussion of heat pumps in low temperature environment [J]. Journal of HV&AC, 1998, 28(6): 34-37 (in Chinese). [2] YAMAGAMI M. Development of burners for 1997, 72(7): 837 (in Japanese). [7] MA G, CHAI Q, JIANG Y. Experimental investigation of air-source heat pump for cold regions. International Journal of Refrigeration, 2003, 26: 12-18. [8] MA Z, YANG Z, YAO Y. Analysis of using air-source heat pump water chiller-heater units in the cold regions. AV&AC,2001,31(3):17-21 (in Chinese). [9] HULTEN M, BERNTSSON T. The Compression/Absorption Heat Pump Cycle-Conceptual Design Improvements and Comparisons with the Compression Cycle. International Journal of Refrigeration, 2002, 25(4): 487-497. [10] TIAN C, SHI W, WANG S. Research on two-stage compression variable frequency air source heat pump in cold regions. ACTA ENERGIAE SOLARIS SINICA, 2004, 25(3): 388-393 (in Chinese).