BS EN :2006 +A1:2010

Similar documents
Weathertightness test to BS EN :2006 +A1:2010 clauses 4.2, 4.5 and 4.14 on a Smart Architectural Aluminium Alitherm 700 reversible window

Weathertightness test to BS 6375: Part 1: 2009 on a Beaufort Secure Design Ltd open outward, single door with side screen

Weathertightness test to BS 6375: Part 1: 2009 on a Beaufort Secure Design Ltd open outward, Bi-folding/ sliding door with standard threshold

BRE Global Test Report

BRE Global Test Report

BRE Global Test Report

BRE Global Test Report

BRE Global Test Report

BRE Global Test Report

BRE Global Test Report

BRE Test Report. Load and Slip Testing of 4 types of Paving Light and 1 Smoke Outlet Panels. Prepared for: Marc Parkinson. BRE Watford, Herts WD25 9XX

BRE Global Classification Report

BRE Global Classification Report

BRE Global Test Report

BRE Global Classification Report

BRE Global Test Report

BRE Global Test Report

BRE Global Ltd Watford, Herts WD25 9XX. d+b facades (UK) Ltd. The Packway, Larkhill, Salisbury, SP4 8PY. Customer Services

Wind uplift testing on the Click Fit PV mounting system to MCS012. Prepared for: Gary Bowden Cleaner Air Solutions UK Ltd.

BRE Global Test Report

BRE Global Test Report

BRE Global Test Report

BRE Global Test Report

Load testing of a PVC coated handrail system. 25 th March Test report number

Evidence of Performance. Class 4. Class E900. Class C3 / B3. Test Report No PR02. DOMIS d.o.o. Miokovci bb Cacak Serbia

Evidence of Performance

Laboratory Airborne and Impact Sound Insulation of a Robust Details Appendix F Floor with PhotonStar LED Ltd. Downlights

TEST REPORT EN : A1:2010

BRE Global Classification Report

BRE Global Classification Report

Classification report for roofs/roof coverings exposed to external fire in accordance with BS EN : 2005+A1:2009

BS8414 Part 1: 2002 Test on a Phenolic Insulated Rainscreen system. Prepared for: Kingspan Insulation Ltd Pembridge Leominster Herefordshire HR6 9LA

BRE Global Assessment Report

EN :2003. TESTS OF INDUSTRIAL, COMMERCIAL and GARAGE DOORS and GATES. A Report To: D4 Products Ltd. Document Reference: WIL

BRE Global Classification Report

Laboratory Airborne Sound Insulation of Stud Walls with Warmcel 500 Insulation. Prepared for:

BS :2005 test on a Kingspan Benchmark External Wall Insulation System

BRE Global Assessment Report

Wooden joinery (windows and doors)

Comparison of UK Window Standards to Canadian Standards

BRE Global Assessment Report

BS 476: Part 3: 2004 test on SureSeal EPDM 1.2mm on a plywood deck

Welcome to a frame-free world

BRE Global Client Report

BS EN :2006. Locking vent lock Uni stop Side fix angel Retro fit angel Clip-in angel

Testing of Three Ply Floor Protection Product Tensile and Tear Strength

Architectural Testing ASTM E283, ASTM E330, ASTM E331 TEST REPORT. Report Number: C Rendered to: Tubelite Inc.

1.1.2 All window frames will be Kite marked to indicate compliance with these standards.

SPECIFICATION For the Supply and Installation of BRITAL SG-2-56-HFF. Two Sided Structurally Glazed Curtain Walling. (Horizontal Structural joints)

NORDAN TIMBER DOOR RANGE NORDAN I1, U1, U2, TE AND TX TIMBER DOORSETS

SPECIFICATION For the Supply and Installation of BRITAL UN Four Sided Unitized Structurally Glazed Curtain Walling

ACOUSTIC PERFORMANCE AND STC RATING OF A PARTITION WALL WITH DOUBLE SOCKETS AND POLYSEAM PUTTY PADS

Loss Prevention Standard

Test Report: Fire resistance test in accordance with BS EN :1999 on a nonloadbearing. incorporating Scolmore Doubled Switched electrical sockets

FENTRIM SEALING TAPES

SPECIFICATION FOR Aluminium alloy windows

D & B INJECTION MOULDERS LTD

8414-1: A1:2017

SECURITY TECHNICAL SPECIFICATION

Welcome to a frame-free world

REPORT NUMBER: SHF-BP-2 ORIGINAL ISSUE DATE: April 24, 2015 EVALUATION CENTER

CERTIFICATE OF FIRE APPROVAL

BS 6180: 1999: Barriers in and about buildings Code of practice - General Contract use Clauses 6.4.1

Client Report : Prepared for : Assessment of energy efficiency impact of Building Regulations compliance. Client report number

Agrément Certificate 90/2548 website: Product Sheet 1

RONACRETE RENDER PRODUCTS RONAFIX CONCRETE RENDER ADMIXTURE

PERFORMANCE TEST REPORT. Rendered to: GLASSCRAFT DOOR COMPANY

MONK W20 range of mild steel windows

Structural Performance Tests of VHB Structural Glazing Tapes

TYVEK ROOF LINING SYSTEMS DUPONT AIRGUARD REFLECTIVE

CERTIFICATE OF FIRE APPROVAL

TESTING APPLICATION STANDARD (TAS) CRITERIA FOR TESTING PRODUCTS SUBJECT TO CYCLIC WIND PRESSURE LOADING

TESTING APPLICATION STANDARD (TAS) CRITERIA FOR TESTING PRODUCTS SUBJECT TO CYCLIC WIND PRESSURE LOADING

Test Report. Test Report Debar Ltd. Page 1 of 20

Fire Test Report. Test Number 1243 Dated 22 September Prepared for:

TRESPA WALL CLADDING SYSTEMS SYSTEM 700 ALUMINIUM SUB-FRAME SYSTEM

April Section 3.3. Built-up Metal Walls

ASTM E 1886 and ASTM E 1996 TEST REPORT. Report No.: A Rendered to: CORAL ARCHITECTURAL PRODUCTS Tuscaloosa, Alabama

CERTIFICATE OF APPROVAL No CF 385 HOLLWAYS DOORS & FRAMES LIMITED

BUILDBASE SUPPLIED BY IKO BREATHER MEMBRANE FOR USE IN TIMBER FRAME CONSTRUCTIONS

Building Regulations

DESIGN DOORS TEL:

DESIGN DOORS TEL:

AAMA THERMAL PERFORMANCE TEST REPORT. Rendered to: TUBELITE, INC.

STEALTH ROOFLIGHTS. Product. Scope. Appraisal No. 987 [2018] Appraisal No. 987 (2018) BRANZ Appraisals

TEST REPORT. Rendered to: TFC A DIVISION OF CENTURION INDUSTRIES, INC. Garrett, Indiana

PERFORMANCE TEST REPORT. Rendered to: GLASSCRAFT DOOR COMPANY

INTERNATIONAL WINDOW TEST REPORT

Loss Prevention Standard

CRITERIA FOR TESTING IMPACT & NON IMPACT RESISTANT BUILDING ENVELOPE COMPONENTS USING UNIFORM STATIC AIR PRESSURE

CR LAURENCE CO, INC. ACOUSTICAL PERFORMANCE TEST REPORT

PERFORMANCE TEST REPORT. Rendered to: TREMCO INC. SERIES/MODEL: Proglaze ETA - System 3 PRODUCT TYPE: Pre-Engineered Air Barrier Transition Assembly

VELUX ROOF WINDOWS VELUX TOP-HUNG ROOF WINDOWS

European Technical Approval ETA-03/0014

CR LAURENCE CO, INC. ACOUSTICAL PERFORMANCE TEST REPORT

SECURITY TECHNICAL SCHEDULE STS204 ENHANCED SECURITY PERFORMANCE FOR WINDOWS TO SATISFY PERFORMANCE FOR WINDOWS TO SATISFY THE REQUIREMENTS OF PAS24

2007 FLORIDA BUILDING CODE TEST PROTOCOLS HVHZ (TAS)

A Guide To: Weatherseal selection & specification in Europe. Ensuring Superior performance

Regulations Detail Sheet 1

ANTIK DOORS. The Antik series combines a traditional look with modern design. Beautiful, stylish doors that will add character to your home.

Transcription:

BRE Test Report Weathertightness test to BS EN 14351-1:2006 +A1:2010 clauses 4.2, 4.5 and 4.14 on an LR4 Conservation rooflight for Lumen Rooflights Ltd Prepared for: Paul Trace Date: 14 March 2016 Report Number: P102903-1000 BRE Watford, Herts WD25 9XX Customer Services 0333 321 8811 From outside the UK: T + 44 (0) 1923 664000 F + 44 (0) 1923 664010 E enquiries@bre.co.uk www.bre.co.uk Prepared for: Paul Trace Managing Director Lumen Rooflight RMD1 Dobles Lane Industrial Estate Holsworthy Devon EX22 6HL BRE is not UKAS accredited to make opinions and interpretation. Any opinions and interpretations included as part of this report are clearly marked as such. 0578

Prepared by Name Malcolm Pound Position Senior Consultant and Laboratory Manager, Building Technology Group Date 14 March 2016 Signature Authorised by Name Dr. Paul Blackmore Position Associate Director, Building Technology Group Date 14 March 2016 Signature This report is made on behalf of Building Research Establishment Ltd (BRE) and may only be distributed in its entirety, without amendment, and with attribution to BRE to the extent permitted by the terms and conditions of the contract. Test results relate only to the specimens tested. BRE has no responsibility for the design, materials, workmanship or performance of the product or specimens tested. This report does not constitute an approval, certification or endorsement of the product tested and no such claims should be made on websites, marketing materials, etc. Any reference to the results contained in this report should be accompanied by a copy of the full report, or a link to a copy of the full report. BRE s liability in respect of this report and reliance thereupon shall be as per the terms and conditions of contract with the client and BRE shall have no liability to third parties to the extent permitted in law. Page 1 of 21

Table of Contents 1 Introduction 3 2 Test programme 4 3 Classification of results 5 4 Test specimen 6 5 Test rig and preparatory procedures 7 6 Summary of test results 8 7 Conclusions 9 8 References 10 Annex A Weathertightness test results 11 Page 2 of 21

1 Introduction At the request of Paul Trace, Managing Director, Lumen Rooflight, RMD1, Dobles Lane Industrial Estate, Holsworthy, Devon, EX22 6HL, BRE issued proposal number P102903 on 07 December 2015. The proposal was accepted on 25 January 2016 and BRE received and tested specimen rooflights on the 24 February 2016. BS EN 14351-1:2006 +A1:2010 1 is the product standard that identifies mandated and non-mandated characteristics for windows and external pedestrian doors for the European market, and it enables products to be CE marked. Designers, specifiers, manufacturers and end users need to identify those characteristics and performance levels appropriate for the selected end use. These will vary from site to site and from country to country. To avoid uneconomical and inappropriate specifications for the UK market recommended levels of performance have been identified. These performance levels (in this case for weathertightness) are in the National Application Document (NAD) BS 6375-1:2015 2. The tests to methods specified in BS 6375-1:2015 are BS EN 1026 3, 1027 4 and 12211 5, they measure the weathertightness of the specimens in terms of air permeability, watertightness and resistance to wind load respectively. Classification of the results is based on BS 6375-1:2015 and BS EN 12207 6, 12208 7, 12210 8. The tests on the specimen were carried out by Mr. M. C. Pound and Ben Holland under the BRE Standard Terms and Conditions of Business for testing and to the UKAS BRE Specific Procedures Series F, as BRE Job number P102903-1000. Tests were witnessed by: Paul Trace Chris Barkwill Managing Director Lumen Rooflights Lumen Rooflights Page 3 of 21

2 Test programme BS 6375-1:2015 specifies that the air permeability test is performed under both positive and negative test pressures and that the average of the measurements defines the results. It also specifies that water tightness test method A is used and that deflections measured during the resistance to wind load test do not exceed 1/150 of the span. The weathertightness test comprised of three parts in the sequence: 1. Air permeability to BS EN 1026: 2000; by application of a series of test air pressure differentials across the specimen with measurement of the air permeability of it at each pressure step. The maximum positive and negative pressure differential was 600 Pa reached in pressure steps of 50, 100, 150, 200, 250, 300, 450 and 600 Pa. 2. Watertightness to BS EN 1027: 2000; by applying specified amounts of water spray to the outside face of the specimen while incrementally increasing the air pressure differential across it. The test pressure, time and position of any water penetration are recorded. The maximum positive air pressure differential was 600 Pa. Pressure (Pa)/time (min) steps were 0/15, 50/5, 100/5,150/5, 200/5, 250/5, 300/5, 450/5 and 600/5. 3. Resistance to wind load to BS EN 12211: 2000; by application of a series of positive and negative test air pressures. Measurements and inspections are made to assess relative frontal deflection and resistance to damage from wind loads. The resistance to wind load test includes a deflection test, a repeated pressure test and operational test, an air permeability test and finally a safety test. For the purpose of the resistance to wind load test three test pressures are defined: P1 P2 P3 applied to measure the deflections of parts of the test specimen. 50 cycles of pulsating pressure to assess performance under repeated wind loads. applied to assess the safety of the test specimen under extreme conditions. The values of P1, P2 and P3 are related as follows: P2 = 0.5P1, P3 = 1.5P1. For these tests the values are: P1 = 2100 Pa, P2 = 1050 Pa and P3 = 3150 Pa. Note: The repeat air permeability test is an integral part of the resistance to wind load test and its significance is as an indicator of damage that may occur during that test. Page 4 of 21

3 Classification of results BS 6375-1:2015 classifies the results for products in the UK. For a window to be included in an exposure category the appropriate test pressures for air permeability, watertightness and resistance to wind shall be attained or exceeded. The relevant product standard BS EN 14351-1:2006 +A1:2010 also states that classification of air permeability is based on the averages of the positive and negative air leakage values at each pressure step. The specimens were tested to a UK exposure category of 2000+ (2100 Pa in this case). The classifications set in BS 6375-1:2015 for a UK exposure category of 2000+ for windows are: Air permeability at Class 2/300 Pa when tested to 300 Pa or class 3 or 4 when tested to 600 Pa, water tightness at class 7A at 300 Pa and resistance to wind load at Class AE2100 at P1 2100 Pa, P2 1050 Pa and P3 3150 Pa. BS EN classifications are explained below: Air permeability: BS EN 12207: 1999. The classification is based on a comparison of the air permeability of the test specimen related to both overall area and length of opening joint. There are four classes; Class 4 is applicable to the most airtight specimens while Class 1 describes those with most air leakage. To meet any class the measured air permeability of the specimen must not exceed the upper limit at any test pressure step in that class. Watertightness: BS EN 12208: 2000. The classification is based on a comparison of the watertightness of the test specimen related to test pressures and duration of the test. There are nine classes; 1A/1B up to 9A for test pressures from 0 Pa to 600 Pa. For specimens that remain watertight over 600 Pa for 5 minutes a class Exxx is used. The xxx is the maximum test pressure e.g. 750 Pa. To meet any class the specimen must remain watertight for 5 minutes up to and at the test pressure set for that class. Resistance to wind load: BS EN 12210: 1999. The classification is based on a comparison of the resistance to wind loads of the test specimen when subjected to test pressures P1, P2 and P3. There are five classes; 1 up to 5 for P1 test pressures from 400 Pa to 2000 Pa. For specimens that are tested to P1 pressures exceeding 2000 Pa a class Exxxx is used. The xxxx is the actual test pressure P1 used e.g. 2400 Pa. To achieve any class the resistance of the specimen to wind load must meet all the requirements for that class. Note: This report has results for air permeability under positive and negative test pressures and a graph showing the average air permeability for them at each pressure step. Page 5 of 21

4 Test specimen The general details about the test specimens supplied by Lumen Rooflights Ltd for these tests are Summarised below and given in full in the annex to this report: Condition: The rooflight specimen was manufactured in January 2016, delivered to BRE on 19 February, stored in the test lab conditions and tested on the 24 February. Type: Frame: Glazing: Seals: Hardware: Fixings: Steel frame members forming a rooflight with one outward opening light with indoor timber liners. Reference: LR4 Conservation rooflight GA. Photographs and drawings in the Annex of this report show details of the window. Mild steel - Powder coated RAL. 9005 black. The rooflight is glazed externally with insulating glass units with 4 mm thick glass (to the indoor face), a 16 mm wide argon gas filled gap and 4 mm thick glass (to the outdoor face). Indoor face is glazed with Pilkington Optitherm S3 and the outer with Pilkington Activ neutral glass. The window frame has Q-lon compressible seal all the way around and also a rubber seal. At the top and bottom there are two rows of seal. The opening light is operated by a manual winder. There are two pivot hinges at the top of the rooflight. For these tests the specimen was fixed with screws and sealed into a timber surround with stiffening timbers. Dimensions: Size of the opening light is 696 mm wide x 993 mm high (overall). Area: 0.69 m² Length of opening joint = 2.88 m Page 6 of 21

5 Test rig and preparatory procedures The test specimen was conditioned for at least 4 hours within temperature and humidity ranges specified in the test standards of 10 C to 30 C and 25% to 75% RH respectively. The water temperature in the watertightness test was within the specified range of 4 C to 30 C. The specimens were mounted in turn in the BRE test rig G, to form one wall of a pressure box, with the outdoor face enclosed in the box. A spray bar with three full circular cone nozzles was mounted in the pressure box to apply water to the outside face of the specimen. The water flow rate per nozzle was 2 L/min in accordance with BS EN 1027 spraying method 1A. Transducers were mounted on independent supports to measure deflections of a frame member. Deflections were measured on the span at the positions indicated in Figure A3. Page 7 of 21

6 Summary of test results The test results for the LR4 Conservation rooflight are summarised in Table 1 below for tests at a UK exposure category of 2000+. Figures show detail of the test specimens and detailed results are given in Annex A. Air permeability Watertightness Resistance to wind loads Requirements Results Requirement Results Requirements Results Class 2 at 300 Pa or Classes 3 and 4 at 600 Pa Met Class 4 for the average of positive and negative test results Class 7A at 300 Pa Class 8A at 450 Pa 1 st water leak at rooflight joints at 600 Pa Class AE2100 P1 = 2100 Pa P2 = 1050 Pa P3 = 3150 Pa Met all of the requirements for Class AE2100 Table 1. Summary of weathertightness test results Page 8 of 21

7 Conclusions When the test specimen LR4 Conservation rooflight was tested to the standards described herein to a UK exposure category of 2000+ it was found to be: Sufficiently airtight to attain Class 4 based on the averages of results under positive and negative test pressures thus meeting the BS 6375-1:2015 requirements and those of BS EN 12207 for Class 4 at 600 Pa. Resistant to water penetration using method 1A up to and at 450 Pa thus exceeding the BS 6375-1:2015 requirements for Class 7A at 300 Pa at a UK exposure category of 2000+. Also met the Class 8A requirement up to and at 450 Pa in BS EN 12208. Resistant to wind loads of ±2100 Pa causing deflections less than 1/150 of the span of a frame member. Resistant to repeated pressure cycles of ±1050 Pa and able to sustain the corresponding safety test pressure of ±3150 Pa. The overall classification for resistance to wind load is Class AE2100 thus meeting the requirements of BS 6375-1:2015 and BS EN 12210. Overall weathertightness performance measured means that the test specimen rooflight in the condition tested are suitable for a UK exposure category of 2000+, as tested and defined in BS 6375-1:2015. Page 9 of 21

8 References 1. BS EN 14351-1:2006 +A1:2010 Windows and doors Product standard. British Standards Institution, London. 2. BS 6375-1:2015. Performance of windows and doors Classification for weathertightness and guidance on selection and specification 3. BS EN 1026: 2000. Windows and doors Air permeability Test method. British Standards Institution, London. 4. BS EN 1027: 2000. Windows and doors Watertightness Test method. British Standards Institution, London. 5. BS EN 12211: 2000. Windows and doors Resistance to wind load Test method. British Standards Institution, London. 6. BS EN 12207: 2000. Windows and doors Air permeability - Classification. British Standards Institution, London. 7. BS EN 12208: 2000. Windows and doors Watertightness - Classification. British Standards Institution, London. 8. BS EN 12210: 2000. Windows and doors Resistance to wind load - Classification. British Standards Institution, London. Page 10 of 21

Annex A Weathertightness test results Pressure differential Pa 50 100 150 200 250 300 450 600 Air flow through the specimen m³/h 0.66 1.16 1.81 1.77 2.60 3.51 4.18 4.94 Air flow per unit area of the specimen m³/h.m² 0.95 1.68 2.62 2.56 3.77 5.08 6.04 7.15 Air flow per unit metre of opening joint m³/h.m 0.23 0.40 0.63 0.61 0.90 1.22 1.45 1.72 Table A1. Air permeability under positive air pressure Pressure differential Pa 50 100 150 200 250 300 450 600 Air flow through the specimen m³/h 0.63 0.87 1.33 2.46 3.08 4.00 4.94 6.38 Air flow per unit area of the specimen m³/h.m² 0.91 1.26 1.92 3.56 4.45 5.79 7.15 9.23 Air flow per metre of opening joint m³/h.m 0.22 0.30 0.46 0.88 1.07 1.39 1.72 2.22 Table A2. Air permeability under negative air pressure Pressure differential Pa 50 100 150 200 250 300 450 600 Average air flow per unit area of the specimen m³/h.m² 0.93 1.47 2.27 3.06 4.11 5.44 6.60 8.19 Average air flow per metre of opening joint m³/h.m 0.23 0.35 0.55 0.75 0.99 1.31 1.59 1.97 Table A3. Averages of air permeability s under positive and negative air pressures Page 11 of 21

Figure A1. Test results: Air permeability under positive and negative air pressure; showing limits and averages of air permeability s measured under positive and negative test pressures Page 12 of 21

Watertightness test Pressure differential Pa 0 50 100 150 200 250 300 450 600 Duration Minutes 15 5 5 5 5 5 5 5 5 Water leaks Nil Nil Nil Nil Nil Nil Nil Nil First water leak after 1 minute at 600 Pa at the bottom of the rooflight Test laboratory conditions: Air temperature 18 C. Test chamber air temperature 18 C Air pressure 1009 mb. Relative humidity 35% at 18 C. Water temperature 15 C Table A7. Watertightness test results Resistance to wind load Deflection test at ± 2100 Pa Position deflection measured Positive pressure P1 to +2100 Pa Deflection Negative pressure P1 to -2100 Pa Deflection mm defl./span mm defl./span Left hand mullion 0.15 1/6000 0.07 1/12857 Note: The deflection at the mid-point of a member is measured relative to its ends, e.g. with reference to Figure A3: Deflection at the mid-point = deflection at the mid-point average of deflections at the two ends of the same member. Table A8. Deflections measured on a frame member in the resistance to wind load test at ±2100 Pa Page 13 of 21

Resistance to wind load Repeated pressure test including the second air permeability test Repeated pressure Damage or functional defects 50 cycles to P2 at ±1050 Pa None Table A9. Damage or functional defects after repeated pressures to P2 at ±1050 Pa Second air permeability test under positive air pressures (part of resistance to wind load test) Pressure differential Pa 50 100 150 200 250 300 450 600 Air flow through the specimen m³/h 0.65 1.09 1.77 1.74 2.57 3.46 4.01 4.79 Air flow through specimen measured at first air permeability test m³/h 0.66 1.16 1.81 1.77 2.60 3.51 4.18 4.94 Comparison to the air permeability measured previously (see Table A1) After the test pressures P1 and P2 were applied the amounts of air flowing through the test specimen were not significantly different to those measured previously Table A10 Second air permeability test results under positive air pressures Second air permeability test under negative air pressures (part of resistance to wind load test) Pressure differential Pa 50 100 150 200 250 300 450 600 Air flow through the specimen m³/h 0.64 0.86 1.32 2.45 3.04 3.99 4.93 6.32 Air flow through specimen measured at first air permeability test m³/h 0.63 0.87 1.33 2.46 3.08 4.00 4.94 6.38 Comparison to the air permeability measured previously (see Table A2) After the test pressures P1 and P2 were applied the amounts of air flowing through the test specimen were not significantly different to those measured previously Table A11. Second air permeability test results under negative air pressures Page 14 of 21

Resistance to wind load - Safety test Safety test Condition after test One pressure pulse to pressure: P3 at then + 3150 Pa No parts became detached and the test specimen remained closed Table A12. Condition of the specimen after the safety test to P3 at ±3150 Pa Figure A2. The indoor face of the LR4 Conservation rooflight test specimen mounted in the BRE Test rig G Page 15 of 21

Deflections measured at points 1, 2 and 3 Figure A3. The indoor face of the LR4 Conservation rooflight test specimen mounted in BRE Test rig G showing points 1, 2 and 3 where deflections were measured Page 16 of 21

Page 17 of 21

Page 18 of 21

Page 19 of 21

Page 20 of 21

Building Research Establishment Ltd Report Ends Report No. P102903-1000 Page 21 of 21