Vibration Serviceability Design and Field Tests of Long-Span Ultra- Slim Composite Floor System for Super Tall Residential Buildings

Similar documents
Structural Design and Optimization of Long-Span Ultra-Slim Composite Floor for Super Tall Residence

EXPERIMENTAL STUDY ON VIBRATION BEHAVIOR OF COLD-FORM STEEL CONCRETE COMPOSITE FLOOR

SHAKING TABLE TEST AND NUMERICAL ANALYSIS ON STRUCTURAL MODEL OF BEIJING NEW POLY PLAZA

VIBRATION EVALUATION OF FLOOR SYSTEMS FOR FOOTFALL USING ADAPT-FLOOR PRO

Research on the Seismic Performance of an Externally Prestressed Rocking Reinforced Concrete Frame

Long-term Stress of Simply Supported Steel-concrete Composite Beams

Tests and Analysis on Vertical Vibration of Long-Span Prestressed Concrete Floor Sysstem Abstract: Keywords: INTRODUCTION Corresponding Author:

Analysis of seismic performance and shaking table tests of the Shanghai Tower

Dynamic Characteristics Analysis of Large Self-anchored Suspension Bridge

Shaking Table Model Test of a HWS Tall Building

Structural Design of Super High Rise Buildings in High Seismic Intensity Area

Non-linear Time History Response Analysis of Low Masonry Structure with tie-columns

Damage-control Seismic Design of Moment-resisting RC Frame Buildings

Minimum slab thickness of RC slab to prevent undesirable floor vibration. Technology, Dhaka-1000, Bangladesh. 2.

Shaking Table Test of Controlled Rocking Reinforced Concrete Frames

Design and Finite Element Analysis of A Spatial Tubular Truss and Its Pin Support

CHAPTER III DYNAMIC BEHAVIOR OF A LABORATORY SPECIMEN

Integrated Optimal Life Cycle Design of Super Tall Buildings with Viscous Dampers

Rong He School of Civil Engineering and Communication, North China University of Water Resources and Electric Power, Zhengzhou, , China

Research on the Influence of Infill Walls on Seismic Performance of Masonry Buildings with Bottom Frame-Shear Walls

Level 6 Graduate Diploma in Engineering Structural analysis

Simulation of Ground-borne Vibration and Noise Due to High -speed. Trains through Changsha Railway Station

ANALYSIS AND ASSESSMENT OF ARTICULATED SKEW HOLLOW SLAB BEAM BRIDGE

Anti-fatigue Performance Analysis on Steel Crane Beam

Research on seismic behavior of Wood-Concrete Hybrid Structure

PSEUDO-DYNAMIC TEST AND NON-LINEAR ANALYSIS OF A 1:10 SCALE PRE-STRESSED CONCRETE CONTAIN VESSEL MODEL FOR CNP1000 NUCLEAR POWER PLANT

SEISMIC CAPACITY ASSESSMENT FOR STREET-FRONT REINFORCED-BRICK BUILDINGS IN TAIWAN

109. Strain modal analysis and fatigue residual life prediction of vibrating screen beam

VIBRATION EVALUATION OF A PARKING STRUCTURE 1

Experimental Study on the Outrigger Damping System for High-Rise Building

Transverse Mechanical Behavior of Hangers in a Rigid Tied Arch Bridge under Train Loads. I: Static and Dynamic Response

Determination of damage location in RC beams using mode shape derivatives

1688. Study on the dynamic response of subway tunnel by viaduct collapsing vibration and the protective measures of reducing vibration

Load Transferring Mechanism and Design Method of Effective Detailings for Steel Tube-Core Concrete Interaction in CFT Columns with Large-Section

SEISMIC DESIGN OF STRUCTURE

Creep and Shrinkage Analysis of Composite Truss Bridge with Double Decks

Pushover Analysis of High Rise Reinforced Concrete Building with and without Infill walls

CRACKING BEHAVIOR AND CRACK WIDTH PREDICTIONS OF CONCRETE BEAMS PRESTRESSED WITH BONDED FRP TENDONS

Seismic Evaluation of a 1930 Steel Bridge with Lightly Reinforced Concrete Piers

EXPERIMENTAL STUDY ON FLEXURAL BEHAVIOR OF RC BEAMS STRENGTHENED WITH SMPM

Research on Bending Bearing Capacity of Simply Supported Reactive Powder Concrete Beams

Structural Performance Assessment and Control of Super Tall Buildings During Construction

Application of Progressive Collapse Analysis in a High-Rise Frame-Core Tube Structure

Design and construction of Hechang Bridge, Quanzhou, China

The Stress-related Damping Ratio of Box Girder with Corrugated Steel Webs

STUDY ON THE TUNNEL SECONDARY LINING CONCRETE CRACKING PERFORMANCE DURING SERVICE PERIOD OF WU- GUANG PASSENGER DEDICATED LINE

3.4.2 DESIGN CONSIDERATIONS

Structural Characteristics of New Composite Girder Bridge Using Rolled Steel H-Section


Performance-based Seismic Design Principles and Objectives of Shanghai Tower

NUMERICAL SIMULATION ON LOCAL BOND-SLIP BETWEEN STEEL AND CONCRETE WITH EXPERIMENTAL VERIFICATION

International Journal of Intellectual Advancements and Research in Engineering Computations

Modal-spectral analysis of a gas storage tank.

Seismic Performance Of R C Flat-Slab Building Structural Systems

THE EFFECT OF AXIAL COMPRESSION RATIO ON SEISMIC BEHAVIOR OF INFILLED REINFORCED CONCRETE FRAMES WITH PROFILED STEEL SHEET BRACING

BEHAVIOR OF STEEL FRAMES WITH AND WITHOUT AAC INFILLED WALLS SUBJECTED TO STATIC AND CYCLIC HORIZONTAL LOADS

FINITE ELEMENT ANALYSIS OF HOLLOW-CORE SLABS. E. Frăţilă a, *, Z. Kiss a

Part III Special Topics of Bridges

EXPERIMENTAL STUDY ON SEISMIC BEHAVIOR OF REINFORCED CONCRETE CORE WALL

Experiment of Reinforce Concrete Beams at Different Loading Rates

Experimental study on seismic behavior of composite concrete and

Research on Design of High Rise Building Based on Seismic Design Theory

CONTROLLING CROSS-LAMINATED TIMBER (CLT) FLOOR VIBRATIONS: FUNDAMENTALS AND METHOD

Experiment and Finite-element-method Analysis of Steel Frame Joints Transferring Forces Outside Box Columns

Forced vibration testing of a thirteen storey concrete building

Study on Shear Lag Effect of Composite Box Girder Bridge with Corrugated Steel Webs

Experimental investigation of cable-stayed timber bridge

Experimental observation of forklift-induced vibrations on a PSC floor

Simplified Finite Element Modelling of Multi-storey Buildings: The Use of Equivalent Cubes

Technical Notes VIBRATION DESIGN OF CONCRETE FLOORS 1. Bijan O Aalami 2 CONTENTS. Post-Tensioning Expertise and Design January 24, 2014

Mechanical Performance of Composite Truss Bridge with Double Decks

Transactions, SMiRT-22 San Francisco, California, USA - August 18-23, 2013 Division V

Comparative Experimental Study on the Seismic Performance of Reinforced Totally-Recycled Concrete Frame and Semi-recycled Concrete Frame

International Journal on Recent and Innovation Trends in Computing and Communication ISSN: Volume: 4 Issue:

Finite element analysis of bending performance on polyurethane composite panel

IJSRD - International Journal for Scientific Research & Development Vol. 5, Issue 06, 2017 ISSN (online):

STUDY ON TORSIONAL RESPONSE OF TALL BUILDING STRUCTURES WITH TRANSFER LAYER UNDER SEISMIC ACTION

Effect of upgrading concrete strength class on fire performance of reinforced concrete columns

Experimental study on the mechanical behavior of RPC filled square steel tube columns subjected to eccentric compression

Seismic behavior of steel plate - concrete composite shear walls

STRUCTURAL PERFORMANCE OF STEEL-CONCRETE-STEEL SANDWICH COMPOSITE BEAMS WITH CHANNEL STEEL CONNECTORS

DESIGN AND FIELD TEST OF BAQIHU BRIDGE IN QUANZHOU CITY, CHINA

3-D finite element analysis on shear lag effect of curved box girder under multi-dimensional seismic excitation

Finite element simulation of railway through concrete-filled steel tube tied arch bridge based on static analysis

Soil-Structure interaction effects on seismic response of a 16 storey RC framed building with shear wall

Parametric Analysis on Buildings with Connecting Corridors Afiya V N

New Replaceable Coupling Beams for Shear Wall Structures

The Influence of the Shape of Slab on Heavyweight Impact Sound Reduction for an Apartment Building

A Study of Efficient Outrigger Structural Systems for Tall Buildings

Static and dynamic analysis of high-rise building with consideration of two different values of subsoil stiffness coefficients

THE EXTENDED N2 METHOD IN SEISMIC DESIGN OF STEEL FRAMES CONSIDERING SEMI-RIGID JOINTS

Study on the effect of the infill walls on the seismic performance of a reinforced concrete frame

Revision and Errata List, March 1, 2003 AISC Design Guide 11: Floor Vibrations Due to Human Activity

BEHAVIOUR OF REINFORCED CONCRETE STRUCTURES IN FIRE

Flexural Behavior of Casing Joint of Square Steel Tube

NODALIZATION OF ISOLATOR FOR FLOATING FLOOR DESIGN. C.K. Hui and C. F. Ng

RESPONSE OF GROUND SUPPORTED CYLINDRICAL TANKS TO HARMONIC LOADING

Warwick FRP Bridge: Design and Performance

TEST STUDY ON BASIC STATIC CHARACTERISTICS OF CABLE SUPPORTED BARREL VAULT STRUCTURE

Application of Isolation Technology in High-voltage Electrical Equipments

Transcription:

Vibration Serviceability Design and Field Tests of Long-Span Ultra- Slim Composite Floor System for Super Tall Residential Buildings *Guo Ding 1), Jun Chen 2), Rong He 3) and Liwei Ye 4) 1), 3) Tongji Architectural Design (Group) Co., Ltd. Shanghai, China 2) Department of Structural Engineering, Tongji University. Shanghai, China 4) Xiamen Wansha tiancheng real estate development Co.Ltd. Xiamen, China 1) 52dg@tjadri.com ABSTRACT The application of long-span ultra-slim composite floor system with no secondary beams can increase the floor clearances, broaden the exterior visions and avoid exposed beams after the repositioning of partition walls during the layout alterations in the whole life cycles of super tall residential buildings. Because of its large flexibility and low damping, the structural design of long-span ultra-slim composite floor system tends to be controlled by vibration serviceability issue rather than safety issue. This paper presents a case study of such a floor system used in a super tall residential building project located in Xiamen city of southeast China. Focuses are placed on design measures to improve the floor vibration serviceability performance, floor responses analysis methods, floor responses field test method and floor vibration serviceability assessment criteria. Two design methods, namely increasing the rebar ratios in floor slabs and using additional steel plates to form composite slab sections, were considered to improve performance of the floor vibration serviceability. Threedimensional finite element method was applied for the analysis of floor vibration responses, and field tests were conducted to update the structural model and verify the structural responses. The current code-based vibration assessment method was evaluated and some suggestions were put forward for the vibration assessment of long-span ultra-slim composite floor system in super tall residential buildings. 1. INTRODUCTION The application of long-span ultra-slim composite floor systems with no secondary beams to super tall residential buildings can not only increase the floor clearances for broaden the exterior visions but also avoid the exposure of beams when users want to change the locations of some partition wall, thus improving the living quality and 1), 3), 4) Structural Engineer 2) Professor

functionality of the residential buildings. However, because of the application of lightweight high-strength materials and its longer spans, such kind of ultra-slim composite floor tends to be more flexible with lower damping and natural frequency if the floor thickness is small. Vibration serviceability problems due to occupants activities, rather than safety issues can become the controlling factor when designing a long-span ultraslim composite floor (Pavic and Reynolds 2002, She and Chen 2009). When designing a long-span composite floor, vibration serviceability requirements involves two aspects, stiffness and vibrations. The stiffness requirement can be met by controlling the displacements and widths of cracks of the floor under static load. But these controlling measures cannot guarantee the vibration serviceability under human activities since the inertial force is ignored. As a result, even the safety criteria are satisfied, the vibration serviceability of the floor can be very poor. The vibration serviceability performance of long-span composite floors has attracted the attentions of engineers. Some guidelines such as the American AISC standard, the British CCIP-016 standard and the Chinese technical guide JGJ3-2010 have explicit requirements concerning vibration serviceability. The long-span ultra-slim composite floor, however, are not covered by these design guidelines. Based on a super tall residential building which has a long-span ultra-slim composite floor, the following efforts are made in this paper. Measures to improve vibration serviceability performance of structures are proposed. Floor vibrations under human activities are predicted and also measured during field tests. Current guidelines on vibration serviceability are assessed. 2. Design of the long-span ultra-slim composite floor A super tall residential building project named Dijingyuan located in the west of Xiamen, which is a city at southeast of China. The total coverage area of this project is 54286.697 square meters in which 15200.3 square meters are covered by 7 buildings. 5 out of the 7 buildings are super-high-rise steel residential buildings with a structural height of 245.75 m. This project will become a new landmark of Xiamen. As a landmark, its structural design has very high expectations for both safety and serviceability. In order to increase the floor clearance which is a requirement of high-end residential buildings, living rooms and dining rooms all adopted a long-span structural form. The largest floor has a dimension of 10.0m 9.8m and was designed to be a castin-site steel-concrete composite floor with a floor thickness of 200mm and a heightspan ratio of 49, making itself a typical long-span ultra-slim composite floor as shown in Fig.1. This long-span ultra-slim composite floor was designed according to the latest design guidelines in China and the vibration serviceability issue of this long-span ultraslim composite floor was analyzed in this paper.

Boundary conditions of the floor: Up-continuous, down-simply-supported, left-simply-supported, right-continuous Fig. 1 Plan view of the long-span ultra-slim composite floor 2.1 Design against loading capacity Preliminary analysis shows that the structural design of this floor is controlled by the vertical vibration serviceability during normal loading state which means the stiffness of the floor controls the design. By comparing different measures to improve stiffness, such as composite slab by steel bar truss and concrete and steel reinforced concrete floor, we decided to increase the rebar ratios in floor slabs and apply additional steel plates to make composite slab sections to increase the stiffness and therefore to improve the vibration serviceability performance of the floor. However, the following requirements should be met during the enhancement of stiffness: (1) The designed steel beams are embedded in the floor and the concrete floor on top of the beams is 70mm s thick as shown in Fig. 2. In order to secure the quality of construction, the maximum steel rebar arrangement is 16@100 in two lays and two directions. (2) Steel plates thicker than 40mm should guarantee their performance in the Z direction. The cost of welding of thick plates is high and the welding quality is difficult to promise. Therefore, the steel plates used to enhance the stiffness should be less than 35mm in thickness. (3) No fire retardant coating will be used for the added steel plates and thus we don't count their contribution to the loading capacity of the floor. Fig. 2 Section of the composite floor

The stiffness contributions of steel plates of different thicknesses to a same floor were analyzed and the results are shown in Fig. 3. It shows that as the thickness of the floor increases, the stiffness of the composite floor increases. When the thickness of the steel plate lies within the range <0.08H slab, the steel plates effectively increase the stiffness of the composite floor. 2.5 2.2 (EI) eq /(EI) c 1.9 1.6 1.3 1.0 0 0.1 0.2 0.3 0.4 0.5 0.6 h steel /H slab Fig. 3 Stiffness contributions of steel plates with different thicknesses Based on the above analysis and the design method of structural members resisting moments in the design guideline for concrete structures GB 50010-2010 (the guideline for short, hereafter), two candidate section designs are shown in Table 1. Designed section I Table 1 Designed sections Designed section II Floor thickness Steel plate thickness Floor thickness Steel plate thickness 200 mm 10 mm 180 mm 16 mm Both loading capacity design and serviceability check of the designed floor with the two designed sections under static load have been done based on the methods of structural members resisting moments in the guideline, respectively. For safety and economy reasons, also the stiffness requirement by the vibration serviceability of longspan floors, section I was finally chosen. The composite floor was designed to have a floor thickness of 200mm with 10mm s thick steel plate. And the steel rebar arrangement of the composite floor is 16@100 in two lays and two directions. 2.2 Design against Vibration serviceability As a high-end residential building, according to the technical guide GJG 3-2010 in China, the vertical modes of a floor should be no smaller than 3Hz and the vertical accelerations should be smaller than the threshold listed in the technical guide. A simplified method to predict the peak vertical accelerations of floors is also provided in Appendix A of the technical guide GJG 3-2010.

Peak 10s RMS acceleration( m/s 2 ) (1) Frequency of the vertical mode People s walking frequencies lie within 1.6Hz to 2.4Hz (Ding and Chen 2016). Most long-span ultra-slim composite floors have a small damping and a low natural frequency. It is crucial to reasonably determine the natural frequencies of a floor. A delicate finite element model was built to predict the natural frequencies of the floor. To get an accurate modal mass, static load on the floor was added to the model. The effective live load on the floor was chosen as 0.3kN/m 2 according to the related guideline (JGJ 3-2010). In order to get an accurate modal stiffness, an equivalent elastic modulus was used to consider the stiffness contribution from steel rebar and embedded steel plates. The equivalent elastic modulus follows Eq. (1). E eq EcIc EsIs EsIs (1 ) E (1) c I E I c c c The thickness of the protective layer c is equal to 15 mm and therefore the equivalent elastic modulus of the above-designed section is 1.85E c. Through a modal analysis, the fundamental vertical mode of the designed longspan composite floor is 7.48Hz, which is larger than the threshold 3.0Hz. It means that the designed long-span composite floor can meet the requirements of vertical frequency. (2) Peak acceleration prediction In order to guarantee the vibration serviceability of the designed floor, the simplified method in the guideline, finite element method and the response spectrum method proposed by Chen et al. (2014), which has been adopted by the Chinese standard Technical Code for Human Comfort of the Floor Vibration, were used to predict the peak of the accelerations of the designed floor. The parameters for each of the three methods are listed in Table 2. Name Model Table 2 Parameters for the prediction of peak accelerations Simplified method in the Response spectrum Finite element method guideline method Fp a g p In which, a is the peak p acceleration of the floor (m/s 2 ); F is the walking p load when the pedestrian is walking at a frequency close to the floor s natural frequency (kn); is the damping ratio of the floor; is the effective weight of the floor (kn). FEM model 15 10 5 0 rms sub rms (5/f) 1.48 sub rms 1 1.5 2.53 5 10 Structure frequency( Hz) 10s RMS acceleration response spectrum

walking force/kn Walking load Structural parameters Fp p e 0 0.35 f n In which, p0 is the amplitude of the walking load, for residential buildings p0 equals 0.30 kn; f n is the vertical natural frequency of the floor (Hz). The vertical natural frequency f n Payload weight ( ) of the impedance Damping ratio 1.2 0.9 0.6 0.3 0 0 0.1 0.2 0.3 0.4 0.5 0.6 time/s Bauman s single step loading, weight 75 kg, walking frequency 2.0Hz Structure arrangements Component parts size Material properties Damping ratio Measured walking load of two consecutive steps based on Chinese samples Vertical natural frequency Modal mass of the floor Damping ratio The peak accelerations predicted by these three methods are shown in Table 3. Two walking routes were considered in the finite element method and they are shown in Fig.4(a). The floor accelerations with route 1 predicted by finite element method are shown in Fig.4(b). Name Table 3 Calculated peak acceleration Simplified method in Finite element method the guideline Response spectrum method Peak acceleration 2 0.016 0.048 0.062 m/s (a) Walking routes

acceleration/(m/s 2 ) 0.06 0.04 0.02 0-0.02-0.04-0.06 0 1 2 3 4 5 6 7 8 time/s (b) Acceleration response at the mid-span of the floor Fig.4 Acceleration response of the floor It is shown that peak accelerations predicted by the three methods differ to a great degree. Peak accelerations predicted by the first two methods can meet the guideline s requirement, but that of the response spectrum method is larger than the threshold 0.05 m/s 2. 3. Field tests of the floor Given that the case floor is a typical long-span ultra-slim composite floor, investigation on the vibration serviceability of such kind of floors are rare. In order to verify the correctness of the structural design against vibration serviceability, field test was conducted on the constructed floor to get its dynamic properties and vibrations. Field test of the floor was conducted on two separate days. The first attempt of field test was done when the floor had been constructed while the cement mortar flooring layer had not been paved. The aim of the first attempt is to measure the stiffness and dynamic parameters (natural frequency and damping ratio) of the longspan composite floor. These measured parameters can be used to verify and update the model built in the vibration serviceability design. The second attempt took place when a 60mm s thick cement mortar flooring layer had been paved and aimed to get the finial stiffness, dynamic parameters and vibration amplitudes of the floor under human activities. The measurements can be used to assess the three vibration serviceability assessment methods. During the field tests, ambient vibration tests were done to get the floor s modal properties and various kinds of human activities were organized on the floor to get the floor s vibrations under human activities (She 2010). Details relating the two kinds of tests are shown in Table 4.

Table 4 Modal test and vibration test Name Modal test Vibration test Arrangement of test points Floor vibration sensitive locations, can be placed on the top surface of the floor Particular location, should be suspended from the bottom surface of the floor Load random excitation(ambient excitation) Organized human activities Measurements Acceleration responses Acceleration responses Data analysis method Frequency domain analysis Time domain analysis Desired parameters Frequency, damping ratio and mode shape Vibration amplitudes Human activities performed include random walking of a single person, random walking of multi-person, fixed-frequency walking of a single person, fixed-frequency walking of multi-person, fixed-frequency bouncing of a single person, fixed-frequency bouncing of multi-person, etc. Besides these activities, we also organized single person jumping cases, single person running cases and multi-person jumping cases. This paper investigates the design method for long-span ultra-slim composite floors against vibration serviceability and thus only measured peak accelerations of the floor from the single person walking cases are presented here. The arrangement of test points is shown in Fig.5. Fig 5 Arrangement of test points From the first attempt of field test on the 200mm bare floor, the first vertical mode frequency and damping ratio were extracted and are shown in Table 5. It shows that the first vertical frequency is around 12.6Hz and the damping ratio is about 1.75%. From the second attempt of field test on the 260mm floor with cement mortar flooring layer paved, the peak acceleration of the floor under a single person walking measured is 0.041 m/s 2. From the field test, we can conclude that the vertical natural frequency and the peak acceleration of the designed floor can satisfy the provisions required in the guideline.

Table 5 Vertical natural frequency and damping ratio extracted from tests Channel 1 2 3 4 5 6 7 8 Frequency/Hz 12.608 12.604 12.676 12.601 12.629 12.602 12.603 12.605 Damping ratio/% 1.75 1.73 1.74 1.77 1.79 1.79 1.77 1.76 4. Model updating of the finite element model The predicted natural frequencies 7.48Hz do not compare well with the measured ones shown in Table 5. The discrepancy is obvious. The mass parameters assigned in the model can result in a mass similar to the real mass given the method used aforementioned. Therefore, it is the inaccurate stiffness, i.e. the modulus of elasticity that contributes most to the discrepancy. The standard value of the compressive strength of a concrete cube given in the guideline has a guarantee rate of 95% and thus the deduced compressive strength of concrete is expected to be smaller than the real strength. Wang et al. (2007) did a statistical analysis about the compressive strength of concrete cubes and concluded that the compressive strength follows the normal distribution. The compressive strength of the C30 concrete cubes follows N(38.37MPa, 6.48MPa). In this paper, based on the empirical relationship between the elasticity modulus and the compressive strength of concrete cubes follows Eq. (2). The elasticity modulus of the C30 concrete with a mean compressive strength 38.37MPa is calculated as 3.22 10 4 MPa. This elasticity modulus is about 1.07 times that in the guideline. 5 10 Ec 34.7 2.2 f cu, k MPa (2) Besides, the elasticity modulus given in the guideline is the calculated elasticity modulus and is the static modulus. When the floor is subjected to human-induced load, considering the influence of strain rate, the elasticity modulus used in vibration serviceability problems should be larger than the static elasticity modulus. With reference to AISC/CISC Steel Design Guide Series No.11 (American Institute of Steel Construction, Inc. 1997) and ATC Design Guide 1 (Applied Technology Council ATC 1999), the elasticity modulus in steel-concrete composite floors can be taken as 1.35 times the static counterpart. According to the above two reasons, the elasticity modulus in the finite element model can be taken as 1.45 times that in the guideline. For C30 concrete, the updated elasticity modulus is 4.35 10 4 MPa. Based on the updated elasticity modulus of C30 concrete, modification was made for the finite element model of the composite floor. The predicted structural responses by the modified model are shown in Table 6.

Table 6 Parameters for the calculation of peak accelerations of the floor Peak acceleration/(m/s 2 ) First natural Name frequency/hz Simplified method in the guideline Finite element method Response spectrum method Calculated 11.4 0.011 0.038 0.045 Measured 12.5 0.041 0.041 0.041 Error 8.8% 73.2% 7.3% 12.2% From Table 6, it is shown that the natural frequency predicted by the updated model compare well with the measured one, thus justifying the method of updating the elasticity modulus of concrete. Comparing the peak accelerations predicted by the three methods with the measurements, it is concluded that the finite element method produces the most accurate response, the response spectrum methods came the second, and the method in the guideline cannot produce responses accurate enough due to its simplicity. 5. CONCLUSIONS From the case study in this paper, we conclude that the vibration serviceability performance of long-span floors can be effectively improved by means of raising the rebar ratio and applying additional steel plates to make composite slab sections. Besides, long-span ultra-slim composite floor system should be encouraged in super tall residential buildings due to its superior architectural functionality. As long-span ultra-slim composite floor system have less damping and lower natural frequencies, it is crucial for the vibration serviceability performance to reasonably predict the natural frequencies. Experience from the study shows that model updating is very important to get a reliable model. Mass parameters should be determined according to the real situation. Elasticity modulus of concrete is the parameter that can be updated. The real elasticity modulus is about 1.05~1.11 times that in the guideline and the dynamic elasticity modulus is around 1.2~1.35 times the static counterpart. The case study in this paper shows that between the frequency controlling methods and peak acceleration controlling method, the second one overweigh the first one. Building a reliable finite element model and doing dynamic analysis are complicated for engineers. Instead, engineers can adopt the response spectrum method to predict the responses of long-span floors. However, vibration predictions based on reliable finite element models are preferred for qualified engineers. REFERENCES American Institute of Steel Construction,Inc. (1997), AISC/CISC Steel Design Guide

Series No.11: Floor Vibrations Due to Human Activity, USA. Applied Technology Council ATC. (1999), Design Guide 1: Minimizing Floor Vibration, CA. Chen, J., Xu, R.T., Zhang, M.S. (2014), Acceleration response spectrum for predicting floor vibration due to occupant walking, Journal of Sound and Vibration, 333, 3564-3579. Ding, G., Chen, J. (2016) Influences of Walking Load Randomness on Vibration Responses of Long-span Floors, Journal of Vibration Engineering, 29(1), 123-131. Ministry of Housing and Urban-Rural Development of the People s Republic of China. (2010), Code for design of concrete structures (GB 50010-2010), Beijing: Architecture and Building Press. Ministry of Housing and Urban-Rural Development of the People s Republic of China. (2010), Technical specification for concrete structures of tall building (JGJ 3-2010), Beijing: China Architecture and Building Press. Pavic, A., Reynolds, P. (2002), Vibration Serviceability of Long-span Concrete Building Floors: Part 1 - Review of Background Information, The Shock and Vibration Digest, 34(3), 191-211. She, X.X., Chen, J. (2009), A Review of Vibration Serviceability for Long-Span Floors, Structural Engineers, 25(6), 144-149. She, X.X., (2010) Vibration serviceability research of long-span concrete floor field measurements and FEM analysis, Master Thesis, Shanghai: Tongji University. Wang, H.Q., Zhao, M., Li, J., and Ding, J.M., (2007), Analysis and Application of Statistical Data About Concrete Strength, Journal of Tongji University (Natural Science), 35(7), 861-865