Powell. Sodium Hypochlorite Fiberglass Reinforced Plastic (FRP) Storage Tanks

Similar documents
- TABLE OF CONTENTS -

- TABLE OF CONTENTS -

Engineering Branch Assets Delivery Group

SPECIFICATION FOR FIBERGLASS REINFORCED PLASTIC CHEMICAL STORAGE TANKS

SPECIFICATION FIBERGLASS REINFORCED PLASTIC LIQUID CHEMICAL STORAGE TANKS

ENGINEERING SPECIFICATION NON-MAGNETIC RAISED FLOOR SYSTEM FOR MRI ROOM APPLICATIONS

ENGINEERING SPECIFICATION PULTRUDED DYNAFORM FIBERGLASS STRUCTURAL SHAPES. March 16,

STANDARD SPECIFICATIONS RTPV100 PLAS-TANKS INDUSTRIES, INC. 39 STANDEN DRIVE HAMILTON, OH TELEPHONE (513) FACSIMILE (513)

ENGINEERING SPECIFICATION PULTRUDED DYNADECK INTERLOCKING FLOORING

Solving Corrosion Problems with VIPEL Composites

ENGINEERING SPECIFICATION FIBERTRED MOLDED STAIR TREADS SECTION 06610

ENGINEERING SPECIFICATION PULTRUDED DYNAFORM FIBERGLASS STRUCTURAL SHAPES FIBERGRATE MOLDED GRATING WITH GRATING PEDESTALS. January 24,

ENGINEERING SPECIFICATION. PULTRUDED PEDESTRIAN FIBERGLASS GRATING SAFE-T-SPAN T1210 VINYL ESTER and ISOPHTHALIC. October 25, 2004 Revision 1

ENGINEERING SPECIFICATION FIBERGRATE 1 INCH DEEP MICRO-MESH MOLDED GRATING SECTION 06610

TAMDID PIPES GRP MANHOLE BROCHURE

Perry Fiberglass Products, Inc. LEADERS IN FIBERGLASS REINFORCED PLASTIC DUCT PRODUCTS

Perry Fiberglass Products, Inc. LEADERS IN FIBERGLASS REINFORCED PLASTIC PIPE PRODUCTS

ENGINEERING SPECIFICATION PULTRUDED FIBERGLASS GRATING SAFE-T-SPAN HIGH LOAD CAPACITY (47% OPEN AREA) VINYL ESTER. January 24,

ENGINEERING SPECIFICATION FIBERGRATE 62% OPEN AREA/ADA COMPLIANT MOLDED GRATING. January 5,

GLASSFIBER REINFORCED PLASTICS (GRP) MOULDED AND PULTRUDED GRATING

ENGINEERING SPECIFICATION FIBERGRATE MOLDED GRATING

FIBERGLASS WET WELLS

ENGINEERING SPECIFICATION PULTRUDED HIGH LOAD CAPACITY (HI) SAFE-T-SPAN FIBERGLASS GRATING. January 24,

Protective Industrial Polymers - USA Manufacturer s Specification February 11, 2015

FIBERGLASS REINFORCED PLASTIC (FRP) LAUNDER COVERS

FIBERGLASS ROUND CONTROL DAMPERS. Model K-RD INTRODUCTION M.K. PLASTICS PROVIDES FOUR DAMPER MODELS K-RD SUGGESTED SPECIFICATION

1.04 REFERENCES STANDARDS.1 For reference standards tests & results refer to Manufactures Product Data Sheets

ENGINEERING SPECIFICATION PULTRUDED DYNARAIL FIBERGLASS GUARDRAIL AND HANDRAIL. January 24,

ENGINEERING SPECIFICATION PULTRUDED DYNARAIL FIBERGLASS GUARDRAIL AND HANDRAIL. January 24,

ENGINEERING SPECIFICATION

GENERAL SPECIFICATION FOR FIRE RATED APPLICATIONS

Corrstop Dual Laminate Equipment. Corrstop. R CS Dual Laminate Equipment

SECTION FRP GRATING, HANDRAIL, AND SUPPORTS

Resin Systems, Inc. NBS Voluntary Product Standard PS PRODUCT STANDARDS

SAMPLE SPECIFICATIONS FOR PREFABRICATED FRP LIFT STATIONS

WEIR PLATES & SCUM BAFFLES

PRODUCT SPECIFICATIONS PULTRUDED GRATING AND TREADS SECTION PART 1 GENERAL

CITY OF ODESSA SPECIAL SPECIFICATIONS ITEM 1000 GLASS-FIBER REINFORCED POLYESTER (FRP) REHAB/REPLACEMENT MANHOLE

SECTION FLAT WALK-ON TYPE ALGAE CONTROL/LAUNDER COVERS

Case study. Investigation into the Failure of an FRP Vertical Cylindrical Tank

San Antonio Water System Specifications for Construction ITEM NO. 853 SANITARY SEWER GLASS-FIBER REINFORCED POLYESTER (FRP) MANHOLES

Dynaform Fiberglass Structural Shapes. Design Guide. High Performance Composite Solutions. Corrosion Resistant. Fire Retardant.

COMPLETE REVISION June Process Industry Practices Vessels. PIP VESFG001 Fiberglass Tank and Vessel Specification

SECTION EXTERIOR INSULATION AND FINISH SYSTEMS

Fiberglass Reinforced Plastics Applications in Gas Cleaning Systems of Sulfuric Acid Plants

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: WATER RESISTIVE BARRIERS/WEATHER BARRIERS REPORT HOLDER: PAREX USA, INC.

FRP Specifications. Section Fiberglass Reinforced Polymer (FRP) Structural Shapes/Plate and Fabrications REVISED

ICBO Evaluation Service, Inc. A subsidiary corporation of the International Conference of Building Officials

LS 486 / GLASS MAT REINFORCED SYSTEM A LAVALINE - SERIES 48 SYSTEM / Vinyl Ester CONCRETE & MASONRY SURFACES

Standard Specification for Fiber-Reinforced Plastic Fans and Blowers 1

San Antonio Water System Standard Specifications for Construction ITEM NO. 853 SANITARY SEWER GLASS-FIBER REINFORCED POLYESTER (FRP) MANHOLES

PROForms. Specifications SECTION FIBERGLASS REINFORCED POLYMER (FRP) PULTRUDED PRODUCTS

New High Temperature Resistant Vinyl Ester

Reinforced Thermoset Plastic Corrosion-Resistant Equipment

This Quality Standard applies unless otherwise specified by drawing or specification.

First Class Building Products, Inc.

ITEM NO. 853 SANITARY SEWER GLASS-FIBER REINFORCED POLYESTER (FRP) MANHOLES

Reinforced Thermoset Plastic Corrosion-Resistant Equipment

FRP REBAR: MDOT APPROVED

SECTION REINFORCING STEEL

The Use of FRP (Fiberglass-Reinforced Plastic) in Phosphate Fertilizer and Sulfuric Acid Processes

Reinforced Thermoset Plastic Corrosion-Resistant Equipment

INSATALLATIONAND REQUIREMENS

SPECIFICATIONS PVC MANHOLE SYSTEM: FIBERGLASS REINFORCED PLASTIC (FRP) MANHOLE LINER. Predl Systems North America Inc.

FRP Specifications. Section Fiberglass Reinforced Polymer (FRP) Pultruded Grating/Treads and Fabrications REVISED

Tooling Resins FOR SMOOTHER, MORE DURABLE MOLDS

BONDING, POTTING, WELDING

TAMDID PIPES ABOVE GROUND FIBERGLASS STORAGE TANKS

FRP Floor Panels Standard Specification

Note: This specification was written for Clarabelle Mill's flotation cells but may have other applications.

FRP Specifications. Section Fiberglass Reinforced Polymer (FRP) Hollow Core Building Panels Products and Fabrications REVISED 11.

June Process Industry Practices Vessels. PIP VEEFG001 Fiberglass Tank and Vessel Design Guidelines

Section [ ] Stormwater Catch Basin Filtration Device

Heating elements shall not be used for FRP tank-containers including tank swap bodies.

EDGEWATER, FLORIDA JUNE 14, 2010

TECHNICAL SPECIFICATION FOR CURED-IN-PLACE MANHOLE REHABILITATION LINER SYSTEM

SECTION PORTLAND CEMENT PLASTER (STUCCO) WITH ACRYLIC FINISH

SECTION FIBERGLASS REINFORCED PLASTIC (FRP) DOORS AND FIBERGLASS RESIN TRANSFER MOLDED DOOR FRAMES

DERAKANE MOMENTUM Epoxy Vinyl Ester Resin

Specifications for Concrete Embedment Liner

Technical Datasheet Ashland Performance Materials

For P&WC Reference Only. Engineering Source for... Qualified Source - Engineering Control. Qualified Source - Laboratory Control

CON-DEK ICC-ES ESR-2097 SYSTEM

Section [ ] Stormwater Catch Basin Filtration Device

Improving the Cosmetic Quality and Finished Durability of Glass Fiber Reinforced Composites. ArmorGuard ARMORCOTE

6.5 oz/yd g/m 2. 35/35 lb f min. 155/155 N min. 1.5% max. each direction Adhesion - Heat Sealed Seam ASTM D751, Dielectric Weld

COREGUARD FORCED ENTRY RESISTANT SECURITY WALL PANELS ARCHITECTURAL INSTALLATION SPECIFICATION PART 1 GENERAL 1.1 REFERENCE

SECTION BORING AND/OR JACKING PIPE

SAFE-TANK DOUBLE WALL TANKS HIGH DENSITY CROSSLINKED POLYETHYLENE STORAGE TANKS WITH OXIDATION RESISTANT LINING SYSTEM (NSF/ANSI 61)

Pultruded Grating. ADDED SAFETY - durable grit surface, permanently bonded, and baked to the grating surface, for a safe, slip-resistant walkway.

High performance resins for FRP composites in structural / construction applications

Application Procedures for Uncured Rubber Linings on Pipe

FRP Fans Blow Away the Competition in Corrosive Applications

FRP Specifications. Section Fiberglass Reinforced Polymer (FRP) Baffle Wall Panel Products and Fabrications REVISED 11.

.4 Submit proof of qualifications and authorization in writing to the Contract Administrator, four (4) weeks prior to commencement of Work.

13340 FIBERGLASS REINFORCED PLASTIC (FRP) ENCLOSURE

Narrow Modular Pavers (NMP) for Sand-Set Installations

SPECIFICATIONS FOR PREMIER-PIPE USA CURED-IN-PLACE TECH LINER

SECTION SLOPED TRANSLUCENT METAL SKYLIGHT SYSTEM

Transcription:

Powell Fabrication & Manufacturing Inc Last Updated: April 21, 2000 Sodium Hypochlorite Fiberglass Reinforced Plastic (FRP) Storage Tanks Part 1 General 1.01 Section includes A. Design and furnishing of FRP storage tanks for the purpose of storing a maximum of 16.5% by weight sodium hypochlorite solution. 1.02 FRP Tank Specifications 1. The sodium hypochlorite storage tank(s) shall be circular, fabricated from FRP, and sized to hold gallons of sodium hypochlorite (16.5% by weight max concentration). The storage tanks shall be orthowound using Derakane 411 premium grade vinyl ester resins. The storage tank supplier shall have at least ten years experience in the installation of similar FRP tanks. The storage tank manufacturer shall be ASME certified to RTP-1, for fiberglass reinforced plastic fabrication. The storage tank supplier shall be Powell Fabrication & Manufacturing, Inc. of St. Louis, Michigan. 2. The tank wall thickness shall consist of the following four components: a. A resin rich corrosion resistant surface layer containing 2 layers of 10 mil Nexus 1012 surfacing veil for a minimum thickness of 0.020". b. An anti-wicking layer consisting of three layers of random chopped strand glass fiber reinforcing, 0.040" each (minimum). It shall consist of not less than 20% and not more than 30% glass fiber by weight. It shall have a minimum thickness of 0.120 inches. Together these two layers represent a corrosion liner of 0.140 inches (minimum). The corrosion liner shall be considered a corrosion allowance and shall not be included in the structural design. c. A structural layer consisting of chopped strand mat & woven roving, or continuous circumferential roving, and unidirectional roving. Nominal resin content shall be 45% to 70%. Reinforcing sequence and laminate thickness shall be as required by design. d. A resin rich non-process side (exterior) surface layer reinforced with type C glass veil. 3. The non-process side layer shall be finished with two top (white) coats containing UV inhibitors. The outer layer of paraffin wax to promote completes curing of resin. 4. The structural layers shall start with a layer of chopped strand mat. A layer of chopped strand mat except at an overlap shall always separate two layers of woven roving.

5. Internal components, which are immersed on both sides, shall be reinforced only with chopped strand mat. 6. Vessel shell laminates shall comply with part 2 of ASME RTP1 (1b 1997). 7. The following manufacturing processes are not allowed: helical filament winding, spray up, pultrusion, press molding, resin injection and/or vacuum bagging. 8. The equipment supplier shall be responsible for the vessel design including the specific seismic design. 9. The equipment supplier shall provide the design calculations for the Engineer s review at the time of submission of fabricated drawings. 10. The design shall be rechecked with the corrosion liner included in the thickness to ensure that stress and strain levels are within acceptable levels in the corrosion liner. 11. Thickness shall be as required by design. For contact molded vessels, the minimum structural thickness shall be as required by the National Bureau of Standards NBS PS15-69. This required thickness should be in addition to the corrosion allowance of 0.140 inches. 12. The corrosion liner shall be cured using BPO-DMA catalyst cure system, followed by a fourhour post cure to provide a Barcol hardness of the minimum recommended by the resin manufacturer. 13. The nozzle sizes and locations shall be as shown on the contract drawings. A side manway shall also be provided as shown on the contract drawings. All nozzles shall be flat faced, 150 pound drilling. Minimum flange thickness shall be that shown in figure 4.6 ASME RTP1 1995 with addition of the corrosion liner thickness. All nozzles 12" diameter and smaller shall have a minimum of 3 gussets. 14. Quality control for visual defects shall be as the following table: Corrosion liners requiring rework in excess of 1% of the surface area of the component shall be cause for rejection. 15. A ladder and handrail (if required) shall be meet OSHA requirements. 16. A 3-stage inspection process shall be performed on the tank during various stages in the construction process. The first inspection shall be performed at the completion of the corrosion barrier and before structural winding occurs. The second inspection will be performed after the tank is removed from the mandrel and before any nozzles are attached. The third inspection shall be a final inspection prior to shipment of the tank. These inspections shall be performed by an independent inspector with at least 5 years of experience with FRP vessels. 17. Where the tank is RTP1 certified, the tank supplier must provide the appropriate documentation.

Table 1 Maximum Allowable Visual Defects Quality Level 1 Visual Defect Corrosion Liner Structural & Finish Layers Air Bubbles - Bubbles trapped within, on, or between plies. (0.015" dia. and larger) Not to be confused with froth. Blisters - Rounded surface elevations resembling a human skin blister. Burned Areas - Dark discoloration and distortion of the laminate from excessive curing temperature. Chips - Small pieces broken off an edge or surface of the laminate. Cracks - Material separation or fracture. Crazing - Fine cracks at or under the surface of the laminate. Delaminations - Separation of the layers of material in a laminate. Dry Spots - Area of surface where the reinforcement has not been wetted with resin. Not to be confused with glinting. Edge Delamination - Separation of the reinforcement layers at the edge of the laminate. Foreign Inclusions - Anything other than raw material components (visible with naked eye) Pits - Small craters in the surface of the laminate. Surface Pinholes - Numerous visible pinholes in the surface of the laminate. Scratches - Shallow marks or grooves caused by mishandling the laminate. Wrinkles - Linear, abrupt change in surface plane due to overlap in reinforcing layer, irregular mold surface, or wrinkled release film, between veil and antiwicking barrier. (Test with pencil point) Max. 1/16" dia., 2 per in 2, averaged over 1 ft 2 area. In no case, more than 4 per in 2 None exposed to surface. (must be covered with resin) 1/16" dia. 2 per yd 2 1/32" deep No exposed surfacing veil. 1/8" but must not decrease the laminate thickness below allowable. Practically achievable but not larger than 1/4" dia. Total combined area of all air bubbles not to exceed 10 in 2 per yd 2 for laminates up to 1/2" thick, and increased proportionately for thicker laminates. In no case more than 4 bubbles per in 2. 3/16" dia 1/16" height 1/8" dia. 1/16" deep 1" dia. 1/64" deep Practically achievable, but not more than 1/4" dia. and 3 per yd 2. 1/8" dia. 4 per yd 2 1/16" deep 1/32" deep 6" long Not applicable Not applicable

Table 1 Maximum Allowable Visual Defects Quality Level 1 Visual Defect Corrosion Liner Structural & Finish Layers resulting in a resin rich area that could be easily chipped. Waviness is allowed provided it does not result in resin rich area.

1.03 Warranty 1. The tank supplier shall warrant the tank(s) to the owner against defects in workmanship and materials at minimum for 2 years from the date of delivery. Part 2 Execution 2.01 Examination and Preparation a. The contractor shall inspect all equipment immediately upon delivery to site. All internal surfaces of FRP equipment shall able smooth and free of cracks and chips. All visible damage shall be reported and repaired. b. Damaged equipment shall not be installed until repairs have been made in accordance with manufacturer's written instructions and approved by the Engineer. Damaged items shall be sent to factory for repair or replacement, unless otherwise approved by the Engineer. 2.02 Equipment Installation a. Install storage tanks in complete conformance with manufacturer's written instructions and requirements and Engineer approved shop drawings. b. Tank shall be installed on a level and smooth concrete base. The concrete base shall be covered with a 1 thick layer of dry Portland cement (no sand, gravel, or water added) to occupy irregularities between base and tank bottom. Do not grout between knuckle radius and concrete base. Grouting will not allow tank to expand and contract as required. Powell Fabrication & Manufacturing Inc 740 East Monroe Road, St. Louis, MI 48880 Phone 989.681.2158 Fax 989.681.5013 e-mail info@powellfab.com www.powellfab.com