INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS IAPMO GUIDE CRITERIA FOR

Similar documents
INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS

City of Muskogee Pollution Control Department POLICY STATEMENT FOR GREASE AND OIL CONTROL

Section 10 Design Criteria: Components

INYO COUNTY ENVIRONMENTAL HEALTH SERVICES RESIDENTIAL ONSITE SEWAGE TREATMENT AND DISPOSAL GUIDE

INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS IAPMO GUIDE CRITERIA FOR RECLAIMED WATER CONSERVATION SYSTEM FOR FLUSHING TOILETS

401 Sanitary Sewer System Design Criteria. The following additional design requirements shall also apply:

THIS IS A COURTESY COPY OF THIS RULE. ALL OF THE DEPARTMENT S RULES ARE COMPILED IN TITLE 7 OF THE NEW JERSEY ADMINISTRATIVE CODE.

Incorrect sizing, improper installation and/or inefficient maintenance will affect the performance of Proceptor separators.

Ordinance 896 EXHIBIT B FOG SEPARATOR REQUIREMENTS

HARNETT COUNTY NC OIL & GREASE CONTROL ORDINANCE

Presented to the IAPMO Standards Review Committee on December 10, 2018

SEPTIC TANK CONSTRUCTION GUIDELINES

SETTLING REVIEW CHECKLIST

Limestone County Water & Sewer Authority

SOUTHWEST METROPOLITAN WATER AND SANITATION DISTRICT. Fats, Oils, and Grease (FOG) Policy. (adopted September 17, 2010)

DRIP EMITTER SYSTEM STUDY GUIDE

GENERAL FATS, OILS, & GREASE (FOG) PERMIT

City of Logan Sanitary Sewer Design Standards

Section FATS, OILS and GREASES CONTROL ORDINANCE A. Scope and purpose B. Definitions

SOUTHERN NEVADA AMENDMENTS TO THE 2012 UNIFORM MECHANICAL CODE

SECTION 2 - DESIGN STANDARDS FOR GRAVITY SANITARY SEWERS

READ ONLY. Adopting Agency BSC SFM. Adopt Entire Chapter Adopt Entire Chapter as amended (amended sections listed below)

Information and Instructions for Obtaining a. Fats, Oils, and Grease Wastewater Discharge Permit

Wastewater Collection. (Sewer Alternatives)

EXHIBIT 2:Optional Online Installation Re-entrainment/scour testing of the Terre Kleen18 Hydrodynamic Separator Stormwater Treatment unit per NJDEP

Fats, Oils and Grease (FOG) Program

INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS IAPMO GUIDE CRITERIA FOR

Industrial Pretreatment Program Grease Abatement Requirements for Food Service Establishments (FSEs)

Read Only Copy Not For Distribution. Chapter 17. Private Potable Water Supply Systems 17.1 GENERAL REGULATIONS 17.2 QUANTITY OF WATER REQUIRED

CONTROL OF FATS, OILS AND GREASE

Core Elements: Fats, Oils, and Grease (FOG) Ordinance No. OCSD-25

Grease Interceptors CEU 245. Continuing Education from the American Society of Plumbing Engineers. March ASPE.

1 Construction The sewage treatment plant (STP) is to be an Icon-Septech Pty Ltd Turbojet 4000 as described below and as shown on the drawings.

1 Construction The sewage treatment plant (STP) is to be an Icon-Septech Pty Ltd Turbojet 5000 as described below and as shown on the drawings.

1. Overview 2 2. Definitions 2 3. Laboratory Testing Criteria 2. A. Laboratory Qualifications 2. B. Analysis of TSS Samples 2. C.

OIL/WATER SEPARATORS & GREASE INTERCEPTORS. Requirements for Oil/Water Separators and Grease Interceptors discharging into Kitsap County Sewer mains

TYPES OF SEWAGE PUMPS. Solids Handling Pumps: Grinder Pumps: Effluent Pumps:

1 Construction The sewage treatment plant (STP) is to be an Icon-Septech Pty Ltd Turbojet 2000 as described below and as shown on the drawings.

Level III Chapter 1 Worksheet

Lifetime Guaranteed Construction with unique built-in installation and maintenance features

TechNews. Part 2: Creative Solutions to Secondary Containment at Electrical Substations December 2018

PORT OF SAN FRANCISCO PLUMBING CODE. Based on the 2016 California Plumbing Code

READ ONLY. Adopting Agency BSC SFM. Adopt Entire Chapter X X X Adopt Entire Chapter as amended (amended sections listed below) X X X X X X

DOWNSTREAM DEFENDER TESTING USING MAINE DEPARTMENT OF ENVIRONMENTAL PROTECTION PROTOCOL UTILIZING OK-110 FEED SAND

SECTION WASTEWATER FORCE MAINS

INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS IAPMO GUIDE CRITERIA FOR

Grease Management. EnduraGreaseManagement.com. Rethinking Grease Interception

ACTIVITY: Dewatering Operations AM 12

NORTH CAROLINA DEPARTMENT OF ENVIRONMENT, HEALTH AND NATURAL RESOURCES DIVISION OF ENVIRONMENTAL HEALTH ON-SITE WASTEWATER SECTION

COMPLIANCE DEPARTMENT

Tank Functions. Solids removal by settling & floatation. Anaerobic digestion Storage of solids % solids removal

SEWER SYSTEM DESIGN GUIDELINES

Recommended Amendments to the 2015 International Plumbing Code North Central Texas Council of Governments Region

SUPPLEMENT EXISTING SEPTIC SYSTEM INSPECTION REPORT WHO IS QUALIFIED TO PERFORM AN INSPECTION?

SECTION WASTEWATER FORCE MAINS

Figure 1. Report of Inspection Process Flowchart.

ATTACHMENT 1 GENERAL FACILITY INFORMATION. BOD5 mg/l mg/l TSS mg/l mg/l NH3-N mg/l mg/l

Amendments to the 2012 International Plumbing Code

REQUEST FOR DEVIATION WATER AND WASTEWATER SYSTEM STANDARD SPECIFICATIONS

Report. Inflow Design Flood Control System Plan St. Clair Power Plant St. Clair, Michigan. DTE Energy Company One Energy Plaza, Detroit, MI

STORM DRAINAGE CHAPTER 11

WASTEWATER & STORM WATER COLLECTION AND REMOVAL

ORDINANCE NO

STORM DRAINAGE CHAPTER 11

Grease Interceptors CEU 266. Continuing Education from the American Society of Plumbing Engineers. December ASPE.

ORDINANCE NUMBER

14. SCREENS. in the Figure 8.1. BARS TROUGH

Sand Interceptor Sector Control Policy For Automotive Shops, Car Washes, & Facilities with Significant Potential for Sand or Inert Debris Discharge

Addendum to the Hydro International s Downstream Defender Conditional Interim Certification

AD NO. TECOM PROJECT NO. 9-CO REPORT NO. ATC-8115 AEC SFIM-AEC-ER-CR FINAL REPORT OF THE COALESCING TUBES TEST

Grease Interceptors. Design & Operation. Material & Characteristics

ON-SITE SEWAGE CONTRACTOR EXAMINATION STUDY GUIDE

Attachment N o F Control & Monitoring

Common Septic System Installation Mistakes

A SIMPLE SOLUTION TO BIG SNAIL PROBLEMS - A CASE STUDY AT VSFCD S RYDER STREET WASTEWATER TREATMENT PLANT

CHAPTER IX RULES AND REGULATIONS FOR GRINDER PUMPS. A. "Department" means Concord Township Sewer Department.

Ohio Administrative Code Tanks, pumps and controls, and building sewers

PERC-RITE DRIP DISPERSAL DESIGN SUBMITTAL American Manufacturing Company, Inc

City of Malibu Stuart Ranch Road Malibu, California Phone (310) Fax (310)

Operation and Maintenance Manual

GREASE MANAGEMENT PROGRAM

Manual - Part 2 - Materials

Enviro Voraxial Technology

On-Site Sanitation (Containment) System. Bhitush Luthra ( Centre for Science and Environment, New Delhi

DIVISION 33 UTILITIES SECTION PACKAGED SEWAGE GRINDER PUMPING UNITS

Site Plan: General: Common Omissions-Mistakes on Plans: Ohio EPA Southeast District Office Logan, Ohio November 22, 2005 Bruce Goff, P.E.

Sanitary Sewer Extensions, Lift Stations, and Force Mains Engineering Report Form. I. General Information. 1. Name of Facility:

Septic Tanks: The Primary Treatment Device of Conventional Septic Systems

Revised 1/20/2014 ARTICLE 9 CONSTRUCTION REQUIREMENTS PART A: GENERAL 9A-1 SERVICE LINES:

PACKAGE TERTIARY FILTER SYSTEM SPECIFICATIONS MODELS TF-2-39-C THROUGH TF-2-53-C

A NEW METHOD FOR EVALUATING PRIMARY CLARIFIERS Alex Ekster and Cristina Pena San Jose/Santa Clara Water Pollution Control Plant City of San Jose

SECTION PACKAGED, SUBMERSIBLE SEWERAGE PUMP UNITS

Report. Inflow Design Flood Control System Plan Belle River Power Plant East China, Michigan. DTE Energy Company One Energy Plaza, Detroit, MI

Chapter 5 Water, Plumbing, and Waste

Table of Contents Rules Concerning Uniform Plumbing Code

1 [Establishment of Regulatory Controls for the Discharge of Fats, Oils and Grease Into Sewers]

Features & Design. Standard Inlet shown with option of 0-90 Adjustable inlet. Lighter FOG s. Designed Flow Path. Food Solids. Lighter Oils & Grease

City of Malibu Stuart Ranch Road Malibu, California Phone (310) Fax (310)

Transcription:

INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS IAPMO GUIDE CRITERIA FOR WASTEWATER INTERCEPTOR SYSTEM (WIS) FOR AN INTERACTIVE MECHANICAL WASTEWATER INTERCEPTOR IGC 245-2007a 1. PURPOSE 1.1 The purpose of this standard is to establish a generally acceptable standard for a mechanical Wastewater Interceptor System (WIS). Its purpose is to serve as a guide for producers, distributors, architects, engineers, contractors, installers, inspectors and users to promote understanding regarding the design intention, mechanical functions, controls and installation. 1.2 The provisions of this standard are not intended to prevent the use of any alternate system or method of grease removal and settled solids management control provided any such alternate meets the intent and requirements and changes are amended to this standard. 2. SCOPE 2.1 This standard covers general requirements, testing requirements, installation instructions, and markings and identification. 2.2 The test procedures and performance requirements in this standard are prescribed to verify the proper performance of the WIS as a pretreatment system that satisfies applicable federal, state and municipal wastewater for acceptable levels of FOG, TSS, ph and discharge velocity into a public or private sewage infrastructure. It also establishes a new operating parameter value for H 2 S. 2.3 A WIS is intended for retrofit into the main building sewer that connects to the POTW sewer lateral and in a manner that avoids building operational disruption. Although WIS units are intended for existing or retrofit construction only they may also be considered for new installation where controlled solids removal is warranted to avoid overburdening a grease interceptor so as to minimize H 2 S gases and to keep ph as close to neutral as possible. 3. REFERENCED STANDARDS 3.1 All standards referenced herein shall be the current edition of that standard as published IGC 245-2007a WIS page 1 of 9

CSA C22.2 No.108 EPA Method 1664 IAPMO/ANSI Z1001 MCAW 150.1 NEMA 250 SM 2540D SM 4500-H + Third Edition UL 778 UPC Liquid Pumps N-Hexane Extractable Material (HEM) and Silica Gel Treated N-Hexane Extractable Material (SGT-HEM) by Extraction and Gravimetry (Oil and Grease and Total Petroleum Hydrocarbons) Prefabricated Grease Interceptors Enclosures for Electrical Equipment (1000 Volts Maximum) Total Suspended Solids Dried at 103-105 C ph Value Wastewater Engineering, Treatment, Disposal and Reuse, Metcalf and Eddy, Inc., McGraw-Hill, Inc Motor-Operated Water Pumps Uniform Plumbing Code 4. DEFINITIONS 4.1 FOG. Nonpetroleum fats, oils and grease. 4.2 Grinder Pump. A non-clogging, submersible type, commercial grade grinder pump designed to accept an inlet mixture of solids and liquids sewage effluent. 4.3 POTW. Publicly owned treatment works. 4.4 Sewage Pump. A non-clogging, submersible type, commercial grade, pump designed to accept sewage effluent in the secondary chamber for spraying waste water back over the primary chamber. 4.5 TSS. Total suspended solids. 4.6 Wastewater. Special Waste as defined in 221.0 of the Uniform Plumbing Code (UPC), Waste as defined in UPC 225, Sewage as defined in UPC 221, or any combination of the foregoing. 4.7 Wastewater Interceptor System. WIS is an interactive wastewater interception system for separating waste materials collected from wastewater (e.g., waste and/or sewage from toilets, urinals and kitchen plumbing fixtures and drains), including FOG and solids, in a common line in a controlled manner. The WIS shall be designed to remove FOG and control solids from multiple waste streams of combined wastewater from both the kitchen waste stream containing FOG and the human sewage waste stream simultaneously. 5.1 Wastewater Interceptor System. 5. GENERAL REQUIREMENTS 5.1.1 Material. The WIS tank shall comply with the material requirements for grease interceptors specified in IAPMO/ANSI Z1001. IGC 245-2007a WIS page 2 of 9

5.1.2 Sizing. The WIS tank size shall be design in the accordance with the following: V (min) = F x R x S Where: V (min) = Minimum WIS Operating Volume in gallons Flow Rate (F) (maximum) = in gallons per minute (gpm) Retention Time = 30 minutes Storage Factor = 25 percent Thus: V (min) = F x 30 x 1.25 Note: The volume of the WIS shall take into consideration the slopped floor, grinder pumps in the primary chamber and sewage pumps in the secondary chamber and the volume of the common dividing wall. 5.1.3 FLOW RATE (F). The flow rate shall be determined based on the total flow rate from all equipment and plumbing fixtures connected to the WIS using one of the following equations: 1) Drainage Fixture Units (DFU) total of less than or equal to 40: F = (0.7 x DFU) 2) 1 SMALL SIZE WIS with DFU total greater than 40 and up to 750: F = (0.2* x DFU) + 20 Where: DFU = Drainage Fixture Unit Values, as established by UPC 702.0. 3) 2 MEDIUM SIZE WIS with DFU over 750 and up to 5000: 4) 3 LARGE SIZE WIS with DFU over 5000: Note: F = Peak Flow Rate (gpm) 5.1.4 RETENTION TIME (R). The minimum retention time of 30 minutes is based on Wastewater Engineering, Treatment, Disposal and Reuse requirements under pg.1028. 5.1.5 STORAGE FACTOR. A minimum of 25% storage capacity is required for floatable fats, oil and grease and settled solids. 5.1.6 Compartment Design. The WIS shall have two compartments, referred to as the primary compartment and secondary compartment. The primary compartment shall be the inlet compartment and comprise not less than two-thirds (2/3) of the total required capacity of the WIS and in all cases shall be longer than the maximum inside width of the primary compartment. The secondary compartment shall be the outlet compartment and comprise not less than one-thirds (1/3) of the total required capacity of the WIS and IGC 245-2007a WIS page 3 of 9

in all cases shall be longer than the maximum inside width of the secondary compartment. The primary chamber shall have a sloped floor at ¼ per foot and with transitional slopes directed towards the two grinder pumps installed on a level surface prior to the baffle or dividing wall of the two chambers. The walls surrounding the grinder pumps shall have rounded corners to avoid solids deposit. In lieu of a one tank system, the primary chamber/compartment can be a separate tank from the secondary chamber/compartment provided that the 2/3 and 1/3 required proportion of volume, respectively, is maintained. An air venting system shall be provided equal to the cross-sectional area of the primary chamber liquid discharge (crossover pipe) to the secondary chamber in order to equalize the cavity air pressure. 5.1.7 WIS Effluent Discharge Sample Port or Box. A sample port or box with a minimum 12 inch diameter and a maximum 24 cover shall be provided on the effluent discharge side of the tank vessel to gather wastewater samples for testing of F.O.G. and TSS. It shall be installed after the solids discharge line coming from the grinder pumps but before the POTW connection. 5.2 Submersible Pumps. The grinder pumps in the primary compartment and the sewage pump in the secondary compartment shall comply with UL 778 and CSA C22.2 No. 108. 5.2.1 The primary compartment shall have at least two grinder pumps for removing the settled solids. The secondary compartment shall have at least two sewage pumps to spray over the solidifying FOG floating in the primary chamber. 5.2.2 Pump Discharge. The grinder pumps discharge flow rate at the WIS Effluent Discharge Sample Port or Box shall be controlled so as not to: a) Exceed the flow rates shown in Table 1, and b) Exceed the TSS limit specified in Section 6.2.2 Table 1 Pipe Size (inch) MaximumFlow (gpm) 3 110 4 260 6 700 8 1300 10 2600 12 3000 5.3 Pump Controls. The operations of the grinder and sewage spray pumps shall be automatically controlled. The controls shall be capable of being programmed (and reprogrammed, as appropriate) to cycle the operations of the pumps at preset intervals and to shut off and reset the operation of the pumps upon any high or low water event or in the case of blockage downstream causing a backup of wastewater into the WIS. IGC 245-2007a WIS page 4 of 9

5.3.1 Control Panel Enclosure. The control panel enclosure shall comply with NEMA Standard 250, Type 3R. If the panel will be exposed to gases from the wastewater, a Type 4X or 12 shall be used. 5.3.2 Each WIS control panel shall be properly mounted to a structurally sound wall and housed within a weatherproof structure and protected from vehicular traffic and vandalism. 5.4 Solids Removal. The WIS shall remove the solids that accumulate at the bottom of the primary chamber automatically and in a controlled manner by means of controls of the grinder pumps and discharge to the passive flow effluent discharge pipe of the second chamber in accordance with Section 6.3 of this standard. 5.5 Shutdown. The WIS shall be equipped with a means to shutdown the operations of the pumps and allow the wastewater to flow by means of gravity through the system in the same manner as a passive flow grease interceptor in the event of a high or low water level within the system. The WIS shall also have means to reset and operate at normal or preset conditions once the normal levels of water are achieved. 5.6 Sprayers. The WIS shall be equipped with an overhead sprayer system in the primary chamber made of non-corrosive materials to spray water from the second chamber over the surface materials floating in the primary chamber. 6. TESTING REQUIREMENTS 6.1 Hourly Average Velocity Pressure (VP) Testing Protocol is as follows: Measure the effluent discharge flow rate and velocity during the grinder pump s operation and off cycles at intervals of five minutes or at least five times each during the pump s on and off cycle for a 1 hour period. Calculate the hourly average flow rate Hourly average velocity at the pipe discharge (from the grinder pump) connection point downstream of the WIS and measured at the WIS Effluent Discharge Sample Port or Box shall not exceed the values shown in Table 2 for each given pipe size. Table 2 Pipe Diameter Minimum 1% Slope Velocity Maximum 2% Slope Velocity Inch nominal feet per second feet per second 4 4.5 5.0 6 5.3 6.0 8 6.1 6.8 10 6.4 7.2 12 7.2 8.1 16 7.6 8.7 18 8.0 9.2 21 9.3 10.7 24 9.6 11.1 IGC 245-2007a WIS page 5 of 9

Note: The following measurement equipment may be used to measure the discharge flow rate from the WIS. A rectangular weir with an open channel flow analyzer, Ultrasonic flow sensor, and sensor mounting hardware. Weir set-up reference was taken from: Kent s Mechanical Engineers Handbook, 12 th Edition, Power, Section 5, Hydrodynamics, Hydraulics, and Pumps. (A Davis model GL 341 channel flow analyzer, model GL 310 ultrasonic flow sensor and model GL 3417 mounting hardware has been found to perform satisfactorily in this application.) 6.2 WIS Effluent Discharge Sampling. Sampling shall be performed by an Industrial Hygiene accredited testing laboratory. Sample specimen gathering shall occur in noncontrolled and real-time operating conditions during (i) a tank occupancy of over 20% of FOG and settled solids (or stressed condition ), and (ii) peak loading, at 5 minute intervals over a one hour period (the monitoring frequency may be less than five minute intervals if the WIS grinding cycle is less than five minutes in duration). Sampling periodicity should be timed to coincide with the WIS discharge cycle to ensure timeweighted averaging of the discharge flow. Take samples from the discharge sample port. Measure the FOG and TSS of each sample. 6.2.1 Sampling Analysis Methods and Procedures. All testing procedures shall be in accordance with the following methods or other officially accepted authority or standards. SAMPLE SPECIMEN TESTING STANDARD METHOD Fats, Oil & Grease (FOG) EPA 4 1664 Total Suspended Solids (TSS) SM 5 2540 D ph SM 5 4500-H + 6.2.2 Performance Requirements. Average FOG, TSS and H 2 S and ph values shall not exceed the limits established by applicable federal, state or municipal authorities or, in the absence of any applicable limits, the following: IGC 245-2007a WIS page 6 of 9 Analyte Limits FOG* 100 mg/l TSS Authority Surcharge Level** H 2 S 10 ppm ph*** 6 to 11 * FOG = Total Oil & Grease - Total Petroleum Hydrocarbons ** That limit above which the applicable authority will assess surcharges. *** ph values shall not be an average, but rather each sample shall not be outside the indicated range. 6.3 Discharge Velocity and Solids Removal Test. Install a WIS in accordance with the manufacturer s installation instructions. For purposes of this test, the WIS may be installed above or below ground. The test setup shall be capable of supplying wastewater to the unit at a controlled rate up to at least 10% in excess of the manufacturer s maximum allowable input flow rate. The inlet pipe shall extend straight,

with no couplings or fittings, a distance of 20 inside diameters before entering the WIS. Slope the inlet pipe toward the WIS at 1/4 inch per foot. Set up a manometer or other measuring device to measure the inlet line head in inches of water column as shown in Figure 1. A clear section of glass or plastic pipe may be used in place of a manometer. Conduct the following tests with the flowing, inlet head equal to one half the inside pipe diameter measured from the inside bottom pipe wall. This is equivalent to the inlet pipe being one-half filled with liquid at all times. The tolerance throughout the test shall be kept within 1/4 inch (± 1/4 inch). Establish a constant flow condition through the WIS using the inlet head specified above. Measure the average flow rate over a five minute period. This shall be noted as the normal gravity flow. With the inlet water flow rate set to normal gravity flow, operate the pumps through three normal pump cycles. Measure the maximum discharge flow rate from the WIS during the three cycles. Maintain the inlet line head at the level needed to achieve normal gravity flow. 6.3.1 Performance Parameter Requirement. a) The effluent discharge flow rate downstream of the pressure relief line of the grinder pump shall not exceed the flow rate produced by normal gravity flow plus the grinder pump intermittent discharge output; b) The effluent discharge velocity shall not exceed the velocity provided for in Section 6.1; and c) The WIS solids discharge rate shall not exceed the TSS limit specified in Section 6.2.2 clear tubing with graduations pipe wall IGC 245-2007a WIS page 7 of 9

Figure 1 7. INSTALLATION INSTRUCTIONS 7.1 The WIS installation instructions shall contain the following: 7.1.1 WIS Tank sizing and design shall be in accordance with manufacturer s specifications and Section 5 of IAPMO IGC XXX. 7.1.2 Each WIS control panel shall be properly mounted to a structurally sound wall and housed within a weatherproof structure and protected from vehicular traffic and vandalism. 8. MARKINGS & IDENTIFICATION 8.1 Each WIS tank shall be permanently and legibly marked with the following: a) Manufacturer s name or trademark; b) Nominal tank size or capacity; and 8.1.1 Each 24 diameter manhole cover shall be stamped Wastewater Interceptor to identify the WSIS tank. 8.2 The control panel enclosure shall be permanently and legibly marked with the following: a) Manufacturer s name or trademark; and b) NEMA (National Electrical Manufacturers Association) enclosure classification Adopted: 7/2007 1 2 Reference for 1 and 2 City and County of Honolulu, Rules Relating to Grease Interceptor Program Compliance, Adopted March 5, 2002 Used ASPE Certified in Plumbing Engineering Examination Review Manual, 2000, Table 7-6, Conversion of Fixtures Units to Equivalent GPM or Engineered Plumbing Design by Alfred Steele, 1982, Table 13-4, Page 137. 3 Use ASPE Adopted Advanced Plumbing Technology by Alfred Steele. P.E., Chapter 12, Preliminary Design and Outline Specification, Estimated Water Requirements. IGC 245-2007a WIS page 8 of 9

4 5 EPA US Environmental Protection Agency SM Standard Methods for the Examination of Water and Wastewater IGC 245-2007a WIS page 9 of 9

INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS IAPMO GUIDE CRITERIA FOR WASTEWATER INTERCEPTOR SYSTEM (WIS) FOR AN INTERACTIVE MECHANICAL WASTEWATER INTERCEPTOR IGC 245-2007a 1. PURPOSE 1.1 The purpose of this standard is to establish a generally acceptable standard for a mechanical Wastewater Interceptor System (WIS). Its purpose is to serve as a guide for producers, distributors, architects, engineers, contractors, installers, inspectors and users to promote understanding regarding the design intention, mechanical functions, controls and installation. 1.2 The provisions of this standard are not intended to prevent the use of any alternate system or method of grease removal and settled solids management control provided any such alternate meets the intent and requirements and changes are amended to this standard. 2. SCOPE 2.1 This standard covers general requirements, testing requirements, installation instructions, and markings and identification. 2.2 A WIS is intended for retrofit into the main building sewer that connects to the POTW sewer lateral and in a manner that avoids building operational disruption. Although WIS units are intended for existing or retrofit construction only they may also be considered for new installation where controlled solids removal is warranted to avoid overburdening a grease interceptor. 3. REFERENCED STANDARDS 3.1 All standards referenced herein shall be the current edition of that standard as published CSA C22.2 No.108 Liquid Pumps IAPMO/ANSI Z1001 Prefabricated Grease Interceptors NEMA 250 Enclosures for Electrical Equipment (1000 Volts Maximum) Third Edition Wastewater Engineering, Treatment, Disposal and Reuse, Metcalf and Eddy, Inc., McGraw-Hill, Inc UL 778 Motor-Operated Water Pumps UPC Uniform Plumbing Code IGC 245-2007a WIS page 1 of 6

4. DEFINITIONS 4.1 FOG. Nonpetroleum fats, oils and grease. 4.2 Grinder Pump. A non-clogging, submersible type, commercial grade grinder pump designed to accept an inlet mixture of solids and liquids sewage effluent. 4.3 POTW. Publicly owned treatment works. 4.4 Sewage Pump. A non-clogging, submersible type, commercial grade, pump designed to accept sewage effluent in the secondary chamber for spraying waste water back over the primary chamber. 4.5 TSS. Total suspended solids. 4.6 Wastewater. Special Waste as defined in 221.0 of the Uniform Plumbing Code (UPC), Waste as defined in UPC 225, Sewage as defined in UPC 221, or any combination of the foregoing. 4.7 Wastewater Interceptor System. WIS is an interactive wastewater interception system for separating waste materials collected from wastewater (e.g., waste and/or sewage from toilets, urinals and kitchen plumbing fixtures and drains), including FOG and solids, in a common line in a controlled manner. The WIS shall be designed to remove FOG and control solids from multiple waste streams of combined wastewater from both the kitchen waste stream containing FOG and the human sewage waste stream simultaneously. 5.1 Wastewater Interceptor System. 5. GENERAL REQUIREMENTS 5.1.1 Material. The WIS tank shall comply with the material requirements for grease interceptors specified in IAPMO/ANSI Z1001. 5.1.2 Sizing. The WIS tank size shall be design in the accordance with the following: V (min) = F x R x S Where: V (min) = Minimum WIS Operating Volume in gallons Flow Rate (F) (maximum) = in gallons per minute (gpm) Retention Time = 30 minutes Storage Factor = 25 percent Thus: V (min) = F x 30 x 1.25 Note: The volume of the WIS shall take into consideration the slopped floor, grinder pumps in the primary chamber and sewage pumps in the secondary chamber and the volume of the common dividing wall. IGC 245-2007a WIS page 2 of 6

5.1.3 FLOW RATE (F). The flow rate shall be determined based on the total flow rate from all equipment and plumbing fixtures connected to the WIS using one of the following equations: 1) Drainage Fixture Units (DFU) total of less than or equal to 40: F = (0.7 x DFU) 2) 1 SMALL SIZE WIS with DFU total greater than 40 and up to 750: F = (0.2* x DFU) + 20 Where: DFU = Drainage Fixture Unit Values, as established by UPC 702.0. 3) 2 MEDIUM SIZE WIS with DFU over 750 and up to 5000: 4) 3 LARGE SIZE WIS with DFU over 5000: Note: F = Peak Flow Rate (gpm) 5.1.4 RETENTION TIME (R). The minimum retention time of 30 minutes is based on Wastewater Engineering, Treatment, Disposal and Reuse requirements under pg.1028. 5.1.5 STORAGE FACTOR. A minimum of 25% storage capacity is required for floatable fats, oil and grease and settled solids. 5.1.6 Compartment Design. The WIS shall have two compartments, referred to as the primary compartment and secondary compartment. The primary compartment shall be the inlet compartment and comprise not less than two-thirds (2/3) of the total required capacity of the WIS and in all cases shall be longer than the maximum inside width of the primary compartment. The secondary compartment shall be the outlet compartment and comprise not less than one-thirds (1/3) of the total required capacity of the WIS and in all cases shall be longer than the maximum inside width of the secondary compartment. The primary chamber shall have a sloped floor at ¼ per foot and transitional slopes directed towards the two grinder pumps installed on a level surface prior to the baffle or dividing wall of the two chambers. The walls surrounding the grinder pumps shall have rounded corners to avoid solids deposit. In lieu of a one tank system, the primary chamber/compartment can be a separate tank from the secondary chamber/compartment provided that the 2/3 and 1/3 required proportion of volume, respectively, is maintained. An air venting system shall be provided equal to the cross-sectional area of the primary chamber liquid discharge (crossover pipe) to the secondary chamber in order to equalize the cavity air pressure. 5.1.7 WIS Effluent Discharge Sample Port or Box. A sample port or box with a minimum 12 inch diameter and a maximum 24 cover shall be provided on the effluent discharge side IGC 245-2007a WIS page 3 of 6

of the tank vessel to gather wastewater samples for testing of F.O.G. and TSS. It shall be installed after the solids discharge line coming from the grinder pumps but before the POTW connection. 5.2 Submersible Pumps. The grinder pumps in the primary compartment and the sewage pump in the secondary compartment shall comply with UL 778 and CSA C22.2 No. 108. 5.2.1 The primary compartment shall have at least two grinder pumps for removing the settled solids. The secondary compartment shall have at least two sewage pumps to spray over the solidifying FOG floating in the primary chamber. 5.2.2 Pump Discharge. The grinder pumps discharge flow rate at the WIS Effluent Discharge Sample Port or Box shall be controlled so as not to: Exceed the flow rates shown in Table 1 Table 1 Pipe Size (inch) MaximumFlow (gpm) 3 110 4 260 6 700 8 1300 10 2600 12 3000 5.3 Pump Controls. The operations of the grinder and sewage spray pumps shall be automatically controlled. The controls shall be capable of being programmed (and reprogrammed, as appropriate) to cycle the operations of the pumps at preset intervals and to shut off and reset the operation of the pumps upon any high or low water event or in the case of blockage downstream causing a backup of wastewater into the WIS. 5.3.1 Control Panel Enclosure. The control panel enclosure shall comply with NEMA Standard 250, Type 3R. If the panel will be exposed to gases from the wastewater, a Type 4X or 12 shall be used. 5.3.2 Each WIS control panel shall be properly mounted to a structurally sound wall and housed within a weatherproof structure and protected from vehicular traffic and vandalism. 5.4 Shutdown. The WIS shall be equipped with a means to shutdown the operations of the pumps and allow the wastewater to flow by means of gravity through the system in the same manner as a passive flow grease interceptor in the event of a high or low water level within the system. The WIS shall also have means to reset and operate at normal or preset conditions once the normal levels of water are achieved. IGC 245-2007a WIS page 4 of 6

5.5 Sprayers. The WIS shall be equipped with an overhead sprayer system in the primary chamber made of non-corrosive materials to spray water from the second chamber over the surface materials floating in the primary chamber. 6. TESTING REQUIREMENTS 6.1 Hourly Average Velocity Pressure (VP) Testing Protocol is as follows: Measure the effluent discharge flow rate and velocity during the grinder pump s operation and off cycles at intervals of five minutes or at least five times each during the pump s on and off cycle for a 1 hour period. Calculate the hourly average flow rate Hourly average velocity at the pipe discharge (from the grinder pump) connection point downstream of the WIS and measured at the WIS Effluent Discharge Sample Port or Box shall not exceed the values shown in Table 2 for each given pipe size. Table 2 Pipe Diameter Minimum 1% Slope Velocity Maximum 2% Slope Velocity Inch nominal feet per second feet per second 4 4.5 5.0 6 5.3 6.0 8 6.1 6.8 10 6.4 7.2 12 7.2 8.1 16 7.6 8.7 18 8.0 9.2 21 9.3 10.7 24 9.6 11.1 Note: The following measurement equipment may be used to measure the discharge flow rate from the WIS. A rectangular weir with an open channel flow analyzer, Ultrasonic flow sensor, and sensor mounting hardware. Weir set-up reference was taken from: Kent s Mechanical Engineers Handbook, 12 th Edition, Power, Section 5, Hydrodynamics, Hydraulics, and Pumps. (A Davis model GL 341 channel flow analyzer, model GL 310 ultrasonic flow sensor and model GL 3417 mounting hardware has been found to perform satisfactorily in this application.) 7. INSTALLATION INSTRUCTIONS 7.1 The WIS installation instructions shall contain the following: 7.1.1 WIS Tank sizing and design shall be in accordance with manufacturer s specifications and Section 5 of this standard. IGC 245-2007a WIS page 5 of 6

7.1.2 Each WIS control panel shall be properly mounted to a structurally sound wall and housed within a weatherproof structure and protected from vehicular traffic and vandalism. 8. MARKINGS & IDENTIFICATION 8.1 Each WIS tank shall be permanently and legibly marked with the following: a) Manufacturer s name or trademark; b) Nominal tank size or capacity; and 8.1.1 Each 24 diameter manhole cover shall be stamped Wastewater Interceptor to identify the WIS tank. 8.2 The control panel enclosure shall be permanently and legibly marked with the following: a) Manufacturer s name or trademark; and b) NEMA (National Electrical Manufacturers Association) enclosure classification Adopted: 7/2007 Revised: 9/2007 1 2 3 Reference for 1 and 2 City and County of Honolulu, Rules Relating to Grease Interceptor Program Compliance, Adopted March 5, 2002 Used ASPE Certified in Plumbing Engineering Examination Review Manual, 2000, Table 7-6, Conversion of Fixtures Units to Equivalent GPM or Engineered Plumbing Design by Alfred Steele, 1982, Table 13-4, Page 137. Use ASPE Adopted Advanced Plumbing Technology by Alfred Steele. P.E., Chapter 12, Preliminary Design and Outline Specification, Estimated Water Requirements. IGC 245-2007a WIS page 6 of 6