Porcelain versus Polymer Insulator- A Changing Era in Transmission Lines

Similar documents
Composite Insulator Components

Vijendra Singh Parihar 1, Prof. Anil Kumar Kori 2 1

Performance Analysis of 33 kv Polymer and Porcelain Insulators under Various Pollution Conditions at Costal Regions

HIGH VOLTAGE INSULATORS. By JP Holtzhausen. Glass. Bushings & hollow core insulators. Cap & pin insulators

Potential and E-Field Calculation Along an Ice- Covered Composite Insulator with Finite Element Method

Comparison of effects of Various Contaminations on SiR insulators

Reprinted from the Proceedings of the 2001 IEEE/PES Transmission and Distribution Conference and Exposition, Atlanta, Georgia.

Effect of UV-Rays and Salt Contamination on 33kV Silicon Composite Insulators

Polluted Outdoor Insulators Maintenance and Washing

INSULATOR REQUERIMENTS:

Cigré WG C Topics: The selection of insulators with respect to polluted conditions

Effect of Metal Ring on the Field Distribution of Outdoor Polymeric Insulator

Pins Insulator. Composite/Polymers Insulators

Predicting Contamination Flashover of Insulators: Successes and Shortcomings of Tests and Simulations

ESDD MEASUREMENTS IN THE POWER SYSTEM OF CRETE

PERFORMANCE ANALYSIS OF OVERHEAD PORCELAIN INSULATOR UNDER DIFFERENT CONTAMINATIONS

Evaluation of Silicone Rubber Insulators used in High-Voltage Transmission Lines Anwar Ul-Hamid, Khaled Y. Soufi, and Ibrahim AI-Hamoudi

Development of Composite Line Spacers for Distribution Lines

A Study of Critical Positive Impulse Flashover of 24 kv Contaminated Insulators

CHAPTER 6 HIGH VOLTAGE ELECTRICAL TESTING RESULTS

Study on Pollution Flashover Performance of Short Samples of Composite Insulators Intended for ±800 kv UHV DC

Mitigating Contamination Related Issues on T&D Equipment. Lily Hoyer Simon Chan

6C-001 High-Voltage Pin-Type Insulator

ILMOS Insulator Leakage Current Monitor

Risk assessment of pollution on a 66kV composite insulator using ANSYS

fire Charcoat Charcoat IC Passive Protection

Data Sheet 110kV TD123II dry type outdoor termination

Journal of Operation and Automation in Power Engineering. Vol. 1, No. 2, Summer & Fall 2013, Pages:

Performance investigation of composite and RTV SIR coated insulators at a coastal test station

EXPERIMENTAL INVESTIGATION OF EFFECT OF UV RADIATION ON FLASHOVER VOLTAGE OF POLYMERIC INSULATORS WITH AND WITHOUT CONTAMINATION

Outdoor High Voltage Non-Ceramic Insulators

A-PDF PPT TO PDF DEMO: Purchase from to remove the watermark

DL/T Translated English of Chinese Standard: DL/T

Study on the dc flashover performance of standard suspension insulator with ringshaped non-uniform pollution

INSULATION, ASSET AND WILDLIFE PROTECTION Steve Parker, Business Development

CONDITION MONITORING OF INSULATORS UNDER POLLUTION ABSTRACT

Selection between indoor or outdoor DC yards D. WU*, U. ÅSTRÖM, L. ARÉVALO, R. MONTAÑO, B. JACOBSON ABB HVDC SWEDEN

Panagiotis Charalampidis

NEW MATERIAL TECHNOLOGY AND PROTECTION DEVICE USED IN 33/11 KV DISTRIBUTION LINE

The Effect of Severity and Location of Pollution on Leakage Current Characteristics of Porcelain Insulators under Different Humidity Condition

General Requirements. Technical Specifications for Insulators of Transmission Lines

General Technical Specification and Execution Procedures for Transmission and Subtransmission Networks Substation Insulators (63 kv- 400 kv)

GROUP A. Polymeric Insulators.

INVESTIGATION OF THE AGING CHARACTERISTICS OF CST TERMINATION MADE OF SILICONE RUBBER AT CONTAMINATION AREA

International Journal of Mechatronics, Electrical and Computer Technology

Data Sheet 110kV TP123-II Porcelain Insulator Outdoor Termination

Research methodology for the life evaluation of Hollow polymer insulators for High Voltage Applications

PI Electrical Equipment - tourse PI 30.2 INSULATION. On completion of this module the student will be able to:

Investigation of leakage current flow through wooden poles structures on overhead distribution system

COASTAL INDIA. Supply & Application of: Epsilon Midsun 570 Gen-4 RTV HVIC (High Voltage Insulator Coating) and

High Quality Porcelain Insulators for Transmission Lines

Midsun HVIC silicone is not affected by UV light, temperature, corrosive environments, or ATH pitting from dry band arcing.

Midsun HVIC silicone is not affected by UV light, temperature, corrosive environments, or ATH pitting from dry band arcing.

Electrical Field Simulation for Different Cases of Polymer Insulators Using FEM

Artificial Accelerated Ageing Test of Silicone Rubber Housing Material for Lightning Arrester

Study on AC Flashover Performance for Different Types of Porcelain and Glass Insulators With Non-Uniform Pollution

ESDD PREDICTION OF OUTDOOR POLYMER INSULATORS. Abdelrahman Khaled

Sediver toughened glass insulators for HVAC applications. Experts & Pioneers USA

Comments on Document from Richard Martin, Canada

COMPARISON OF THE SPECIFIC SURFACE CONDUCTIVITY AND ESDD APPROACHES TO ASSESSMENT OF SALT DEPOSITS ON NATURALLY POLLUTED INSULATORS. 1.

Polymer Insulators and Coatings in the Cretan Power System. The Transmission Line Case

094: 2000 CEB STANDARD. MEDIUM VOLTAGE PIN INSULATORS & HARDWARE (12kV & 36 kv) CEYLON ELECTRICITY BOARD SRI LANKA

Porcelain Insulator Performance under Different Condition of Installation around Aligarh

Pollution Performance of HVDC SiR Insulators at Extra Heavy Pollution Conditions

Energy Division Insulators

Composite Outdoor High Voltage Insulators in Crete - 37 Years of Experience

Diagnostic Techniques of Composite Insulators

SPECIFICATION FOR DISC INSULATORS (Standard Type)

LIGHTNING IMPULE PERFORMANCE OF POLLUTED MEDIUM VOLTAGE INSULATORS

Application Note. Capacitor Selection for Switch Mode Power Supply Applications

Comparative study on field collected samples of aged silicon rubber composite coatings for high voltage insulators

TEMPERED GLASS INSULATORS

INCLINED PLANE TESTS OF COMPOSITE, SILICONE RUBBER AND COMPOSITE SILICONE RUBBER COATED MATERIALS

POLLUTION PERFORMANCE OF SILICONE AND EPDM INSULATOR PROFILES

Transmission Silicone Insulators Line Post 69 kv to 230 kv

Different Characteristics of Artificially Polluted High Voltage Composite Insulators

ECONOMIC ANALYSIS OF 400 KV TRANSMISSION TOWERS WITH CROSS ARMS INSULATORS

Experimental analysis of hydrophobic characteristics of Silicone rubber (SiR) insulators under different climatic conditions

COMPARATIVE LABORATORY PERFORMANCE CHARACTERISATION OF SILICONE RUBBER TEXTURED INSULATORS

Si-COAT 570 RTV Silicone HVIC. Reliability & Beyond. Seminar Presentation

Electric field analysis of 132kV EPDM insulator and correlation with ageing features

Safety Considerations When Using Optocouplers and Alternative Isolators for Providing Protection Against Electrical Hazards

A Proper Design of Wind Turbine Grounding Systems under Lightning

Critical design, testing and manufacturing features for the selection of high quality composite insulators for transmission overhead lines

CO 2 Cleaning and Its Effectiveness in Cleaning Energized Medium-Voltage Equipment

DISTRIBUTION SILICONE INSULATORS Deadend / Suspension 15 kv to 69 kv

Polymer and FRP Technology - An Alternative to Conventional Porcelain for Future Power Sector

Volcanic Ash Contamination of High Voltage Insulators

Characterisation of Textured Insulators for Overhead Lines and Substations

EPSILON EM-SILPROCOAT RTV ANTI-CORROSION RUBBER COATING TECHNICAL DATASHEET & SPECIFICATIONS

Failure of a suspension or tension insulator

Offshore Wind Turbines Power Electronics Design and Reliability Research

A Discussion of Porcelain-Insulator Cutouts

EELE408 Photovoltaics Lecture 18 Photovoltaic Arrays & Modules

093 : 2000 CEB STANDARD MEDIUM VOLTAGE PIN POST INSULATORS AND HARDWARE CEYLON ELECTRICITY BOARD SRI LANKA

What to Look for in a Good Quality Arrester

Silicone rubber Product information

INSULATORS NEW. See page J-4 for more information.

Innovative New Live Line Tool and Framing Designs Facilitating Safe and Efficient Cross-arm Replacement

DESIGN TEST REPORT. GAMMA Insulators 6184R-70 ANSI Class 55-3 Pin Type Insulator..

Transcription:

Porcelain versus Polymer Insulator- A Changing Era in Transmission Lines K. R. Suri a, A. Gupta b, Y. Anand b, S. Anand b General Manager (Retd.), Power Grid Corporation of India Limited School of Energy Management, Shri Mata Vaishno Devi University, Katra, India Article Info Article history: Received 15 April 2015 Received in revised form 30 April 2015 Accepted 20 May 2015 Available online 15 June 2015 Keywords Porcelain, Transmission Lines, Transient faults, Environmental challenges 1. Introduction India is one among the top 10 most polluted countries in the world. The urbanization and industrialization are the major sources to an increased pollution level in the country. The thick approach to capitalism has failed to put a check on the pollution. Environmental monitoring regulations and protections acts are also not matching with pace of development. A substantial increase in the industrial sector has also evolved to be as a host to modern technologies giving birth to newer chemicals, emissions etc. The graphical representation of the pollution level in India is given below in Fig.1 [1]. Many authors have carried out the work on the different aspects of the insulators on the transmission lines to evaluate the better performance options. A study was conducted on the on the combination of critical flashover (CFO) voltages of the fibreglass distribution and with polymer and porcelain insulators and the results obtained indicated that added CFO voltage by fibreglass pole is highest at dry condition with negative polarity lightning impulse, and has the lowest value at wet condition with positive polarity lightning impulse [2]. Again a study of the electric field distribution along creepage path of a cap and pin porcelain insulator string of transmission line have been carried out using Finite element method (FEM). The electric field behaviors of insulator using in polluted areas were analyzed considering the pollution layer conductivity and dry band width parameters [3]. A study examining the flow of leakage current on Corresponding Author, E-mail address: anandsanjeev12@gmail.com All rights reserved: http://www.ijari.org Abstract For the past few years with an increase in the globalization, the environmental challenges and an increase in pollution levels have become a global phenomenon as well as matter of discussion. The power transmission lines passing through transverse areas within the country as well as worldwide are facing various problems related to environment and pollution. Such an exponential increase in the pollution levels lead to frequent faults in transmission lines which finally lands to permanent breakdown of transmission lines. These breakdowns sometimes may leads to collapse of grid and are also inconvenient to everyone besides interrupting the growth of nation as well as society breakdown. Over the years engineers and scientists have made efforts to meet such threats and to overcome situations rising form the failure of transmission lines the environmental challenges and an increase in pollution levels. The scientific community proposes a solution to resolve transmission failure by adopting polymer insulators instead of conventional porcelain insulators because the demand is on increase by virtue of its proven inactive use. In this article, an effort has been made to understand difference between the two and agency would decide the type of insulators to be deployed for ensuring long life of transmission line with respect to rate of rise of pollution in country. sand-polluted composite insulators has been carried out which subsequently shortens the insulator life or lead to flashover thus interrupting the power supply. The study also derives the probabilistic features of the insulator s leakage current, which in turn enables a risk assessment of insulator failure [4]. Fig: 1. Trend of pollution level in India [1] A study on the electrical reliability of DC line ceramic or composite insulators which can lead to their failure have been carried out and the results obtained showed that the environment of dc lines is more damaging to insulation than that of comparable ac lines. The result obtained also revealed that thermal breakdown and ionic migration is the reason for breakdown of ceramic insulators [5]. The effects of pollution and high altitude on the flashover performance of short samples of five kinds of UHV/EHV dc composite long rod insulators were analyzed and the results obtained indicate that influence of salt deposit density on the flashover voltage is related with the profile and the material of the insulator. The values of exponent so obtained are smaller than those of porcelain or 502

glass cap-and-pin insulators, clearly indicating that the composite insulators have certain advantages in severe pollution regions [6]. A finite element technique was employed to investigate the insulator surface electric field under dry sand-pollution conditions with different sand grain sizes for an ABB designed composite insulator. The technique was used to simulate the insulator and seek electric field distribution on the polluted insulator model as well as around it and clearly justify the use of such insulators in these critical areas [7]. Pollution problem in transmission system starts when pollutants existing in air settle on the surface of insulator subsequently degrading the electrical properties of insulators. Different agencies like CPRI/CEA & world level affected utilities have conducted studies on pollution levels from time to time [8]. Pollution on insulators appears in following ways; a) Bird dropping b) Brick kilns c) Thermal plants d) Industry discharge chemicals/fly ash e) Agricultural ash/ burning, wild fire etc. f) Mineral handling process g) Salt due to coastal areas h) Cement industry, oil refineries etc i) Commercial and domestic vehicles (railway yards, highway crossings etc.) The pictorial representation of the pollution deposit can be seen in Fig.2 (a) & (b) as given under- Fig: 2(a). Source of Pollution on Insulators from Power Plants Fig: 2(b). Source of Pollution on Insulators from brick kilns The level of deposit on insulators mostly depends upon wind speed and direction. It also depends upon the area /locality from source of pollution. Clouds & fog during winters acts as a catalyst to create flashovers. 2. Measurement of deposition on insulators The deposits on insulators are measured in a technical terms called as ESDD (equllient salt deposit density) and can be seen in Fig.3. Fig: 3. Deposition of Pollution on Insulators Due to the deposition on the insulators, the pollution levels has been categorised as given blow in Table1- S. No Level ESDD (mg/sq.cm) 1. Light 0.03-0.06 2. Medium 0.06-0.20 3. Heavy 0.20-0.60 4. Very Heavy >0.60 There occurs a change in the insulation distance with an increase in the pollution level and is a gradual phenomenon. Table: 2. Insulation Distance have also been Categorized System volts Minimum creep distance (mm) Moderate Heavy Pollution Pollution 72.5 1100 1700 125 1850 2800 145 2250 3400 245 3800 5600 420 6480 9660 Table: 3.There is a strict need to design insulators depending upon the requirement which can overlook the pollution from the different agencies. The insulators can also categorized on the basis of pollution level as well as creep distance S. No. Pollution level Minimum creep distance (mm/kv...phase to phase) 1. Light 16 2. Medium 20 3. Heavy 25 4. Very Heavy 31 Again, the time has arrived to ensure long trouble free life of insulators/ transmission lines, and the same can be done with the design of insulators for 36 kv/ mm. The Government of India is putting up all efforts to control pollution levels but due to deforestation and urbanisation. The pollution mapping is continuous type of job and need to 503

review after every 2/3 years for awareness towards the technocrats as well a civil society. Also stringent enforcement of laws is a must thing. 3. Replacement of conventional Porcelain insulators with polymer based insulators With passage of time conventional type porcelain insulators are being replaced by polymers and are giving better performance in polluted areas. In our country the process of replacement of conventional insulators is still developing and was considered for the use for the last 8 to10 years and in large scale for the last 5 to 6 years. The polymer based insulators were in use worldwide for the last 25 years. In our country their performance in long run is yet to be established and particularly in areas where temperature falls below -10oC [9]. 4. Comparative study of the conventional Porcelain insulators with polymer based insulators A comparative study of the conventional Porcelain insulators with polymer based insulators has been presented considering various parameters which include general, technical as well as miscellaneous (other) factors. The comparative study has been tabulated below in Table 4 given below [10]- Comparison of Polymer versus Porcelain Insulators General Comparison Factors Ceramics Polymer Weight Heavy and the approx. weight of 400 kv string is 135 kg Lighter and offer an equal as well as better strength. Approx. wt of 400 kv string is about 20 kg Fragile Ability Highly fragile to shock & vibrations Not fragile to shocks Packing and Transport Risky and expensive Easy and economical Installation Risky, expensive & more labour is Very easy and economical required Handling Difficult and needs to be handle with Easy to handle care Maintenance Cost Being fragile in nature the maintenance Low when compared to porcelain cost is moderately high Vandalism (stone pelting/ gun shots) More susceptible Highly resistant Breakages & Secondary Damage Highly fragile, about 10-15% breakage are reported during transportation, Flexible, highly resistant to breakage. But susceptible to cuts and scratches storage and installation Technical Comparison Mechanical failure Life span reduces with time because Single piece. Hence no such problems Resistance to flashovers and punctures separation due to pins getting eroded Resistance is lower but can sustain maximum of 2 to 3 flashovers and then require replacement occured High resistive and if once the flashover takes place, the insulator needs to be replaced immediately Anti tracking and erosion resistance Low tracking resistance Excellent tracking resistance and also avoids erosions or tracking of the housing materials Dielectric strength Reduces with age Excellent insulation performance Contamination and pollution Affected Less affected Hydrophobicity Non-hydrophobicity, as porcelain forms water films on the surface making easy path leading to flashovers Hydrophobicity properties of silicon rubber provide better behaviour and resists wetting by forming beads of water without the need of washing or greasing even in humid or polluted climates. Hence, low failure rate combined with low overall operating and maintenance costs Self cleaning quality Dirt, sand, salt & snow are easily attracted but gets cleaned during rains Due to hydrophobicity, the self cleaning is required Tensile strength Good Excellent due to crimping technology Maintenance Needs maintenance like cleaning,washing and greasing No maintenance. Difficult to work on insulator due to dimension limitations Performance in snow Better Comparatively poor, develops cracks with passage of time Manufacturing process Long manufacturing process leading to Pollution free, safe and less process 504

Safety Design Volume 3, Issue 2 (2015) 502-506 ISSN 2347-3258 long delivery schedule, manufacturing process causes pollution and health risk Susceptible to explosion & breakages, due to high fragile properties Design flexibility is limited. Requires larger and heavier towers for installation and more space time. Hence short delivery periods Provide high level of safety, superior flexibility and strength. Not susceptible to explosion. Insulator design allows for adaptations to suit specific needs such as creep distance subsequently resulting in space saving and lower cost Other factors Part replacement Possible Not Possible shelf life Excellent Develops fungus/algae susceptible to reptiles/rats (Storage) Nil Very easy and eats way Life Expectancy > 25 Years in Non-Polluted areas Yet to established in Long Run. 5. Advantages of Polymer based insulators i. One of another major advantage of polymers is that voltage distribution is uniform all along length of string, hence no chance of flash over /overshoot exists. ii. Another advantage of polymers is of its flexibility in design/shape. It can be given any type of shape to obtain required creep distance suitable to customers. The different figures indicating the polymer based insulators are given below in Figures 4(a)-(d). Fig: 4(c). Fig: 4(a). Fig: 4(b). Fig: 4(d). 6. Limitations of Polymer based insulators i. Eating by rats etc during storage ii. Notching by birds 7. iii. In the event of damage, whole string requires replacement. Whereas in porcelain replacement of damaged /broken insulators is possible. iii. Bad storage- Due to bad storage petticoat has a tendency to shear. Polymers have also tendency to develop algae, fungus and lichens. This is bluish-green and yellowish type deposit on petticoats. This reduces 505

ph value, lowers hydrophobicity and decolourisation, finally drying the bands leading to breakage of the insulators. The pictures of different limitations of the polymer based insulators are presented below in figures 5(a)-(d) Fig: 5(c). Fig: 5(a). References Fig: 5(b). [1] The Atlantic, face book, Air pollution map, 2014 [2] S. Grzybowski, X. Li. Added CFO Voltage by the Fibreglass Distribution Line Pole. Proceedings of the 2001 IEEE/PES Transmission and Distribution Conference and Exposition, Atlanta, Georgia, 2001 [3] P. Hong, V. Top. Electrical field behaviour of transmission line insulators in polluted area. International Symposium on Electrical Insulating Materials (ISEIM), 2008, 530-533. [4] Mohammed El-Shahat, H. Anis. Risk assessment of desert pollution on composite high voltage insulators. Journal of Advanced Research, 2014, 5(5), 569 576 [5] R. Mailfert, L. Pargamin, D. Riviere. Electrical Reliability of DC Line Insulators. Electrical Insulation, IEEE Transcations, 1981, EI-16(3), 267-276 7. Conclusions Fig: 5(d). The present study can be concluded in a way that polymer requires testing / inspection from time to time, particularly when stored in open. Periodical cleaning will retain its properties directly relating to prolong shelf life. However, the Power grid and other transmission utilities have changed porcelains to polymers in recent times (since 2011-12) which eventually showed a drastic fall in transient faults. Such technology in the power transmission has also increased system security and reliability. [6] X. Jiang, J. Yuan, Z. Zhang, J. Hu, L. Shu. Study on Pollution Flashover Performance of Short Samples of Composite Insulators Intended for ± 800 kv UHV DC, IEEE Transactions on Dielectrics and Electrical Insulation, 14(5), 2007, 1192-1200 [7] Mohammed El-Shahat, Hussein Anis. Assessing Partial Discharge on Composite Insulators under Desert Pollution Conditions, International Journal of Emerging Technology and Advanced Engineering, 3(7), 2013, 492-499 [8] CEA report on insulators, 2008 [9] Aging of polymer insulators, University of Engineering and Technology, Taxila, Pakistan [10] Ceramic and Non-Ceramic insulators, article A00038, University of Firat 506