Air-Water Systems. Chilled Ceilings and Beams TROX USA. Principle of Operation. Radiant Effect on Occupants. Early 1980 s. Chilled Ceiling Panels

Similar documents
Chilled Beams. The new system of choice?

FUNDAMENTALS OF CHILLED BEAMS ANSI/ASHRAE STANDARD , METHODS OF TESTING CHILLED BEAMS

Modular Active Chilled Beams

Milwaukee, WI. Darron Rempel

Underf loor For Schools

Redland Tech Center Rockville, MD. Shawn Pepple Construction Management April 14, 2009

Comparison of Air Distribution Systems

SURNA Grow Facility: Systems Comparison - IEA

HVAC SYSTEM DESIGN PROCESS

2-Pipe fan coil terminal units were selected as the parallel system to handle the remaining sensible cooling load.

EMD SERONO RESEARCH CENTER EXISTING

The Milton S. Hershey Medical Center Academic Support Building. AE Senior Thesis Kari Anne Donovan Mechanical Option

Teague Research Center

Under-Floor Air Distribution System (UFAD): Energy and Thermal Comfort Analysis

Mechanical Systems Project Proposal

Implementing Demand Controlled Ventilation to Meet ASHRAE Standard By KlasC. Haglid, P.E., R.A., CEM

ANSI/ASHRAE STANDARD , METHODS OF TESTING CHILLED BEAMS

Air distribution and temperature control in classrooms

South Jefferson High School Huyett Road Charles Town, WV 25414

Georgetown University New Science Center

Thesis Proposal. Clemson University Advanced Material Research Laboratory Anderson, SC. David Anderson Mechanical Option. Photo by Fred Martin

Technical Report Three Mechanical Systems Existing Conditions Evaluation

Sample Reports. for. HAP v4.90 Example Problem

The pros and cons of chilled beams

Planning for Biomed Facility Puts Energy Efficiency Under Microscope

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 9/30/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma

NEWMOA June 30, Fran Boucher LEED AP, Certified Energy Manager Senior Energy Engineer

Chilled Beams Selection BY DAN INT-HOUT, FELLOW ASHRAE; AND LILLI WILBAR

Depth: Mechanical Redesign

YORK PASSIVE CHILLED BEAMS ENGINEERING GUIDE

Mechanical Technical Report Three Mechanical Systems Existing Conditions Evaluation

Reducing Hospital Energy Use and Maintaining Savings. Glen Anderson, PE

Demonstration of modeling of radiant cooling system in design builder. Prashant Bhanware & Bharath Reddy

Energy Efficiency in Building Active Design Part II

Grunenwald Science and Technology Building

Coach House: Hunziker Hall:

THERMAL STRATIFICATION PERFORMANCE OF UNDERFLOOR AIR DISTRIBUTION (UFAD) SYSTEMS

WESTINGHOUSE ELECTRIC NUCLEAR

How to Reduce Energy Use in Your Labs by Up to 50%

Sample Reports. for. HAP v4.80 Example Problem

AN INNOVATIVE DEDICATED OUTDOOR AIR APPLICATION FOR A GOVERNMENT OFFICE TOWER. MICHAEL HALLENBECK, PE, CEM Southland Industries

Mechanical Systems Proposal

EADQUARTERS. Thesis Revised Proposal. Stephanie Kunkel Mechanical Option

SHIYUN CHEN ADVISOR: DR. BAHNFLETH. 1 Executive Summary Building Summary 3. 3 Existing Mechanical System. 4

Seminar 4 Energy Performance of Active Chilled Beam Installations

Performance Evaluation of a Passive Chilled Beam System and Comparison with a Conventional Air System

Energy Recovery Ventilation & ERV Basics The New Custom Express Tool

Retrocommissioning Investigation Report

You Can t Afford Discomfort. Dan Int-Hout Chief Engineer, Krueger Richardson, Texas

Access Floor Systems Underfloor Air Distribution Modular Power Distribution

Ceiling Radiant Cooling Panels

Ceiling Radiant Cooling Panels

Technical Report Three

Smart Labs: Building Next Generation Labs While Maintaining Safety and Comfort

VANZELM E N G I N E E R S

Principles of Ventilation and Air Conditioning Design & Installation

HVAC SYSTEM SCHEMATIC DESIGN

UNDERFLOOR AIR DISTRIBUTION INTEGRATED WITH AN INDIRECT AND DIRECT EVAPORATIVE COOLING ASSISTED 100% OUTDOOR AIR SYSTEM

Mechanical Systems Redesign Proposal. Thesis Proposal. Morton Hospital Expansion

DISPLACEMENT VENTILATION

Optimizing Indoor Environments for Occupant Satisfaction. Presented by: Kelli Goldstone April 2016

Application of Advanced Energy Technologies

White Paper ENVELOPE-FIRST APPROACH TO NET-ZERO ENERGY BUILDINGS

MODULE 5 HVAC FUNDAMENTALS OF MODERN LABORATORY DESIGN

Does NZEB pose a conflict to Good Indoor Air Quality? REHVA summit November 2017

COMMERCIAL LOAD ESTIMATING. Load Estimating Level 3: Block and Zone Loads. Technical Development Program

HVAC SYSTEM DESIGN PROCESS

Interdisciplinary Science and Engineering Building

Energy Recovery Process Cooling Example. Presentation - Overview. Air Change Australia Pty Ltd. Air Change Energy Recovery Range

CHAPTER/REGIONAL TECHNOLOGY AWARD - SHORT FORM

Oklahoma University Children s Medical Office Building

Attaining Thermal Comfort in. Buildings with Predominantly. Glazed Facades. presented to: ANSYS Boston Regional Conference

Energy Conservation and Mold Prevention at Ft. Polk Barracks 10 top items 1. Building air tightness

EnergyPro Building Energy Analysis. Single-story School Building

The Ed Roberts Campus

Façade Existing Conditions

Interdisciplinary Science and Engineering Building

Hourly Analysis Program v.4.1 Page 1 of 1

Control Strategies Affected by Changes to 90.1

Cost Benefits of SunGuard SN 54

Evaluation of Underfloor Air Distribution

LINDQUIST CENTER RETROCOMMISSIONING STUDY UI #

Management Committee December 3, Johnson County Community College Retrocommissioning Report

Retrocommissioning Investigation Study of the Sheraton Chicago Hotel

Compliance Certificate

Using CFD to Wring Out Energy Efficiency in Laboratory Settings

Xavier Energy Initiative

David H. Koch Institute for Integrative Cancer Research Senior Capstone Mechanical Option. Proposal

ASHRAE s LowDown Showdown

Proceedings of BS2013: 13th Conference of International Building Performance Simulation Association, Chambéry, France, August 26-28

The bitterness of poor quality is remembered long after the sweetness of low price is forgotten!

IDEA Synopsis Submission

Hourly Analysis Program v.4.1 Page 1 of 1

TDPs provide you with new technical training materials designed to help your contractors, engineers, and designers to effectively design, specify,

IN THIS ISSUE INTRODUCTION BACKGROUND. March 2018 High Humidity in Winter: Analysis for Multi-Family Passive House Projects

Hospitality. Comprehensive asset management & revenue enhancement capabilities

DEMAND CONTROLLED VENTILATION (DCV) SYSTEMS

Karl Helmink, P.E., CEM Retrocommissioning Manager University of Illinois. Retrocommissioning Saving the Planet One Building at a Time

What s My Baseline? ASHRAE

Star. by Fläkt Woods. iq Star Astra Energy efficient chilled beam

Transcription:

Air-Water Systems and Beams Early 1980 s 1980 1990 2005 Buildings well insulated for heating Advent of personal computers Need to remove heat from space Limited space available TROX USA 1 2 Principle of Operation Chilled Ceiling Panels Radiant Effect on Occupants Chilled Ceiling Panels CWS = 59 to 62ºF CWR = 62 to 66ºF Dry Bulb Temp. 77 F 45% Radiant 55% Convective Effective Radiant Temp. 74.5 F 3 4 1

Cooling Capacity Comparison Chilled Ceiling Systems Flow Cross Section Ratio 1 : 327 Improved thermal comfort Minimal space requirements 18 x 18 Air Duct Low energy cooling solution Limited Cooling Capacity 25 BTUH/FT 2 of active panel 18 BTUH/FT 2 of floor area (based on 70% active ceiling) 1 diameter Water Pipe 5 6 and Beams Early 1990 s Passive Chilled Beams 1980 1990 2000 2005 Ceiling manufacturers begin to sell high free area perforation panels competitively Convective coils replace ceiling panels Passive Beams Increased equipment loads Greater occupant densities Inadequate perimeter cooling 7 8 2

Passive Chilled Beams Passive Chilled Beam Air Distribution Pattern Concrete soffit 9 10 Passive Chilled Beams Recessed Passive Beams Exposed Beams Support Rods Recessed Beams W W x 2 11 12 3

Passive Beam Installations Exposed Passive Beam Support Rods Heat Transfer Coil Cabinet 13 14 Passive Beam Installations and Beams Mid 1990 s 1980 1990 2000 2005 Passive Beams Active Beams Continually increasing sensible loads Greater occupant densities Gypsum board tiles become common Combine cooling and ventilation 15 16 4

Active Chilled Beams Active Chilled Beam Air Distribution Pattern Primary air supply Concrete soffit Suspended Ceiling 17 18 Active Chilled Beams Active Beam Installation Sensible loads up to 100 BTUH/FT 2 Primary air delivered at conventional (50 to 55ºF) temperatures at or near minimum ventilation flow rate Can be used with fiberglass ceiling tiles or without any ceiling 19 20 5

Typical Output Device Watts / Capacity device Chilled WK-D-UM Ceiling Cooling Watts Effect /M 2 Floor (BTUH/FT Area 2 ) Comparative Energy Costs $1.50 25 75 BTUH/FT W/m2 2 18 52 BTUH/FT W/m2 2 TCB Passive (Passive) Beam 400 300 BTUH/LF W/m 40 120 BTUH/FT W/m 2 2 DID Active (Active) Beam 800 530 BTUH/LF W/m 100 160 BTUH/FT W/m 2 2 Typical Annual HVAC Energy Cost ($/FT 2 ) $0.50 Chilled Ceiling with Natural Ventilation $0.90 Passive Beam with Displacement Ventilation $1.00 Active Chilled Beam VAV System LEGEND Cost to transport air Cost to cool air Cost to transport water Cost to chill water 21 22 Passive Chilled Beams For UFAD Applications UFAD Perimeter Treatment Decoupled Sensible Cooling System 1980 1990 2000 2005 Passive Chilled Beam Passive Beams Floor Diffusers 23 24 6

Supply Airflow Requirements Fan Terminals vs. Chilled Beams Active Chilled Beams For Laboratory HVAC Applications For a floor plate that is 60% interior space Fan Powered Perimeter Solution: Interior: 0.6 CFM/ft 2 Perimeter (design): 3.0 CFM/ft 2 Perimeter Diversity: 70% Overall : 1.2 CFM/ft 2 1990 2000 2005 Passive Beams Chilled Beam Perimeter Solution: Interior: 0.6 CFM/ft 2 Perimeter: 0.6 CFM/ft 2 Overall : 0.6 CFM/ft 2 Active Beams Active Beams for Lab HVAC 50% 50% reduction in in supply supply airflow airflow 25 26 Laboratory Design Issues Case Study Space sensible heat gains of 60 to 75 BTUH/FT 2 Ventilation requirements of 6 to 8 ACH -1 Laboratories where chemicals and gases are present require 100% OA All air systems require 16 to 20 ACH -1 to satisfy sensible load Active beams remove over 60% of sensible heat via chilled water circuit Require only 40% the primary airflow rate (6-8 ACH -1 ) of all-air system Laboratory Design for Pharmaceutical Company Location: St. Louis, MO Outdoor Design Conditions: 94DB/75WB Laboratory Space: 54,000 FT 2 Minimum Ventilation Rate: 8 ACH -1 Space Sensible Heat Gain: 72 BTUH/FT 2 27 28 7

Equipment Requirements Energy Comparisons Case Study, 94/75F Outdoor Design Equipment Conventional VAV Active Chilled Beam Active Chilled Beam (Parallel Sensible Cooling) Air Handling Units Cooling 180,000 CFM 1,477 Tons 72,000 CFM 587 Tons Reduced fan power 32 % from Base VAV Heating 21,617 lbs/hr 8,588 lbs/hr Reduced cooling energy 46 % from Base VAV Duct Distribution Control Points 285,493 lbs. 800 214,120 lbs. 800 Reduced ductwork sizes 18-20 ACPH to 6-8 ACH -1 Chilled Beams 1,056 Higher Pumping energy 15% - Offset by other savings Piping Distribution Sensible Cooling Chiller System 4,200 LF 200 Tons Higher cooling system efficiencies Overall 35% Reduction in Energy Costs 29 30 Equipment Requirements Displacement Beams Equipment Conventional VAV Active Chilled Beams Air Handling Units $2,264,335 $899,610 Cooling $1,627,799 $646,717 1990 2000 2005 Heating Duct Distribution Control Points $244,267 $1,481,709 $1,200,000 $97,046 $1,111,282 $1,140,000 Passive Beams Chilled Beams $1,652,984 Active Beams Piping Distribution $266,444 Sensible Cooling Chiller System Totals $6,818,109 $265,373 $6,079,456 Displacement Beams 31 32 8

Displacement Conditioning Heat Source 33 34 Displacement Conditioning Advantages Displacement System Air Handling Unit Design Minnesota Elementary School Identical classrooms 1600 CO 2 Concentration (PPM) 1400 1200 1000 800 600 400 Mixed Air System (UV) Displacement System Tests conducted over two week period CO 2 concentration at six foot level monitored Mixed system: 1200 PPM DV System: 400 PPM Exhaust Air 2700 CFM @ 84 F Outside Air 2700 CFM @ 94 F Return Air 8100 CFM @ 83 F Supply Air 8100 CFM @ 63 F Time 35 36 9

Displacement with Induction Cooling mode operation Displacement with Induction Air Handling Unit Design 100% Exhausted Optional Heat Recovery Airflow quantities based on 6 classrooms per AHU Return Air 450 CFM (82 to 85ºF) Exhaust Air 2700 CFM @ 84 F Return Air 450 CFM @ 83 F Primary Airflow 450 CFM (52 to 55ºF) Room Air 900 CFM (75 to 78ºF) Chilled Water Supply Airflow 1350 CFM (62 to 68ºF) Outside Air 2700 CFM @ 94 F Primary Air 2700 CFM @ 51 F Room Air Induction 37 38 and Beams Early 2000 s The Future CHW & HW piping Sprinkler pipes Primary air duct 1980 1990 2000 2005 Control valves & actuators Passive Beams Active Beams Lighting Multi-service Beams Reduced trade coordination Reduced construction cycles Production vs. construction PA system Occupancy and/or smoke sensors 39 40 10

Multi Service Beams Indirect Lighting 41 42 Passive Multi-Service Beam Production vs Construction o Reduce on site fixed costs o Reduce trade coordination o Improved quality control o Reduce design coordination o Reduce construction schedule o Deliver building earlier 43 44 11

MSCB Economics Cost Calculations Class A Office Building Location: Chicago, Illinois 250,000 NSF, 200,000 RSF 10 Floors, 25,000 ft 2 per floor Construction Cost: $150 per ft 2 Fixed Site Costs: 12% Construction Time: 24 months Net Lease Rate: $25 per ft 2 45 46 Capital Costs First Cost Comparison Conventional VAV System Building Construction Cost: 250,000 ft 2 x $150/ft 2 = $37,500,000 HVAC Run out Costs: 250,000 ft 2 x $8/ft 2 = $2,000,000 Air Handling Units: 300,000 CFM x $2.25/CFM = $675,000 Multi-service Beams $2,675,000 $10.70/ft 2 Fixed Site Costs: 12% of $37,500.000 = $4,500,000 $43,000 per week Construction Loan Interest: 5% of 18,750,000 = $938,000* $18,000 per week MSCB s: 7600 lf x $550/lf = $4,180,000 Air Handling Units 120,000 CFM x $2.25/CFM = $270,000 Air Cooled Chillers 240 Tons x $1000/Ton = $240,000 Accelerated Revenue: 200,000 ft 2 x $25/ft 2 = $5,000,000 $96,000 per week $157,000 per week Less: Lighting Installation Costs ($1 per ft 2 ): Less: Suspended Ceiling ($4 per ft 2 ): $4,690,000 $250,000 $1,000,000 $18.76/ft 2 $3,440,000 $13.76/ft 2 * Annual interest cost Premium for MSCB over VAV: $765,000 $3.06/ft 2 47 48 12

Actual Scenario (worst case): Owner is able to rent 25% of space immediately MSCB reduce construction time by 10% (10 weeks) Capital Costs Payback Analysis Worst Case Scenario Initial Cost Premium: = $765,000* Early Delivery Worst Case Cash Flow Effect: = $850,000 Building Construction Cost: 250,000 ft 2 x $150/ft 2 = $37,500,000 Fixed Site Costs: 12% of $37,500.000 = $4,500,000 $43,000 per week Construction Loan Interest: 5% of 18,750,000 = $938,000* $18,000 per week Accelerated Revenue: 25% x 200,000 ft 2 x $25/ft 2 = $1,250,000 $24,000 per week Immediate Payback! $85,000 per week x 10 weeks * Annual interest cost Net cash result $850,000 HVAC Energy Savings ($0.50/ft 2 ) $125,000 annually 49 50 13