[Type text] Heber Light & Power. Developers & Excavators. Electrical Service Requirements Manual

Similar documents
SALEM CITY POWER ELECTRICAL REQUIREMENTS & STANDARDS MANUAL

UNDERGROUND SERVICES - GENERAL SERVICE AND MULTI-UNIT RESIDENTIAL

NORTHEASTERN REMC ELECTRIC STANDARDS MANUAL

NORTHEASTERN REMC ELECTRIC STANDARDS MANUAL

Contact Clark Public Utilities Construction Services department at (360) to initiate a request for service.

(Condensed from National Electric Code)

Section 7: Specifications

Please check with your local inspection authority for any additional requirements before installation.

Underground Service Requirements and Instructions

If a new residence s electrical service is not located within 200 feet of existing

Basic Service. This Section provides information regarding a. Introduction

Electric Service Handbook

GENERAL NOTES PEDERNALES ELECTRIC COOPERATIVE, INC. RESIDENTIAL AND COMMERCIAL AMP METER LOOP SPECIFICATIONS

Effective June, Eaton-Durham Model # UTRS223ACH. Siemens, Model # SUAS877-PG. (or Landis & Gyr # UAS877-PG) Milbank. Model # U1980-O.

Electric Engineering Division RESIDENTIAL CONDUIT RULES AND REGULATION. S:\COO_ACM_US_Electric_Telecommunications\COO_ET_Engineering\Conduit Policies

COMMERCIAL CONDUIT RULES AND REGULATIONS

UNDERGROUND SERVICES SECONDARY

Section 2: Underground

ELECTRICAL SERVICE UPGRADE RESIDENTIAL AND COMMERCIAL QUICK INFORMATION REFERENCE

UNDERGROUND SERVICES (RESIDENTIAL) SINGLE FAMILY RESIDENTIAL, DUPLEXES, OR TOWNHOUSES

Huntsville Utilities Underground Residential Service Requirements

PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES

ANY SPECIFICATION DRAWINGS OR DATED PRIOR TO SEPTEMBER 2015 WILL NOT BE HONORED.

Merrimac Municipal Light Department. Commercial Developments Policy

a) Line and load compartments must be separated by a stable barrier.

Specifications for Residential Underground Electric Service Installation

Underground Residential Distribution (Specifications for Installation) PES March 2008 Spec 11

Electric Service Requirements & Guidelines

Post Office Box 500 Carson, WA Phone (509) Fax (509) Toll Free (800)

6. SECONDARY SERVICES (under 600 volts) 6.1 AVAILABILITY For the electrical characteristics of available secondary services see Section 3.4.

ELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS

Gas meter clearances and service installation requirements

Electric Service Standards

RESIDENTIAL QUICK REFERENCE

TABLE OF CONTENTS. PUD SERVICE TERRITORY & CONTACTS... Page 1. NEW SERVICE QUESTIONNAIRE... Page 2. TRENCHING SECONDARY (120/240 volts)...

Welcome to Douglas County PUD

6. SECONDARY SERVICES (under 600 volts) 6.1 AVAILABILITY For the electrical characteristics of available secondary services see Section 3.4.

Member Service Electric Wiring Guidelines

Revisions for the 2015 Edition of the "Specifications and Requirements for Electric Installations (Bluebook)"

Specifications for Residential Overhead Electric Service Installation

OVERHEAD SERVICES - SECONDARY

Electric Service Handbook

OVERHEAD SERVICES - RESIDENTIAL & GENERAL SERVICE. See Chapter 3, Section 3.01 for more information about point of entrance (POE).

TEMPORARY METER POLE INSTALLATION

STREET LIGHTING. Springville City Power standard street lights will be installed in accordance with Springville City Power's Line Extension Policy.

OPERATING PROCEDURE NO. 310

Specifications for Residential Overhead Electric Service Installation

SECTION CONDUITS AND BOXES PART 1- GENERAL. A. Work covered by this section includes the furnishing and installation of conduits and boxes.

PRIMARY LINE EXTENSION

Residential Electric Policy

Specifications for Electrical Underground Residential Distribution Systems

ELECTRICAL UTILITY CONSTRUCTION REQUIREMENTS FOR PLATS & LAND DEVELOPMENT

Indianapolis Power & Light Company

METERING INSTALLATION

4. GENERAL REQUIREMENTS

The Official Meter Manual of JCREMC. Created by the Engineering Dept.

For more information contact: Engineering Department (800) Ext RURAL RESIDENTIAL SERVICE INSTALLATION GUIDE.

TEMPORARY FACILITIES

Specifications for Electrical Underground Distribution Systems from Overhead Transformation, Apartments & Condominiums

1. Contractor shall obtain a valid electrical permit from the Town of Perinton.

VOLUME 15 Section 6: Gas Metering Guidelines

PAYSON CITY POWER AND LIGHT. Electrical Construction Standard Specifications

CONSTRUCTION HANDBOOK Guidelines and Information for Members, Builders & Developers

3. Intermediate metal conduit (IMC). 4. Electric metallic tubing (EMT). 5. Flexible metal conduit (FLEX). 6. Polyvinyl chloride conduit (PVC).

City of Santa Monica Building and Safety Division

A. All materials shall be tested and listed by an OSHA approved Nationally Recognized Testing Laboratory (NRTL).

4. GENERAL REQUIREMENTS

New Construction Handbook

Welcome to Douglas County PUD

ELECTRIC DEPARTMENT CONSTRUCTION STANDARDS

Central Lincoln PUD Commercial Service Guidelines & Standards

Gainesville Technical Center 5399 Wellington Branch Drive Gainesville VA Phone (703)

ANCHORAGE MUNICIPAL LIGHT & POWER ENGINEERING DIVISION

SERVICE ENTRANCES. OPPD S Electrical Service Designer (ESD) shall designate the Point Of Entrance.

Tucson Electric Power Company Rules and Regulations

SECTION GROUNDING

OVERHEAD SERVICE. Table of Contents - Section 400

Electric Service Requirements Service Assembly Guide. Homer Electric Association, Inc Lake St. Homer, AK

WIRING RULES AND REGULATIONS OF TOMBIGBEE ELECTRIC POWER ASSOCIATION

SERVICE ENTRANCE SPECIFICATIONS FOR RESIDENTIAL AND COMMERCIAL

SPECIAL SPECIFICATION 6666 Charter Communications System

DOWNTOWN UNDERGROUND NETWORK SECONDARY SERVICES GUIDELINES

CITY OF UNION, OREGON TECHNICAL SPECIFICATIONS SECTION 9 UNDERGROUND UTILITIES

Large Basic Service. This Section applies to members requiring new. Introduction. Service Types

SECTION UNDERGROUND ELECTRICAL CONSTRUCTION

An altered service that is moved, upgraded (ex., 200 to 400 amp) or changed to meet today's standards for electric service.

Electric Service Standards

A. Product Data: For surface pathways, wireways and fittings, floor boxes, hinged-cover enclosures, and cabinets.

ELECTRICAL SAFETY Information Bulletin

UNIFORM STANDARD DRAWINGS CLARK COUNTY AREA, NEVADA YEAR 2015 REVISIONS

Central Lincoln PUD Single-Family Residential Guidelines & Standards April 21, 2017

Section 4 Underground Service

ATTACHED/DETACHED GARAGE BUILDING PERMIT APPLICATION

INDEX. Page SECTION 1.0: SCOPE Toronto Hydro Requirements Ontario Electrical Safety Code 1 SECTION 2.0: PURPOSE 1

CONSOLIDATED EDISON CO. OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY DISTRIBUTION ENGINEERING DEPARTMENT NON-NETWORK SYSTEMS SECTION

DESIGN STANDARDS SECTION DS 7 STREET LIGHTING

Indianapolis Power & Light Company

TS 803 DUCTS DUCT INSTALLATION, PROTECTION AND MARKING WITHIN A TRENCH OPEN TRENCH DUCT INSTALLATION PROFILE

Transcription:

[Type text] Heber Light & Power Developers & Excavators Electrical Service Requirements Manual May 2017

E.1.1 - GENERAL REQUIREMENTS PURPOSE This section was prepared to aid developers, contractors, engineers and customers in establishing electric service for new and remodeled structures. We recognize that you may require personal assistance from our staff, and we encourage you to contact us by calling Heber Light & Power Power to discuss electric service requirements with us. It is the desire of Heber Light & Power, and the local electrical code enforcing authority to provide you, the Customer (developers, contractors, owners, etc.) with high quality, safe electric service. In order to avoid unnecessary repetition, the "Power Company" as used in the following pages shall mean Heber Light & Power. The requirements are intended to apply to new developments. As a general rule, if the matter in question is not presented herein, then it is not allowed unless approved by the Power Company. Any power required for private use (i.e. light, sprinkler, etc.) shall be metered. CODES AND ORDINANCES It is necessary that the construction of new or remodeled installations conform to applicable provisions of the National Electrical Code (NEC), National Electrical Safety Code (NESC), and State of Utah Electrical Service Regulations, as well as City and County ordinances and codes. This includes OSHA rules both during construction and maintenance. CHANGES OR CONFLICTS IN REQUIREMENTS AND GUIDELINES Some of the information in this section is based on the aforementioned governmental codes and ordinances as well as Heber Light & Power specific requirements as stated herein. These requirements and guidelines are issued with the intent of complying with all applicable codes, ordinances, regulations, and tariffs; however, in the case of conflict, the appropriate regulation, tariff, code, or ordinance will supersede the interpretation offered in this manual. In addition, these requirements are subject to change in the event that the governing codes, ordinances, regulations, or tariffs are changed. The Power Company should be consulted in case of doubt on the applicability of any item. The phrase "consult Power Company" as used in this manual shall mean a consultation with Heber Light & Power Superintendent is to be made for each and every installation or project. APPLICATION FOR SERVICE It is important that the Power Company office be provided as early as possible with accurate load information and the date when the Customer will require service, so all necessary arrangements for the service may be completed. Request for service to large residential developments normally require 60 days advance planning by the Power Company in order to serve the load. Installations requiring transformers or other equipment not in stock may require six months lead time or more. The Power Company is available to provide advice on service requirements and related problems relative to electric energy utilization for new, existing, and reconstructed installations. The Developer will be held liable for any damage to Power Company equipment. When conditions are encountered during construction that require changes in the initial, agreed upon service arrangements, the Power Company must be consulted so mutually satisfactory alternative arrangements can be made. Adequate notice must be given to the Power Company and approval granted regarding changes or additions. TYPES OF SERVICE FURNISHED The electric service available is 60 hertz (cycles), alternating current, single or three-phase. The secondary voltages and connections available are given below: Overhead Service (Not Included) Underground Service Single-phase, 120/240 volt, three-wire, grounded Three-phase, 208Y/120 volt, four-wire, grounded, wye Three-phase, 480Y/277 volt, four-wire, grounded, wye The nominal primary voltage of Heber Light & Power's power distribution system may differ from one service area to another. Under certain conditions, primary delivery will be supplied at the distribution voltage standard for the location at which it is requested. GENERAL REQUIREMENTS ELECTRIC 1.1 GENERAL REQUIREMENTS DATE: 10/11/2011 REV: B REV DATE: 07/01/2014

TRENCHING E.2.1 - TRENCHING & CONDUITS The developer is to provide the trench for all required conduit systems and, following installation of the conduit by the Developer (see 5.4 CONDUITS), backfill to meet Power Company requirements.the Power Company, under the terms of Heber Light & Power's Line Extension policy, will install both primary (medium voltage 12.47 kv or 4.16 kv) and secondary cables (below 480 volts). To assure the final grade has been established, the trenching will be started after the curbs and gutters have been installed unless approved by Heber Light & Power. Call Before You Dig Utah Law Section 54-8A-1 through 54-8A-11 requires the Blue Stakes One Call Location Center be notified at least two working days prior to excavation. The excavation must not be started until locations have been made. Depth SEE CHART ON E.2.2 FOR TRENCHING DEPTHS. The property owner is responsible at their own cost to insure that proper burial depth clearance listed below is maintained even after excavation of the property. Any questions on impaired burial depths should be immediately brought to the attention of the Power Company. Under certain conditions, with prior Power Company approval, cable/conduit systems may be buried with less cover provided that mechanical protection is installed by the Developer to the Power Company's specifications. Width All trenches shall meet OSHA requirements. Primary/secondary combined trenches shall be a minimum of 18 inches wide at the bottom. Trenches 12 inches wide will be approved for a single service only. Backfill The developer will be responsible for backfilling trenches he provides. The Developer must provide 12" of sand to be placed on top of conduits and shall have red warning tape on top of sand.where trenches cross structural fill, typical of road crossings, the trench backfill shall consist of like kind structural fill. All primary trenches and all road crossings trenches (including secondary) shall be compacted to 95% compaction of the maximum dry density as determined by ASHTO T-99 (standard). All primary and secondary conduit systems shall have placement of red warning tape 6" below final grade. The tape shall be of the type specific for the application. Joint Use Typically, joint use between other utilities of Power Company trenches is not allowed unless approved by the Power Company. Any joint use between telephone, TV, and other electrical communication cables must be pre-approved by the Power Company and installed in accordance with the Power Company specifications. The Power Company normally will not install electrical cables in a common trench with non-electric utilities such as water, gas, and sewer, unless unusual conditions such as adverse soil or route restrictions exist. All such installations require the prior approval of the Power Company. Transformers and Secondary Boxes To schedule a Heber Light & Power employee to open a transformer or secondary box please call 435-654-2913 Do Not open transformers or secondary boxes under any circumstance. Anyone opening an HL&P transformer, switch, junction box, secondary box or any other Heber Light & Power equipment will be subject to a trespassing fine. Pulling Wire When conduits are terminated inside a transformer or secondary box Do Not attempt to pull or push wire into the conduit. Call 435-654-2913 to schedule an Heber Light & Power employee to pull the wire into the conduit. TRENCHING & CONDUITS ELECTRIC 2.1 TRENCHING & CONDUITS DATE: 10/11/2011 REV: C REV DATE: 05/01/2017

E.2.2 - TRENCHING & CONDUITS POWER WILL NOT BE CONNECTED UNLESS A TRENCH INSPECTION WAS PERFORMED BY AN HL&P EMPLOYEE. CALL 435-654-2913 TO SCHEDULE A TRENCH INSPECTION TELEPHONE 95% COMPACTION REQUIRED CABLE TV 6" RED WARNING TAPE SEE CHART FOR DEPTH 18" MINIMUM 6" MIN. COVER SAND PRIMARY CONDUIT 4" MIN. SECONDARY CONDUIT 3" BEDDING (SAND) UNDISTURBED EARTH BACKFILL COMPACTED TO 95% SAND WITH RED WARNING TAPE ON TOP VOLTAGE AND DEPTHS: VOLTAGE TRENCH DEPTH COVER SECONDARY 42" 36" PRIMARY 54" 48" 6" CONDUIT 78" 72" 1. SECONDARY CONDUITS SHALL BE BURIED AT THE SAME DEPTH AS PRIMARY, IF NO PRIMARY IS TO BE INSTALLED USE THE ABOVE CHART FOR SECONDARY DEPTHS. 2. THERE SHALL BE A 4" MINIMUM SEPARATION BETWEEN CONDUITS. 3. A MINIMUM OF 12" SEPARATION BETWEEN ELECTRICAL AND OTHER UTILITIES IS REQUIRED. 4. ALL CONDUITS SHALL BE BURIED A MINIMUM OF 48" UNDER PAVED SURFACES AND RAILROADS. TRENCHING & CONDUITS ELECTRIC 2.2 TRENCHING & CONDUITS DATE: 10/11/2011 REV: D REV DATE: 09/29/2015

E.2.3 - TRENCHING & CONDUITS CONDUITS The Power Company requires the use of conduit for all underground primary and secondary cable installations, including lighting circuits. Rigid galvanized steel or gray electrical grade PVC schedule 40 (underground only) conduit are acceptable materials for conduits installed by the Customer. All 90-degree bends are to be a minimum of 36" radius for 3" pipe, 36" radius for 4" pipe, and 36" radius for 6" pipe. All primary elbows are to be PVC for 3", 4" and 6" conduits Rigid elbows to be used when going up a pole. All conduits shall be terminated at the open end with plastic bushings. All underground metallic conduit must be tape wrapped with suitable tape for the application. Residential primary conduit sizes must be three (3) inch. Secondary conduit size shall be three (3) inches from transformers to junction domes and (3) inches from transformer or dome to resident. All conduits end points shall be sealed or taped to prevent debris from plugging the conduit and future use (1" PVC painted red). The Developer shall be responsible for cleaning conduits if the Power Company is unable to install or pull the service cable. Along with conduits extending to secondary junction boxes, each transformer pad and secondary box shall have ten (10) foot conduit stub-outs for interconnection to adjacent homes. Prior to backfilling, the Developer must notify the Power Company (435-654-2913) for trench inspection, following the inspection the Power Company shall issue a notice to proceed slip, allowing backfilling. Power will NOT be connected unless a trench inspection has been performed and approved. TRENCHING & CONDUITS ELECTRIC 2.3 TRENCHING & CONDUITS 10/12/2011 REV: C REV DATE: 09/29/2015

E.3.0 - TEMPORARY POWER PEDESTAL TEMPORARY METER SOCKET & SERVICE PEDESTAL 120 VOLT SINGLE POLE GFCI BREAKER REQUIRED OR GFCI PROTECTED OUTLET 240 VOLT DOUBLE POLE GFCI BREAKER REQUIRED N TO TRANSFORMER OR SECONDARY BOX SECONDARY CONDUCTORS MUST BE LONG ENOUGH TO REACH CONNECTION TERMINALS 8'-0" COPPER GROUND ROD 1. Place temporary next to power source without blocking the openings. 2. Call the Building Inspector for a temporary service inspection. 3. Conductors must be long enough to enter under the base of the transformer or secondary box and long enough to connect to the terminals. Failure to provide wire that is long enough will result in a return visit charge. 4. The temporary service must be provided with all inspection covers in place before energizing service. 5. Heber Light & Power is not responsible for damaged temporary services such as faulty breakers or GFCI outlets. UNDERGROUND TEMPORARY POWER PEDESTAL TEMPORARY PEDESTAL ELECTRIC 3.0 TEMPORARY PEDESTAL 05/01/2017 REV DATE:

E.3.1 - RESIDENTIAL SERVICES APPROVED WEATHER HEAD MINIMUM OF 24" ABOVE ROOF AND TO BE 2" RIGID CONDUIT. #6 CU SOLID WIRE 2" RIGID CONDUIT METER SOCKET SHALL BE LOCATED BETWEEN 5' AND 6' ABOVE ALL 400 AMP SERVICE PANELS SHALL HAVE A LEVER OR LINK BYPASS RIGID STAND PIPE ANCHORED TO BUILDING FOUNDATION USING 3/8" BOLTS AND UNISTRUT AND UNISTRUT CLAMP 36" MIN. 5' MIN. - 6' MAX. 24" MIN. 24" RIGID STEEL SWEEP (MIN) 5/8" x 8'-0" COPPER GROUND ROD AND UFER GROUND PVC SCH 40 METAL CONDUIT BELOW GRADE SHALL BE SUITABLY COVERED WITH CORROSION PROTECTION TAPE. RIGID CONDUIT STAND PIPE SHALL BE 3 INCH SERVICE SIZES AND WIRE SIZES: 100 AMP OR LESS #2 WIRE 125 AMP 1/0 WIRE 150 AMP 2/0 WIRE 200 AMP 4/0 WIRE 400 AMP 350 OR PARALLEL 4/0 WIRE ABOVE 400 AMP CALL 435-654-2913 FOR INFORMATION SEE SHEET E.3.2 FOR SIDE VIEW RESIDENTIAL SERVICES ELECTRIC 3.1 RESIDIENTIAL SERVICE 10/12/2011 REV: B REV DATE: 07/01/2014

E.3.2 - RESIDENTIAL SERVICES 2" RIGID CONDUIT 10' MAX. 3'-0" MIN. ALL 400 AMP SERVICE PANELS SHALL HAVE A LEVER OR LINK BYPASS GAS METER 3'-0" MIN. RIGID STEEL 5'MIN. - 6' MAX. 36" MIN. METER SHALL BE INSTALLED AS FAR FORWARD AS POSSIBLE WITH A 10' MAXIMUM. RIGID STEEL 24" RADIUS (MIN) METER SHALL NOT BE INSTALLED WITHIN A 3' RADIUS OF THE GAS LINE ENTRANCE TO THE HOUSE. SEE SHEET E.3.1 FOR FRONT VIEW RESIDENTIAL SERVICES ELECTRIC 3.2 RESIDIENTIAL SERVICE DATE: 10/12/2011 REV: B REV DATE: 07/01/2014

E.3.3 - RESIDENTIAL SECONDARY RISER 10' x 3" RIGID CONDUIT 12" STANDOFF 1 - CUSTOMER SHALL SUPPLY (3) 10' x 3" RIGID CONDUITS 2 - CUSTOMER SHALL SUPPLY (3) 12" STANDOFFS 3 - CUSTOMER SHALL INSTALL (1) 10' LENGTH OF CONDUIT 4 - CUSTOMER SHALL INSTALL (1) 12" STANDOFF AT 5'-0" HIGH 5 - CUSTOMER SHALL INSTALL (1) 24" RIGID 90 SWEEP (MIN) CUSTOMER SHALL PULL WIRE THROUGH CONDUITS AND LEAVE ENOUGH WIRE OUT OF THE TOP TO REACH THE TOP OF THE POLE PLUS 5 EXTRA FEET FOR HL& P CONNECTIONS 5'-0" 24" METAL SWEEP (MIN.) TRENCH BOTTOM RESIDENTIAL SECONDARY RISER ELECTRIC 3.3 RESIDIENTIAL SECONDARY RISER DATE: 04/18/2014 REV DATE: 04/18/2014

E.4.1 - SECONDARY JUNCTION BOXES TOP VIEW FRONT VIEW SIDE VIEW 36" MIN. 2-4" MIN. 3" CONDUIT TO TRANSFORMER 3" CONDUIT TO RESIDENT 1. DEVELOPER SHALL PROVIDE MINIMUM SPACING BETWEEN CONDUITS. 2. DEVELOPER TO SEAL ALL CONDUIT ENDS WITH TAPE TO PREVENT PLUGGING 3. DEVELOPER IS RESPONSIBLE FOR TRENCHING AND BACK FILLING. 5. DEVELOPER SHALL USE ONE OF THE TWO ACCEPTABLE JUNCTION BOXES LISTED ABOVE. SECONDARY JUNCTION BOXES ELECTRIC 4.1 SECONDARY JUNCTION BOXES DATE: 10/12/2011 REV DATE: 10/12/2011

E.5.1 - SINGLE PHASE PAD MOUNTED TRANSFORMER NOTE: 1. DEVELOPER TO SUPPLY TRENCHING, CONDUITS AND BACKFILL. NOTE: 1. POWER COMPANY TO SUPPLY BASES AND TRANSFORMERS.. 3" CLR. TYP. LOW VOLTAGE 48" MIN. 2'-0" APPROX. 6" 12" 42" SIDE VIEW FRONT VIEW 26" 42" 3'-0" APPROX. SEE NOTE 2 HIGH VOLTAGE 2"-4" 1. FILL MATERIAL UNDER THE CONCRETE PAD OR BASE SHALL BE ROADBASE MEETING STATE SPEC. AND SHALL BE COMPACTED TO 95%. ROADBASEFILL SHALL EXTEND FROM THE BOTTOM OF THE TRENCH TO THE TRANSFORMER PAD AND SHALL EXTEND 3' ON THE BACK AND SIDES AND 1' ON THE FRONT. 1 PHASE PAD TRANSFORMER ELECTRIC 5.1 1 PHASE PAD TRANSFORMER DATE: 10/12/2011 REV DATE: 10/12/2011

E.5.2 - SINGLE PHASE TYPICAL CONDUIT INSTALLATION FOR RESIDENTIAL SUBDIVISION 1. THE DEVELOPER IS RESPONSIBLE FOR THE INSTALLATION OF RIGID GALVANIZED STEEL, OR GRAY ELECTRICAL GRADE PVC SCHEDULE 40 (UNDERGROUND ONLY) CONDUIT. 2. ALL STUB OUTS MUST POINT IN THE GENERAL DIRECTION OF THE FRONT CORNER OF BUILDING AND MUST EXTEND BEYOND PROPERTY LINE OF THE LOT BEING SERVED. ALL SERVICE CONDUITS SHALL BE STUBBED 10' BEYOND TRANSFORMER PAD PROPERTY LINE 3. FOR RESIDENTIAL SERVICES USE 3" CONDUIT TO RESIDENT AND 3" CONDUIT TO SECONDARY JUNCTION DOME. 4. PRIMARY CABLE CONDUIT SHALL BE A MINIMUM OF 3". THE DEVELOPER IS REQUIRED TO COORDINATE WITH THE POWER COMPANY FOR SPECIFIC CONDUIT SIZES REQUIRED. 5. CONDUITS MUST BE BURIED A MINIMUM OF 36" DEEP. (SEE CHART BELOW). 6. ALL CONDUITS SMALLER THAN 6" SHALL USE PVC 90'S AND FITTINGS. RIGID SHALL BE USED ON RISER POLES OR WHERE OTHERWISE SPECIFIED BY THE POWER COMPANY. 7. ALL SERVICE CONDUITS SHALL BE STUBBED 10' BEYOND TRANSFORMER PAD ALL CONDUITS INSTALLED WITH 90 DEGREE ELBOWS AND PROTECTIVE CAPS SECONDARY PRIMARY 5/8" x 8'-0" COPPER GROUND ROD 2"-4" VOLTAGE AND DEPTHS: VOLTAGE TRENCH DEPTH COVER SECONDARY 42" 36" PRIMARY 54" 48" 48" MIN. SEE CHART SECONDARY CONDUIT PRIMARY CONDUIT NOTE 3 NOTE 4 1 PHASE CONDUIT INSTALLATION ELECTRIC 5.2 1 PHASE CONDUIT INSTALLATION DATE: 10/12/2011 REV DATE: 10/12/2011

E.5.3 - SINGLE PHASE TRANSFORMER PAD OR SECONDARY DOME LOCATION WITH PLANTER AND SIDEWALK 10' P.U.E. LINE PUBLIC UTLITY EASEMENT PROPERTY LINE PUBLIC UTLITY EASEMENT TRANSFORMER PAD SECONDARY DOME FRONT PROPERTY LINE (10' P.U.E.) FRONT PROPERTY LINE (10' P.U.E.) TRENCH TRENCH SIDEWALK 4'-0" PARK STRIP (PLANTER) CURB 1. ALL TRENCHING, TRANSFORMERS AND SECONDARY DOMES SHALL BE LOCATED WITHIN THE PUBLIC UTILITY EASEMENT (P.U.E). 2. TRANSFORMERS AND SECONDARY JUNCTION BOXES TO BE LOCATED AS PER THE ELECTRICAL DESIGN PROVIDED BY. 3. TRANSFORMER AND OTHER EQUIPMENT FRONTS TO BE INSTALLED SO THAT THE FRONTS ARE FACING THE SIDEWALK.. 4. CONDUITS SHALL BE CAPPED 2" ABOVE. 5. NO OBSTRUCTIONS SHALL PERMITTED BE WITHIN 10' OF THE FRONT AND 3' ON THE SIDES AND BACK OF ANY ELECTRICAL EQUIPMENT. EQUIPMENT LOCATION SPEC. ELECTRIC 5.3 1 PHASE TRANSFORMER PAD DATE: 10/12/2011 REV DATE: 10/12/2011

E.5.4 - SINGLE PHASE TRANSFORMER PAD OR SECONDARY DOME LOCATION WITH SIDEWALK AND NO PLANTER 10' P.U.E. LINE PUBLIC UTLITY EASEMENT PROPERTY LINE PUBLIC UTLITY EASEMENT TRANSFORMER PAD SECONDARY DOME FRONT PROPERTY LINE (10' P.U.E.) FRONT PROPERTY LINE (10' P.U.E.) TRENCH TRENCH SIDEWALK CURB 1. ALL TRENCHING, TRANSFORMERS AND SECONDARY DOMES SHALL BE LOCATED WITHIN THE PUBLIC UTILITY EASEMENT (P.U.E). 2. TRANSFORMERS AND SECONDARY JUNCTION BOXES TO BE LOCATED AS PER THE ELECTRICAL DESIGN PROVIDED BY. 3. TRANSFORMER AND OTHER EQUIPMENT FRONTS TO BE INSTALLED SO THAT THE FRONTS ARE FACING THE SIDEWALK.. 4. CONDUITS SHALL BE CAPPED 2" ABOVE. 5. NO OBSTRUCTIONS SHALL PERMITTED BE WITHIN 10' OF THE FRONT AND 3' ON THE SIDES AND BACK OF ANY ELECTRICAL EQUIPMENT. EQUIPMENT LOCATION SPEC. ELECTRIC 5.4 1 PHASE TRANSFORMER PAD DATE: 10/12/2011 REV DATE: 10/12/2011

E.5.6 - SINGLE PHASE AND THREE PHASE PAD MOUNTED TRANSFORMER CLEARANCES BACK 3'-0" MIN. MINIMUM CLEARANCE 3'-0" MIN. 3'-0" MIN. FRONT 10' MIN. 10' MIN. 3' MIN. 10' MIN COMBUSTIBLE NON-COMBUSTIBLE 10' CLEAR AREA IN FRONT OF EQUIPMENT TO ALLOW FOR THE USE OF HOT STICKS (NOTE 2) 10' CLEARANCE FROM ANY TRANSFORMER SURFACE IF STRUCTURE IS OF COMBUSTIBLE MATERIAL 3' CLEARANCE TO ANY NON-COMBUSTIBLE BUILDING SURFACES THAT DO NOT HAVE ANY OPENINGS CLOSER THAN 10' 1. CONSULT NATIONAL ELECTRIC SAFETY CODE, NEC, STATE AND LOCAL BUILDING AND FIRE CODES FOR ADDITIONAL REQUIREMENTS. 2. FRONT OF PAD MOUNTED TRANSFORMER TO BE LOCATED AWAY FROM BUILDING WALLS OR OTHER BARRIERS TO ALLOW FOR SAFE WORKING PRACTICES. 3. CONSULT THE POWER COMPANY FOR ADDITIONAL CLEARANCES THAT MAY BE REQUIRED FOR DOORS, WINDOWS, FIRE ESCAPES, AIR VENTS, ETC. 4. WHEN PAD MOUNTED TRANFORMERS OR OTHER EQUIPMENT ARE INSTALLED WHERE IT MAY BE STRUCK BY A MOTORIZED VEHICLE THE CUSTOMER WILL INSTALL AND MAINTAIN POWER COMPANY APPROVED BARRIER POST TO PROTECT THE EQUIPMENT. TRANSFORMER CLEARANCES ELECTRIC 5.6 TRANSFORMER CLEARANCES DATE: 10/12/2011 REV DATE: 10/12/2011

E.5.7 - EQUIPMENT EROSION PREVENTION TYPICAL ENCLOSURE RETAINING WALL INSTALLED BY THE DEVELOPER 6" MIN. ABOVE GRADE ORIGINAL GRADE A 4' SIDEWALK PRELIMINARY SLOPE 4'-0" 1'-0" PAD SIZE + 18" 18" 1. WHEN IT BECOMES NECESSARY TO NOTCH-OUT OR FILL A SLOPE TO INSTALL AN ENCLOSURE OR TRANSFORMER, THE CLEARED AREA SHOULD BE SUFFICIENT SIZE TO ACCOMMODATE THE ENCLOSURE AND SHORINGS. THE FRONT OF THE PAD SHALL BE PLACED 2" (MAX.) ABOVE THE SIDEWALK. 2. AREA UNDER AND BEHIND PAD MUST BE LEVEL AND COMPACTED. 3. A RETAINING WALL IS REQUIRED IF DIMENSION "A" IS GREATER THAN 12". 4. SIDE RETAINING WALLS ARE ALSO REQUIRED IF DIMENSION "A" IS GREATER THAN 18". RETAINING WALL SHALL BE 6" ABOVE EXISTING GRADE AND 18" FROM EACH SIDE AND BEHIND ENCLOSURE. 5. ALL GRADING SHALL BE PERFORMED BY DEVELOPER. 6. CONTACT THE POWER COMPANY IF ASSISTANCE IS REQUIRED. EQUIP. EROSION PREVENTION ELECTRIC 5.7 EQUIP. EROSION PREVENTION DATE: 10/12/2011 REV DATE: 10/12/2011

E.5.8 - THREE PHASE TRANSFORMER CONCRETE PAD WITHOUT CT RACK 5 8" x 8' COPPER GROUND ROD 15.5" 70" PRIMARY SECONDARY 5" 4" DIA. CONDUIT 17" 42" 17" 76" #4 BARS @ 12" O.C. BOTH WAYS 12" (TYP) 6" 1. CONCRETE SPECIFICATION - CLASS "B" CONCRETE MINIMUM. THREE PHASE TRANSFORMER PAD ELECTRIC 5.8 THREE PHASE CONCRETE PAD SCALE: 1/2"=1'-0" DATE: 12/01/2010 REV DATE: 12/01/2010

E.5.8 - THREE PHASE TRANSFORMER CONCRETE PAD WITHOUT CT RACK 5 8" x 8' COPPER GROUND ROD 15.5" 60" PRIMARY SECONDARY 5" 4" DIA. CONDUIT 17" 42" 17" 76" #4 BARS @ 12" O.C. BOTH WAYS 12" (TYP) 6" 1. CONCRETE SPECIFICATION - CLASS "B" CONCRETE MINIMUM. THREE PHASE TRANSFORMER PAD ELECTRIC 5.8.3 THREE PHASE CONCRETE PAD SCALE: 1/2"=1'-0" DATE: 12/01/2010 REV DATE: 12/01/2010

E.5.8 - THREE PHASE TRANSFORMER CONCRETE PAD WITHOUT CT RACK 5 8" x 8' COPPER GROUND ROD 16"-0" 7'-0" PRIMARY SECONDARY 1'-0" 4" DIA. CONDUIT (TYP) 1'-6" 4'-0" 1'-6" 7'-0" #4 BARS @ 12" O.C. BOTH WAYS 12" (TYP) 6" 1. CONCRETE SPECIFICATION - CLASS "B" CONCRETE MINIMUM. THREE PHASE TRANSFORMER PAD ELECTRIC 5.8 THREE PHASE CONCRETE PAD SCALE: 1/2"=1'-0" DATE: 12/01/2010 REV: B REV DATE: 09/29/2015

E.5.9 - THREE PHASE TRANSFORMER PAD WITH METERING STATION 12'-0" 2'-0" 4" DIA. CONDUIT 5 8" X 8' COPPER GROUND ROD 4'-0" 2'-0" 1'-6" 4'-0" 3" RIGID CONDUITS INSTALLED BY DEVELOPER #4 BARS @12" O.C. BOTH WAYS GALVANIZED CAPS (TYP) METER BASE INSTALLED BY DEVELOPER CONCRETE PAD INSTALLED BY DEVELOPER 6" MIN. 30" MIN. 5'-6" 7'-0" MAX. GALVANIZED UNISTRUT CONNECTED BACK TO BACK AND CLAMPED TO THE CONDUIT. INSTALLED BY DEVELOPER. 2' MIN. 1. CONCRETE SPECIFICATION - CLASS "B" CONCRETE MINIMUM 2. WILL NOT PULL OR TERMINATE COMMERCIAL SERVICES FROM SECONDARY SIDE OF TRANSFORMER. 3. DEVELOPER SHALL TERMINATE ALL CABLES FROM THE CT CANS IN. 4. CONTRACTOR SHALL TERMINATE ALL CABLES THEY RUN. 3 PHASE TRANSFORMER PAD ELECTRIC 5.9 3 PHASE TRANSFORMER PAD DATE: 10/12/2011 REV DATE: 10/12/2011

E.7.1 - SECTIONALIZERS & SWITCHES CONDUIT PLACEMENT FOR SECTIONALIZERS FRONT VIEW 1'-0" (TYP) SIDE VIEW 2" 6" 2" SEE NOTE #6 FOR CONDUIT SIZES (2) 5/8" x 8' COPPER GROUND RODS SEE NOTE #6 FOR CONDUIT SIZES TOP VIEW 1. ALL 90 DEGREE ELBOWS 6" OR LARGER SHALL BE PVC SCH. 40 UNLESS GOING UP A RISER POLE, THEN USE RIGID STEEL ELBOWS. 2. JUNCTION BOXES AND BASE WILL BE PROVIDED AND INSTALLED BY THE POWER COMPANY. 3. THE POWER COMPANY SHALL PROVIDE ALL GROUND RODS AND SUBSEQUENT MATERIALS TO COMPLETE THE INSTALLATION. 4. SEE SHEET E.2.2 FOR TYPICAL TRENCH CROSS SECTION DRAWING. 5. CONDUIT SIZES AND LOCATIONS WILL BE PROVIDED BY THE POWER COMPANY ON THE SUBDIVISION ELECTRICAL PLANS. SECTIONALIZERS & SWITCHES ELECTRIC 7.1 SECTIONALIZERS & SWITCHES DATE: 10/12/2011 REV DATE: 10/12/2011

E.7.3 - SECTIONALIZERS & SWITCHES CONDUIT PLACEMENT FOR SWITCHES * 10' MIN. CLEARANCE IN FRONT AND REAR 4'-6" (TYP) 3'-0" 6'-8" (4) 5/8" x 8' COPPER GROUND RODS 3'-0" 10'-0" MIN. CLEARANCE IN FRONT AND REAR 3'-0" 1'-0" (TYP) (4) 5/8" x 8' COPPER GROUND RODS 1. ALL 90 SWEEPS 3" OR LARGER SHALL BE 36" RADIUS OR LARGER. 2. SWITCHGEAR AND BASE WILL BE PROVIDED AND INSTALLED BY THE POWER COMPANY. 3. THE POWER COMPANY SHALL PROVIDE ALL GROUND RODS AND SUBSEQUENT MATERIALS TO COMPLETE THE INSTALLATION. 4. SEE SHEET E.2.2 FOR TYPICAL TRENCH CROSS SECTION DRAWING. 5. CONDUIT SIZES AND LOCATIONS WILL BE PROVIDED BY THE POWER COMPANY ON THE SUBDIVISION ELECTRICAL PLANS. SECTIONALIZERS & SWITCHES ELECTRIC 7.3 SECTIONALIZERS & SWITCHES DATE: 10/12/2011 REV DATE: 10/12/2011