FACILITY COMPONENTS - ELEMENTARY SCHOOL

Similar documents
FACILITY COMPONENTS - ELEMENTARY SCHOOL

FACILITY COMPONENTS - MIDDLE SCHOOL

Facility Improvements

Facility Improvements

Deficiency ID Qty UoM Priority. K Play Area Requires Impact Resistant Material Ea. 2

Chenango Valley Central School District Potential Capital Project BCK-IBI Group Project No October 23, 2017

Deficiency ID Qty UoM Priority. Concrete Walks Are Damaged And Require Replacement ,000 SF 3

CM ASSIGNMENT OF TEMPORARY FACILITIES see included IU Project Site Requirements

Appendix J - Custom Uniformat for EDU Migration

ADDENDUM 2 - JULY 14, 2015

Facility Improvements

Amos Alonzo Stagg Elementary School 7424 S Morgan St Chicago, IL 60621

A/E Design Deliverable Checklist

DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT

SEATON ELEMENTARY SCHOOL

Stephen Decatur Classical Elementary School 7030 N Sacramento Ave Chicago, IL 60645

1.0 Total Points % 2.1 Building Exterior Elements % 2.2 Accessibility % 2.3 Structural %

Facilities Feasibility Study Matthew A. Henson ES Condition Assessment

John T Pirie Fine Arts & Academic Center ES 650 E 85th St Chicago, IL 60619

James E McDade Elementary Classical School 8801 S Indiana Ave Chicago, IL 60619

DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT

WILKINSON ELEMENTARY SCHOOL

TABLE OF CONTENTS Public Safety Building

1.0 Total Points % 2.1 Building Exterior Elements % 2.2 Accessibility % 2.3 Structural %

Table of Contents. Division 2 Site Work Site Preparation Site Demolition Tree Protection Excavation, Trenching, and Backfilling for Utilities

LECKIE ELEMENTARY SCHOOL

RAYMOND EDUCATION CAMPUS

TABLE OF CONTENTS. (Δ = Rev 11/15) Update #7

TABLE OF CONTENTS. (Δ = Rev 04/17) Update #8

Charles H Wacker Elementary School

LASALLE - BACKUS EDUCATION CAMPUS

TABLE OF CONTENTS. (Δ = Rev 06/08)

Franklin Hall Renovation TABLE OF Document Indiana University Bloomington

Timberglen Recreation Center Summary

School Construction Authority Architecture & Engineering

Facilities Feasibility Study Laurence G. Paquin Building Condition Assessment

Collins Middle School

4.1.3 Project Manual

Frederic Chopin Elementary School

DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT

SERIES 0 BIDDING REQUIREMENTS AND CONTRACT FORMS

Facilities Feasibility Study Frederick Douglass HS Condition Assessment

A/E Design Deliverable Checklist

GARFIELD ELEMENTARY SCHOOL

Overbrook Theater / Fruenthal Foundation Art Center. 1.0 Total Points % 2.1 Building Exterior Elements %

Mills Elementary School Site Summary

DOCUMENT B. 2. The low bidder shall submit this Expanded Subcontractors Listing to the Owner within 24 hours after the bid opening.

3. 21st Century Learning A. Districtwide Flexible Learning $600,000 Subtotal $600,000

RECAPP Facility Evaluation Report

OFFICE OF EDUCATIONAL FACILITIES FLORIDA BUILDING CODE SECTION 423 APPLICATION MATRIX

KU West Campus LEEP II High Bay Facility Project # , A (c)

PROCUREMENT AND CONTRACTING DOCUMENTS GROUP

POWELL ELEMENTARY SCHOOL

COOLIDGE SENIOR HIGH SCHOOL

March 2018 Progress. Work Completed, Week Ending 3/23/18:

Minuteman Regional Vocational Technical School

LOGAN SCHOOL SCHOOL WITHOUT WALLS AT LOGAN

Simcoe County District School Board. 5yr Condition Assessment 2006/07 to 2010/11. Hillcrest PS (Barrie), 9205

HUGHES STADIUM CONTROLLED MAINTENANCE THROUGH 2020 Description of Projects on Facilities Management List September 18, 2014

Northwestern Facilities

Edmonton Public School District No. 7

1.0 Total Points % 2.1 Building Exterior Elements % 2.2 Accessibility % 2.3 Structural %

STUART-HOBSON MIDDLE SCHOOL

DESIGN & CONSTRUCTION GUIDELINES

DIVISION 2 SITE DEVELOPMENT DESIGN CONSIDERATIONS SECTION DESIGN GUIDELINES DUVAL COUNTY PUBLIC SCHOOLS

PROGRAM COST MODEL. for. PEER Tall Buildings Study Concrete Structural Option Los Angeles, California

M-DCPS MASTER SPECIFICATION GUIDELINES TABLE OF CONTENTS (TOC) Division 2 SITEWORK Last Revised

VOLUME 4 DIVISION SPECIFICATIONS

Minnie Mars Jamieson Elementary School 5650 N Mozart St Chicago, IL 60659

A UCC Building permit is not required for the exceptions listed below for COMMERCIAL application: (403.42): Building construction for the following:

Schedule of Values Cruise Terminal 2 Expansion

DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT

BRANDYCHASE CONDOMINIUM ASSOCIATION, INC. MAINTENANCE, REPAIR, AND INSURANCE RESPONSIBILITY CHART AUTHORITY FOR MAINTENANCE. Sec. 2(d)(1) and 17(b)(1)

CONSTRUCTION DOCUMENTS CHECKLIST for the 2012 Michigan Building Code Including Building Permit Application Checklist

Building Excellence IV Capital Levy Projects Under Construction

Simcoe County District School Board. 5yr Condition Assessment 2006/07 to 2010/11. Warnica PS, 9283

George Armstrong International Studies ES 2110 W Greenleaf Ave Chicago, IL 60645

Louis A Agassiz Elementary School

M-DCPS MASTER SPECIFICATION GUIDELINES TABLE OF CONTENTS (TOC) Division 2 SITEWORK Last Revised

M-DCPS MASTER SPECIFICATION GUIDELINES TABLE OF CONTENTS (TOC) Division 2 SITEWORK Last Revised

State of Ohio Ohio School Facilities Commission TABLE OF CONTENTS

Lake Highlands North Recreation Center Summary

Charles H Wacker Elementary School 9746 S Morgan St Chicago, IL 60643

Exhibit A Library Shell Construction

REHABILITATION STANDARDS CHECKLIST

The Report: Priority 1 thru 5 $ 2,933,064 New Construction $ 6,797,031 Less Redlined Items $ 218,060

Classification of Property

James Lick High School

FRANKLIN VILLAGE APARTMENTS Building I Franklin Street Morristown, NJ Block: 3901 Lots: 4,5,6

N o v e m b e r

Perkins Bass Elementary School 1140 W 66th St Chicago, IL 60621

LUFacilities Policy Service Level Agreement v1.1

T H E T O W N O F G U I L F O R D V E R M O N T

Project Status Report Property and Finance Committee Meeting August 6, 2013

K.B. Polk Recreation Center Summary

PHYSICAL EDUCATION September 30, 2010

Uniform Construction Code

Thurgood Marshall Recreation Center Summary

DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT

Transcription:

SITE AREAS Parking and Access - Buses 1.0 2.0 0.16 Five fewer bus stalls than minimum standard. Parking and Access - Service / Delivery 1.0 1.0 0.08 No delivery parking adjacent to delivery entrance. Parking and Access - Staff 1.0 3.0 0.24 Twenty fewer stalls than minimum standard. Parking and Access - Visitors 0.0 1.0 0.00 Designated visitor parking not provided. Student Drop Off - Pick Up 0.0 2.0 0.00 No on-site student drop-off / pick-up area. Street Frontage Sidewalks 2.0 1.0 0.16 On-Site Walkways 2.0 1.0 0.16 Stairs and Ramps NA 0.0 0.00 Hard Surface Play Areas 1.0 3.0 0.24 21,000 SF less than minimum standard. Lawns 2.0 2.0 0.31 Grass Play Area 2.0 3.0 0.47 Athletic Surfacing 2.0 1.0 0.16 Climbing Equipment Ground Surface 3.0 1.0 0.24 Dumpster Area 0.0 1.0 0.00 None. Dumpsters located in parking lot. Portable Classroom Infrastructure 3.0 1.0 0.24 SITE IMPROVEMENTS Fences and Gates 2.0 2.0 0.31 Backstop Fencing 3.0 1.0 0.24 Pipe Rail Gates and Railings 0.0 1.0 0.00 No pipe rail gates at delivery area and parking lots. Retaining Walls 4.0 1.0 0.31 Bicycle Racks 1.0 0.5 0.04 Bicycle racks are rusting and three are located in an unsupervised area near the gym. Dumpsters 2.0 1.0 0.16 Exterior Benches 1.0 0.5 0.04 No benches at hard surface play area. Exterior Waste Receptacles 1.0 0.5 0.04 Insufficient quantity. Exterior Bleachers NA 0.0 0.00 Flag Pole 2.0 0.5 0.08 Climbing Equipment 1.0 2.0 0.16 Wood equipment is old and does not meet minimum standard. Playground Equipment 1.0 2.0 0.16 Insufficient quantity of backboards, pickle ball courts and box hockey. Playground Striping 1.0 1.0 0.08 No basketball court striping in playshed. No box hockey circles. Reader Board 3.0 1.0 0.24 Site Sign 1.0 1.0 0.08 Wood sign is deteriorated, does not meet minimum standard, and school address not provided. Traffic Control Signs 2.0 1.0 0.16 Pavement Markings 2.0 1.0 0.16 11/21/2008 DS - Facility Component Assessment Page 1 of 7

LANDSCAPING Shrubs / Groundcover 2.0 2.0 0.31 Trees 1.0 2.0 0.16 No street trees at front of school. Wetlands NA 0.0 0.00 Irrigation System 2.0 2.0 0.31 UTILITIES Water System 2.0 3.0 0.47 Sanitary Sewer System 2.0 3.0 0.47 Storm Drainage System 2.0 3.0 0.47 Natural Gas Service 2.0 1.0 0.16 Fuel Storage Tanks NA 0.0 0.00 Electrical Service 2.0 3.0 0.47 Telephone Service 2.0 3.0 0.47 Cable Television Service 2.0 1.0 0.16 Internet Connection 2.0 3.0 0.47 Energy Usage - MBTUs / SF Building 1.0 5.0 0.39 Energy consumption level does not meet minimum standards. Water Usage - Domestic Water / SF Bldg. 1.0 5.0 0.39 Domestic water usage level does not meet minimum standards. Water Usage - Irrig. Water / SF Landscape 2.0 2.0 0.31 STRUCTURE Foundation 2.0 5.0 0.78 Floor Structure 2.0 5.0 0.78 Wall Structure - Bearing 1.0 5.0 0.39 Some walls do not meet minimum standard. Wall Structure - Non Bearing 2.0 5.0 0.78 Roof Structure 1.0 5.0 0.39 Some roof components do not meet minimum standards. BUILDING ENVELOPE Floors 4.0 3.0 0.94 Exterior Wall Surface 2.0 3.0 0.47 Exterior Wall Insulation 1.0 1.0 0.08 No exterior wall insulation except at gym and office area addition. Exterior Windows 1.0 3.0 0.24 Single-pane glazing does not meet minimum standard. Exterior Doors 2.0 1.0 0.16 Soffits 2.0 1.0 0.16 Flashing 2.0 1.0 0.16 Trim 2.0 1.0 0.16 Gutters and Downspouts 2.0 1.0 0.16 11/21/2008 DS - Facility Component Assessment Page 2 of 7

Roof Membrane 1.0 3.0 0.24 Roof membrane quality does not meet minimum standards and is past life expectancy. Roof Insulation 1.0 1.0 0.08 Insulation quantity does not meet minimum standard. Roof Accessories 2.0 1.0 0.16 Skylights 1.0 1.0 0.08 Skylights do not meet minimum standard for load capacity. Fall Arrest System 0.0 1.0 0.00 None at sloped metal roof area. Canopies 2.0 1.0 0.16 INTERIORS Floors - Classrooms 1.0 3.0 0.24 Carpet is in poor condition and no walk off mats at exterior doors. Floors - Corridors and Stairs 1.0 3.0 0.24 Carpet is in poor condition. Floors - Gymnasium 2.0 2.0 0.31 Floors - Kitchen 1.0 1.0 0.08 Floor tile does not meet minimum standard. Floors - Library 1.0 1.0 0.08 Carpet is in poor condition. Floors - Restrooms 1.0 1.0 0.08 Floor tile does not meet minimum standard. Floors - Support Spaces 2.0 1.0 0.16 Walls - Classrooms 2.0 3.0 0.47 Walls - Corridors and Stairs 2.0 3.0 0.47 Walls - Gymnasium 2.0 1.0 0.16 Walls - Kitchen 2.0 1.0 0.16 Walls - Library 2.0 1.0 0.16 Walls - Restrooms 2.0 1.0 0.16 Walls - Support Spaces 2.0 1.0 0.16 Asbestos-Containing Materials 2.0 1.0 0.16 Interior Doors 2.0 2.0 0.31 Door Hardware 2.0 2.0 0.31 Automatic Door Opener 2.0 1.0 0.16 Overhead Doors and Grilles 2.0 1.0 0.16 Interior Windows 2.0 1.0 0.16 Operable Walls NA 0.0 0.00 Ceilings - Classrooms 2.0 3.0 0.47 Ceilings - Corridors 2.0 3.0 0.47 Ceiling height does not meet minimum standard. Ceilings - Gymnasium 2.0 1.0 0.16 Ceilings - Kitchen 1.0 1.0 0.08 Ceiling height does not meet minimum standard. Ceilings - Library 3.0 1.0 0.24 Ceilings - Restrooms 2.0 1.0 0.16 11/21/2008 DS - Facility Component Assessment Page 3 of 7

Ceilings - Support Spaces 2.0 1.0 0.16 EQUIPMENT AND SPECIALTIES Marker Boards 2.0 1.0 0.16 Tackboards 2.0 1.0 0.16 Interior Signage 3.0 1.0 0.24 Toilet Partitions 2.0 0.5 0.08 Toilet Accessories 2.0 0.5 0.08 Lockers 0.0 2.0 0.00 None. Residential Appliances 3.0 1.0 0.24 Projection Screens 1.0 0.5 0.04 Projection screen in gym not motorized. Stage Curtains 2.0 1.0 0.16 Window Covering 1.0 1.0 0.08 Window coverings are in poor condition and do not meet minimum standard. Cabinets - Classrooms 2.0 3.0 0.47 Cabinets - Offices 2.0 1.0 0.16 Cabinets - Storage 2.0 1.0 0.16 Cabinets - Support Spaces 2.0 1.0 0.16 Display Cases 0.0 1.0 0.00 No permanent display cases. Equipment - Art 2.0 1.0 0.16 Equipment - Classrooms 3.0 3.0 0.71 Equipment - Food Service 1.0 2.0 0.16 No cook top and combi-oven. Dishwasher and convection ovens past life expectancy. Equipment - Gymnasium 1.0 1.0 0.08 No motorized or side-swing basketball backboards. Equipment - Library 3.0 1.0 0.24 Equipment - Offices / Workrooms 3.0 1.0 0.24 Equipment - Support Spaces 2.0 1.0 0.16 Furniture - Classrooms 1.0 3.0 0.24 Furniture - Library 2.0 1.0 0.16 Furniture - Offices / Workrooms 1.0 1.0 0.08 Furniture - Support Spaces 1.0 1.0 0.08 Some teacher desks do not meet minimum standards. Classroom furniture is mismatched and some is in poor condition. Some desks do not meet minimum standards and most of which are in marginal condition. Some desks do not meet minimum standards and most of which are in marginal condition. Artwork NA 0.0 0.00 Elevator NA 0.0 0.00 Vending Machines 0.0 0.5 0.00 None. Wheelchair Lift NA 0.0 0.00 MECHANICAL 11/21/2008 DS - Facility Component Assessment Page 4 of 7

Fire Suppression System 0.0 3.0 0.00 No fire sprinkler system. Plumbing Insulation 2.0 1.0 0.16 Domestic Water Equipment 2.0 3.0 0.47 Domestic Water Quality 1.0 3.0 0.24 One sink does not minimum water quality standards. Soil and Waste 2.0 3.0 0.47 Plumbing Fixtures 2.0 3.0 0.47 Natural Gas Piping 2.0 1.0 0.16 HVAC Duct Insulation 2.0 1.0 0.16 HVAC Pipe Insulation 2.0 1.0 0.16 Hydronic Piping 2.0 3.0 0.47 Hydronic Pumps 2.0 1.0 0.16 Refrigerant Piping 2.0 1.0 0.16 HVAC Ductwork 2.0 3.0 0.47 HVAC Fans 2.0 2.0 0.31 Heating / Ventilation System - Clrms. 2.0 3.0 0.47 Heating / Ventilation System - Gym 2.0 1.0 0.16 Heating / Ventilation System - Library 2.0 1.0 0.16 Heating / Ventilation System - Offices 1.0 1.0 0.08 Main office area overheats. Heating / Ventilation System - Wkrm. 2.0 1.0 0.16 Heating / Vent. System - Support Spaces 2.0 1.0 0.16 Air Terminal Units 2.0 1.0 0.16 Ventilation Hoods 1.0 1.0 0.08 No ventilation hood at kiln. Boilers 1.0 3.0 0.24 Boilers are past life expectancy. Furnaces NA 0.0 0.00 Heat Exchangers NA 0.0 0.00 Refrig. Compressors and Condensers 2.0 1.0 0.16 Water Chillers NA 0.0 0.00 Exhaust Fans 2.0 1.0 0.16 Heat Pumps NA 0.0 0.00 Fan Coil Units 2.0 1.0 0.16 Unit Ventilators 2.0 3.0 0.47 Unit Heaters 2.0 3.0 0.47 Automatic Controls 2.0 3.0 0.47 ELECTRICAL 11/21/2008 DS - Facility Component Assessment Page 5 of 7

Transformers 2.0 1.0 0.16 Switchgear 1.0 1.0 0.08 Switchgear does not have capacity to meet the calculated load. Panelboards 1.0 1.0 0.08 Some panels have fuse type breakers. Power Distribution 2.0 3.0 0.47 Power Conditioning 2.0 1.0 0.16 Wiring Devices 2.0 1.0 0.16 Electrical Outlets - Classrooms 2.0 3.0 0.47 Electrical Outlets - Library 2.0 1.0 0.16 Electrical Outlets - Offices / Wkrms. 2.0 1.0 0.16 Electrical Outlets - Support Spaces 2.0 1.0 0.16 Electrical Outlets - Emergency Power 3.0 1.0 0.24 Circuit Protection Devices 2.0 1.0 0.16 Packaged Generator 2.0 2.0 0.31 Battery Equipment 2.0 1.0 0.16 Lighting - Exterior - Bus Loading 1.0 1.0 0.08 Lighting level does not meet minimum standard. Lighting - Exterior - Main Entry 1.0 1.0 0.08 Lighting level does not meet minimum standard. Lighting - Exterior - Parking 1.0 2.0 0.16 Lighting level does not meet minimum standard. Lighting - Exterior - Pathways 1.0 1.0 0.08 Lighting level does not meet minimum standard. Lighting - Exterior - Playground 2.0 0.5 0.08 Lighting - Exterior - Playshed 2.0 0.5 0.08 Lighting - Exterior - Service / Delivery 1.0 1.0 0.08 Lighting level does not meet minimum standard. Lighting - Classrooms 1.0 3.0 0.24 Lighting level does not meet minimum standard. Lighting - Corridors 1.0 2.0 0.16 Lighting level does not meet minimum standard. Lighting - Emergency 1.0 1.0 0.08 Lighting level does not meet minimum standard. Lighting - Gymnasium 1.0 1.0 0.08 Lighting level does not meet minimum standard. Lighting - Kitchen 1.0 1.0 0.08 Lighting level does not meet minimum standard. Lighting - Library 1.0 1.0 0.08 Lighting level does not meet minimum standard. Lighting - Restrooms 1.0 1.0 0.08 Lighting - Support Spaces 1.0 1.0 0.08 Lighting level does not meet minimum standard. Lighting - Stage 3.0 1.0 0.24 Automatic Lighting Control 2.0 1.0 0.16 Exit Signs 2.0 1.0 0.16 Data Communications Cabling 3.0 3.0 0.71 Data Communications Equipment 1.0 2.0 0.16 Equipment other than UPS does not meet minimum standards. 11/21/2008 DS - Facility Component Assessment Page 6 of 7

Data Comm. Outlets - Classrooms 2.0 3.0 0.47 Data Comm. Outlets - Library 2.0 1.0 0.16 Data Comm. Outlets - Office / Wkrms. 2.0 1.0 0.16 Data Comm. Outlets - Support Spaces 2.0 1.0 0.16 Wireless Data Communications 2.0 1.0 0.16 Telephone / Intercom / Clock System 2.0 3.0 0.47 Telephone Handsets 4.0 1.0 0.31 Sound System 2.0 1.0 0.16 Television System 2.0 1.0 0.16 Audio - Video System 2.0 1.0 0.16 Intrusion Detection 2.0 1.0 0.16 Video Surveillance 2.0 1.0 0.16 Fire Detection and Alarm 2.0 3.0 0.47 TOTALS 42.6 11/21/2008 DS - Facility Component Assessment Page 7 of 7