EXPERIMENTAL EVALUATION OF THE INFLUENCE OF SEISMIC CLIPS ON GRID JOINTS IN A SUSPENDED CEILING SYSTEM

Similar documents
Shake table tests of perimeter-fixed type suspended ceilings

Seismic performance of suspended ceilings: Critical review of current design practice

Fully-Floating Suspended Ceiling System: Experimental Evaluation of Structural Feasibility & Challenges

Ductile moment-resisting connections in glulam beams

SEISMIC QUALIFICATION AND FRAGILITY TESTING OF SUSPENDED CEILING SYSTEMS

Development of fragility functions and seismic design procedure for automatic fire sprinkler systems

Technical Services Information Bureau

Available at: Last Modified: December 2012

METAL SUSPENSION SYSTEMS FOR LAY-IN PANEL CEILINGS: 2001 CBC IR

Seismic design of interior overhead non-structural elements

PERFORMANCE OF CEILINGS IN THE FEBRUARY 2011 CHRISTCHURCH EARTHQUAKE

P. Armaos & D.M. Thomson

Experimental study on the seismic performance of RC moment resisting frames with precast-prestressed floor units.

Seismic Performance of Hollow-core Flooring: the Significance of Negative Bending Moments

Store No MAY 13 Addendum No. 1 SECTION ACOUSTICAL PANEL CEILINGS

Assessment of Collapse Capacity of RC Buildings Based on Fiber-element Modelling

Suspension Systems for Acoustical Lay-in Ceilings Seismic Design Categories D, E & F

WHAT YOU NEED TO KNOW

The cracking behaviour of reinforced concrete beams under static and dynamic loading

QUALITY CONTROL TESTING OF PLASTERBOARD FOR BRACING APPLICATIONS. Y L Liew Vicroads Victoria, Australia

The Design of the Suspended T-bar Ceilings in accordance with AS for the New Royal Adelaide Hospital

Basic Suspension Systems

BRANZ FACTS RESILIENT NON-STRUCTURAL ELEMENTS SEISMICALLY RESILIENT NON-STRUCTURAL ELEMENTS # 3. Restraint systems

PRESTON HEALTH SERVICES ARCHITECT'S NO. 2700

Modelling of RC moment resisting frames with precast-prestressed flooring system

METALWORKS RH215 Faceted Custom Hook-on Panels

Shake Table Testing of a Low Damage Steel Building with Asymmetric Friction Connections (AFC)

EXPERIMENTAL INVESTIGATION ON THE INTERACTION OF REINFORCED CONCRETE FRAMES WITH PRECAST-PRESTRESSED CONCRETE FLOOR SYSTEMS

Seismic Suspension System Solutions

Construction Standards PAGE

Survey and Testing of Pre-1988 Braced Frame Structures From The West Coast of the United States

SECTION ACOUSTICAL PANEL CEILINGS

SEISMIC QUALIFICATION TESTS OF SPRINKLER SYSTEMS A STUDY FOR FLEXHEAD INDUSTRIES PART 1

FIRE RATED EXPOSED GRID CEILING SYSTEM

TOWARDS A NEW DELIVERY APPROACH TO IMPROVE THE PERFORMANCE OF NON- STRUCTURAL ELEMENTS IN NEW ZEALAND

Union County Vocational - Technical Schools Scotch Plains, New Jersey

Flexural, Axial Load and Elongation Response of Plastic Hinges in Reinforced Concrete Member

SECTION NON-STRUCTURAL SEISMIC DESIGN CRITERIA PART 1 - GENERAL 1.1 RELATED DOCUMENTS

Seismic Technical Guide

ShortSpan Brochure1 6/14/05 4:39 PM Page 1 CEILING SYSTEMS

DIVISION: FINISHES SECTION: SUSPENSION SYSTEMS SECTION: ACOUSTICAL CEILING SUSPENSION ASSEMBLIES REPORT HOLDER:

Installation Guide December 2012

Effect of reinforcing steel bond on the seismic performance of lightly reinforced concrete walls

MORE INFORMATION BPLA

SEISMIC CEILING SUSPENSION

SECTION COMPOSITE CORE ACOUSTICAL PANEL CEILINGS. Sound-Rite Inc. #9, rd Avenue NE Calgary, AB T2A 7P3

Generic Seismic Design

A. This Section includes ceilings consisting of acoustical panels and exposed suspension systems.

Student Services & Classroom Addition

Spectral Design Analysis of Sliding Hinge Joints and HF2V Devices for Seismic Dissipation

1. anticipated ground motion 2. type of soil in a specific geographic area 3. seismic use group designation

Establishing the resilience of timber framed school buildings in New Zealand

BRACED FRAME USING ASYMMETRICAL FRICTION CONNECTIONS (AFC)

METALWorkS. RH200 Custom Hook-on Panels. General Installation Instructions. Ceiling 1.0 GENERAL Site Conditions Product Description

AS/NZS :2017. Australian/New Zealand Standard. Bridge design. Part 6: Steel and composite construction AS/NZS :2017

Current Seismic Code Development and Adoption

Beam-column joint tests with grade 500E reinforcing

CYCLIC BEHAVIOR OF AN INNOVATIVE STEEL SHEAR WALL SYSTEM

HIGH PERFORMANCE WOODEN BUILDING SUBJECTED TO SEISMIC ACTION

Simple Complex Simple Complex

Seismic Ceiling Suspension Guide

Experimental studies on cyclic behaviour of steel base plate connections considering anchor bolts post tensioning

Union County Vocational - Technical Schools Scotch Plains, New Jersey

Available at: Last Modified: December 2012

Review of buckling restrained brace design and behaviour

DIVISION: FINISHES SECTION: SUSPENSION SYSTEMS SECTION: ACOUSTICAL CEILING SUSPENSION ASSEMBLIES REPORT HOLDER:

The influence of plasterboard clad walls on the structural behaviour of low rise residential buildings

STEEL PALLET RACKS Experimental characterization of the cross- and down-aisle seismic behaviour

Development of High Performance Structural Timver Systems for Non Residential Buildings in New Zealand and Australia

Modelling of post-tensioned precast reinforced concrete frame structures with rocking beam-column connections

Section 1: Summary and recommendations Volumes 1 3

Deformation Capacity of RC Structural Walls without Special Boundary Element Detailing

FASTLOCK SUSPENDED CEILING GRID ECOPLUS SYSTEMS. FasTLock SUSPENDED CEILING GRID. Stronger, more durable

AN OVERVIEW OF NONSTRUCTURAL COMPONENTS RESEARCH AT THREE U.S. EARTHQUAKE ENGINEERING RESEARCH CENTERS

THE SEISMIC PERFORMANCE OF FLOORING SYSTEMS EXECUTIVE SUMMARY. Dene Cook 1

Quantifying Building Engineering Demand Parameters in Seismic Events

DIVISION 5 METALS SECTION COLD-FORMED METAL FRAMING

The Development of Strain Penetration in Lightly Reinforced Concrete Shear Walls

CEILING SYSTEMS. What You Need to Know The Basics NEW Armstrong Seismic Rx A Code-Compliant Solution

SEISMIC PERFORMANCE OF CONCRETE TILT-UP BUILDINGS: CURRENT WALL-TO-SLAB CONNECTIONS

Seismic Technical Guide

Behavior of Reinforced Concrete Walls with Mesh Reinforcement Subjected to Cyclic Loading

Residual Stress Effects on the Seismic Performance of Low-Rise Steel Frames

Interaction between ductile RC perimeter frames and floor slabs containing precast units

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

Understanding cladding damage: A numerical investigation into a Christchurch earthquake case study

Performance-Based Seismic Design of Non-Structural Building Components

In-plane testing of precast concrete wall panels with grouted sleeve

System S 3 cliq. Exposed, seismic resistant. OWAlifetime collection

SEISMIC VULNERABILITY ASSESSMENT OF STEEL PIPE SUPPORT STRUCTURES

INELASTIC SEISMIC RESPONSE ANALYSES OF REINFORCED CONCRETE BRIDGE PIERS WITH THREE-DIMENSIONAL FE ANALYSIS METHOD. Guangfeng Zhang 1, Shigeki Unjoh 2

PROPOSED DEVELOPMENT OF A DAMAGE-RESISTING ECCENTRICALLY BRACED FRAME WITH ROTATIONAL ACTIVE LINKS.

CEILING DIAPHRAGM ACTIONS IN COLD FORMED STEEL- FRAMED DOMESTIC STRUCTURES

EXPERIMENTAL STUDY ON SEISMIC BEHAVIOR OF REINFORCED CONCRETE COLUMNS UNDER CONSTANT AND VARIABLE AXIAL LOADINGS

An Experimental Investigation of the Seismic Response of a Bridge due to Simultaneous Horizontal and Vertical Excitations

Christchurch City Council

MIDPLY Portal Frame as Lateral Bracing System in Light- Frame Wood Buildings

STRUCTURAL FIRE PERFORMANCE OF STEEL PORTAL FRAME BUILDINGS

Cyclic Loading Tests Of Steel Dampers Utilizing Flexure-Analogy of Deformation

Transcription:

EXPERIMENTAL EVALUATION OF THE INFLUENCE OF SEISMIC CLIPS ON GRID JOINTS IN A SUSPENDED CEILING SYSTEM Abstract Atefeh Pourali, Rajesh P. Dhakal, Gregory MacRae and Ali S. Tasligedik University of Canterbury Christchurch, New Zealand Suspended ceiling failure is frequently reported as a cause of financial loss following earthquakes. In typical suspended ceilings, the seismic inertial force flows from the tiles to the transverse grid members (i.e. cross tees) to the longitudinal grid members (i.e. the main tees) to the buildings through the perimeter supports. Hence, the ceiling system is only as strong as the weakest of the load path components. Experimental tests of different suspended ceiling components have identified the grid connections and rivet fixtures as the weakest components. Following these findings, the study reported herein aims at experimentally investigating the possibility of strengthening the connection between cross tees and main tees in suspended ceilings through the addition of a seismic clip. Different failure mechanisms were identified in the monotonic experiments. The tensile and compressive capacities of the grid joint with and without seismic clips in each failure mode were quantified and comparisons were made between the as-built and strengthened connections. The results showed an improvement in the load bearing capacity of the joints under monotonic tension and compression loading. The seismic clip also increased the deformability of the joint while it still carried reasonable amount of axial load. Introduction Perimeter-fixed suspended ceilings commonly used in commercial and educational buildings in New Zealand (NZ) consist of a grid system and lay-in acoustic tiles. The grid/suspension system consists of main tees (MTs) and cross tees (CTs) forming frame modules that support the tiles. The CT and MT ends are either fixed on perimeters via rivets or the suspension system is back braced to the upper floor. Unsatisfactory performance of such ceilings during earthquakes has raised concerns in the past (Dhakal 2010, Dhakal et al. 2011). Failure of ceilings results in costly and time consuming repairs and replacements. Damage to services and engineering systems within the ceiling plenum space can be critical and negatively affect the serviceability and performance of buildings. Identifying the performance issues and damage states in suspended ceilings has been the subject of many recent studies (ANCO 1983, Badillo-Almaraz et al. 2007, Paganotti 2010, Ryu et al. 2013, Soroushian et al. 2014, Pourali et al. 2015 & 2016). Reports are available in literature on shake table tests of full sized suspended ceilings (Badillo-Almaraz et al. 2007, Ryu et al. 2013, Pourali et al. 2015) and investigation of the capacity of individual ceiling components under monotonic and cyclic loads (Paganotti 2010, Soroushian et al. 2014, Pourali et al. 2016). Guidelines and recommendations for seismic design and installation of suspended ceilings have also been produced (AS/NZS 2785:2000, CISCA 2004, NZS 1170.5:2004, ASTM 2011, USG 2012, Armstrong 2013), and fragility curves for ceiling systems and components have also been developed (Badillo-Almaraz et al. 2007, Ryu et al. 2013). These provide valuable information for the industry in terms of the capacity and shortcomings of suspended ceiling systems. However, gaps still remain in the areas of retrofitting existing ceilings or developing more resilient ceiling systems. According to capacity design principles, a ceiling system s strength is defined by its weakest loadbearing component. Researchers (Badillo-Almaraz et al. 2007, Paganotti 2010, Ryu et al. 2013, Pourali et al. 2016) have identified that the weakest components of suspended ceiling system are the CT-MT connections and rivet fixtures around the perimeters of the ceiling grid. The rivets can be strengthened by increasing their size. However, the CT-MT connection still remains the weakest element contributing to ceiling system failure. The primary goal of the experiments reported in this paper is to investigate the effectiveness of a proposed suspended ceiling CT-MT joint strengthening solution. Monotonic tension and compression

tests are conducted on two configurations of CT-MT joints; the connection as built in practice and the connection strengthened with a cross-shaped seismic clip. The experiments aim to quantify the load bearing capacity of each connection configuration and provide qualitative endorsement of the proposed strengthening solution. Description of Experimental Program Test Specimen. Commonly available standard CT and MT sections in NZ were selected for testing (USG 2012 and USG 2011) that were also consistent with previous experiments conducted at the University of Canterbury (Paganotti 2010, Pourali et al. 2016). The seismic clips for strengthening the connection point is a proprietary product provided as a 4-way seismic separation joint (Figure 1a). Details of the sections and components used are provided in Table 1. Figure 1. (a) DH4 seismic clip as seismic joint; (b) CT-MT connection specimen with seismic clip and 2 rivets on CTs. Table 1. Details of Components used in Tests CT Section MT Section Seismic Clip Rivet DX30M-1200 (24 mm 32 mm) DX38D-3600 (24 mm 38 mm) DH4 1/8 or 3.2 mm AA 4-4 The cross-shaped specimens consisted of one horizontal MT and two vertical CTs that passed and connected through a MT slot. The MT length was such that specimens could fit in the test machine. Each CT was 300 mm long, making the CT part altogether 600 mm long. The cut ends of the CTs were flattened by pressure and screwed to the loading arms of the test machine. Two configurations of specimens were tested experimentally. The first consisted of MT and CTs, while the second used a seismic clip pushed in place on top of the CT-MT joints, fastened to CTs via two 3.2 mm Aluminium rivets (Figure 1b). The rivet on each wing was placed 10 mm from the clip edges. Test Setup. An Instron Universal Testing machine was used for tension and compression loading with strain control. The tension or compression forces and displacements applied were measured through a load cell and a potentiometer installed on the upper arm of the machine (Figure 2a). The test setup in the tensile tests consisted of the cross-shaped specimens and measurement instruments. The seismic clip maintained orthogonality between CTs and MT. In specimens without seismic clips, elastic strings were used to straighten up the MT without interfering with the load path. In compression tests, boundary conditions were introduced via additional components in the test setup in order to simulate the effect of ceiling tiles (Figure 2b). The rig consisted of a timber panel and eight 50 mm 50 mm 5 mm angles. The angles were screwed to the timber panel 4 mm from the edge of the

grids to allow for limited in-plane buckling. The MT piece was held horizontal to represent the effect of tiles, however small lateral displacements were allowed, as for real installations tiles are about 5 mm smaller than the module formed by the grids (this difference in size facilitates the installation of tiles in practice). Figure 2. Test setup in (a) tension, and (b) compression tests Experimental Program. Four series of ten tests were carried out, with 40 monotonic tests recorded in total, refer Table 2 for details. The loading rate in both tensile and compressive tests was 0.5 mm/min and the tests were continued until either brittle failure or very large deformations occurred at the CT- MT joint. Table 2. List and Number of Specimens Test Series Name Test Description No. CT-MT-T CT-MT connection in tension 10 CT-MT-C CT-MT connection in compression 10 CT-MT-CL-T CT-MT connection with seismic clips in tension 10 CT-MT-CL-C CT-MT connection with seismic clips in compression. 10 Experimental Results & Observations Tests under Tension. The CT-MT joint was observed to carry the axial load through an interlocking mechanism as shown in Figure 3. For this mechanism to work to its desired capacity, the CT latches (Figure 3-a) must be fully engaged and the load path needs to be aligned with the joint. Any rotations or small deformations may lead to latches disengaging and with no other mechanical fastening in the joint, they may carry a lower force than expected and easily disconnect under tension.

Figure 3. Mechanism of failure due to yielding in CT clip with the clip well engaged. In tension tests without clips two failure mechanisms were observed: i) failure with complete engagement of CT clips (Figure 3-b) (referred to as TF1 ), and ii) failure with premature disengagement of CT clips (referred to as TF2 ). Figure 3b-c show gradual yielding of a CT clip when latches on two connected CTs were engaged. In a less desirable condition, the latches prematurely released allowing the clips to slide past each other. When this occurred only the top and bottom dents in CT latches were observed to pull against the MT slot briefly before the joint disconnected, exposing the ceiling to local failure of grids and panel dislodgement. The premature failure in the CT clip resulted in failure of the joint at almost 30% of its intended capacity (Figure 5). With seismic clips added during tensile tests the CT-MT joint remained capable of transferring forces and withstanding deformations, despite the disengagement of the CT clip latches. The difference between specimens with good or premature engagement was mainly in the rate of deformation and development of buckling in the joint (Figure 4). Even after premature failure, unlike connections without seismic clip, the joint continued carrying forces (Figure 6). Complete joint failure involved total loss of load bearing capacity, which occurred after relatively large displacements between the disconnected CT clips. The use of seismic clips in this example increased the deformability of the CT-MT joint significantly. The final tensile failure modes with seismic clip were recorded as failure of the lower rivet connecting seismic clips to CT (Figure 4c) or tearing of the CT web at the location of rivet hole (Figure 4b). Figure 4. Failure of CT-MT joint with seismic clip in tension.

Figure 5. Results of tensile tests on CT-MT joints without seismic clips with (a) complete CT clip engagement and (b) CT clip disengaged. Figure 6. Results of tensile tests on CT-MT joints with seismic clips with (a) complete CT clip engagement and (b) CT clip disengaged. Comparing the median response curves for the two aforementioned conditions (CT clip engaged and disengaged) from Figure 5 and Figure 6 shows that adding seismic clips increased the load bearing capacity and deformability of the joint in both cases. Nevertheless, the stiffness of the joint was not significantly affected by this change. Tests under Compression. Compression failure mechanisms of CT-MT joints included in-plane and out-of-plane yielding of CT clips and penetration of CT section into MT web. The majority of specimens without seismic clips first underwent yielding in the CT clip latches. This was quickly followed by lateral buckling of the CT clip (Figure 7a). However, in some cases, CT clips were not engaged in the load path and slid parallel to each other and into the MT slot (Figure 7b), eventually tearing into the MT web (Figure 7c). Unlike tensile tests, the ultimate forces in compression tests were not significantly affected by the engagement of CT latches. This is due to the similarity of load bearing mechanism after the disengagement of the latches.

Figure 7. Failure of CT-MT joint in compression. With the addition of seismic clips, the deformation in the joint area changed to out-of-plane buckling as the seismic clip reduced the sideway deformation of the CT clip (Figure 8b). Here the CT clips bent about their major axis (Figure 8a), and afterwards the CT section pressed to the MT web, and consequently the force-displacement curves did not show a brittle failure as they did under tension (Figure 9). The addition of seismic clips increased the maximum force carried by the joint (Figure 9). This addition had no effect on the stiffness of the CT-MT joint. Figure 8. Failure in CT-MT joints with seismic clip: (a) bending in CT clip, and (b) out of plane buckling Figure 9. Results of compression tests on CT-MT joints (a) with, and (b) without seismic clips.

Development of Fragility Curves The fragility curves presented here are based on one damage limit state; The failure force is the maximum joint force carried before brittle failure, with a rapid drop in force or large deformations. Fragility curves for the tested specimens are created using lognormal distributions. Under tension the results showed a larger dispersion than in compression tests (Figure 10) due to the different performance of the joint with regard to the engagement of CT clip in carrying load. Separating the fragility curves in two categories based on the addition of seismic clips (Figure 10) quantified the improvement resulting from the strengthening solution. This improvement was more noticeable in tension tests due to the failure mode and the level of involvement of the seismic clip in load bearing. To determine the capacity of the entire ceiling system, fragility curves from Figure 10 need to be compared with the fragility curves previously derived for other components of a suspended ceiling e.g. end fixing rivets or MT splices (Figure 11) (Pourali et al. 2016, Paganotti 2010). When making such comparisons, it is important to consider that these results were obtained for standard grids which have a lower capacity than heavy-duty grids (Refer Section 2.1). Based on the comparisons in Figure 11, it is clear that the addition of seismic clips significantly improves the performance in tension, and some improvement can be observed in compression, too. However, Figure 11b emphasises that the strengthening solution needs to be accompanied with improvements in other components such as end fixing rivets. Figure 10. Fragility curves for all CT-MT joint tests (a) with, and (b) without seismic clip.

Figure 11. Fragility curves comparing other ceiling components (Paganotti 2010, Pourali et al. 2016) with CT-MT connections (a) without, and (b) with seismic clips. Conclusions Monotonic tension and compression tests were carried out on suspended ceiling cross tee-main tee (CT-MT) connection specimens with and without seismic clips. Results showed that using seismic clips improved CT-MT connection performance in two ways: i) increasing the capacity, and ii) adding deformability. During these tests different failure modes were observed in the connection point including disengagement of the CT clip, engagement and yielding of the CT clip, deformation and buckling of the CT clip, and penetration of CT clip into the MT web. When seismic clips were added, initial failure always occurred in the CT clip, followed by larger deformations and bending in the seismic clips. Comparison showed that using seismic clips in all cases increased the failure force in the connection. This improvement however, must be accompanied by strengthening the splices on MTs (e.g. by using a 2-way seismic separation joint clip) and increasing the size or number of end fixing rivets. With these improvements, if seismic clips are added, the system capacity will increase and the failure mode will no longer be brittle. The connection with clip underwent a number of failure and yielding phases while still carrying forces as large as that of the CT-MT connection alone. This ductility in the grid of suspended ceilings can delay the spread of damage and allow for the safe evacuation of occupants while still showing signs of damage. Acknowledgements The financial support towards the completion of this research project has been provided by the Natural Hazard Research Platform. The authors also acknowledge the extensive support from the University of Canterbury Structures Laboratory personnel throughout the experimental program. References ANCO Engineers Inc., 1983, Seismic Hazard Assessment of Non-Structural Ceiling Components: Phase I, Report No. 1249.12, Grant 8114155, National Science Foundation, Culver City, California, USA. Armstrong, 2013, Seismic Design Guide New Zealand Version, Suspended Ceiling Systems, Armstrong, Auckland, New Zealand. ASTM, 2011, E580/E580M-11b 2011.Standard Practice for Installation of Ceiling Suspension Systems for Acoustical Tile and Lay-in Panels in Areas Subject to Earthquake Ground Motions, PA, USA.

Australian/New Zealand Standard, 2000, AS/NZS 2785:2000 Suspended ceilings - Design and Installation, Standards New Zealand, Wellington, NZ. Badillo-Almaraz H., Whittaker A. S. and Reinhorn A. M., 2007, Seismic Fragility of Suspended Ceiling Systems, Earthquake Spectra, 23(1): 21 40. Ceilings and Interior Systems Construction Association CISCA, 2004, Guidelines for Seismic Restraint for Direct Hung Suspended Ceiling Assemblies, Seismic Zones 3-4, Ceiling and Interior Systems Construction Association, Illinois, USA. Dhakal R. P., 2010, Damage to Non-Structural Components and Contents in 2010 Darfield Earthquake, BNZSEE, 43(4): 404-411. Dhakal R. P., MacRae G. A. and Hogg K., 2011, Performance of Ceilings in the February 2011 Christchurch Earthquake, BNZSEE, 44(4): 379-389. New Zealand Standard, 2004, NZS 1170.5:2004, Structural Design Actions Part 5: Earthquake Actions-New Zealand, Standards New Zealand, Wellington, NZ. Paganotti G., 2010, Behaviour of Suspended Ceiling System during Seismic Events: Development of Fragility Curves, Masters Thesis, Politecnico Di Milano, Italy. Pourali A., Dhakal R. P., MacRae G. A. and Paganotti G., 2016, Seismic Fragility of Suspended Ceiling Systems Used in NZ Based on Component Tests, BNZSEE, Vol. 49, No. 1, March 2016. Pourali A., Dhakal R. P., MacRae G. A. and Tasligedik A. S., 2011, Shake Table Tests of Perimeter- Fixed Type Suspended Ceilings, Proceedings of NZSEE Conf., Rotorua, NZ, 10-12 April 2015. Rondo, 2008, DUO Two-way Exposed Suspended Ceiling Grid System, Rondo, Auckland, NZ. Ryu K. P., Reinhorn A. M., and Filiatrault A., 2013, Capacity Evaluation of Suspended Ceiling Systems, Technical Report MCEER-13-XXXX, Buffalo, NY, USA. Soroushian, S., Maragakis, M., & Jenkins, C., 2014, Axial capacity evaluation of typical suspended ceiling joints, Earthquake Spectra. 2014 Oct 31. USG Australia, 2011, DONN Brand Grid Suspension System, USG Australia, Auckland, NZ. USG Australia, 2012, Generic Seismic Design for USG DONN Exposed Grid Suspended Ceilings, Auckland, New Zealand.