UNDERWATER BRIDGE INSPECTION REPORT STRUCTURE NO CR 27 OVER THE RED LAKE RIVER DISTRICT 2 PENNINGTON COUNTY

Similar documents
UNDERWATER BRIDGE INSPECTION REPORT RED RIVER OF THE NORTH DISTRICT 4 - CLAY COUNTY, CITY OF MOORHEAD

UNDERWATER BRIDGE INSPECTION REPORT RED RIVER OF THE NORTH DISTRICT 4 - CLAY COUNTY

UNDERWATER BRIDGE INSPECTION REPORT DISTRICT 6 - RICE COUNTY

UNDERWATER BRIDGE INSPECTION REPORT STRUCTURE NO CSAH NO. 3 OVER THE RED LAKE RIVER DISTRICT 2 - PENNINGTON COUNTY

UNDERWATER BRIDGE INSPECTION REPORT DISTRICT 4 - WILKIN COUNTY

UNDERWATER BRIDGE INSPECTION REPORT STRUCTURE NO CSAH NO. 15 OVER THE ARCOLA CHANNEL HENNEPIN COUNTY

UNDERWATER BRIDGE INSPECTION REPORT DISTRICT 3 - MORRISON COUNTY

UNDERWATER BRIDGE INSPECTION REPORT DISTRICT 7 WATONWAN COUNTY

UNDERWATER BRIDGE INSPECTION REPORT STRUCTURE NO MSAS NO. 119 OVER THE RED LAKE RIVER DISTRICT 2 - POLK COUNTY, CITY OF EAST GRAND FORKS

UNDERWATER BRIDGE INSPECTION REPORT STRUCTURE NO CSAH NO. 5 (FRANKLIN AVENUE) OVER THE MISSISSIPPI RIVER HENNEPIN COUNTY

UNDERWATER BRIDGE INSPECTION REPORT STRUCTURE NO COUNTY STATE AID HIGHWAY 10 OVER THE POMME DE TERRE RIVER DISTRICT 4 STEVENS COUNTY

UNDERWATER BRIDGE INSPECTION REPORT STRUCTURE NO. 69J13 RAILROAD STREET OVER STORM SEWER CITY OF DULUTH

UNDERWATER BRIDGE INSPECTION REPORT STRUCTURE NO. 55J11 TWP 197 (70 TH AVE NW) OVER A STREAM DISTRICT 6 OLMSTED COUNTY

UNDERWATER BRIDGE INSPECTION REPORT STRUCTURE NO CR 958 OVER A STREAM ST. LOUIS COUNTY

UNDERWATER BRIDGE INSPECTION REPORT STRUCTURE NO TRUNK HIGHWAY NO. 3 rd Avenue/Central Avenue OVER THE MISSISSIPPI RIVER

2016 UNDERWATER BRIDGE INSPECTION REPORT. CSAH 22 over POMME DE TERRE RIVER. Date of Inspection: Equipment Used: 06/18/2016. County Highway Agency

2016 UNDERWATER BRIDGE INSPECTION REPORT. CSAH 3 over RED LAKE RIVER. Date of Inspection: Equipment Used: 09/26/2016. County Highway Agency

2016 UNDERWATER BRIDGE INSPECTION REPORT. ST GERMAIN over MISSISSIPPI RIVER. Date of Inspection: Equipment Used: 09/30/2016

2016 UNDERWATER BRIDGE INSPECTION REPORT. CSAH 14 over OTTER TAIL RIVER. Date of Inspection: Equipment Used: 07/26/2016. County Highway Agency

2017 UNDERWATER BRIDGE INSPECTION REPORT BRIDGE # CSAH

2016 UNDERWATER BRIDGE INSPECTION REPORT. CSAH 20 over POMME DE TERRE RIVER. Date of Inspection: Equipment Used: 06/18/2016. County Highway Agency

2016 UNDERWATER BRIDGE INSPECTION REPORT. CSAH 31 over RABBIT LAKE NARROWS. Equipment Used: Life Jacket, Probing Rod, Other - boat, hammer

COLLEGE DR (126) over MISSISSIPPI RIVER

Cast in place concrete parapet and Ministry standard sidewalk railing.

ESTABLISHING A SOLID FOUNDATION FOR NEW BRIDGE CONSTRUCTION REPLACEMENT OF BRIDGE OVER THE SOUTH CANADIAN RIVER NEAR PURCELL, OKLAHOMA

US 278 East Bound and West Bound. MacKay Creek and Skull Creek. Cursory Above Water and Underwater Investigation Of. Over

2017 UNDERWATER BRIDGE INSPECTION REPORT. CSAH 8 over KNIFE RIVER. Date of Inspection: Equipment Used: 04/06/2017. County Highway Agency.

SIAMA. SIAMA Asset Management Technologies Level-2 Bridge Condition Inspection

2017 UNDERWATER BRIDGE INSPECTION REPORT. CSAH 7 over ST LOUIS RIVER. Date of Inspection: Equipment Used: 09/12/2016. County Highway Agency

2016 UNDERWATER BRIDGE INSPECTION REPORT. CSAH 108 over PALEFACE RIVER. Date of Inspection: Equipment Used: 06/18/2016. County Highway Agency

PONTIS BRIDGE INSPECTION FIELD MANUAL FOR OKLAHOMA BRIDGES

2017 UNDERWATER BRIDGE INSPECTION REPORT. CSAH 25 over ROOT RIVER. Date of Inspection: Equipment Used: 10/21/2016. County Highway Agency

SOUTHEAST TEXAS CONTINUING EDUCATION BRIDGE INSPECTION, MAINTENANCE AND REPAIR

1 layer of untreated timber running planks, 254 mm x 89 mm.

2017 UNDERWATER BRIDGE INSPECTION REPORT. CEDAR (10TH) over MISS R; BNSF STS. Date of Inspection: Equipment Used: 07/07/2017

2017 UNDERWATER BRIDGE INSPECTION REPORT. ELM WAY over MINNESOTA RIVER. Date of Inspection: Equipment Used: 06/07/2017. County Highway Agency

Two glulam slab girders, 365 mm x 1825 mm spaced at 3065 mm c/c.

2017 UNDERWATER BRIDGE INSPECTION REPORT. PLYMOUTH AVE over MISSISSIPPI RIVER. Date of Inspection: Equipment Used: 06/02/2017

APPENDIXB PHOTOGRAPHS B - 1

2 AVE SW(MSAS 123) over CANNON RIVER

FRST 557 Lecture 7b Cross Drainage Structures: Culverts and Bridges

ICE Pier Conditions 1995 Divers' reports of the condition of the ice piers in New Castle Harbor. 1995?

Ontario Structure Inspection Manual Inspection Form Structure Number: 12

2016 UNDERWATER BRIDGE INSPECTION REPORT. CSAH 11 over CANNON RIVER. Equipment Used: A-62. County Highway Agency. Inspected By: Owens, Garrett

2016 UNDERWATER BRIDGE INSPECTION REPORT. MUN 28 over RIVER DR/OTTER TAIL RIVE. Date of Inspection: Equipment Used: 10/17/2016

VDOT s Experience with Reinforced Concrete and Metal Culverts

Mn/DOT BRIDGE INSPECTION REPORT

State of New Jersey NEW JERSEY DEPARTMENT OF TRANSPORTATION 1035 PARKWAY AVENUE P.O. Box 600 TRENTON, NEW JERSEY

MISENER DAM. Site Number LYNN STREET, PORT DOVER km N of Highway 6

Appendix A. Sample Inspection Report

LAKE CHEMUNG DAM LOCATION MAP

2017 UNDERWATER BRIDGE INSPECTION REPORT. QUAKER AVE over Minnesota River. Date of Inspection: Equipment Used: 05/25/2017. County Highway Agency

VENISON CREEK BRIDGE

NORWICH ROAD BRIDGE. Site Number D00016 NORWICH ROAD, DELHI. 1.0 km N of King Street Delhi

Bridge Asset Management City of Battle Creek Planning and Projects

2016 UNDERWATER BRIDGE INSPECTION REPORT. CSAH 133 over WHITEFACE RIVER. Date of Inspection: Equipment Used: 06/24/2016. County Highway Agency

RECOMMENDED PROCEDURES FOR RAILWAY CULVERT INSPECTION

VDOT s Strategic Approach to Bridge Management and Maintenance

STRUCTURES INSPECTION CERTIFICATION TRAINING COURSE

Inspection Form Completion

RETROFIT AND REPLACEMENT OF DUMBARTON RAILROAD BRIDGES

The Leader in Underwater Piling Repair Technology

LYNNVILLE ROAD BRIDGE. Site Number D00027 LYNNVILLE ROAD, CONCESSION 11, WINDHAM. 2.3km W of Highway 24

BRIDGE INSPECTION REPORT

LOT 4 CONCESSION 11-12, N. WALSINGHAM

DIVISION 31 EARTHWORK SECTION TIMBER PILES

Inspection Frequency MiSIM Chapter 3

MEMORANDUM. Norm Evenstad, Water Resources Program Coordinator, Natural Resources Conservation Service (NRCS), Salt Lake City, Utah

2016 UNDERWATER BRIDGE INSPECTION REPORT. CR 356 over STREAM. Date of Inspection: Equipment Used: 06/20/2016. County Highway Agency.

Village of Hasting-on-Hudson, NY DRAFT Water Tower Evaluation Attorney-Client Work Product For Discussion Purposes Only

3. INSPECTION FINDINGS

East Lyme Middle School EAST LYME MIDDLE SCHOOL

The Chief Estimator Software. Item Cost Summary Bridge & Overpass Projects

ERRATA SHEET RECORDING AND CODING GUIDE FOR THE STRUCTURE INVENTORY AND APPRAISAL OF THE NATION=S BRIDGES REPORT NO. FHWA-PD , DECEMBER 1995

MICHIGAN DEPARTMENT OF TRANSPORTATION

MICHIGAN DEPARTMENT OF TRANSPORTATION

Cochran Mill Road Bridge over Tuscarora Creek

BRANT - NORFOLK TOWNLINE ROAD

Arnold Mill Rd (SR 140) Over Little River

2016 UNDERWATER BRIDGE INSPECTION REPORT. CSAH 15 over ARCOLA CHANNEL. Date of Inspection: Equipment Used: 09/07/2016. County Highway Agency

MINNESOTA DEPARTMENT OF TRANSPORTATION BRIDGE SCOUR EVALUATION PROCEDURE FOR MINNESOTA BRIDGES

2016 STRUCTURE INSPECTION APPRAISAL REPORT. Prepared For: THE CORPORATION OF THE TOWNSHIP OF AMARANTH COUNTY OF DUFFERIN

RENTON CONCESSION CULVERT. Site Number COUNTY ROAD 5, WOODHOUSE. 0.4 km S of Highway #3

Superstructure Guidelines

PLANNING AND DESIGN PARAMETERS BRIDGE STRUCTURES. Engr. Ericson Mammag Feasibility Study Preparation CHARM2 Project

STRUCTURAL EVALUATION REPORT

Final Estimates Level 2

A STRUCTURAL ASSESSMENT STUDY ON THE SUSTAINABILITY OF SULTAN ISKANDAR BRIDGE KUALA KANGSAR PERAK MALAYSIA

SCOPE OF WORK. Consultant: An individual or firm, who is contracted to furnish services outlined in this scope of work.

Municipal Structure Inspection Form Structure Number: 5

EAST ¼ LINE BRIDGE, CONCESSION 2

DECOU ROAD BRIDGE. Municipal Structure Inspection Form NORFOLK COUNTY. Site Number DECOU ROAD, SIMCOE. 1.Okm E of Willow Drive

MICHIGAN DEPARTMENT OF TRANSPORTATION

System Preservation in Louisiana

Marina Coast Water District Marina, CA Steel Reservoir #2

Alberta Transportation Bridge Inspection & Maintenance System (Web 2005) Bridge. Bridge Inspection Form Type Lot No. 2

Strengthened Bascule Piers for the Newly Rehabilitated Bridge of Lions

Fracture Critical Bridge Inspection. Presented by MN/DOT Bridge Safety Inspections

2008 Bridge Load Rating Class 101

Transcription:

UNDERWATER BRIDGE INSPECTION REPORT STRUCTURE NO. 57521 CR 27 OVER THE RED LAKE RIVER DISTRICT 2 PENNINGTON COUNTY PREPARED FOR THE MINNESOTA DEPARTMENT OF TRANSPORTATION BY COLLINS ENGINEERS, INC. JOB NO. 5221 (CEI 34)

MINNESOTA DEPARTMENT OF TRANSPORTATION UNDERWATER BRIDGE INSPECTION REPORT SUMMARY: The substructure units inspected at Bridge No. 57521, Piers 1 and 2, were found to be in good condition with no defects of structural significance at this time. The channel bottom around the substructure units was well established and in stable condition with no evidence of significant scour. INSPECTION FINDINGS: (A) The 16 inch diameter steel pipe pile encasements over the H-piles of both piers were coated from top of pile down 5 feet. The piles exhibited random minor areas of coating loss on less of 1% of total surface area. In the locations of coating loss, the encasement exhibited minor corrosion with no section loss. From 5 feet below the top of encasement to channel bottom, the encasements were coated with only a primer coat. In the areas where the encasements were not top coated, the encasements exhibited corrosion on up to 75% of total surface area. The corrosion consisted of rust nodules up to ¼ inch in diameter and minor pitting (less than 1/32 inch deep). (B) A minor accumulation of timber debris consisting of logs and branches up to 6 inches in diameter and a steel I-beam were observed extending from south shoreline to easternmost pile of Pier 1. The debris accumulation extended from the channel bottom to the waterline and was approximately 10 feet long (N/S) by 5 feet wide (E/W). (C) The channel bottom at Piers 1 and 2 consisted of sand, gravel, cobbles up to 6 inches in diameter, and riprap up to 2 feet in diameter with up to 3 inches of probe rod penetration possible.

RECOMMENDATIONS: (A) Reinspect the submerged substructure units at the normal maximum recommended (NBIS) interval of five (5) years.

MINNESOTA DEPARTMENT OF TRANSPORTATION UNDERWATER BRIDGE INSPECTION 1. BRIDGE DATA Bridge Number: 57521 Feature Crossed: Red Lake River Feature Carried: TWP Road CR 27 Location: District 2 Pennington County Bridge Description: The bridge superstructure consists of three spans of cast-in-place reinforced concrete structure. The superstructure is supported by two reinforced concrete abutments and two reinforced concrete piers. The piers are supported on steel H-piles and they are numbered 1 and 2 starting from south to north. 2. INSPECTION DATA Professional Engineer Diver: Bradley A. Syler, P.E., S.E. Dive Team: John J. Loftus, Valerie Roustan Date: August 18, 2007 Weather Conditions: Partly Cloudy, 69 o F Underwater Visibility: 4 feet Waterway Velocity: 1.5 f.p.s

3. SUBSTRUCTURE INSPECTION DATA Substructure Inspected: Piers 1 and 2. General Shape: The pier caps are concrete with an oblong rectangular shape having rounded noses, and are founded on H-piles with steel shell pile (concrete filled) encasements. Maximum Water Depth at Substructure Inspected: Approximately 5.6 feet. 4. WATERLINE DATUM Water Level Reference: Top of pier cap on east end of Pier 1. Water Surface: The waterline was approximately 12.2 feet below the reference. Waterline Elevation 1154.8. 5. NBIS CODING INFORMATION (Minnesota specific codes are used for 92B and 113) Item 60: Substructure: Code 7 Item 61: Channel and Channel Protection: Code 7 Item 92B: Underwater Inspection: Code B/08/07 Item 113: Scour Critical Bridges: Code F/07 Bridge is scour critical because abutment or pier foundation is rated as unstable due to observed scour at bridge site. Yes X No

Photograph 1. View of Pier 1, Looking Northwest. Photograph 2. View of Pier 1 and South Abutment, Looking Southeast.

Photograph 3. View of Pier 2, Looking Northwest. Photograph 4. View of Pier 2, Looking South.

MINNESOTA DEPARTMENT OF TRANSPORTATION OFFICE OF BRIDGES AND STRUCTURES DAILY DIVING REPORT INSPECTORS: Collins Engineers, Inc. DATE: August 18, 2007 ON-SITE TEAM LEADER: Bradley A. Syler, P.E., S.E. BRIDGE NO: 57521 WEATHER: Partly Cloudy, 69 o F WATERWAY CROSSED: Red Lake River DIVING OPERATION: X SCUBA SURFACE SUPPLIED AIR OTHER PERSONNEL: John J. Loftus, Valerie Roustan EQUIPMENT: Scuba, U/W Light, Scraper, Lead Line, Probe Rod, Camera TIME IN WATER: 8:45 a.m. TIME OUT OF WATER: 9:10 a.m. WATERWAY DATA: VELOCITY 1.5 f.p.s VISIBILITY 4.0 feet DEPTH 5.6 feet maximum at Pier 1 ELEMENTS INSPECTED: Piers 1 and 2 REMARKS: Overall, the 16 inch diameter steel pipe pile encasements over the H-piles of both piers were coated from top of pile down 5 feet. The coating exhibited random minor areas of coating loss on less of 1% of total surface area. In the location of coating loss, the encasement steel exhibited minor corrosion with no section loss. From 5 feet below the top of encasement to channel bottom, the encasements were not top coated and there was only a primer coating on the encasements. In the areas where the encasements were not top coated, the encasements exhibited corrosion on up to 75% of total surface area. The corrosion consisted of rust nodules up to ¼ inch in diameter and minor pitting (less than 1/32 inch deep). A minor accumulation of debris consisting of logs and branches up to 6 inches in diameter and a steel I-beam was observed extending from south shoreline to easternmost pile of Pier 1. The debris extended from the channel bottom to the waterline and was approximately 10 feet long (N/S) by 5 feet wide (E/W). FURTHER ACTION NEEDED: YES X NO Reinspect the submerged substructure units at the normal maximum recommended (NBIS) interval of five (5) years.

MINNESOTA DEPARTMENT OF TRANSPORTATION OFFICE OF BRIDGES AND STRUCTURES UNDERWATER INSPECTION CONDITION RATING FORM BRIDGE NO. 57521 INSPECTION DATE August 18, 2007 INSPECTORS Collins Engineers, Inc. NOTE: USE ALL APPLICABLE CONDITION ON-SITE TEAM LEADER Bradley A. Syler, P.E., S.E. DEFINITIONS AS DEFINED IN THE MINNESOTA WATERWAY CROSSED Red Lake River RECORDING AND CODING GUIDE INCLUDING GENERAL, SUBSTRUCTURE, CHANNEL AND PROTECTION, AND CULVERTS AND WALL DEFINITIONS TO COMPLETE THIS FORM. CONDITION RATING SUBSTRUCTURE CHANNEL GENERAL UNIT REFERENCE NO. MAXIMUM DEPTH OF WATER PILING COLUMNS, SHAFTS, OR FACES* FOOTINGS DISPLACEMENT OTHER (BRACING) OVERALL SUBSTRUCTURE CONDITION CODE* SCOUR EMBANKMENT EROSION EMBANKMENT PROTECTION OTHER (DRIFT/DEBRIS) OVERALL CHANNEL & PROTECTION CONDITION CONCRETE STEEL TIMBER LOSS OF SECTION PREVIOUS REPAIR OR MAINTENANCE OTHER UNIT DESCRIPTION 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 Pier 1 2.7 7 N N 9 N 7 8 8 8 7 7 N 8 N 8 N N Pier 2 2.2 7 N N 9 N 7 8 8 8 N 8 N 8 N 8 N N *UNDERWATER PORTION ONLY REMARKS: Overall, the 16 inch diameter steel pipe pile encasements over the H-piles of both piers were coated from top of pile down 5 feet. The coating exhibited random minor areas of coating loss on less of 1% of total surface area. In the location of coating loss, the encasement steel exhibited minor corrosion with no section loss. From 5 feet below the top of encasement to channel bottom, the encasements were not top coated and there was only a primer coating on the encasements. In the areas where the encasements were not top coated, the encasements exhibited corrosion on up to 75% of total surface area. The corrosion consisted of rust nodules up to ¼ inch in diameter and minor pitting (less than 1/32 inch deep). A minor accumulation of debris consisting of logs and branches up to 6 inches in diameter and a steel I-beam was observed extending from south shoreline to easternmost pile of Pier 1. The debris extended from the channel bottom to the waterline and was approximately 10 feet long (N/S) by 5 feet wide (E/W). NOTES: ATTACH SKETCHES AS NEEDED, IDENTIFY REMARK BY REFERRING TO UNIT REFERENCE NO. AND REMARK NO. USE GENERAL SECTION TO IDENTIFY OVERALL PRESENCE OF SPALLS, CRACKS, CORROSION, ETC.