SECTION PART 1 GENERAL

Similar documents
SECTION GROUNDING AND BONDING

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

SECTION GROUNDING AND BONDING

SECTION GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

SECTION GROUNDING AND BONDING

SECTION GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY

SECTION GROUNDING

Essex County College - West Essex Campus Addition And Renovations dlb # / 11-14

A. All materials shall be tested and listed by an OSHA approved Nationally Recognized Testing Laboratory (NRTL).

SECTION GROUNDING AND BONDING

CONTENTS. B. System Design and Performance Requirements

NYULMC AMBULATORY CARE CENTER FIT-OUT PHASE 1 Perkins & Will Architects PC 222 E 41st ST, NYC Project: Issued for GMP March 15, 2017

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

SECTION LIGHTNING PROTECTION SYSTEM

SECTION GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS

CONSULTING ENGINEERS 5145 Livernois, Suite 100 Troy, Michigan Tel: Fax:

SECTION FACILITY LIGHTNING PROTECTION

This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update.

A. The work consists of furnishing a Chiller Noise Reduction System as listed in the specifications.

SECTION ENCLOSED BUS ASSEMBLIES

Kaf-Tech Product Specification

SECTION (16071) - VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS

DESIGN GUIDELINES WIRING AND CONDUITS PAGE 1 of 7

SECTION ENCLOSED BUS ASSEMBLIES

A. Product Data shall be provided for each type of product indicated.

This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update.

UNDERGROUND SERVICES SECONDARY

B. Insulated Conductors: Stranded copper wire, green or green with yellow stripe insulation, insulated for 600 V, and complying with UL 83.

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 26 ELECTRICAL SECTION RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS

2003 International Residential Code ELECTRICAL PROVISIONS ONLY October 2005 EDITORIAL CHANGES SEVENTH PRINTING

SECTION SECONDARY UNIT SUBSTATIONS

Student Services & Classroom Addition

NORTHEASTERN REMC ELECTRIC STANDARDS MANUAL

1. Fence and gate posts, rails, and fittings. 2. Chain-link fabric, reinforcements, and attachments.

SECTION EARTHING AND EARTH FAULT PROTECTION

UNIFIED FACILITIES GUIDE SPECIFICATIONS

SECTION CHAIN-LINK FENCES AND GATES 02821/1

Standard of Practice - Campus Electrical Distribution System

SERVICES CHAPTER 35. wire. For all other installations, the rating of the ungrounded conductors shall be not less than 60 amperes.

SECTION A. ASTM B3 - Standard Specification for Soft or Annealed Copper Wire; 2013.

SECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES

EFFECTIVE DATE: November 1, 2011, unless a later date is cited at the end of a section. [ NMAC - Rp,

2008 NEC Guide Lines for Home Owner Doing Electrical Work on their Property

Youngstown State University

1.05 Power System Fault and Coordination Study with Arc Flash Calculations

A. Section includes busway and fittings including plug-in units.

SECTION PATHWAYS FOR COMMUNICATIONS SYSTEMS

Design Standard Conduit for Electrical Systems

SECTION CONDUITS AND BACKBOXES FOR COMMUNICATIONS SYSTEMS

SECTION BUSWAYS

A. Product Data: For surface pathways, wireways and fittings, floor boxes, hinged-cover enclosures, and cabinets.

1. Telecommunications mounting elements. 2. Backboards. 3. Telecommunications equipment racks and cabinets. 4. Grounding.

The University of Texas at Austin September 30, 2011

B. Provide a complete conduit system with associated couplings, connectors, and fittings.

Inspection Guide for PV Systems in One- and Two- Family Dwellings (For Rooftop Photovoltaic Systems meeting the Standard Plan)

NORTHEASTERN REMC ELECTRIC STANDARDS MANUAL

DIVISION 26 RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS PART 1 - GENERAL RELATED DOCUMENTS

SECTION LOW-VOLTAGE TRANSFORMERS

1. Hangers and supports for electrical equipment and systems.

SECTION CONDUITS AND BOXES PART 1- GENERAL. A. Work covered by this section includes the furnishing and installation of conduits and boxes.

CHAPTER 13 GROUNDING AND BONDING

CONSTRUCTION SPECIFICATION FOR GROUNDING

SECTION WIRE, CABLE AND BUSWAYS. A. This section specifies providing wire, cable and busways.

OVERHEAD SERVICES - SECONDARY

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

SECTION VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS

IMPORTANT CODE UPDATE ENFORCEMENT DATE FOR NEW NATIONAL ELECTRIC CODE IS SET FOR MAY 1, 2013

A. Provide a complete Distribution Panelboard system as indicated on the drawings, and as specified herein.

SECTION BASIC ELECTRICAL REQUIREMENTS

Essex County College - West Essex Campus Addition And Renovations dlb # / SECTION CABLE TRAYS FOR COMMUNICATIONS SYSTEMS

SECTION PATHWAYS FOR ELECTRONIC SAFETY AND SECURITY

SECTION PARK NON-SEGREGATED BUS SPECIFICATION

A. This section includes building wire and cable rated 600V and less Full Short Circuit Device, Coordination and Arc Fault Study

EFFECTIVE DATE: July 1, 2008, unless a later date is cited at the end of a section. [ NMAC - Rp,

NORTHWESTERN UNIVERSITY PROJECT NAME JOB #

A. Basket Cable Tray: A fabricated structure consisting of wire mesh bottom and side rails.

SECTION WIRE AND CABLE Raceways and Conduit Motor Power and Control Wiring.

8. REVENUE METERING. Operational Excellence Model. 8.1 Introduction

8.1.2 Under no circumstances shall a service entrance be left unmetered. Notify the Company if an unmetered service is encountered.

SECTION HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS

SECTION VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS

SECTION MINOR ELECTRICAL DEMOLITION

Replace 210.8(a)(7) with: Sinks. Where receptacles are installed within 6 feet of the outside edge of a sink. Page 1 of 5

NEC 2014 Code Changes

Section 7: Specifications

Student Services & Classroom Addition SECTION VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS

WIRE AND CABLE Raceways and Conduit Motor Power and Control Wiring.

Repair Maintenance Hangar Phase II August 2010 SECTION LIGHTNING PROTECTION SYSTEM PART 1 GENERAL

GLENWOOD PLACE 2 MAR 2015

SPECIAL SPECIFICATION 6499 Environmentally controlled Communications Building

3. Intermediate metal conduit (IMC). 4. Electric metallic tubing (EMT). 5. Flexible metal conduit (FLEX). 6. Polyvinyl chloride conduit (PVC).

SOUTHERN NEVADA AMENDMENTS TO THE 2018 NATIONAL ELECTRICAL CODE

SECTION (Master Template Final-05) ELECTRICAL BOXES. A. Provide boxes for electrical equipment and wiring devices as follows:

6. SECONDARY SERVICES (under 600 volts) 6.1 AVAILABILITY For the electrical characteristics of available secondary services see Section 3.4.

DOWNTOWN UNDERGROUND NETWORK SECONDARY SERVICES GUIDELINES

Grounding & Bounding. 1. Bonded Connected to establish electrical continuity and conductivity.

SOUTHERN NEVADA AMENDMENTS TO THE 2017 NATIONAL ELECTRICAL CODE

Transcription:

SECTION 16060 GROUNDING AND BONDING PART 1 GENERAL 1.1 SUMMARY A. Section Includes: Grounding of electrical systems and equipment and basic requirements for ground for equipment, circuits, and systems. Grounding requirements specified in this Section may be supplemented by special requirements of systems described in other Sections. B. Related Sections: 1. Section 13100 - Lightning Protection for additional grounding and bonding materials. 2. Section 16120 Conductors and Cables for requirements for grounding conductors. 1.2 SUBMITTALS A. Product Data: For following: 1. Ground rods. 2. Connectors and connection material. 3. Grounding fittings. B. Informational Submittals: Submit following: 1. Qualification Data: For firms and persons specified in Quality Assurance Article. 2. Field Test and Observation Reports: Submit written test reports to include following: a. Test procedures used. b. Test results that comply with requirements. c. Results of failed tests and corrective action taken to achieve test results that comply with requirements. 1.3 QUALITY ASSURANCE A. Testing Agency Qualifications: In addition to Section 01400 requirements, be a Nationally Recognized Testing Laboratory (NFTL) meeting OSHA criteria for accreditation of testing laboratories, Title 29, Part 1907; or be full-member company of NETA, InterNational Electrical Testing Association. 1. Testing Agency's Field Supervisor: Currently certified by InterNational Electrical Testing Association or National Institute for Certification in Engineering Technologies, to supervise onsite testing. B. Electrical Components, Devices, and Accessories: Listed and labeled, NFPA 70, Article 100, by testing agency acceptable to authorities having jurisdiction, and marked for intended use. 1. Comply with UL 467. C. Comply with NFPA 70; for medium-voltage underground construction, comply with IEEE C2. D. Comply with NFPA 780 and UL 96 when interconnecting with lightning protection system. PART 2 PRODUCTS 2.1 MANUFACTURERS A. Available Manufacturers: Subject to Section 01600 and compliance with requirements, manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following: 1. Grounding Conductors, Cables, Connectors, and Rods: a. Chance/Hubbell. b. Heary Brothers Lightning Protection Co. c. Kearney/Cooper Power Systems. d. Raco, Inc.; Division of Hubbell. e. Thomas & Betts, Electrical. f. Manufacturer providing equal product in accordance with Section 01600. 10-01053.00/01-15-03/Revised: 08-29-03 16060-1 GROUNDING AND BONDING

2.2 GROUNDING AND BONDING PRODUCTS A. Governing Requirements: Where types, sizes, ratings, and quantities indicated are in excess of National Electrical Code (NEC) requirements, more stringent requirements and greater size, rating, and quantity indications govern. 2.3 GROUNDING CONDUCTORS A. For insulated conductors, comply with Section 16120 - Conductors and Cables. B. Material: Copper. C. Equipment Grounding Conductors: Insulated with green-colored insulation. D. Isolated Ground Conductors: Insulated with green-colored insulation with yellow stripe. On feeders with isolated ground, use colored tape, alternating bands of green and yellow tape to provide minimum of three bands of green and two bands of yellow. E. Grounding Electrode Conductors: Stranded cable. F. Underground Conductors: Bare, tinned, stranded, unless otherwise indicated. G. Bare Copper Conductors: Comply with: 1. Solid Conductors: ASTM B3. 2. Assembly of Stranded Conductors: ASTM B8. 3. Tinned Conductors: ASTM B33. H. Copper Bonding Conductors: 1. Bonding Cable: 28 kcmil, 14 strands of No. 17 AWG copper conductor, 1/4 inch in diameter. 2. Bonding Conductor: No. 4 or No. 6 AWG, stranded copper conductor. 3. Bonding Jumper: Bare copper tape, braided bare copper conductors, terminated with copper ferrules; 1-5/8 inches wide and 1/16 inch thick. 4. Tinned Bonding Jumper: Tinned-copper tape, braided copper conductors, terminated with copper ferrules; 1-5/8 inches wide and 1/16 inch thick. I. Grounding Bus: Bare, annealed copper bars of rectangular cross section, with insulators. Provide clear lexan cover plate over face of ground bus. Provide stand-offs as required. 2.4 CONNECTOR PRODUCTS A. Comply with IEEE 837 and UL 467; listed for use for specific types, sizes, and combinations of conductors and connected items. B. Bolted Connectors: Bolted-pressure-type connectors, or compression type, heavy duty type. C. Welded Connectors: Exothermic-welded type, in kit form, and selected per manufacturer's written instructions, for specific types, sizes, and combinations of conductors. D. Grounding Terminal Lugs: Shall be of cast construction utilizing a high copper content hard alloy. The lug shall have machined mating surfaces, two 9/16 inch diameter through holes at NEMA spacing and two cap and eye cable clamps. Various cable clamping ranges from 14-8 through 600-800 shall be provided each as required for its specific application, or as indicated on the drawings. 2.5 GROUNDING ELECTRODES AND TEST WELLS A. Grounding Rods: Copper-clad steel. 1. Size: 3/4 inch by 120 inches. 2.6 EQUIPOTIAL GROUNDING SYSTEM A. Provide an equipotential grounding system in each operating room. All metal objects likely to become energized in the OR room shall be grounded via a dedicated, insulated grounding conductor to the room ground bus. See detail on drawings. B. Room ground bus shall consist of an isolated ground bar mounted in a recessed metal junction box with stainless steel cover, Square D or approved equal. 10-01053.00/01-15-03/Revised: 08-29-03 16060-2 GROUNDING AND BONDING

C. Room ground modules shall contain four grounding receptacles, Hampden Type SLR, in a recessed metal box with stainless steel cover, Square D or approved equal. Provide one 8 foot grounding cord for every two grounding receptacles. PART 3 EXECUTION 3.1 APPLICATION A. Use only copper conductors for both insulated and bare grounding conductors in direct contact with earth, concrete, masonry, crushed stone, and similar materials. B. In raceways, use insulated equipment grounding conductors. C. Exothermic-Welded Connections: Use for connections to structural steel and for underground connections, except those at test wells. D. Equipment Grounding Conductor Terminations: Use bolted pressure clamps. E. Ground Rod Clamps at Test Wells: Use bolted pressure clamps with at least two bolts. F. Grounding Bus: Install in electrical and telephone equipment rooms, where as indicated. G. Underground Grounding Conductors: Use copper conductor, No. 2/0 AWG minimum. Bury at least 24 inches below grade or bury 12 inches above duct bank when installed as part of duct bank. 3.2 EQUIPMENT GROUNDING CONDUCTORS A. Comply with NFPA 70, Article 250, for types, sizes, and quantities of equipment grounding conductors, unless specific types, larger sizes, or more conductors than required by NFPA 70 are indicated. B. Install equipment grounding conductors in all feeders and branch circuits. C. Busway Supply Circuits: Install insulated equipment grounding conductor from grounding bus in switchgear, switchboard, or distribution panel to equipment grounding bar terminal on busway. D. Isolated Grounding Receptacle Circuits: Install insulated equipment grounding conductor connected to receptacle grounding terminal. Isolate grounding conductor from raceway and from panelboard grounding terminals. Terminate at equipment grounding conductor terminal of applicable derived system or service, unless otherwise indicated. E. The equipment grounding terminal buses of the normal and emergency branch circuit panelboards serving the same patient vicinity shall be bonded together with an insulated continuous copper No. 10 AWG conductor. Conductor shall be run in minimum 3/4 inch conduit. F. Nonmetallic Raceways: Install equipment grounding conductor in nonmetallic raceways unless they are designated for telephone or data cables. G. Signal and Communication Systems: For telephone, alarm, voice and data, and other communication systems, provide No. 6 AWG minimum insulated grounding conductor in raceway from grounding electrode system to each service location, terminal cabinet, wiring closet, and central equipment location. 1. Service and Central Equipment Locations and Wiring Closets: Terminate grounding conductor on 1/4-by-2-by-12-inch grounding bus. 2. Terminal Cabinets: Terminate grounding conductor on cabinet grounding terminal. H. Common Ground Bonding with Lightning Protection System: Bond electrical power system ground directly to lightning protection system grounding conductor at closest point to electrical service grounding electrode. Use bonding conductor sized same as system grounding electrode conductor, and install in conduit. 10-01053.00/01-15-03/Revised: 08-29-03 16060-3 GROUNDING AND BONDING

3.3 COUNTERPOISE A. Ground steel framework of building with driven ground rod at base of every corner column and at intermediate exterior columns at distances not more than 60 feet apart. Provide grounding conductor (counterpoise), electrically connected to each ground rod and to each steel column, extending around perimeter of building. Use tinned-copper conductor not less than No. 2/0 AWG for counterpoise and for tap to building steel. Bury counterpoise not less than 18 inches below grade and 24 inches from building foundation. 3.4 INSTALLATION A. General: Ground electrical systems and equipment according to NEC requirements, except where Drawings or Specifications exceed NEC requirements. B. Electrical Room Grounding Bus: Space 1 inch from wall and support from wall 6 inches above finished floor, except as otherwise indicated. C. Ground Rods: Install at least three rods spaced at least one-rod length from each other and located at least same distance from other grounding electrodes. 1. Drive ground rods until tops are 2 inches below finished floor or final grade, unless otherwise indicated. 2. Interconnect ground rods with grounding electrode conductors. Use exothermic welds, except at test wells and as otherwise indicated. Make connections without exposing steel or damaging copper coating. D. Grounding Conductors: Route along shortest and straightest paths possible, unless otherwise indicated. Avoid obstructing access or placing conductors where they may be subjected to strain, impact, or damage. E. Bonding Straps and Jumpers: Install so vibration by equipment mounted on vibration isolation hangers and supports is not transmitted to rigidly mounted equipment. Use exothermic-welded connectors for outdoor locations, unless disconnect-type connection is required; then, use bolted clamp. Bond straps directly to basic structure taking care not to penetrate any adjacent parts. Install straps only in locations accessible for maintenance. F. Metal Water Service Pipe: Provide insulated copper grounding conductors, in conduit, from building's main service equipment, or grounding bus, to main metal water service entrances to building. Connect grounding conductors to main metal water service pipes by grounding clamp connectors. Where dielectric main water fitting is installed, connect grounding conductor to street side of fitting. Bond metal grounding conductor conduit or sleeve to conductor at each end. G. Water Meter Piping: Use braided-type bonding jumpers to electrically bypass water meters. Connect to pipe with grounding clamp connectors. H. Bond interior metal piping systems and metal air ducts to equipment grounding conductors of associated pumps, fans, blowers, electric heaters, and air cleaners. Use braided-type bonding straps. I. Bond each aboveground portion of gas piping system upstream from equipment shutoff valve. J. Bond the new electrical service grounds to the existing hospital electrical service grounds as indicated on the drawings. 3.5 CONNECTIONS A. General: Make connections so galvanic action or electrolysis possibility is minimized. Select connectors, connection hardware, conductors, and connection methods so metals in direct contact will be galvanically compatible. 1. Use electroplated or hot-tin-coated materials to ensure high conductivity and to make contact points closer to order of galvanic series. 2. Make connections with clean, bare metal at points of contact. 3. Coat and seal connections having dissimilar metals with inert material to prevent future penetration of moisture to contact surfaces. 10-01053.00/01-15-03/Revised: 08-29-03 16060-4 GROUNDING AND BONDING

B. Exothermic-Welded Connections: Comply with manufacturer's written instructions. Welds that are puffed up or that show convex surfaces indicating improper cleaning are not acceptable. C. Equipment Grounding Conductor Terminations: For No. 8 AWG and larger, use pressure-type grounding lugs. No. 10 AWG and smaller grounding conductors may be terminated with winged pressure-type connectors. D. Noncontact Metal Raceway Terminations: If metallic raceways terminate at metal housings without mechanical and electrical connection to housing, terminate each conduit with grounding bushing. Connect grounding bushings with bare grounding conductor to grounding bus or terminal in housing. Bond electrically noncontinuous conduits at entrances and exits with grounding bushings and bare grounding conductors, unless otherwise indicated. E. Tighten screws and bolts for grounding and bonding connectors and terminals according to manufacturer's published torque-tightening values. If manufacturer's torque values are not indicated, use those specified in UL 486A. F. Compression-Type Connections: Use hydraulic compression tools to provide correct circumferential pressure for compression connectors. Use tools and dies recommended by connector manufacturer. Provide embossing die code or other standard method to make visible indication that connector has been adequately compressed on grounding conductor. G. Moisture Protection: If insulated grounding conductors are connected to ground rods or grounding buses, insulate entire area of connection and seal against moisture penetration of insulation and cable. 3.6 FIELD QUALITY CONTROL A. Testing: Engage qualified independent testing agency to perform following field quality-control testing: B. Testing: Perform following field quality-control testing: 1. After installing grounding system but before permanent electrical circuitry has been energized, test for compliance with requirements. 2. Test completed grounding system at each location where maximum ground-resistance level is specified, at service disconnect enclosure grounding terminal, and at ground test wells. Measure ground resistance not less than two full days after last trace of precipitation, and without soil being moistened by any means other than natural drainage or seepage and without chemical treatment or other artificial means of reducing natural ground resistance. Perform tests, by fall-of-potential method according to IEEE 81. 3. Provide drawings locating each ground rod and ground rod assembly and other grounding electrodes, identify each by letter in alphabetical order, and key to record of tests and observations. Include number of rods driven and their depth at each location and include observations of weather and other phenomena that may affect test results. Describe measures taken to improve test results. a. Equipment Rated 500 kva and Less: 10 ohms. b. Equipment Rated 500 to 1000 kva: 5 ohms. c. Equipment Rated More Than 1000 kva: 3 ohms. d. Substations and Pad-Mounted Switching Equipment: 5 ohms. e. Manhole Grounds: 10 ohms. f. Signal and communication systems. 5 ohms. 4. Excessive Ground Resistance: If resistance to ground exceeds specified values, notify Owner promptly and include recommendations to reduce ground resistance. C. The effectiveness of the grounding system in patient care areas shall be determined by voltage and impedence measurements as indicated in NFPA-99. Voltage and impedance measurements shall be recorded in each patient area by taking measurements with respect to a reference point. Voltage measurements shall be made under non-fault conditions between a reference point and exposed fixed electrical equipment. Impedence measurements shall be made between the reference point and the grounding contact of 10 percent of all receptacles in each patient care vicinity. The voltage limit shall be 20 mv. The impedence limit shall be 0.1 ohms. A tabulated report shall be prepared and given to the Owner which shall include all measurements recorded at each location in each room or area. 10-01053.00/01-15-03/Revised: 08-29-03 16060-5 GROUNDING AND BONDING

D. Report: Prepare test reports, certified by testing organization, of ground resistance at each test location. Include observations of weather and other phenomena that may affect test results. Describe measures taken to improve test results. END OF SECTION 10-01053.00/01-15-03/Revised: 08-29-03 16060-6 GROUNDING AND BONDING